Indian Institute Of Technology Tender

Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.

Indian Institute Of Technology - IIT Tender

Works
Electrical and Electronics
Eprocure
Opening Date18 Nov 2024
Closing Date11 Dec 2024
Tender Amount₹ 1,45,32,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
The floodlight shall be designed for operation in ambient temp -10°C to + 50°C with PF 0.95. Lifetime of 50K @L70. Product should be suitable for Operating voltage range - 100 - 300 V ac, continuous operation (6-8 Hrs. per day). The ingress protection should be minimum IP66 with an IK rating of 08.Optical compartments/external IP67 driver shall be maintenable/replaceable without impacting the LED Units.

-

-

-

... More
While accessing the gear compartment / external driver, the optical compartment should not be opened. The luminaire driver should have a 6KV onboard surge protection and an external 10KV/5KA SPD duly bolted in the luminaire for extra safety. The luminaire should be of Class B Serviceability. The wattage of each LED should be greater than 1 watt and less than 5 watt. Only high power single white LED chip with ceramic based suitable for outdoor use is allowed. Multi chip, array multi die, mid power, integrated arrays and COB's are not permitted. High power LED used in the luminaire should be SMD type only of make Lumileds, Bridgelux, Osram, Nichia and CREE & no other make. The luminaire should be capable of withstanding voltage stress of 440V for 8 Hrs., should have an auto shutdown @325V and have an auto recovery feature. The drivers should be a potted driver not a printed circuit board without casing, mounted inside the luminaire as per the enclosed specification.

72

-

-

... More
Supplying& Laying of following sizes PVC XLPE insulated alu/cu Conductor armored LTUG cable in a 50 mm to 100 mm dia HDPE DWC pipe in a trench of 50cm wide and 75cm depth including earth work excavation in all soils and sub soils and back filling, consolidated in a regular interval of 25cm thick rammed and complying with standard specification including cable route markers in every 50m span.

-

-

-

... More
3.5c X 300 sq.mm ( Alu)

400

-

-

... More
3.5c X 120 sqmm ( Alu)

1000

-

-

... More
Supplying and making end termination for following sizes alu/cu Conductor LT UG cable using suitable compression gland with required copper ferulles / socket and other jointing materials

-

-

-

... More
3.5c X 300 sq.mm ( Alu)

20

-

-

... More
3.5c X 120 sqmm ( Alu)

16

-

-

... More
Kiosk MV Panel

-

-

-

... More
Supply , Erection,Testing and commissioning of suitable size extendable floor mounting cubical type following Kiosk LT Main Panel board suitable for 415V 3ph 4 wire 50Hz AC supply system fabricated in a compartmentalized design from CRCA sheet steel of 2mm thick for frame works and cover with 3mm thick removable gland plate ,cleaning and finishing with 7 tank process for powder coating with siemens grey having extensible type copper busbar of suitable capacity as per the incomer ACB /MCCB/SDF ratings with DMC/SMC busbar suppotrs with short circuit withstand capacity of 31MVA / 1Second , bottom base channel of 100mmX 50mm X 5mm. .The In/Out going Cable entry should be from the rear side of the panel.

-

-

-

... More
2 separate run of 25 x 5 mm copper earth bus painted in green colour should be provided all along the panel and connected to the main grid. Interconnectios should be taken to metering chamber, MCCB's, ACB's, FSU's etc sothat all current carrying components are effectively earthed.

-

-

-

... More
PANEL-1 ( In Stadium)

-

-

-

... More
Incomer

-

-

-

... More
400A TPN MCCB 36kA with micro processor based trip units ,front operated rotary handle and with ON/OFF/TRIP indications- 2 Nos

-

-

-

... More
Outgoings

-

-

-

... More
250A TPN MCCB 36kA with micro processor based trip units ,front operated rotary handle and with ON/OFF/TRIP indications- 8 Nos

-

-

-

... More
630A Copper Busbars

-

-

-

... More
Three phase indication lamps with toggle switch-1set, microprocessor based digital multi function meter with communication port and the facility for active and reactive power measurements -1set with required CTs and control fuses etc should be provided for each incomers. Necessary Spreaders / extended copper bus bars of suitable rating with required holes should be provided for the cable and bus bar terminations.The handle should be pad lockable type in both ON/OFF positions.The work should be inclusive of providing mechanical interlocking arrangement between incomers ..Necessary drawing approval ( With QAP and GTP) should be obtaied from the Engineer incharge before fabrication.

1

-

-

... More
Panel- 2 ( At Sarayu SS)

-

-

-

... More
630A TP ACB 50 kA- 1 No (MDO independent manual spring closing mechanism-1no, microprocessor release for o/c , e/f and short circuit protection-1no, breaker ON/OFF/Trip indication Lamps) with CTs and multifunction meter. The size of the ACB is match with the existing panel and to be coupled with the existing MV Panel with supplying fixing of suitable rating of copper busbars

1

-

-

... More
Supply, Erection, Testing and Commissioning of copper plate earth by excavation of soil and sub soil , back filling with equal layers of salt and charcoal and the excavated soil , ramming, consolidating, Masonry construction, heavy duty cover slab etc. The GI pipe should be 25mm dia and 3mt long bolted with 600 x 600 x 3 mm thick copper plate at the bottom. 2R of 25 x 3 mm copper flats should be taken from the copper plate to the top of theGI pipe and clamping with suitable clamps

12

-

-

... More
Earthing the installation with the following sizes of earth wires. The rate shall be inclusive of spacer clamp for main earth flat suitable clamping with the MS flats for earth wires including crimping of socket etc.or laying below 0.5m from ground level including earth work excavation and refilling the excavated soil.

-

-

-

... More
25 x 6mm GI flat

250

-

-

... More
Annual Maintenance Contract for 5 consecutive year after warrantee

-

-

-

... More
Cost of comprehensive maintenance of installation other than LED fittings that includes routine, preventive & breakdown maintenance for period of five years including repair/replacement of worn out items with minimum downtime and warranttee & guarantee of repaired/replaced items after completion. (The amount quoted for this item will not be taken into account for deciding the lowest tender, but will be executed as a separate supplementary contract after the completion of the warantee period.

-

-

-

... More
1st year (Rate Only)

1

-

-

... More
2nd year (Rate Only)

1

-

-

... More
3rd year (Rate Only)

1

-

-

... More
4th year (Rate Only)

1

-

-

... More
5th year (Rate Only)

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.