Tamil Nadu Agricultural University Tender
Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Tamil Nadu Agricultural University - TNAU Tender
Coronavirus COVID 19
Eprocure
Opening Date22 Nov 2019
Closing Date23 Jan 2020
Tender Amount₹ 2,01,79,410 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 1,26,500Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2019_TNAU_148508_1Bid Award Id
ViewTender No
H/DB/TRANSFORMER/19 DT.19.11.19Tender Authority
Tamil Nadu Agricultural University ViewPurchaser Address
-Website
http://http://www.tnau.ac.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply and providing cable end termination of 3 core 240 Sq.mm XLPE Armed HT UG Aluminium cable Indoor Kit (Make: Raychein RPG/ M Seal/Denson/Equivalent) (SD.No.Ref.242)
2
-
-
... More
Supply and providing cable end termination of 3 core 185 Sq.mm XLPE Armed HT UG Aluminium cable Outdoor Kit (Make: Raychein RPG/ M Seal/Denson/Equivalent) (SD.No.Ref.242)
2
-
-
... More
Supply and providing cable end termination of 3 core 240 Sq.mm XLPE Armed HT UG Aluminium cable outdoor Kit (Make: Raychein RPG/ M Seal/Denson/Equivalent)(SD.No.Ref.242)
2
-
-
... More
Supply, Erection, Commissioning and Testing of 800 A, 11KV 25 KA Horizontal Draw out and vertical isolation HT outdoor type five panel (1 I/C +4 O/G) Vacuum Circuit Breaker fitted with Manual/Motor spring charing mechanism with 230AC motor along with motor control panel switch, shunt trip coil of 110V DC, Closing coil of 110V DC, Auxiliary Contact 6NO+6NC, mechanical ON/OFF indicator, mechanical operation, Anti Pumping feature, Automatic safety shutter and push button arrangements with1 No.of 800A VCB as incomer and 4No.of 800A VCB as outgoing out door line up panel with required accessories as given below (Make: Magawin/ Pentagon/ ABB/ Crompton Greaves). The testing and commissioning report from the manufacture must be handed over to the Engineer-In Charge after the Installation. (Special item)
1
-
-
... More
Vacuum Circuit Breaker
800 A, 11KV 25 KA Horizontal Draw out/isolation HT outdoor type Vacuum Circuit Breaker.
Potential Transformer
Three Phase, Resin cast, Dry type PT with HT/LT fuses of ratio 11kV/110V, Core1: Cl- 1.0, 100VA with HT Primary Fuses.
Current Transformer
Single Phase , Resin Cast, Dry type Current transformer of suitable Ratio:5-5A, Core1: Cl. 0.5/7.5VA for metering, Core2: Cl:5P10/7.5VA for protection (For transformer) 1 Set= 3Nos.
Single Phase , Resin Cast, Dry type Current transformer of suitable Ratio:5-5A, O/G:2, suitable ratio /5-5A, Core 1: Cl 0.5/7.5VA for metering, Core2: Cl:5P10/7.5VA for protection (O/G) 1 Set of 3 Nos.
Meters
96mm.sq.Cl:.05 Digital Ammeter with inbuilt selector switch (I/C-1 No & O/G-4Nos)
96mm.sq.Cl:.05 Digital Voltmeter with inbuilt selector switch (I/C-1 No)
-
-
-
... More
Protection Relay
Numerical type Triple pole Non-Directional, IDMT Combined 3 O/C+1 EF draw out type relay with High Set (L&T make)
Auxiliary Relays
Transformer fault annunciation type Auxiliary Relay (O/G end)
Mater trip relay (I/C-1 No & O/G-4Nos)
Indication Lamps
VCB off / on / Auto trip/ Trip circuit healthy/spring charge indication (I/C-1 No & O/G-4No)
RYB Indication (Incomer only)
Push Button
Trip Circuit Healthy Push Button (I/C-1 No & O/G-4Nos)
Annunciator
Facia, Static type Annunciator with inbuilt alarm, accept, test, reset push button with buzzers (O/G end) (8 Window)
Control Switches
Breaker Control switch (Close-Neutral- Trip) (I/C-1 No & O/G-4Nos)
Bus Bar
Main Bus: 800Amps Aluminium Busbar with insulation. (I/C-1 No & O/G-4Nos)
Common for Switchgear
Control Wiring (I/C-1 Set & O/G-4 Set)
-
-
-
... More
Heater ON/OFF Switch with filament type 200W space heater and thermostat, Single phase switch with socket, Cubicle illumination lamp, Door limit switch, MCBs/Fuses for AC/DC Control. (I/C-1 Set & O/G-4Set)
Power pack-230V AC to 110V DC (I/C-1 No & O/G-4No)
Enclosure
MS Steel Sheet enclosure suitable for Outdoor Installation with MS base channel with provision of future extension. (I/C-1 Set & O/G-4Set)
Termination
Incoming (Excluding cable termination kits, lugs and glands) (Bus bar) (Rear Cable bottom entry)
Outgoing (Excluding cable termination kits ,lugs and glands) (Bus bar) (Rear Cable bottom entry)
Surge Arrester 9KV/10KA (3 Nos= 1set) (Incoming side)
Castle Interlock Key (2 Base +1 Key) (Incoming side)
-
-
-
... More
Supply, Erection, Commissioning and Testing of 800 A, 11KV 25 KA Horizontal Draw out and vertical isolation HT outdoor type four panel (1 I/C +3 O/G) Vacuum Circuit Breaker fitted with Manual/Motor spring charing mechanism with 230AC motor along with motor control panel switch, shunt trip coil of 110V DC, Closing coil of 110V DC, Auxiliary Contact 6NO+6NC, mechanical ON/OFF indicator, mechanical operation, Anti Pumping feature, Automatic safety shutter and push button arrangements with1 No.of 800 ACB as incomer and 3 No.of 800 A VCB as outgoing out door line up panel with required accessories as given below(Make: Magawin/ Pentagon/ ABB/ Crompton Greaves). The testing and commissioning report from the manufacture must be handed over to the Engineer-In Charge after the Installation. (Special item)
1
-
-
... More
Vacuum Circuit Breaker
800 A, 11KV 25 KA Horizontal Draw out/isolation HT outdoor type Vacuum Circuit Breaker.
Potential Transformer
Three Phase, Resin cast, Dry type PT with HT/LT fuses of ratio 11kV/110V, Core1: Cl- 1.0, 100VA with HT Primary Fuses.
Current Transformer
Single Phase , Resin Cast, Dry type Current transformer of suitable Ratio:5-5A, Core1: Cl. 0.5/7.5VA for metering, Core2: Cl:5P10/7.5VA for protection (For transformer) 1 Set= 3Nos.
Single Phase , Resin Cast, Dry type Current transformer of suitable Ratio:5-5A, O/G:2, suitable ratio /5-5A, Core 1: Cl 0.5/7.5VA for metering, Core2: Cl:5P10/7.5VA for protection (O/G) 1 Set of 3 Nos.
Meters
96mm.sq.Cl:.05 Digital Ammeter with inbuilt selector switch (I/C-1 No & O/G-3Nos)
96mm.sq.Cl:.05 Digital Voltmeter with inbuilt selector switch (I/C-1 No)
3 Phase, 4 wire, 3 element digital multifunction meter (I/C-1 No & O/G=3 Nos)
-
-
-
... More
Protection Relay
Numerical type Triple pole Non-Directional, IDMT Combined 3 O/C+1 EF draw out type relay with High Set (L&T make)
Auxiliary Relays
Transformer fault annunciation type Auxiliary Relay (O/G end)
Mater trip relay (I/C-1 No & O/G-3Nos)
Indication Lamps
VCB off / on / Auto trip/ Trip circuit healthy/spring charge indication (I/C-1 No & O/G-3No)
RYB Indication (Incomer only)
Push Button
Trip Circuit Healthy Push Button (I/C-1 No & O/G-4Nos)
Annunciator
Facia, Static type Annunciator with inbuilt alarm, accept, test, reset push button with buzzers (O/G end) (8 Window)
Control Switches
Breaker Control switch (Close-Neutral- Trip) (I/C-1 No & O/G-4Nos)
Bus Bar
Main Bus: 800Amps Aluminium Busbar with insulation. (I/C-1 No & O/G-4Nos)
-
-
-
... More
Common for Switchgear
Control Wiring (I/C-1 Set & O/G-4 Set)
Heater ON/OFF Switch with filament type 200W space heater and thermostat, Single phase switch with socket, Cubicle illumination lamp, Door limit switch, MCBs/Fuses for AC/DC Control. (I/C-1 Set & O/G-4Set)
Power pack-230V AC to 110V DC (I/C-1 No & O/G-4No)
Enclosure
MS Steel Sheet enclosure suitable for Outdoor Installation with MS base channel with provision of future extension. (I/C-1 Set & O/G-4Set)
Termination
Incoming (Excluding cable termination kits, lugs and glands) (Bus bar) (Rear Cable bottom entry)
Outgoing (Excluding cable termination kits ,lugs and glands) (Bus bar) (Rear Cable bottom entry)
Surge Arrester 9KV/10KA (3 Nos= 1set) (Incoming side)
Castle Interlock Key (2 Base +1 Key) (Incoming side)
-
-
-
... More
Supply, erection, commissioning and testing of Outdoor type 1000 KVA (11/.433 KV) 3 Phase, 50Hz, ONAN Cooled oil immersed copper wounded Outdoor type step down low loss transformer (IS:1180) complete with first filling of IS:335 ISI marked filtered & Dehydrated transformer oil and other standard fitting /suitable accessories and 17 position on load tap changer (OLTC) tapping range from +5% to -15% in steps of 1.25% Each) with Remote Tap Cubical Changer (RTCC) panel & Automatic Voltage Regulator (AVR) with Vector Group Dyn-11 with suitable HV and LV cable box, Buchholz Relay (Contacts for alarm & Trip) with OTI & WTI (Contacts for alarm and trip). (Make: ITE/ CREL/ Rowsons/ OEM) . The neutral should be connected with 400/5A CT coil on a suitable MS box with copper bus bar arrangement and the CT should be interconnected with the ACB with 2 of 4 sq.mm copper armoured cable. The transformer should be supplied with first filling of oil. (Special item)
1
-
-
... More
Terminal arrangement:- HV-Cable box,LV-Flange to suit bus duct.All removable covers shall be provided with weather proof hot oil resistant, resistance gaskets, to prevent leakage of water in to core, and oil from the tank with Transformer. The transformer should be insured during the transportation, The transportation, loading and unloading charges been included in the data. The item should be testing as per the CEIG standard rules and commissioning report from the manufacture must be handed over to the Engineer -In Charge after the Installation. (ISI 1180-Level-2) (Special item)
-
-
-
... More
Supply, erection, commissioning and testing of 250 KVAR, 12 stage switching, sequence automatic power factor correction floor mounting stand vermin proof cubical panel board made of 16 SWG CRCA sheet steel with supply and fixing of the following interior mounting capacitor chamber relay with metering chamber and Compartmentalised out going feeders with suitable capacity MCCB with panel board with provision for louvers and cooling fan for proper ventilation to manage heat load incoming - 630A TPN MCCB with rotary handle. (Havells Make/ C&S/ OEM) (Special item)
1
-
-
... More
Supply, installation, commissioning and testing of 650 KVA silent diesel engine generator set 415 volts, 3 phase, 4 wire engine as per IS 1001/10002 and alternator as per IS 1336 complete with foundation, control panel with necessary meters and floor mounted including acoustic enclosure sound proof canopy to ensure pollution free complying with all latest CPCB norms as per ISO 3046 for pollution and noise complete of capacity 650 KVA diesel engine developing 828 BHP at 1500 RPM complete with the following:- (Make of DG set :Cummins/ Kirloskar/ Caterpiller/ OEM)The testing and commissioning report along with operation manual and other connected documents should be handed over to the Engineer In-Charge. The test run of the DG Should be 5 Hours from variable load to full load using variable resistive load. (Special item)
1
-
-
... More
(a) Diesel Engine :- Diesel engine of required capacity multi cylinder inline, 4 stroke cycle, heavy duty water cooled radiator, adequate BHP and cooling for system at a speed of 1500 RPM rating for continuous duty and comprising of the following:-
(i) Well designed air handling system with
(a) Dry type, replaceable paper element air cleaner with restriction indicator
(b) Air to air aftercooling
(c) Optimized turbocharger for increased altitude capabilities
(ii) Optimized fuel consumption with
(a) Inline fuel pump with mechanical governor
(b) Spin on fuel filter
(iii) Standard integral set-mounted radiator system, designed and tested for 50°C ambient temperatures
(iv) Full flow spin on lube oil filter
(v) First fill of lube oil and coolant
(vi) Electrical starter motor with soft start engagement feature
(vii) Suitable coupling and guard
(viii) Fly wheel with starter ring
(ix) Fuel and lubricant oil filter
(x) Water pump and lub oil pump
-
-
-
... More
(xi) Electric starting system with battery charging alternator and axil type starter motor including suitable adequate number of high capacity maintenance free lead acid battery as per manufacture requirement including self starter connection cable.
(xii) Hospital grade Silencer suitably optimized to meet stringent noise emission standards laid down by CPCB
(b) Engine instrument panel shall be comprise with the following:-
(i) Engine Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish and Aluminium bus bars with suitable capacity with incoming/outgoing terminals, Indicating lamps for ‘Load ON’ and ‘Set Running’, Instrument fuses duly wired and ferruled ,MCCB of suitable rating with overload and short circuit protections.
(ii) The control panel consists of the following parts
(a) Microprocessor based generator set monitoring and control system. This control includes an include operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics.
-
-
-
... More
(i) LED backlit LCD display with tactile feel soft-switches and generator set status LED lamps
(ii) Remote start-stop, Auto/Manual,Test operation features
(iii) Engine Metering: Oil pressure, Engine temperature, Starting battery voltage, Engine running hours no of starts, warming up period etc
(iv) AC Alternator Metering: L-L Voltage and L-N Voltage, Current (phase and total), kVA (phase and total) and Frequency .
(v) Engine Protection: Low lube oil pressure, High/Low coolant temperature, Battery Over/Under Volts, Fail to Crank / Start, Sensor failure, cranking lockout, Low fuel level.
(vi) AC Alternator Protection: Over/Under Voltage, Over/Under Frequency,
(vii) Data Logging: Engine Hours, total (viii) Emergency stop push button on control panel and canopy
(ix) 12 Volt DC operation
(x) Sleep mode
(xv) Safety alarm against high water temperature and lub oil pressure
-
-
-
... More
(c) Alternator :- Alternator self existed, self regulated,Brushless type, Screen protected, Revolving field, alternator conforming to IS13364 520 KW/ 650 KVA at the speed of 1500 RPM at 415 volt, 50 Hz, 3 phase, 4 wire system, phase sequence UVW PF 0.8 with advance electronic voltage regulator at the variation of 1% class F insulation and IP23 enclosure directly coupled with engine (Make of Alternator :- Stamford)
(d) Fuel tank: DG set should have built in fuel tank made out from 2mm thick MS sheet and fuel gauge of adequate capacity running for 12 hrs.
-
-
-
... More
Supply, installation, commissioning and testing of 365 KVA silent diesel engine generator set 415 volts, 3 phase, 4 wire engine as per IS 1001/10002 and alternator as per IS 1336 complete with foundation, control panel with necessary meters and floor mounted including acoustic enclosure sound proof canopy to ensure pollution free complying with all latest CPCB norms as per ISO 3046 for pollution and noise complete of capacity 365 KVA diesel engine developing 448 BHP at 1500 RPM complete with the following:- (Make of DG set :Cummins/ Kirloskar/ Caterpiller/ OEM). The testing and commissioning report along with operation manual and other connected documents should be handed over to the Assistant Executive Engineer (Ele). The test run of the DG Should be 5 Hours from variable load to full load using variable resistive load. (Special item)
1
-
-
... More
(a) Diesel Engine :- Diesel engine required capacity multi cylinder inline, 6 stroke cycle, heavy duty water cooled radiator, adequate BHP and cooling for system at a speed of 1500 RPM rating for continuous duty and comprising of the following:- (i) Well designed air handling system with
(a) Dry type, replaceable paper element air cleaner with restriction indicator
(b) Air to air aftercooling
(c) Optimized turbocharger for increased altitude capabilities
(ii) Optimized fuel consumption with
(a) Inline fuel pump with mechanical governor
(b) Spin on fuel filter
(iii) Standard integral set-mounted radiator system, designed and tested for 50°C ambient temperatures
(iv) Full flow spin on lube oil filter
(v) First fill of lube oil and coolant
(vi) Electrical starter motor with soft start engagement feature
(vii) Battery charging alternator
(viii) suitable DC battery
(ix) Suitable coupling and guard
(x) Fly wheel with starter ring
(xi) Fuel and lubricant oil filter
(xii) Water pump and lub oil pump
-
-
-
... More
(xiii) Electric starting system with battery charging alternator and axil type starter motor including adequate number of suitable high capacity maintenance free lead acid battery as per manufacture requirement including self starter connection cable.
(xv) Hospital grade Silencer suitably optimized to meet stringent noise emission standards laid down by CPCB
(b) Engine instrument panel shall be comprise with the following:-
(i) Engine Control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish and Aluminium bus bars with suitable capacity with incoming/outgoing terminals, Indicating lamps for ‘Load ON’ and ‘Set Running’, Instrument fuses duly wired and ferruled ,MCCB of suitable rating with overload and short circuit protections.
(ii) The control panel consists of the following parts
(a) Microprocessor based generator set monitoring and control system. This control includes an include operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics.
-
-
-
... More
(i) LED backlit LCD display with tactile feel soft-switches and generator set status LED lamps
(ii) Remote start-stop, Auto,Manual,Test operation features
(iii) Engine Metering: Oil pressure, Engine temperature, Starting battery voltage, Engine running hours no of starts, warming up period etc
(iv) AC Alternator Metering: L-L Voltage and L-N Voltage, Current (phase and total), kVA (phase and total) and Frequency .
(v) Engine Protection: Low lube oil pressure, High/Low coolant temperature, Battery Over/Under Volts, Fail to Crank / Start, Sensor failure, cranking lockout, Low fuel level.
(vi) AC Alternator Protection: Over/Under Voltage, Over/Under Frequency,
(vii) Data Logging: Engine Hours, total (viii) Emergency stop push button on control panel and canopy
(ix) 12 Volt DC operation
(x) Sleep mode
(xv) Safety alarm against high water temperature and lub oil pressure
-
-
-
... More
(c) Alternator :- Alternator self existed, self regulated,Brushless type, Screen protected, Revolving field, alternator conforming to IS13364 292 KW/ 365 KVA at the speed of 1500 RPM at 415 volt, 50 Hz, 3 phase, 4 wire system, phase sequence UVW PF 0.8 with advance electronic voltage regulator at the variation of 1% class F insulation and IP23 enclosure directly coupled with engine (Make of Alternator :Stamford)
(d) Fuel tank: DG set should have built in fuel tank made out from 2mm thick MS sheet and fuel guage of adequate capacity running for 12 hrs.
-
-
-
... More
2500 A Bus duct: Fabrication, supply erection and commissioning of bus duct for 1000 KVA Transformer and connected to the 1600A ACB panel input supply, The bus duct should be vermine proof made up of 2 mm CRCA Sheet, powder coated paint with bus bar. 2runs 100x6mm Al. flat /per phase (RYB) (totally 6 run) and 1 run 100x6mm Al. flat for neutral the bus duct will be fabricated for out door and indoor application at partial feeding arrangement in out door canopy arrangement. with 2 runs of 50 x 6mm Aluminium flat for earthing of bus duct continuous run.
The bus – duct shall be designed for the above current ratings and for a maximum temperature rise of 400C over an ambient temperature of 45°C. The bus- bars shall be of uniform cross section along its entire length. No tapering of the bus bars’ cross-section is allowed. The bus duct shall be painted after suitable pre treatment of all structural steel and plates with anti-corrosive epoxy base primer paint & two coats of anti corrosive epoxy base paint externally with a colour of pebble / flint gray shade RAL 7032and dried in a oven. The enclosure shall conform to IP: 54 for indoor, as per Indian Standards. (Special item)
20
-
-
... More
Inner surface of the bus – duct shall be coated in the rubber paint. The bare bus –bars shall be provided with a coat of Matt finish, The joints in the bus –bars shall be of the bolted type and it shall be ensured that the following precautions are observed. i). The contact pressure must be ample and this shall be maintained during the time the panel is in service. ii. The surfaces of the conductors must be clean.
iii. With flat conductors, the overlap should be equal to or greater than the width of the bars or ten times the thickness of the bar whichever is greater. iv. The joints shall be treated by the application of joint compound to render the joint moisture-proof. v. For the joints use of bolts of cadmium plated high-tension MS bolts having expansion characteristics due to temperature change similar to the conductor may be used with steel nuts. vi. Smearing the surfaces with oxide inhibiting grease just prior to making the joint in order to preserve the efficiency of the joints. Minimum phase and earth clearance required shall be maintained at joints. The joints shall be thoroughly shrouded.
-
-
-
... More
The bus bar arrangement shall generally conform to IS: 5578 and IS: 11353. The bus – duct shall be also supplied with suitable earth bus running all along the length of the bus – duct made of copper strips. Current density at any part shall not exceed prescribed limits. Two copper flats of same phase shall be stacked together or the spacing between them shall be maximum of the thickness of one conductor. The busbars shall be phase identified by colour, at intervals. Colour code shall be RED, YELLOW and BLUE for phase and BLACK for the neutral bus – bar. Bus – bars shall be supported on tough, non-hygroscopic, resin bonded self-extinguishing fire retardant insulators preferably of SMC / DMC with ribbed construction to prevent tracking due to dust paths. Bus – bars and supports shall withstand the maximum stresses that are induced in the event of. The short-circuit currents being as specified.
-
-
-
... More
Supply and fixing of 2500 Aluminium flexible joint with 2 No.of 100x6mm for each phase and 1 No.of 100x6mm for Neutral and1 No. of 50x6mm for Earth with necessary connection complete arrangements (Special item)
10
-
-
... More
Special Earthing as per the ISI specification of 8 feet depth with an earth electrode of size 600 x600 x3 mm thick burried copper plate directly in ground level with top edge of the earth plate not less than 1.8mtr below normal ground level, connected to copper flat of 32mmx6mm thickness through 1.8 metre cast iron pipe of dia not less than 80mm by means of bolt, nuts, check nuts and washers of Brass /Stainess Steel with necessary masonry work with 38mm RCC cover slab for earth pit masonry work completed all as directed by the Engineer-In Charge .(SD.No.Ref.233)
10
-
-
... More
Special Earthing as per the ISI specification of 8 feet depth with an earth electrode of size 600 x600 x6 mm thick burried galvanised iron plate directly in ground level with top edge of the earth plate not less than 1.8mtr below normal ground level, connected to copper flat of 32mmx6mm thick through 1.8 metre cast iron pipe of dia not less than 80mm by means of bolt, nuts, check nuts and washers of Brass /Staines Steel with necessary masonry work with 38mm RCC cover slab earth pit masonry work completed as directed by the Engineer-InCharge . (SD.No.Ref.233)
30
-
-
... More
Supply and run of 32mmx6mm tinned copper flat with necessary clamps/support on wall/ floor/ground for earth connection. (SD.No.Ref.76)
200
-
-
... More
Supply and run of 32mmx6mm Galvanised iron flat with necessary clamps/support on wall/ floor/ground for earth connection (SD.No.Ref.76)
600
-
-
... More
Supply and run of 25mmx3 mm Galvanised iron flat with necessary clamps/support on wall/ floor/ground for earth connection.(SD.No.Ref.76)
400
-
-
... More
Supply and fixing of Galvanised iron powder coated 14 SWG cable tray of size 300mm x50 mm on wall/floor with suitable hardware support channel materials complete. (Special item)
20
-
-
... More
Supply and clamping of 3½ x185 sq.mm Copper cable in the cable tray/ on wall with necessary clamping arrangements (Make: Havells/ Polycab/ Gloster/ Equivalent) (SD.No.229)
550
-
-
... More
Supply and Mounting of 2500A rating three tier MV ACB Floor Mounting Pattern 6.10 ft (H)x16 ft (L)x2.25 ft (B) with 2.0 mm CRCA sheet steel with powder coated cubical panel board interconnecting with suitable interlock and key arrangements with 1600A FP MDO ACB as incoming with earth fault relay for 1000KVA transformer and 1 No.of 1000A FP MDO ACB as incoming for 650 KVA DG Set Incoming and 630A MDO ACB for 365KVA DG set Incoming aloung with suitable CT coil arrangements, Earth Fault Relay, FRP safety shutter assembly with 2 run of 100mmx12mm (2500A rating) aluminium flat for each phase and 1 run of 100mmx12mm (1450A rating) aluminium flat for neutral with 1 Nos. of 1000A FP SFU with HRC fuse link for inter connect both DG Sets throgh bus chamber by operating 3 interlocking with 2 key operation arrangements, 630 A FP SFU with HRC fuse link for 250A APFC panel, 8 Nos.of 400A TP SFU with HRC fuse link for feeder switches, 4Nos.of 315A TP SFU with HRC fuse link for feeder switch and 2 No.of 100A TFP SFU with HRC fuse link SHEET STEEL ENCLOSURE SWITCHES for power house as outgoing with interconnecting the switch with 50mm x 6 mm aluminium flat. Suitable multi-function meter(VLL,VLN,AMP,HZ) along with suitable CT coils.
1
-
-
... More
The panel board should be fixed on a suitable angle iron frame work with suitable bolt and nut with painting of suitable colour for power wiring and lock and key arrangements(Switch should be disconnector fuse units in open execution (interior for cubical) switches and ACB should be C&S /L&T/ Equivalent make). The danger notice sticker and other safety notice should be provided as per the Electrical Inspectorate norms.The MV panel should be designed as per the direction of Engineer In-Charge. (Special Item)
-
-
-
... More
Supply and clamping of 3 core 400.sqmm LTUG armoured aluminium cable (XLPE/ PVC) on post/ or on wall with necessary clamping arrangements complete. Make: (Havells/ Polycab/ Glostar). The cable should be grade confirming to IS: 7098.(SD.No.Ref.231)
150
-
-
... More
Supply and clamping of 2 core 300.sqmm LTUG armoured aluminium cable (XLPE/ PVC) on post/ or on wall with necessary clamping arrangements complete.The cable should be grade confirming to IS: 7098. Make: (Havells/ Polycab/ Glostar). (SD.No.Ref.231)
250
-
-
... More
Supply and providing of 3 Nos of end termination for 400 sq.mm XLPE LTUG aluminium armoured cable with suitable Heat Sinkable cable Slvees 0.5 mt for each cable with suitable colour indication for Phase and Neutral with necessary aluminium socket by crimping etc. (SD.No.Ref.242)
6
-
-
... More
Supply and providing of 2 of 300 sq.mm end termination for XLPE LTUG aluminium armoured cable with suitable Heat Sinkable cable Slvees 0.5 mt for cable along with suitable colour indication for Phase and Neutral with necessary aluminium socket by crimping etc. with electrical connection. (SD.No.Ref.242)
10
-
-
... More
Supply and providing of end termination for 3 1/2 x 300sq.mm XLPE LTUG copper armoured cable with necessary copper socket by crimping etc. with electrical connection. (SD.No.Ref.242)
10
-
-
... More
Supply and fixing of brass gland for 2 core 300sqmm.PVC/XLPE armoured LTUG cable with earth connection.(SD.No.Ref.195)
10
-
-
... More
Supply and fixing of brass gland for 3 core 400 sqmm.PVC/XLPE armoured LTUG cable with earth connection.(SD.No.Ref.195)
6
-
-
... More
Wiring with 2x1.5 sqmm (22/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V grade in suitable heavy gauge conduit pipe on wall and ceiling with MS accessories MS switch box and 5A F.T. switch with painting of suitable colour earth wire connecting 1.0 sq.mm copper wire for light / Fan Point (For electronic regulator) (5 Points Per Coil) (SD.No.1)
54
-
-
... More
Supply and fixing of 4' 18W Crystal Glass LED Tube Light Fitting with PVC round blocks on wall or ceiling with PVC unsheathed copper leads from terminals to the fitting. (Havells / Philips / Equivalent) (SD.No.Ref.87)
27
-
-
... More
Supply and fixing of 1200mm (48") High speed AC Ceiling fan complete with stepped electronic 300W regulator with 300mm down rod on the existing clamp (Make : Crompton /Havells /Usha /Equivalent) (SD.No.Ref.110)
7
-
-
... More
Supply and fixing of 1 No. 5Amps and 1 No.of 15A combined flush type wall socket with control switches concealed in suitable MS Box with painting covered with Hylem sheet in flush with wall with earth connection. (SD.No.Ref.139)
6
-
-
... More
Supply and fixing of 5/15 A 3 Pin combined flush type wall socket with 15A flush type switch concealed in suitable MS Box flush with wall with painting.(SD.No.137)
4
-
-
... More
Supply and fixing of 375mm (15") Sweep (light duty ) Exhaust Fan complete with necessary wall opening and making of the wall (SD.No.114)
6
-
-
... More
Supply and fixing of louver shutters arrangements for 375mm (15") Sweep (light duty) AC Exhaust Fan. (SD.No.Ref.121)
6
-
-
... More
Supply and run of 2 of 1.5 sqmm (22/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable heavy gauge M.S. conduit pipe on wall and ceiling with continuous earth wire connection 1sqmm wire with painting of suitable colour. (SD.No.42)
100
-
-
... More
Supply and run of 2 of 2.5 sqmm (36/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable heavy gauge M.S. conduit pipe on wall and ceiling with continuous earth wire connection of 1sqmm wire with painting of suitable colour.(SD.No.Ref.44)
100
-
-
... More
Supply and run of 4 of 4 sqmm (56/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable heavy gauge M.S. conduit pipe on wall and ceiling with continuous earth wire connection of 1.5 sqmm wire with painting of suitable colour.(SD.No.49)
30
-
-
... More
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure Distribution board with Double door(Metal) 1No 40 Amps DP MCB as incoming and 6 Nos 6 Amps to 32 Amps SPMCB outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB's should be with ISI mark (Like Legrand/Hager/MDS make). with IP 42 protection.(SD.No.Ref.167)
2
-
-
... More
Supply and fixing of Horizontal type 4 way MCB distribution board in sheet steel enclosure Double door(Metal) with 63A 4 pole MCB isolator as incoming and 2 Nos.40 A DP MCB and 8 Nos.of 6 to 32A SP as outgoing in flush with wall and making good of the concealed portion with earth connection. The MCBDB and MCB's should be with the ISI mark (like Legrand/Hager/MDS make) with IP42 protection.(SD.No.Ref.179)
2
-
-
... More
Supply and fixing of 30W LED Street light fitting with 19mm dia GI pipe (Class B) with 1 No.19mm GI Bend complete on the wall with 16A aerial fuse unit on MS plate with PVC unsheathed Cu.Leads, with MS clamp and aluminium painting. (Make : Philips/ Havells/ Equivalent).(SD.No.Ref.95)
20
-
-
... More
Supply and fixing of 400A FP 25KA MCCB with suitable spreader termination with rotary handle on a suitable 16 SWG MS powder coated box on wall with suitable end termination and gland connection on a suitable angle iron frame with necessary masonry works. (Special item)
3
-
-
... More
Supply and fixing of Cable Route Indicator for HT Cable on the ground complete with masonry work. (Special item)
30
-
-
... More
Supply and fixing of Air termination rod of size 60 cm height which is mounted on 100mm x100mm GI plate on wall/floor with suitable insulator with necessary connection complete. (Special item)
21
-
-
... More
Supply and fixing of Safety Accessories to the HT Power Room and LT Power Room as per Electrical Inspectorate Norms. The items are given below
1. 2Mx1M Rubber Mat suitable for 11KV (10mm) installation confirming to IS (5Sets)- 2 Nos
2.First Aid Box complete with First Aid Medicines (2 Nos)
3.Shock Treatment Chart fixed in glass frame (3 Nos)
4.Fire Bucket (4 Nos) made out of 40x40x6 mm MS angle -2 Set 5.Hand Gloves 11KV Grade (4Nos)
6.Danger Board (HT-5 Nos& LT -5 Nos)
7.Fire Extinguisher Co2, 4.5Kg. confirming to TAC Norms (6 Nos) 8.Earth Discharge Rod (2 Sets) (Special item)
1
-
-
... More
Supply and Installation of 5.10 feet (L) x 3.10 feet(H) x 1.2 feet(B) 16 SWG MS sheet powder coated indoor feeder box with 4 run of 25mm x 3mm for Phase and neutral copper flat busbar arrangements with provision of 1 No of 250A FP MCCB (36KA braking capacity) with thermal magnetic release setting as incoming , 2 Nos of 160A TP MCCB and 2 No of 100A TP MCCB and 2 No.of 63A TP MCCB (36KA Breaking Capacity make ) with Thermal magnetic release and Adjustable overloaded setting as outgoing on a suitable angle iron frame with suitable CT Coil and Multifunction meter (Voltage, Ammeter/ Frequency) (Elmesure make & Model: OM1300 ACC.05) necessary Concreting and masonry works complete. (Special item)
1
-
-
... More
Supply and fixing of 6 way Vertical TPN MCCB double door Distribution Board with 160A 18KA MCCB( C&S Make and CAT No.CSA3C4P ) as incoming and 2 Nos.100A TP MCB isolator, 2 Nos of 63A TP MCB isolator and Nos of 32A TP MCB isolator as outgoing in flush with wall and making good of the concealed portion with earth connection. The MCCBDB and MCB's should be with the ISI mark (Make:Legrand (MDS) / Hager (L&T) / Equivalent). (SD.No.Ref.179)
2
-
-
... More
Supply and run of 4 of 10sq.mm (140/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth connection of 1.5sq.mm copper wire with painting of suitable color. (SD.No.62)
108
-
-
... More
Supply And clamping of 3½ x 300sq.mm aluminium armoured LTUG Cable on wall of on postwith MS clamps. (SD.No.231)
100
-
-
... More
Fabrication, supply and erection of double pole structure comprising of 2 Nos. 200mm x100 mm RSJ (11 m length ) poles with PCC (1:3:6) for bedding size of (H:0.15m xL:0.6m x B:0.6m) and mass concrete above bedding size of (H:1.8m xL:0.6m x B:0.6m) and coping PCC (1:3:6) of size (H:0.5m xL:0.6m x B:0.6m) with hand fixing of 7 Nos. of 100 x 50 MS channel (3.35 m length ) with suitable MS clamp sets on RSJ poles including the charges of RSJ pole holes provision, hardware materials with earthwork for pole erection. Supply and fixing of 3 Nos. 11 KV strain disc insulator complete set, 1 set of Gang operated 11 KV 400A horizontally operated pin insulator type AB switch complete with guide operating handle at 1.1 to 1.2m above ground level with 400 Amps fuse set, with lock arrangements on suitable double channel and angle iron cross arm with channel, 3 Nos.
1
-
-
... More
11 KV Lighting arrestor, 6 Nos.11 KV Pin Insulator set, 1 set 11 KV HG fuse and 2 SWG copper wire for jumper including RYB insulating materials, hardware materials, binding wire materials, 11 KV bimetallic clamp set, DangerNotice Board (2 Nos), Anti Clambing device-2 set and painting of one coat red oxide with two coat aluminium painting for AB switch, poles with other MS parts with earth connections complete arrangements for SS yard etc as per the direction of the Engineer In-Charge. (Special item)
-
-
-
... More
Obtaining Safety Certificate by Design, Preparation of Electrical Drawings for Additional and alteration of power room High Tension and Low Tension layout along with load calculation, drawings for site plan physical layout, schematic diagram, etc. drawings submitted to CEIG Office and got approval, preparation of completion report forwarding to CEIG Office, arranging inspection, getting defect reports from CEIG Office, preparation and forwarding of rectification report to the CEIG Office and certification including all connected works. (Special item)
1
-
-
Evaluation Notes How It Works ?
Potential Partner