Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Provn Of Single Living Officer Accn (capt) At Mil Stn Under Ge Sukna (fire Fighting And Alarm System in East Sikkim, Sikkim, with an estimated contract value of Rs. 7,00,000. The bid opening date for this tender is 07-11-2026 and the last date for bid submission is 28-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - Sikkim Tender
Opening Date7 Nov 2026
Closing Date28 Nov 2026
Tender Amount₹ 7,00,000
Costs
EMD
₹ 14,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Provn Of Single Living Officer Accn (capt) At Mil Stn Under Ge Sukna (fire Fighting And Alarm System
Contact
Tender Id
2026_MES_797878_1Tender No
CWE/136-WE/68 OF 2026-27Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply and fixing Two Nos Hose Pipe of 63 mm dia 15 Mtr long Re-inforced Rubber Lined (RRL), Synthetic fibre, circular woven jacketed, Hose tested to working pressure 12 kg/sq cm, burst pressure 36 kg/sq cm bursting pressure 32 Kg/Sq cm including Gun metal male and female instantaneous type coupling approved by the Dept complete in all respects. Hose shall conform to IS 636 Type II and coupling heavy quality conforming to IS 903-1985 with ISI certification all as specified and as directed.
5
-
-
... More
Supply and fixing Fire Hose Cabinet internal fabricated from 18 gauge MS Sheet of fully welded construction with hinged double front door with locking arrangement and partially glazed with 4 mm thick glass, stove enameled fire red finish out side and brilliant white inside yard with "Fire Hose" written on front suitable to house 2 x 15 Mtr two length of hose with couplings, conforming to IS 884 with branch pipe. One Fireman's axe, first aid fire hose reel and hydrant outlet. Size of cabinet 800 x 600 x 250 mm (HxBxD) all as specified and as directed.
5
-
-
... More
Providing and fixing standard short size Gun metal branch pipe with gun metal nozzie 16 mm dia outlet with standard male instantaneous spring lock type 63 mm die coupling. Branch pipe and nozzle shall confirm to IS 903-1985 all as specified and as directed.
5
-
-
... More
Supply and fixing Gun metal collecting head with 100 mm dia, 2.0 Mtr high instantaneous type inlet and flanged outlet with built-in check valve for fire brigade connection to extended down comers including necessary supports complete in all respects as per standard design..
1
-
-
... More
Supply and fixing single acting Air-cushion Tank of 200 mm with 25 mm Gun metal Stop valve, Air- release valve complete as required all as specified and as directed.
1
-
-
... More
Supply and fixing hand operated butterfly valve of size 100 mm dia, class-1, conforming to type PN 1.6 of IS: 13095-1991 of pressure not less than 15 Kg / Sqcm complete with flanges, bolts, nuts, gasket etc as per specifications complete in all respect all as specified.
3
-
-
... More
Providing and fixing Cast Iron double flanged horizontal type gun metal seat non-return sluice valve of size 100 mm dia conforming to class-1 of IS: 5312, reflux swing check type with required flanges including nuts, bolts, 1.5 mm thick compressed asbestos gasket including painting complete.
2
-
-
... More
Supply, fixing and installation of Manual Call Point resettable type enclosed in the sturdy boxes and connected with the centrol panel installed at ground floor level for direct communication and effecting immediate response of fire service and other allied services, complete including all fixing arrangements as required at site The unit must be intelligent analogue addressable and can be connected on the same two core loop and loop powered. The device shall be equipped with the latest sate of the art microprocessor which shall hold the fire algorithms and the microprocessor shall have the intelligence to announce the alarm directly to the fire alarm control panel in case if the MCP is called for alarm ell as specified and as directed.
5
-
-
... More
Supply installation, testing and commissioning of fire terrace pump electric driven horizontal end suction, centrifugal type conforming to IS 12469:1988 with Cl casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continous operation with range of operation 0% to 150% of rated capacity for 440 Volt, three phase, 50 Hz, 30 Mtr head, 900 LPM discharge all as specified and as directed
1
-
-
... More
Supply and fixing Gun metal Fire brigade inlet connection (suction collecting head) consisting of Two nos 63mm dia instantaneous type male couplingas per IS 5131 with built in check valve and 150mm dia sluice valve (one no 150mm dia NRV), and 150mm dia flanged outlet complete with all accessories all as specified.
1
-
-
... More
Supply & fix MS cabinet (approx 750 mm x 600mm x 450 mm) to enci fire brigade inlet connections fabricated from 16 gauge sheet with full front glass door and locking arrangement painted and mounted on masonry platform complete.
1
-
-
... More
Materials and labour for Earthing complete with MS galvanized earth Plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with 32x6 mm galvanized iron strip by means of nuts. bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point including providing funnel land watering pipe 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC(1:2:4) cover slab (re inforced with 8mm dia TMT bar @ 15 cm C/C hothways and suitable handle made of 10mm dia) including necessary earth work, excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-1(2009) complete including test point and testing on completion all as specified.
3
-
-
... More
Supply, laying, jointing & testing LT XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade ISI marked with stranded aluminium conductor of size 16 Sq mm 4 core fixed to wall or laid in floor through and including Gl pipe/ PVC Pipe etc for connection between ground floor control panel to Terrace Pump at Terrace complete all as specified & as directed.
20
-
-
... More
Supply and fixing PVC insulated heavy duty copper conductor 2.5 Sqmm 2 Core, working voltage 1100 volts conforming to IS: 1554 part -1, drawn through ERW steel conduit for Fire Alarm System.
Note: Steel conduit with conduit accessories shall be measured & paid separately).
200
-
-
... More
Supply and fixing XLPE insulated heavy duty FRLS copper ammoured conductor 2.5 Sqmm 6 Core, with working voltage 1100 volts conforming to IS: 1554 part -1, all as specified and as directed. (From Control panel to Jockey pump)
20
-
-
... More
Supply and fixing for rigid ERW steel conduit 25 mm dia screwed & to be laid concealed inside walls / roofs / ceilings of Junction / Terminal Boxes but inclusiveof all fittings such as bends, elbows, reducers,bell mouth tube ends & ali fixing accessories such as couplers, lock nuts/saddles pipe hooks etc. complete.
140
-
-
... More
Supply and fixing for rigid ERW steel conduit 20 mm dia screwed & to be laid concealed inside walls / roofs / ceilings of Junction / Terminal Boxes but inclusiveof all fittings such as bends, elbows, reducers, bell mouth tube ends & all fixing accessories such as couplers, lock nuts/saddles pipe hooks etc. complete.
40
-
-
... More
Supply, installing, testing and commissioning of analogue addressable Fire Alarm Control panel with 48 hrs battery back up complying with BS EN 54 Single loop panel of capacity from 99 / detectors & 99 modules upto 200 detector and modules including battery and battery charger etc. The panel shall consisting with 80 character LCD display and RS 485 for networking all as specified and as directed.
1
-
-
... More
Fire Alarm Sounders / Sirens Electronic type horizontal single stage Each continous normal operation for atleast 50 minutes with sound level 65 D3 to 120 DB measured at 1.5 Mtr with sound output variation of + 5 DB, 1000 m range complete all as specified.
1
-
-
... More
Supplying, installing, testing and commissioning of Analogue Addressable Electronic Hooter cum Strobe (loop powered) all as specified and as directed.
5
-
-
... More
Supply & fixing pressure gauge 100 mm dia with ball valve of pressure 25 Kg/ Sqcm necessary fittings, connections and supports testing and commissioning as specified and as directed.
2
-
-
... More
Supply & fixing pressure switch adjustable type, suitable for fire fighting system, ecessary fittings, connections and supports testing and commissioning as specified and as directed.
1
-
-
... More
Supply, install, testing and commissioning of indoor cubical type LT Control Board, factory fabricated CPRI type tested with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-43 & general construction confirming to IS-13947, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the incoming MCCB rating. The panel board shall be fabricated out of 2.0 mm thick CRCA sheet duly pre-treated & powder coated, supporting frame made out of 50 x 50 x 6 mm angle iron suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl PCC platform/plinth of suitable size complete all as specified & as directed with & incl the following accessories.
BUS-BAR & INTERNAL CONNECTIONS:
The bus-bars shall be made up of 04 Nos tinned copper 150 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all intemal connections form main bus-bars to switch gears etc.
PROVISION FOR CABLE ENTRY :
The provision for cable entry/exit shall be provided in the bottom for both incomming & out-going cables.
1
-
-
... More
INCOMING
(i) MCCB FP, 80 Amps rating, Ics=100%lcu, 16 KA breaking capacity, adjustable thermal magnetic release - 01 No
OUTGOING/INSTRUMENTATION SYSTEM:
(i) MCCB FP, 63 Amps rating, Ics=100%lcu, 16 KA breaking capacity, adjustable thermal magnetic release - 01 No
(ii) MCCB FP, 32 Amps rating, Ics=100%lcu, 15 kA breaking capacity adjustable thermal magnetic release - 01 No.
(iii) SPN 10 Amps, 10 kA-01 No
(iv) Fully Automatic Panel mounted open execution star-delta starter suitable for 10 HP induction motor for Terrace Pump 415 volts, including overload relay, auto timer & single phase preventer etc complete -01 No
(v) Auto Control System for Start/Stop of Terrace Pump controlled through pressure switch (paid separately) and other switching control from Fire Control Panel with necessary microproceesor controlled relay etc - 01 Set
(vi) Digital voltmeter with inbuilt selector switch, 3 phase, Accuracy Class- 1.0, Flush mounting 96 x 96 mm, Input voltage mesurement range 50-520 Volts AC (P-PO-01 No.
(vii) Digital Ammeter with inbuilt selector switch and CT coil with suitable ratio, 3 phase, Accuracy Class - 1.0, Flush mounting 96 x 96 mm, 4 digit for 0-80 Amps - 01 No.
(viii) Indicator lamp with LED (Red, Yellow & Blue), Set of Three -01 Set.
-
-
-
... More
Note:-(i) Design/ drawing of the Panel Board showing the dimensions shall be obtained from manufacturer/ Supplier & shall be got approved from the Dept before placing final order to the manufacturer.
(ii) Anything missed out in the technical specification but technically required for efficient working is deemed to be included in the quoted rates.
-
-
-
... More
Note:- (i) The Complete Fire Fighting and Alram System and its automatic operation etc shall be accordance to the relevant IS/IEC/NBC/NFPA. The scheme shall be approved by the Dept befre excution of work.
(ii) Anything missed out above but technically required for efficient operation of Fire Fighting and Alarm system are deemed to be included in the quoted rates.
-
-
-
... More
Note 1:- (Applicable for all parts/items) : The bidders/contractors are advised to read tender document, all drawings & all corrigendum / amendments and general condition of contracts before entry / quoting the rates.
Note 2:-The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount.
-
-
-