Public Works Department Tender
Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Public Works Department - PWD Tender
Electrical Goods and Equipments
Electrical and Electronics
Eprocure
Opening Date23 Feb 2024
Closing Date28 Feb 2024
Tender Amount₹ 74,00,000
Costs
EMD
₹ 47,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PWD_429245_1Bid Award Id
ViewTender No
27(1)/SE/2023-24dt19.02.2024Tender Authority
Public Works Department ViewPurchaser Address
-Website
http://tntenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Wiring with 2 x 1.5 sq.mm. (22 / 0.3 ) PVC insulated single core unsheathed copper conductor cable of 1100V grade in suitable heavy gauge MS conduit pipe on wall and ceiling with MS accessories with MS switch Box and 5A FT switch with painting of suitable colour continuous earth wire connection of 14 SWG TC wire for light point / fan point (for electronic regulator)(5 points per coil) (Lift well)
6
-
-
... More
Supply and fixing of 1 no.6A two module 5 pin socket, 1 no. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End.
26
-
-
... More
Supply and run of 2 of 1.5 sq.mm. (22 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour.
80
-
-
... More
Supply and fixing of 5A 3 pin and 2 pin combined flush type wall socket with 5A flush type switch on suitable MS box.
6
-
-
... More
Supply and run of 2 of 1.5 sq.mm. (22 / 0.3) PVC insulated SC unsheathed copper conductor of 1100V grade in suitable gauge MS conduit pipe on wall and ceiling with continuous earth wire connection of 14 SWG TC wire with
painting of suitable colour.
30
-
-
... More
Supply and fixing of single box type 4'-20 W LED fitting (Higher End) with CRCA body complete with TW round blocks on wall or ceiling with 20 W LED tube with PVC unsheathed Copper leads from terminals to the fitting.
191
-
-
... More
Supply and fixing of 18W LED square type Recess Cum surface mounting fitting (Havells make Trim Clipon / Eq) of cool white output with integral driver and PVC unsheathed copper leads from terminals to the fitting with necessary connections complete.
19
-
-
... More
Supply and fixing of 24W LED square type Recess Cum surface mounting fitting (Havells make Trim Clipon / Eq) of cool white output with integral driver and PVC unsheathed copper leads from terminals to the fitting with necessary connections complete.
16
-
-
... More
Supply and fixing of 9W LED lamp (Havells / Eq) in existing BH point.
18
-
-
... More
Supply and fixing of WT bulk head fitting with guard suitable for 9W LED lamp (Havells /Eq) with lamp.
32
-
-
... More
Supply and fixing of 48W LED street light fitting with LED (Higher end) with 32mm dia. GI pipe (class B) with 1no.32 mm GI bend complete on the existing post/ on wall with PVC unsheathed copper leads with MS clamps and with painting.
9
-
-
... More
Supply and fixing of 1200mm (48") sweep AC ceiling fan High speed complete with 2 module 100W fan step regulator (Higher end) with 300mm down rod on the existing fan clamp.
90
-
-
... More
Supply and fixing of 300mm (12") sweep (light duty) AC exhaust fan complete without provision of hole in the wall.
13
-
-
... More
Supply and fixing of louvers shutters for 300 mm (12") sweep AC exhaust fan.
13
-
-
... More
Supply and fixing of 16"(400 mm) wall mounting fan (Orient Electric Wall-49) with remote with suitable clamps and necessary conections complete.
2
-
-
... More
Supply and fixing of 3nos.6A two module 5 pin socket, 3 nos. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. (Higher End)
22
-
-
... More
Supply and fixing of 1no. 6/16A two module socket, 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End.
1
-
-
... More
Supply and Run of 2 of 2.5 sq.mm. (36/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection of 14 SWG TC wire and making good of the concealed portion with suitable colour.
190
-
-
... More
Supply and fixing of 3nos.6A two module socket , 1 no. 6/16A two module socket , 3 nos. 6A one module switch, 1 no. 16A one module switch with module cover plate (plastic) on suitable module concealed Box (GI) in flush with wall with connections. Higher End.
96
-
-
... More
Supply and fixing of 20A DP plug and socket in sheet enclosure with 32A DP MCB in flush with wall with earth connection (For AC Plug)
13
-
-
... More
Supply and fixing of 32A DP MCB in sheet steel enclosure in flush with wall with earth connection. (The MCB and metal enclosure should be of Higher End)
7
-
-
... More
Supply and fixing of 8way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1no. 32A DP MCB switch as incoming and 6nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End
9
-
-
... More
Supply and run of 2 of 4sqmm (56/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable PVC rigid pipe concealed on wall and ceiling with continuous earth wire connection of 14SWG TC wire with painting of suitable colour.
1270
-
-
... More
Supply and fixing of 12way single pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1no. 32A DP MCB switch as incoming and 10nos. 6A to 32A SP MCB as outgoing in flush with wall with earth connection only. Higher End
2
-
-
... More
Supply and run of 2 of 6sqmm (84/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable PVC rigid pipe concealed on wall and ceiling with continuous earth wire connection of 14SWG TC wire with painting of suitable colour.
40
-
-
... More
Supply and fixing of 32A FP MCB in sheet steel enclosure in flush with wall with earth connection. (The MCB and metal enclosure should be of Higher End).
22
-
-
... More
Supply and run of 4 of 4sqmm (56/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14SWG TC wire and making good of the concealed portion with suitable colour.
375
-
-
... More
Supply and fixing of 63A FP MCB in sheet steel enclosure in flush with wall with earth connection. (The MCB and metal enclosure should be of Higher End). (Lift Machine Room)
1
-
-
... More
Supply and clamping of 3-1/2 x 35 sq.mm. PVC aluminium LTUG armoured cable on post or on wall with MS clamps. (Lift )
25
-
-
... More
Supply and fixing of 7 segment 6 way triple pole neutral MCB distribution board in sheet steel enclosure double door type with metal door with IP 42 protection with 63A 4 pole MCB as incoming and 3Nos 63A DP RCCB as sub incomer and 18Nos. 6 A to 32 A SP MCB as outgoing in flush with wall and making good of the concealed portion with earth connection. (The MCB DB and MCB's should be of Higher End)
8
-
-
... More
Supply and fixing of Vertical type 4 way triple pole neutral MCB distribution board in sheet steel enclosure double door type with metal door with IP 42 protection with 63A 4 pole MCB as incoming and 4Nos 32A TP MCB as outgoing in flush with wall and making good of the concealed portion with earth connection. (Higher End)
8
-
-
... More
Supply and run of 4 of 10 sqmm (140/0.3) PVC insulated SC unsheathed Cu.Conductor of 1100V Grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection of 14SWG TC wire and making good of the concealed portion with suitable colour.
320
-
-
... More
Supply and fixing of Vertical type 4 way triple pole neutral MCB distribution board in sheet steel enclosure double door type with metal door with IP 42 protection with 100A 4 pole MCB as incoming and 3Nos 63A TP MCB & 3Nos 6A to 32A SP MCB as outgoing in flush with wall and making good of the concealed portion with earth connection. (Higher End)
3
-
-
... More
Supply and clamping of 3-1/2 x 50 sq.mm. PVC aluminium LTUG armoured cable on post or on wall with MS clamps.
40
-
-
... More
Supply and fixing of brass cable gland for 3-1/2 x 50 sq.mm. PVC armoured aluminium LTUG cable with earth connection.
6
-
-
... More
Supply and providing cable end termination of 3-1/2 x 50 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
6
-
-
... More
Supply and fixing of Vertical type 8 way triple pole neutral MCCB distribution board in sheet steel enclosure double door type with metal door with IP 43 - IK 09 protection with 125A 4 pole MCCB as incoming and 8Nos 63A TP MCB as outgoing in flush with wall and making good of the concealed portion with earth connection. (The MCCB DB and MCB's should be of Higher End)
5
-
-
... More
Supply and clamping of 3-1/2 x 70 sq.mm. PVC aluminium LTUG armoured cable on post or on wall with MS clamps.
140
-
-
... More
Supply and fixing of brass cable gland for 3-1/2 x 70 sq.mm. PVC armoured aluminium LTUG cable with earth connection.
12
-
-
... More
Supply and providing cable end termination of 3-1/2 x 70 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc with electrical connection complete
12
-
-
... More
Supply, fabrication, erection and comissioning of 315A capacity dust and vermin proof cubical panel board size of 4' X 1' X 4' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with 1 1/4" x 1/4" tinned cu. Flat for 3 phase, 1 " x 1/4" tinned cu flat for neutral, 1" x 1/8" tinned cu flat for earth connections with bus bar insulators. The following tinned Cu flat should be used for interconnection between busbar and switches: 1 1/4" x 1/4" tinned cu. Flat for interconnection of 1No 315A incoming switch to bus bar, 1" x 1/4" tinned cu. Flat for interconnection of 2Nos 200A Outgoing switches to bus bar and 1" x 1/8" tinned cu. Flat for interconnection of 2Nos 100A Outgoing switches to bus bar
1
-
-
... More
A separate chamber on top of one side should be provided with multi function meter to display Line & Phase Voltage, Phase Current, Power Factor and Frequency with one set of LED pilot lamp, fuse holder with suitable HRC fuse for each phase with suitable CT coil arrangements. The panel should be fabricated as per relevant IE rules & CEIG specification for accommodation of 5Nos 3 phase switches and supply & fixing of the following switches. 1. 315 A TPN switch disconnector fuse units interior only with HRC fuses double break - 1No
2. 100A TPN switch disconnector fuse units interior only with HRC fuses double break - 2Nos 3. 200A TPN switch disconnector fuse units interior only with HRC fuses double break - 2Nos
-
-
-
... More
In each cubical switch, live portion of bus bar should be shrouded by 6mm thick hylum sheet separators, and properly earthed by tinned solid copper flat as I.E rules CEIG sepecifications.The earth bus with two runs of 1" x 1/8" tinned copper flat must be run all round the panel to provide double earth connection. The panel should be painted with two high quality enamel paint over one coat of red oxide primer, the cable size, capacity of switch, location etc., should be marked with white paint and 1No metallic danger board affixed complete with mounting on suitable base channel iron frame work support complete. (The TPN switches should be L&T / Siemens make only)
-
-
-
... More
Supply and fixing of 315A TPN switch disconnector fuse units in sheet steel enclosure with HRC fuses double break on suitable angle iron frame work with MS cable entry boxes with earth connection only.
1
-
-
... More
Supply and clamping of 3-1/2 x 240 sq.mm. PVC aluminium LTUG armoured cable on post or on wall with MS clamps.
50
-
-
... More
Supply and fixing of brass cable gland for 3-1/2 x 240 sq.mm. PVC armoured LTUG cable with earth connection.
4
-
-
... More
Supply and providing cable end termination of 3 1/2 x 240 sqmm PVC LTUG Aluminium armoured cable withnecessary aluminium cable sockets by crimping etc. with electrical connection comple)
4
-
-
... More
Supply and Erection of 10kVA Online UPS suitable for 3phase AC input & 1phase AC output Digital pure sine wave (Luminous make /Eq) to provide minimum 1 hour battery backup using suitable batteries of SMF type with MS rack with 24 months warranty including erection and transportation charges.
1
-
-
... More
Supply and Erection of 15kVA Online UPS suitable for 3phase AC input & 1phase AC output Digital pure sine wave (Luminous make /Eq) to provide minimum 1 hour battery backup using suitable batteries of SMF type with MS rack with 24 months warranty including erection and transportation charges.
1
-
-
... More
Suppply and installation of 400A Sandwich type Silver Flashed, Bimetal Copper Contact, Aluminum busway (3L+N+PE), with Original Mylar insulation from DuPont, 100% N, 40kA for 1 sec, 50% Integral Earth, Dual Housing (1.6mm thick Aluminum + 1.6mm thick Electro-galvanized steel), Paint: Epoxy electrostatic powder finish Color: ANSI 49 gray,Temp rise: 55 deg. over ambient of 40 deg. Rated insulation & operating voltage = 1000V
-
-
-
... More
400A Straight Riser Length-IP 54 (L&T/Eq)
30
-
-
... More
400A Flange end (L&T/Eq)
2
-
-
... More
125A 4P Tap off box with MCCB (L&T/Eq)
5
-
-
... More
100A 4P Tap off box with MCCB (L&T/Eq)
3
-
-
... More
End Cover (L&T/Eq)
2
-
-
... More
Spring Hanger (L&T/Eq)
10
-
-
... More
Supply & Erection of End Feed Enclosure with 4P 400A, 50KA MCCB with Aluminium Bus Bar Interconnection and Accessories. (L&T/Eq)
2
-
-
... More
Supply, Fabrication and fixing of MS structural supports for Rising Main and as required comprising of channels, angles on coat of red oxide and two coats of synthetic paint. Complete set.
250
-
-
... More
Supply & Erection of 2 Run-25 x 6 mm Alu. External Earth Strip
30
-
-
... More
Supply and clamping of 3-1/2 x 150 sq.mm. PVC aluminium LTUG armoured cable on post or on wall with MS clamps.
20
-
-
... More
Supply and fixing of brass cable gland for 3-1/2 x 150 sq.mm. PVC armoured aluminium LTUG cable with earth connection.
6
-
-
... More
Supply and providing cable end termination of 3-1/2 x 150 sq.mm. PVC LTUG aluminium armoured cable with necessary aluminium cable sockets by crimping etc., with electrical connection complete.
6
-
-
... More
Supply, Erection, Testing, Commissioning & Handing over of 125kVA Diesel Generator set, 0.8PF, Three phase, 415 Volts, 50 c/s, 1500 RPM CPCB approved canopy compressing of Engine 154 BHP / Suitable BHP, 4 Cylinder of liquid cooled clockwise rotating, feed pump with 100 KW / 125 KVA operating capacity brush less alternator close coupled underneath fuel tank standard, safeties LOP with stop solenoid, battery with lead, Electric start and vibration fitting & accessories as detailed below including transportation & unloading charges
1
-
-
... More
A. Engine : water cooled diesel engine, Cylinder - 4, suitable for generating application with a Engine Rated output of 158HP as per ISO 8528- part 1 at 1500 RPM under NTP condition. The Engine shall comprise the following standard scope of supply:
(Make Kirloskar green / Cummins / Eq)
1) Dry type Air cleaner
2) Expansion bellow
3) Radiator with pusher type fan and mounting 4) Lube oil cooler
6) Full flow Lube oil filter
7) Fuel filter (pre and Micro)
8) In-line Mono-block fuel injection pump 9) Electronic governor
10) Battery charging alternator
11)12V Volt electric starter motor
14) Fly wheel with Starter ring and bell housing suitable for close coupling.
-
-
-
... More
SAFETY SYSTEM OF ENGINE: The Engine shall trip for the following conditions with visual alarm device
1) Low lubricating Oil pressure
2) High Water temperature
3) Vee- belt failure and over speed
The following visual indicator should also be provide Low Battery Indication
-
-
-
... More
B.12V / 24 Volt Electronic Starting Equipment : Complete with starter motor, dynamo, standard batteries 25 plate / 180 AH with 120 sqmm cable, flexible exhaust piping of 50cms length.
-
-
-
... More
C. Engine instrument panel mounted: Starting push button / starting key, lubricating oil temporature gauge, lubricating oil pressure gauge, safety control for over speed, hour meter ( mechanical ) and RPM indicator, battery charging ammeter. The engine should be capable of providing 10% over load for one hour an every 11 hours continuous at full load.
-
-
-
... More
D. ALTERNATOR: 125 KVA / 100 KW capacity of brush less alternator AC three phase 415 Volts, 50 Hz, 0.80 PF 4 wire self excited, self regulated design to run at 1500 RPM under NTP conditions confirming to IS 4722 BS EN 60034-1 to be coupled directly to the diesel engine and test certificate. (Make : Stamford / Kirloskar)
-
-
-
... More
E. BASE FRAME: The base frame should be fabricated MS channel frame of rigidly welded construction for mounting the generator set. The engine and alternator should be coupled by suitable designed diaphram type flexible coupling with guard and mounted on the base frame with proper alignment. The supply of generator set including loading, unloading and transporation charges.
-
-
-
... More
F. AMF CONTROL PANEL: (CUBICAL ) The AMF control panel ( Cubicle ) should be fabricated with vermin proof and dust proof of best quality sheet steel and floor mounted with removable rear panels and hinged front door with enamel painted and incorporating the following with suitable provision for connecting incoming and outgoing leads have been made on the control. (1)Micro processor based KG943(L1) Controller mounted are fixed in power panel.
(2) DC Ammeter (Make:AE/Meco/IMP/Equivalent)
(3) Stop Push Button, Red Mush room Head
(Make:Teknic/Esbee/Kaycee/Equivalent)
with 1NO+1NC,10A,230V
(4) Battery Charger 12VDC (Make:Cotmac/NHP/Equivalent) Note: This will be in addition to the battery charging alternator fitted to the Engine (5) Control Terminals 4.0 Sqmm -36 Nos (Make:Elmex/Phonix/Connectwell/Equivalent)
(6) NO Elements 6A -2 Nos (Make:Teknic/Esbee/Equivalent) (7) Speed POT 5K,ohm,3W (Make:Pankaj/Potel/Equivalent)
-
-
-
... More
(8) Plug in type relays with base 12v DC, 1C/o -7Nos (Make:OEN/PLA/Equivalent)
(9)Relays with Base 230VAC,5A (Make: OEN/PLA/Equivalent) (10) MCB/Fuse 1pole,32A,B-curve,10KA/32A (Make:Schneider/ABB/legrand/Equivalent) (11) Hooter, Electronic Solid state12V DC (Make:Mimic/Acme/Hella/Equivalent)
(12) ECD card ESD5200 series/Equivalent (Make: CGL/Kirlosker/Cummins/Equivalent)
-
-
-
... More
(13) Control cables 1.5/2.5/4.0 sqmm Cu. Multistranded -1 set
(Make: Finolex/RR/Polycab/Equivalent) (14) GCU connectors 2way,4way and 24 way with mate in lock – 1set
(make:Molex/Minifit/Equivalent)
(15) Mating plugs -1 set
(Make: AMP/TPK/TYCO/Equivalent)
(16) Current transformer – 3 Nos
(Make: Kappa/AE/IMP/AMOL/Equivalent)
(17) HRC fuse Base HB 400 and fuse link HN 200A – 6 Nos (Make:L&T/C&S/Siemens/ABB/Equivalent)
(18) Earth fault relay of suitable capacity with display in AMF panel
(Make:OEN/PLA/Equivalent)
(19) Power contactor 4P AC duty with wide band coil, 2NO+2NC auxillary contacts-2Nos (Make:L&T/C&S/GE/Schnieder/Equivalent)
-
-
-
... More
(20) BUSBARS-1 set
For Phase:25x10mm Aluminium or copper Equivalent
For Neutral: 25x6mm Aluminium or copper Equivalent
For Earth: 25x3mm Aluminium or copper Equivalent
-
-
-
... More
Note : 1. The control panel should be complete with necessary fuses, cables, labels other accessories with neutral isolation arrangements.
-
-
-
... More
2.The engine should trip for the following conditions with Audio and Visual annuniciation a. Low lubricating Oil pressure b. High water/coolant temperature c. Engine Over speed d. Low fuel level e. Engine under speed f. Low water/coolant level in radiator g. Under voltage h. Over voltage i. Under frequency j. over frequency
-
-
-
... More
3. The controller has data logging facility for 50 faults recorded &option for RS232/RS485 for remote monitoring /BMS Integeration.
-
-
-
... More
G. Fuel Tank - 290 liters:Removable fuel tank shall be fabricated out of 14SWG CRCA MS sheet and is part of base frame. It is duly painted and fitted with inlet and outlet connections and mechanical fuel gauge and drain plug and suitable fuel lines within acoustic enclosure. Fuel tank should be easily be accessible for cleaning or any maintenance.
-
-
-
... More
H. ACOUSTIC ENCLOSURE: Supply of the Acoustic Enclosure suitable for 125 KVA Diesel Generator set. The Acoustic enclosure shall be of nut bolt type construction with the provision to assemble and dismantle easily and designed to sult all weather conditions. The construction details / specifications of
-
-
-
... More
ACOUSTIC MODULES Outer Body 16 SWG CRCA sheet stee l.Door : 2mm thick CRCA sheet. Inner surface : 0.8mm thick GI perforated sheet. Perforation area should be 2/ 3 of total area.Insulation : 100mm thick fire retardant Rock wool / Equivalent mineral wool ( Density 80 / 100 kg / m3 ) or as approved by competent authority to suit CPCB norms. SKELETON STRUCTURE. Channels : Should not be less than ISMC 75 and ISMC 100.
-
-
-
... More
Cleats : Should not be less than angle 40x 6mm and 50x6mm.The sheet metal component shall be pretreated by seven tank process. (Decreasing tank, Water rinsing acid pickling tank, Water rinsing tank, Phophate tank and possivation tank and power coating spray painting using electrostratic method. )The joints should be designed in such a way that the airborne noises are prevented.For larger panels, special care should be taken to prevent deformation. Adequate ventilators should be provided that the generator performance is not affected and also that temperature inside is limited. The maximum permissible sound pressure level should be 75 dBA at 1 metre distance from the enclosure surface.The control panel is suitably designed to mounted inside the enclosure and enclosure door is provided with panel viewing window made from glass / acrylic and sealed with neoprene rubber gasket. The enclosure should be complete with
-
-
-
... More
A. Arrangement for power cable connection for supply to load.
-
-
-
... More
B. Residential exhaust silencer with flexible base arrangements.
-
-
-
... More
C. Suction louvers.
-
-
-
... More
D. Discharge louvers.
-
-
-
... More
E. Openable and lockable doors on both the sides ( two doors in each side with air tight Neoprene rubber gasket.)
-
-
-
... More
F. Interior lighting arrangement - 1 No lamp with ON / OFF switch.
-
-
-
... More
G. Lifting arrangements.
-
-
-
... More
The emergency stop and a suitable meter with display to indicate inside ambient temperature of the enclosure panel. The enclosure should be only polyprolyster based coated inside and outside. The enclosure provided shall be only approved by the engine manufacturer of the engine provided for Diesel Generator set, mounted inside and should be to the satisfaction of inspection / testing authority concerned. Filling of fuel and lubricants to run and test the genset at full load for 8Hours.
-
-
-
... More
Providing suitable concrete foundation with cement concrete 1 : 2: 4 with sand cushion all around the foundation erection of 125kVA Generator set over the existing foundation and erection of generator set with proper alignment over the existing foundation
1
-
-
... More
Supply and fixing of GI Hot Dip / powder coated 16 SWG cable Tray with 300mm width and 50mm height with suitable clamps and necessary connection complete.
70
-
-
... More
Supply and fixing of 65mm (2½") G.I. pipe (Class B) of 6 metre length with 300mm x 300mm x 6mm MS base plate duly welded at the bottom with concreting & masonry work for fixing the post (for cable tray)
4
-
-
... More
Supply and Run of 1 of No.8 SWG copper wire in suitable PVC rigid pipe on wall / floor / ground for earth connection
50
-
-
... More
Supply and run of 25mm x 3mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection.
50
-
-
... More
Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm, with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry.
10
-
-
... More
GST
1
-
-