Rajasthan State Road Development And Construction Corporation Limited Tender

If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.

Rajasthan State Road Development And Construction Corporation Limited - RSRDC Tender

Works
Civil And Construction
Building Construction
Electrical and Electronics
Electrical Works
Eprocure
Opening Date22 Aug 2024
Closing Date10 Sep 2024
Tender Amount₹ 9,25,00,000 
Notes
Download

Costs

  • EMD

    ₹ 18,50,000
  • Document Cost

    ₹ 5,900
  • Tender Fee

    ₹ 2,500

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Get the Best Price For TMT
Starting from
₹44,400/MT*
Rajasthan

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Add Extra for Laying of one number XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground including excavation of trench of size 120 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth

200

46600

233

... More
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
11 KV End Termination Kit Indoor type

-

-

-

... More
3 core 120/150/185 Sq.mm

12

70344

5862

... More
11 KV End Termination Kit Outdoor type

-

-

-

... More
3 core 120/150/185 Sq.mm

1

8063

8063

... More
11 KV Straight Through Joint Kit

-

-

-

... More
3 core 240/300 Sq.mm

2

28714

14357

... More
SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated 304 (Non-Ferrite Non-Magnetic Grade) stainless steel enclosure of thickness 2.5mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for gas tank. Vacum Interrupter of VCB should be RMU Manufacturer’s own make. Each feeder of RMU should have voltage presence indicator. . and compring of followings:- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder. - 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.- 1 No. Manometer for each tank,- 1 nos. Fault Passage indicator,-Right angle boots for all the feeder Modules All the type test certificates as per IEC from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR

-

-

-

... More
Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch

1

465880

465880

... More
SITC of HT metering cubical panel as approved By DISCOMs fabricated out of 18 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX 6mm having provision for Following: (i)Provision for fixing Trivector / Import - Export Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set with Copper strip for Connection (To be supplied by DISCOMs), (iii)Test terminal Block, (iv) 6mm thick Bakelite sheet on all sides, (V) 3/6 corex 1.5 / 2.5 Sq.mm copper cable for interconnections, etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

1

32051

32051

... More
SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-

-

-

-

... More
(a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided

-

-

-

... More
(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.

-

-

-

... More
[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )

-

-

-

... More
(d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.

-

-

-

... More
(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.

-

-

-

... More
(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )

-

-

-

... More
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.

-

-

-

... More
(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

70

418250

5975

... More
Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Electrolytic grade Aluminium bus bar 6010 grade

160

86720

542

... More
Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS

4

13008

3252

... More
Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Ring type tape wound CT

-

-

-

... More
C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA

90

70920

788

... More
C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA

6

5514

919

... More
Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Red/yellow/Green colour

70

11900

170

... More
Blue / white Colour

26

6760

260

... More
SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
4 pole MCCB With Thermal Magnetic release

-

-

-

... More
up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,

31

220472

7112

... More
125 Amp , 25 kA, adjustable O/L & adjustable S/C setting,

2

16782

8391

... More
160 Amp , 25 kA, adjustable O/L & adjustable S/C setting,

56

662760

11835

... More
250 Amp , 35 kA, adjustable O/L & adjustable S/C setting,

1

19792

19792

... More
630 Amp , 50 kA, adjustable O/L & adjustable S/C setting,

4

138052

34513

... More
4 pole MCCB With Microprocessor based release with adjustable O/L & S/C setting with Inbuilt Instantaneous and Ground fault Protection.

-

-

-

... More
400 Amp , 50 kA

1

40781

40781

... More
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
4 x 6.0 sq.mm

80

22080

276

... More
4 x 10.0 sq.mm

80

42480

531

... More
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Single pole MCB (With B/C curve tripping Characteristics)

-

-

-

... More
0.5 A to 5 A rating

114

33744

296

... More
Double pole MCB(With B/C curve tripping Characteristics)

-

-

-

... More
6 A to 32 A rating

12

6792

566

... More
Triple pole MCB (With B/C curve trippingCharacteristics)

-

-

-

... More
40 A rating

84

116256

1384

... More
50/63 A rating

12

16608

1384

... More
Four pole MCB (With B/C curve tripping Characteristics)

-

-

-

... More
40 A rating

96

166882

1738.36

... More
50/63 A rating

108

188460

1745

... More
Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB as outgoing ,made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only ) complete with insulated 160 (upto 160 A Incomer) / 250 Amp.  copper bus bar, neutral bars with shrouds,  earth bar , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, ferrules,  detachable gland plate, including making connections, testing etc. as required.  OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Double door IP-43 & IK-09 with Provision of Incomer MCCB 100/ 125 A Rating with Metal end box

-

-

-

... More
6 Way

14

178514

12751

... More
Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A Rating with Metal end box

-

-

-

... More
6 Way

1

15274

15274

... More
Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specification for electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating. Appropriate type test certificate / OEM test report shall be submitted . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Open execution type 

-

-

-

... More
125 A

14

100086

7149

... More
160 A

14

122500

8750

... More
Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Extended Rotary Handle

25

67825

2713

... More
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity 99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
6.0 Sq. mm

-

-

-

... More
4 core

400

66400

166

... More
10.0 Sq. mm

-

-

-

... More
4 core

400

76800

192

... More
16.0 Sq. mm

-

-

-

... More
4 core

400

92800

232

... More
35.0 Sq. mm

-

-

-

... More
3.5 core

100

34700

347

... More
70.0 Sq. mm

-

-

-

... More
3.5 core

300

183000

610

... More
95.0 Sq. mm

-

-

-

... More
3.5 core

300

229500

765

... More
185.0 Sq. mm

-

-

-

... More
3.5 core

200

283000

1415

... More
240.0 Sq. mm

-

-

-

... More
3.5 core

400

693200

1733

... More
300.0 Sq. mm

-

-

-

... More
3.5 core

600

1267200

2112

... More
400.0 Sq. mm

-

-

-

... More
3.5 core

120

324720

2706

... More
Add extra in item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.

400

45600

114

... More
Add Extra for Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points :- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth

400

50800

127

... More
Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same

400

5600

14

... More
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
3.5 x 35.0 sq.mm

24

6192

258

... More
3.5 x 70.0 sq.mm

120

45840

382

... More
3.5 x 95.0 sq.mm

14

8414

601

... More
3.5 x 185.0 sq.mm

4

4288

1072

... More
3.5 x 240.0 sq.mm

24

28176

1174

... More
3.5 x 300.0 sq.mm

16

23056

1441

... More
3.5 x 400.0 sq.mm

4

8280

2070

... More
4 x 6.0 sq.mm

20

3440

172

... More
4 x 10.0 sq.mm

24

4440

185

... More
4 x 16.0 sq.mm

36

6804

189

... More
P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
50 mm

250

21250

85

... More
110 mm

150

33900

226

... More
160 mm

220

80520

366

... More
200 mm Dia.

220

108680

494

... More
SITC of following capacity IK10 Sandwich Type Rising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6 standard & IS 8623 P-II and Manufactured in India for use on 3 phase 4 wire , 50% internal earth , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 4 as per IS1892, with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminium (with 6101 or 63401 grade) bus bars, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonary and repairing the same etc. as required. Type Tests reports like (i) Short Circuit Test (ii) Degree of Protection (iii) Temperature rise test of Rising main in CPRI / UL / ASTA accrediated lab will be submitted by OEM.

-

-

-

... More
Routine test as per OEM's QAP in It's own Manufacturing facility in India shall be witnessed by department Engineer virtually / Physically. Complete Installation of Rising Mains shall be Vetted by Manufacturer before Comissioning. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Sandwich Type Bus Rising Main

-

-

-

... More
630 amps 40 KA SC for 1 sec

100

2114200

21142

... More
Sandwich Type Bus Duct

-

-

-

... More
1600 Amps 80kA SC for 1 sec

16

476512

29782

... More
Out Door Bus Duct IP66 with Canopy

-

-

-

... More
1600 Amps 80kA SC for 1 sec

10

352110

35211

... More
SITC of Bus Rising Main OEM manufactured following capacity End Feed Unit Confirming to ANSI C37.23 standard & IS 8623 P-II suitable for Sandwich / Compact Air Insulated type for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB/ACB (but without MCCB/ACB), Interlocking feature complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
For 630 Amp. (Without MCCB)

4

90964

22741

... More
SITC of Bus Rising Main OEM manufactured following capacity Plug in / Tap off Box suitable for Sandwich / Compact Air Insulated type bus bar trunking Confirming to ANSI C37.23 standard & IS 8623 P-II & IEC-60947-2-2000 for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCB/MCCB / ACB (but without MCB/MCCB/ACB) with Interlocking complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Plug in Box suitable for Sandwich Type Bus rising Main

-

-

-

... More
160/200/250 amps (Suitable for MCCB) without MCCB

56

651504

11634

... More
SITC of Bus Rising Main OEM manufactured Tinned copper flexible joint with enclosure of following capacity with Transformer / DG / Panel as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1600 Amp.

4

341252

85313

... More
Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-

-

-

-

... More
(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole

-

-

-

... More
(b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts

-

-

-

... More
© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt

-

-

-

... More
(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm.

-

-

-

... More
(d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.

-

-

-

... More
(e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
17.2 mm thick and 3 Mtr. Long

24

168240

7010

... More
Plate Earthing as per IS:3043 with copper Earth plate of purity 95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

8

121152

15144

... More
Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25mm x 3mm G.I. ( Hot Dipped ) Strip

100

10500

105

... More
50mm x 6mm copper strip

50

206000

4120

... More
32mm x6mm G.I. ( Hot Dipped ) Strip

80

19600

245

... More
50mm x 6mm G.I. ( Hot Dipped ) Strip

80

32480

406

... More
Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity 95% thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
8 SWG G.I. ( Hot Dipped ) Wire

994.65

19893

20

... More
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

900

121500

135

... More
Providing and laying Non Pressure NP-3 class R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. (Excavation of Earth & Back filling with compaction is to be Paid Extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
300 mm dia

150

137550

917

... More
labour charges for Excavating trenches of required width for pipes dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr.:

-

-

-

... More
Ordinary Rocks

100

30500

305

... More
Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
150mm x 50mm x 1.6mm

50

33750

675

... More
300mm x 50mm x 1.6mm

50

52650

1053

... More
450mm x 50mm x 2.0mm

50

93800

1876

... More
Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy =125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @=300 V AC and Auto resetting Safety , Power Factor 0.95 driver Efficiency 85% ,THD(I) 10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current 750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI 70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
LED Street Light fixture with Minimum lumen output 11225 lm

16

108240

6765

... More
Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Poles with Octagonal Cross Section

-

-

-

... More
7 Mtr.

16

210432

13152

... More
Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Single arm overhang

16

30224

1889

... More
Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles, High mast Poles as per Drawing attach at Table P-4 with Following Procedure & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
A) Excavation of Pit for Foundation Size upto required depth from Ground level

-

-

-

... More
B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete.

-

-

-

... More
C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness

-

-

-

... More
D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete.

-

-

-

... More
E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal

-

-

-

... More
F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations.

-

-

-

... More
G) Providing and Laying Reinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days.

-

-

-

... More
H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face.

-

-

-

... More
Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr.

16

127088

7943

... More
Providing & Fixing of IK08 IP65 protected Top/Bottom mounted LED Post top Luminarie made of single piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser and Aluminium anodised with sand blast reflector. The System level Luminous efficacy ≥ 100 Lumen/W. SMD LEDs is to be used, System CRI70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency 85%, PF0.9, THD10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . Driver current 750mA. Fixture must be in compliance with BIS Standards and Trade mark Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Minimum lumen output 4500 lm Post top Luminarie

3

24585

8195

... More
Supply installation testing & Commissioning of high mast lighting system (as per PLG 07 of ILP UK techinical report no 7 of ILE UK /IS:875 Part-1 – 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by piecewise single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement (winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19 costruction 3 no. rope for lantern carrage & 2 no. rope for winch assembly ) foundation bolt, torque limiter,EPR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135.etc. as required on Existing Foundation. ( See table P - 03 for specs.) OEM Must have Type test certificate for wind tunnel test . All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
20.0 Mtr Hm (in 2 section) suitable for 12 No. Luminaries

1

330476

330476

... More
Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated potted driver as a unique BIS R number having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate. The System level Luminaire efficacy =125 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @=300 V AC and Auto resetting Safety .Power Factor 0.95 , THD(I) 10% , driver current =750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min =4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI70 and CCT 5700K ±355K. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture shall be IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
High Power LED Flood Light Minimum lumen output 25000 lm

12

186996

15583

... More
Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
40 mm Dia.

10

9580

958

... More
Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler with hermetically sealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick) and tank (0.5 mm thick) , stainless steel water tray,minimum two nos Brass Chrome plated faucets and suitable drainage system complete in all respect with required height MS fabricated and Painted Angle iron frame ( Cost of frame to be paid Extra )complete in all respect of the following capacity. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs

6

455268

75878

... More
Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
11 KV, Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage 45 KV AC (rms)

30

61290

2043

... More
Providing & Fixing of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
One day & week reserve (digital type )

4

16400

4100

... More
P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
4.0 Sq.mm 3 core flat / Round

160

34240

214

... More
Providing & Fixing of BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan Conforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1200 mm Sweep BEE 1 Star rated (service value =4.0 to 4.5 )

537

1014930

1890

... More
Providing & Fixing of 400 mm Sweep BLDC technology Oscillating type Wall mounting / Pedestal type fans with Three speed, ON and OFF position, Double Wall bearing with front and back 120 or more ribs guard; Three no. blades, noise level should be = 75 dB, including fixing with anchor bolts, making connection testing etc. as required. ( With Remote ) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Wall mounting type with Service value 2.0 CMM /W, Min. Air Delivery 71 CMM

20

93980

4699

... More
Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
300 mm sweep(900/1400 RPM)

40

127000

3175

... More
Providing & Fixing of of ventilating fans Capacitor start, copper wounded, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
250 mm sweep

40

78280

1957

... More
Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
300 mm sweep

15

27330

1822

... More
P & F of Gravity Louver shutter of superior quality made out of frame of 18 swg M.S. sheet & Louvers made from 24 swg MS Sheet with enamel paint including cost of nuts, bolts, etc as reqd. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Up to 380 mm size

40

11480

287

... More
Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap action adjustable thermostat , Dual indicating lamps Injected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top with Portable Residual Current Device ( PRCD ) , including making inlet, outlet Flexible alloy connection, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25 Ltr.

10

115680

11568

... More
35 Ltr.

7

97790

13970

... More
Providing & Fixing of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD 10% , P. F.≥0.95, CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1170mm(+/-10%) LED batten with min. lumen output 2200 lm

348

171216

492

... More
Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / Sqaure SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency 85% . System Lumen efficacy of ≥ 110 lm / watt, THD 10 % , Pf.≥0.95, CRI 80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.

-

-

-

... More
OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Recessed Mounting

-

-

-

... More
Minimum lumen output 1300 lm

100

104600

1046

... More
Minimum lumen output 1950 lm

150

217650

1451

... More
Surface Mounting (with extruded alumn. Housing )

-

-

-

... More
Minimum lumen output 1950 lm

300

486000

1620

... More
Providing & Fixing of IP20, 2'x2' LED Surface/ Recessed mounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency 85% , with Short & Open circuit protection (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD 10 % , p.f.≥0.95,CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.

-

-

-

... More
OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Recessed Mounting

-

-

-

... More
Minimum lumen output 4200 lm

150

447600

2984

... More
Surface Moutning

-

-

-

... More
Minimum lumen output 4200 lm

150

496200

3308

... More
Providing & Fixing of IP20 SMD Mid Power LED batten with integrated box (min.1200mmx40mmx60mm including reflector) with replacable driver fixture made from Powder coated Extruded aluminium housing ,Min. lumen output 4400 lm, System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 4.0 KV with Short & Open circuit protection,THD 10% , P. F.≥0.95, CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.

-

-

-

... More
OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

200

324000

1620

... More
SITC of Indoor Type Floor mounted metal clad 11 KV, 630 Amps 3 phase, 50 Hz Vacuum Circuit Breaker (VCB) Panel Fabricated by System Integrator of VCB Manufacturer as per IEC 62271-1,100,200 Standard made from Powder painted pre-fabricated, CRCA sheet steel /High quality Aluminium-Zinc (Aluzinc) coated sheet steel. Fabrication shall be done through CNC turret press and CNC bending machine having a rupturing capacity of 500 MVA, 26.3 KA breaking capacity for 3 sec, Internal arc type tested for 26.3KA for 1 sec with AFLR clasification totally enclosed with Aluminium bus bar of 630 Amps for each phase, flush front, Horizontal isolation, Horizontal drawout type with Electrical and Mechanical interlock and automatic safety shutter gear including padlocking arrangement, isolation plugs, assambly of 3 vaccum interrupters (VCB manufacturer's own make) , with each pole individually encapsulated by epoxy insulations to make it dust proof and self - aligning finger type isolating contacts, truck having integral racking with necessary interlocks (for insertion and removing of VCB), manual and automatic motor charged independent closing/ tripping spring , trip free operating mechanism with closing and tripping push buttons and mechanical breaker.

-

-

-

... More
interconnected with HT sleeve bus bar of 630 Amps , Basic Insulation level (BIL) : 28KV (RMS) / 75KV (Peak) and Altiude less than 1000 meters, including all protection, indication, Operation, monitoring and control and accessories etc. as required. Factory Tests of VCB panel as per System Integrator's QAP in it's own Manufacturing facility shall be witnessed by department Engineer virtually / Physically. (Cost of RCC Foundation / Steel Structure to be paid Extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Incoming Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB operationg mechanism should be of M2 duty for minimum 10000 mechanical operation. - Closing & tripping coil of VCB should be of continious rating to achive minimal failure. - Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement) - VT Ratio: 11KV/1.732/110V/1.732/110V/1.732, -Core 1: 0.5, 20VA should be floor mounted and to be connected from the back side of the panel. - Numerical relay (should be VCB manufacturer's own make) having protections of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input , programable 6 Digital Output and programable 4 nos. LED at HMI. - Ammeter with Selectorswitch and Volt meter with Selector switch - Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA, KVAR, PF, KWH, KVARH, KVAH, A,V etc. - Trip circuit supervision relay (feature of numerical relay) - LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC) and 8/12 window Annunciator.

1

604949

604949

... More
Outgoing Panel comprising of following: - VCB 630 Amps . VI of VCB should be sealed for 30000 operation. VCB operationg mechanism should be of M2 duty for minimum 10000 mechanical operation. - Closing & tripping coil of VCB should be of continious rating to achive minimal failure. - Resin Cast type CT having Ratio : 400-200A/ 1-1 A, Core1: 5P20, 5 VA; Core 2: 0.5, 5 VA (How ever CT Ratio shall be decided as per load requirement) - Numerical relay (should be VCB manufacturer's own make) having protections of 50,51, 50N,51N,TCS. The relay shall have programable 4 digital Input , programable 6 Digital Output and programable 4 nos. LED at HMI. - Ammeter with Selectorswitch and Volt meter with Selector switch - Multifunction Meter of Acc Class 0.5, having facility to monitor KW, KVA, KVAR, PF, KWH, KVARH, KVAH, A,V etc. - Trip circuit supervision relay (feature of numerical relay) - LR, TNC switch, indication lamp - CB ON/OFF, spring charge, Auto trip, TCS healthy etc., Space heaters - Power Pack (230V AC- 110V DC)

2

1168178

584089

... More
Non BSR Item

-

-

-

... More
SITC of Radiator Cooled and Turbo charged Silent DG Set (As per latest CPCB - IV Emission norms) having specifications as per A, B, C, D, E, F,G,H & I

-

-

-

... More
A) 1500 RPM Diesel Engine conforming to BS:649/5514 of suitable BHP (up to 82.5 kVA 6 cylinder or Below required, 125 kVA & Above ratings 6 cylinder or above required ) capable of taking 10% over loading for one hour after 12 hours of continuous operation., Dry exhaust mainfold with Hospital grade silencer and catalytic convertor(isolated from main DG chamber), up to 3 M exhaust piping (with LRB insulation & Alum. cladding ) as required .

-

-

-

... More
B) AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS/IEC 60034-1. . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled

-

-

-

... More
C) CPCB / ARAI approved Standard canopy with Weatherproof, powdercoated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with sidewall fabricated from 1.6 mm CRCA sheet & filled with glasswool (96Kg/m3) / Foam. as per IS8183 the doors of 28/40/50/85mm thick as perrating and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/opening are sealed with neoprene /EPDNgaskets. The DG Set has Inbuilt / External in fuel tank to run 6 to 8 Hrs as per OEM standard, with protection and tripping of DG set against temperature of more than 50 degree centigrade.

-

-

-

... More
D) Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger, Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring like Running Hour, RPM, Low Lube Oil tripping & control system, Panel mounted MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :

-

-

-

... More
E) (i) Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (ii).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (iii)Accoustic glass wool wall thickness should not be less then 100mm for rating above 250 KVA.

-

-

-

... More
F) First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department.

-

-

-

... More
G) Servicing Contract of DG Set from OEM's Authorised Service Dealer as per OEM guidelines during the DLP period shall be done by contractor including all consumables, actual charges shall be reimbursed to the contractor by End User Department.

-

-

-

... More
H) Manufacturer / OEM must have its authorized service dealer in Rajasthan. Which can provide service within 6 Hours of compalint registration.

-

-

-

... More
I) DG set will be offered for Inspection and Testing at Manufacturer's Works in presence of Departmental Engineers. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
500 KVA at 0.8 pf 415V 50Hz 3-ǿ

2

11039490

5519745

... More
Non BSR

-

-

-

... More
Supply installation testing & Commissioning of Copper wound distribution Transformer With OLTC, RTCC & AVR Having Tapping Range +5% to -15% Tapping in Steps Of 1.25% of following rating and % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled losses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core design including standard accessories like conservator with prismatic oil level gauge , silica gel breather, Bucholz relay, pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box, LT cable box with Busbar connection for outgoing cables, , temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device, Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test in OEM's own lab shall be witnessed by Department engineer Physically.

-

-

-

... More
Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge. Approved Makes:- Uttam Bharat/Danish/Vardhman/RTS/United

-

-

-

... More
1000 KVA with % Impedance 5.0

2

6064904

3032452

... More
Non BSR MAIN LT Panel

-

-

-

... More
SITC of IP-42 and general construction confirming to IEC 61439-1&2. type tested assembly (TTA) wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g) as below:-

1

6913372

6913372

... More
(a) Panel having short circuit withstand capacity of minimum of 50 kA for 1s (Icw rating) at 415 V, 50 HZ AC supply, Rated Impulse withstand voltage (Uimp) of 12kV for withstanding against transient Overvoltages, mechanical impact level of IK10 level and internal arc for 50kA for 0.3 second with aluminum busbar and fully type tested at an Independent Laboratory, Type test certifacte has to be submitted for all rating of LV Switchgear to be used in Panel.

-

-

-

... More
(b) All four Horizontal Busbars shall be in same compartment. Certified design of switchboards shall be proven design from OEM (Switchgear Manufacturer). OEM name should be mentioned on top of each column of switchboard. Also, OEM Partnership Certificate shall be furnished by Panel builder. Panel shall be fabricated with a double door arrangement. Front Door shall be fitted with transparent Glass to allow maintenance staff to visually access device status, meter readings, indicating lamp status without opening the door.

-

-

-

... More
© Panels and cubicles shall be fabricated with CRCA Sheet Steel of thickness, same as as per OEM Design. Sheet Steel having vibration free structure chemically treated with nine tank process before painting for surface treatment and powder coated, with suitable electrolytic grade high conductivity Aluminium busbar extensible type, busbar supports,

-

-

-

... More
(d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.

-

-

-

... More
(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.

-

-

-

... More
(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm

-

-

-

... More
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test and Heat run test(type test) shall also be carried out.

-

-

-

... More
Approved Makes of Panel :- Engineer & Engineers/Ankit Electricals/Johns Electrical/Precesion/Zeniya/Expert Engineers/Bafna Electric Co.

-

-

-

... More
All the Main panel incomer shall have 3 pole + neutral type 1 + 2 SPD & all the sub main panel incomer shall have 3 pole + neutral type 2 SPD with suitable rating 4 pole MCB.

-

-

-

... More
PROVISION OF BUSDUCT/CABLE MUST BE AS PER SLD.

-

-

-

... More
Note:

-

-

-

... More
The incoming of Transformer feeders as shown on drawing shall be connected through bus duct. The suitable adopter box shall be provided on top only and DG feeders & Solar Incommer through cable from bottom.

-

-

-

... More
All Intelligent ACB shall have Micro processor based O/C, S/C & E/F. All ACB's shall have Ics=Icu=Icw as per BOQ for 1Sec & should be supplied with Adopter Terminal Connections whose orientation can be changed on site. Specification of ACB as per BSR 20222

-

-

-

... More
All Intelligent MCCB shall have Micro processor/Thermal Megnatic based release. With Ext rotary handel & spreader link. All CTs and PTs shall be cast resin type. All MCCB shall have Ics = 100% Icu & should have Isolation Feature & Class II Front Face as standard.Specification of MCCB as per BSR 20222

-

-

-

... More
The LT Panel manufacturer shall provide necessary,CT's Aux. contacts; multiply those contacts in the respective panels etc. to hook up in to PLC system

-

-

-

... More
INCOMING

-

-

-

... More
TRANSFORMER INCOMER (2 Nos. * 1000 KVA) one set for each incomer

-

-

-

... More
2 No. 1600 A, 50KA FP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor based O/C, S/C & E/F releases

-

-

-

... More
2 No. 230 volt D.C.Shunt release

-

-

-

... More
2 No. 230 volt A.C.closing coil

-

-

-

... More
2 No. 415 volt A.C. under voltage release.

-

-

-

... More
4 Set of CTs 1600 A/ 5A, 15VA class-1 for metering & APFC

-

-

-

... More
2 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB. CL1.0 with Rs485

-

-

-

... More
2 Set of O/C, S/C, and E/F relay

-

-

-

... More
2 No Breaker control switch

-

-

-

... More
2 Set of phase indication lights R,Y,B.

-

-

-

... More
2 set of ON-OFF-TRIP ckt. Healthy. indication lights

-

-

-

... More
2 No Spring charged indication.

-

-

-

... More
D.G. PANEL INCOMERS (2 Nos * 500 KVA DG set) one set for each incomer

-

-

-

... More
2 No. 800 A, 50KA FP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor based O/C, S/C & E/F releases.

-

-

-

... More
2 No. 230 volt D.C.Shunt release

-

-

-

... More
2 No. 230 volt A.C.closing coil

-

-

-

... More
2 No. 415 volt A.C. under voltage release.

-

-

-

... More
2 Set of CTs 800 A/ 5A class-1 for metering

-

-

-

... More
2 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB. CL1.0 with Rs485

-

-

-

... More
Battery charger 230 V/ 24 V DC, 20 A with DC ammeter and DC voltmeter. Charger should have all basic protections like over load, over Voltage reverse polarity etc.

-

-

-

... More
2 Set of O/C, S/C, and E/F relay

-

-

-

... More
2 No Reverse power relay

-

-

-

... More
2 No Breaker control switch

-

-

-

... More
2 Set of phase indication lights R,Y,B.

-

-

-

... More
2 set of ON-OFF-TRIP ckt. Healthy. indication lights

-

-

-

... More
2 No Spring charged indication.

-

-

-

... More
SOLAR POWER PLANT INCOMERS

-

-

-

... More
250A FP 25kA TM Based MCCB With O/C+S/C Protection

-

-

-

... More
1 Set of CTs 250A/ 5A class-1 for metering

-

-

-

... More
1 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB.

-

-

-

... More
1 Set of phase indication lights R,Y,B.

-

-

-

... More
1set of ON-OFF-TRIP ckt. Healthy. indication lights

-

-

-

... More
BUS BARS:-

-

-

-

... More
2400 Amps. 4P aluminium bus bars

-

-

-

... More
BUS COUPLER:-

-

-

-

... More
1 No. 1600 A, 50KA FP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor based O/C, S/C & E/F releases

-

-

-

... More
1 sets Breaker Control switch

-

-

-

... More
1 Sets of phase indication lights R,Y,B.

-

-

-

... More
1 sets of ON-OFF-TRIP ckt. Healthy. indication lights

-

-

-

... More
Interlocking: Transformer incomers , DG Panel Incommers, and bus couplers shall be electrically and interlocked so that no different source can be paralled at any point of time.

-

-

-

... More
OUTGOINGS:-

-

-

-

... More
6 Nos. 630 A FP MCCB , 36KA, with M.R. releases for O/C, & S/C.

-

-

-

... More
6 Nos. 400 A FP MCCB , 36KA, with M.R. releases for O/C, & S/C.

-

-

-

... More
5 Nos. 250 A FP MCCB , 36KA, with T.M. releases for O/C, & S/C.

-

-

-

... More
1 Nos. 200 A FP MCCB , 36KA, with T.M. releases for O/C, & S/C.

-

-

-

... More
2 Nos. 160 A FP MCCB , 36KA, withT.M. releases for O/C, & S/C.

-

-

-

... More
4 Nos. 100 A FP MCCB , 25KA, with T.M. releases for O/C, & S/C.

-

-

-

... More
4 nos 63 Amp 4P MCB (10KA)

-

-

-

... More
APFC SECTION (2nos * 360 Kvar)

-

-

-

... More
Incomer 2 No. 800A ,3POLE ,Microprocessor based MDO ACB with 230 V A.C. spring charged motor with Indicating Lamp & A/M Selector Switch.

-

-

-

... More
2 No.12 step APFC Relay (intelligent micro-processor based with current sensitivity less than 1%)

-

-

-

... More
2 Set phase indication lights (R, Y, B)

-

-

-

... More
1200 Amps. TP&N aluminium bus bars (50 KA)

-

-

-

... More
12 No.160 Amps. TPN MCCB (16 KA) with thermal magnetic release

-

-

-

... More
4 nos 63 Amp TP MCB (10KA) D curve

-

-

-

... More
2 nos 16 Amp TP MCB (10KA) D curve

-

-

-

... More
6 nos 10 Amp TP MCB (10KA) D curve

-

-

-

... More
12 No. 50 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tuned Harmonic Al reactor filter

-

-

-

... More
4 No. 25 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tuned Harmonic Al reactor filter

-

-

-

... More
2 No. 5 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tuned Harmonic Al reactor filter

-

-

-

... More
4 No. 2 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tuned Harmonic Al reactor filter

-

-

-

... More
2 No. 1 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tuned Harmonic Al reactor filter

-

-

-

... More
12 No. 50 KVar. TP capacitor duty contactors.

-

-

-

... More
4 No. 25 KVar. TP capacitor duty contactors.

-

-

-

... More
2 No. 5 KVar. TP capacitor duty contactors.

-

-

-

... More
4 No. 2 KVar. TP capacitor duty contactors.

-

-

-

... More
2 No. 1 KVar. TP capacitor duty contactors.

-

-

-

... More
26 No. Auto-Off-Manual selector switch.

-

-

-

... More
26 Sets self illuminated Red-Green ON-OFF push buttons.

-

-

-

... More
4 Sets of Axial flow fans with thermostate.

-

-

-

... More
Auto synchronisation :-The Auto synchronisation cum AMF panel should be capable for two nos external source and Two nos DG sets.

-

-

-

... More
Suitable PLC for synchronisation & AMF operation of four DG sets - 1 nos

-

-

-

... More
Synch Controller

-

-

-

... More
Digital I/P module

-

-

-

... More
Digital O/P module

-

-

-

... More
Suitable slot I/O rack with power supply

-

-

-

... More
Analouge I/P module

-

-

-

... More
KW tranducer

-

-

-

... More
EEPROM memory module

-

-

-

... More
Phase angle tranducer

-

-

-

... More
Operator interface 3" diagonal with key pad

-

-

-

... More
Communication cable from Operator interface to PLC

-

-

-

... More
Hooter for varios status annunciation

-

-

-

... More
A/M Selectror Switch, Push Button, Indicating Lights, DC Amp & Volt Meter, Auxilary Contactors for Ac & DC, Auxilary Relay Card, Control MCBs and all the software required for proper operation

-

-

-

... More
1 KVA online UPS with half an hour battery (SMF) back up for start operation

-

-

-

... More
SITC of RO water system with Filtration stage = Particulate filter-Membrane life enhancer filter - sediment filter - Pre carbon filter -RO Membrane filter - Post carbon filter,Input power Rating - 230 V AC , 50 HZ, Percentage of Rejection TDS - 90% or better having following Features (a) Double purification by RO with ESS or latest technology with TDS indicator (b).Spin welded RO Membrane Housing to prevent tempering (c). Push fit components for leak proof performance (d). Fully automatic operation with auto start and auto off (e). SS/ABS construction for corrosion free lifespan (f). Equally suitable for water from all bore wells,,overhead storage tanks,water tankers and even municipal taps (g) RO Membrane Flushing - Auto Flush @ Every Start , Every Stop and every One Hour of working for one minute. complete in all respect with following capacity.(Make: Eureka Forbes/Kent).

-

-

-

... More
Purification capacity- 50 LPH,Duty Cycle 270-500 liters/day,

9

509400

56600

... More
P & F of Early streamer Emission type lightning arrester on GI mast with air terminal configured as spheroid which is comprised of separate electrically isolated 4 panels surrounding an earthed central finial, the terminal shall be tested by CPRI for impulse current of 45 kA ( 8 / 20 Sec ) with 5 positive & 5 negative impulse, the arrester having following protection radius at level 1

-

-

-

... More
60 - 79 Mtr.

2

394000

197000

... More
S & Laying of down conductor of 70 Sq.mm single core insulated flexible copper cable with accessories as required.

80

56000

700

... More
Supply, installation, testing & commissioning of the following: IGBT based Rectifier & Inverter 60 KVA parallel True Online Double Conversion UPS having Inbuilt Isolators at UPS input,output and bypass, suitable for unbalanced, 3 Phase input and 3 phase 415 V output UPS system with Inbuilt isolation transformer with suitable stand at UPS Input and Inbuilt Static & Maintenance Bypass, UPS should have Unity output power factor (KVA=KW) at 40deg without derating, THDi 5%, UPS suitable for operating in parallel and each comprising as per technical specification complete as required. Make: Numeric / Relio/ Emerson / APC

-

-

-

... More
VRLA sealed maintenance free batteries for 60 KVA UPS system, for providing 30 minutes back up to each 60 KVA UPS. Each bank of batteries shall comprise of 75AHx 60 Nos. of SMF batteries etc as per specifications as required.(cost Included in above).Make: Exide /Quanta/ Panasonic

-

-

-

... More
Matching cabinet to house SMF batteries for 60 KVA UPS system along with interconnecting links and I/c S/F MCCB as required.(Cost Included in above).

2

4473572

2236786

... More
Supply, installation, testing & commissioning of Wall mounted Led Patient Bed light IP20 consuming a total system wattage of 31W with options of glare free downlight for reading and examination, up light for ambient lighting delivering an initial system lumen of 2533 lumens. Housing: non corrosive Extruded Aluminium with extruded ribbed translucence PMMA diffuser and self illuminated rocker switches. The luminaire shall have variable adjustment 10W Upward, 20W downward and 0.5W LED Bulb for generating multiple lighting modes as per the needs of Patient and doctor as well. The luminaire shall have optional suspended remote power switch for easy use in case of critical patrient care. The operating CCT shall be 5700K with CRI of ≥80. The luminaire shall be with electronic driver with input voltage range of 150 to 270V ,PF ≥ 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacture. Similar to Wipro (Cat No: LW04-411-XXX-57-WS) or equivalent in Philips/Cropmton/Bajaj.

120

955800

7965

... More
HVAC WORK

-

-

-

... More
PWD Electric BSR 2022

-

-

-

... More
Supply , Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1.5 TR ISEER not less then 4.6

15

874935

58329

... More
1.8 TR ISEER not less then 4.6

50

3321600

66432

... More
SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves, chase cutting, supports, making good the same with sand cement plaster etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

280

556360

1987

... More
Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
20 mm

180

34020

189

... More
25 mm

340

77860

229

... More
32 mm

100

29600

296

... More
Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

65

37700

580

... More
Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
2 core x 1.5 Sq.mm

500

47000

94

... More
4 core x 2.5 Sq.mm

400

92800

232

... More
Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive) & fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
0.60 mm

320

310400

970

... More
0.80mm

280

323400

1155

... More
1.00mm

35

48510

1386

... More
1.25mm

35

58205

1663

... More
Supply , Installation, Testing and Comissioning of site fabricated ducting made from aluminium sheet conforming to IS:737, Grade 31000 fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports , angle , expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
0.60 mm

100

123600

1236

... More
0.80mm

200

308000

1540

... More
SITC of air cooled ducted split type air conditioning machine with each having a capacity and details as mentioned below suitable for operation on factory charged R-32/R-410A Green refrigerant comprising of Scroll /rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system, Suitable capacity squirrel cage induction motor with class 'B' insulation suitable for operation on sigle / three phase supply, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine isolation / disconnect switch, valves and accessories to inter connect compressor and condender including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L , U/V, phase reversal protection, single phase preventors etc complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
5.5 TR

1

162002

162002

... More
8.5 TR

8

1814312

226789

... More
11 TR

2

579142

289571

... More
Supply and Installation of Box type EU13 Hepa Filter of 99.997% efficiency down to 0.3 micron particle size installed in zero leakage Aluminium frame as per ISO 14644-1 clean room including sealing and packing material cost like silicon and hardware cost and Labour cost. NABL accredeated / appropriated lab testing reports with OEM certificate must submitted to engineer in charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
305 mm Thick

5

189290

37858

... More
Supply and fixing of acoustic lining of ducts with chemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour absorption 0.002 gm / Sqcm, including cost of adhesive etc. complete in all respect. All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
10 mm thick

100

75500

755

... More
Supplying, installing, testing and balancing of extruded Aluminium Powder coated supply/return Grilles with fixed bars at front having 0 / 15 / 30 / 45 degrees deflection as required. with Flange size 20 mm with rounded edges including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

40

253800

6345

... More
Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Supply Air Diffuser with Volume Control damper

7

85533

12219

... More
Return Air Diffuser without Volume Control damper

7

68985

9855

... More
Supplying, installing and balancing of extruded Aluminium powder coated fresh air inlet louvers with bird screen & volume control damper fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

4

33484

8371

... More
Supply , installation, testing & balancing of 20 Gauge G I Damper with brass bushes and 6" pitch multiblade box type galvanised sheet steel construction volume control damper for Ducting and air washers to be provided with suitable links and quadrants for control of volume of air as per specifications complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

10

51280

5128

... More
Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia

-

-

-

... More
50 mm dia per running inch length

45

3600

80

... More
100 mm dia per running inch length

50

8000

160

... More
150 mm dia per running inch length

60

14460

241

... More
200 mm dia per running inch length

60

20040

334

... More
P & F of Fire retardent flexible canvass connection made of fibreglass weave having silver grey silicon rubber coating, of height 200 mm with sufficient fold to avoid transmission of vibration with GI frame ,Gasket Nut Bolts for air cooling Plants/AHU/FCU etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

25

50575

2023

... More
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

800

108000

135

... More
Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
150mm x 50mm x 1.6mm

100

67500

675

... More
300mm x 50mm x 1.6mm

100

105300

1053

... More
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity 99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
16.0 Sq. mm

200

46400

232

... More
4 core

-

-

-

... More
10.0 Sq. mm

180

34560

192

... More
4 core

-

-

-

... More
6.0 Sq. mm

230

38180

166

... More
4 core

-

-

-

... More
Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
4 x 6.0 sq.mm

10

1720

172

... More
4 x 10.0 sq.mm

8

1480

185

... More
4 x 16.0 sq.mm

18

3402

189

... More
P & F of trap door for AHU / FCU's  in existing false ceiling duly made from 12 mm thick laminated board, hinged with wooden frame of cheed wood size 50mm x 80mm, Frame suspended with MS strip 25 x 3 mm with ancor fastner min 8 supports from ceiling, Hinges, Locking arrangement etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

35

176925

5055

... More
Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required. All as per pre approved by Engineer in charge.

-

-

-

... More
13mm thick for indoor Application

180

166680

926

... More
19mm thick for Outdoor Application with 26 SWG Aluminium Cladding

180

262800

1460

... More
NON BSR ITEMS

-

-

-

... More
Supplying, installing, and testing of Al volume control damper within ducts to be provided with suitable links, levers and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system as per approved shop drawings Supplying, installing, and testing of GI volume control damper within ducts to be provided with levers and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system, Frame of the VCD shall be constructed from 18 gauge sheet & blades shall be constructed from 20 gauge sheet Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro

10

125000

12500

... More
SITC of Digital thermostat with cooling & heating mode including necessary control wiring to maintain the inside design condition as required Make:- Simens , Honeywell, Belimo

10

30000

3000

... More
Supplying, installation, testing and commissioning of fire dampers, the blades and frame shall be min. 1.6 mm thick GI and factory fitted in a sleeve made out of 1.6 mm thick GI of min. 400 mm long, as & where required, of required sizes including control wiring. The damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal. CBRI tested and certified for 90 minute fire rating etc. complete as required and as per specifications. (Total assembly should be UL listed)Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro

-

-

-

... More
Fire Damper

7

60900

8700

... More
Actuator

21

176400

8400

... More
Supply, installation testing, commissioning and validation of Laminar Flow Units (LFU) comprising of Terminal EU 13 HEPA Filters of 99.997% Efficiency down to 0.3 Micron particle size installed in zero leakage Al frame with Al perforated plate type Al grille with Al VCD, LFD laminar flow diffusers are constructed from 18 swg aluminium sheet, perforated face with approx. 50% perforation od size 900x600mm-6nos, 600x600mm-3nos, including the cost of supply air 18 gauge Al plinum of size 8'x6'x1.5'/2', including all connection complete in all respect. Make:- Systemair, Ravistar, MetalJoint, Airmax, Mapro

-

-

-

... More
LFU Size : 2400 x 1800 mm ( +/- 100mm )

8

1000000

125000

... More
SITC of Analogue, Megnehelic Differential Pressure Gages, Die Cast Al. case, 4" dial face, Zero Center Range 30-0-30 Pa with SS Boxes Breathing Pipe & Standard accessories.

10

150000

15000

... More
SITC of 2.0 mm thick (both base & cover) GI sheet raceway for copper piping from outdoor unit to shaft, The raceway shall be fixed on the floor with the help of suitable size galvanized MS angle support at 8" distance as approved from engineer incharge of size 400mm x 150mm.

30

90000

3000

... More
SITC of air cooled ducted split air conditioning machine with each having a capacity and details as mentioned below suitable for operation on refrigerant comprising of Scroll / Rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system, Suitable capacity squirrel cage induction motor with class 'B' insulation suitable for operation on 415 + 10% volts, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine isolation / disconnect switch as per specifications, Suction line insulation with minimum 19 mm thick polyvinyl rubber insulation, valves and accessories to inter connect compressor and condender including pressure testing, vacuum. Pipe shall be hard drawn copper, Necessary starters suitable for compressor motor complete with O/L , U/V, phase reversal protection, single phase preventors etc complete as required.(Make: Daikin, Hitachi, Toshiba,Mitshibushi, Bluestar,LG)

-

-

-

... More
CONDENSING SPLIT AC - 11 TR CAPACITY,WITH R-410 (DOUBLE CIRCUIT)

2

384000

192000

... More
CONDENSING SPLIT AC - 16.5 TR CAPACITY, WITH R-410 (DOUBLE CIRCUIT)

8

2368000

296000

... More
Supplying, installing, testing and commissioning of double skin construction Air Handling Units as per specification.All AHU's shall be draw thru type, complete with pre & fine filter section, minimum 6 row deep 2 nos ( one working + one standby) DX coil of copper tube & aluminium fins, flexible duct connection, squirrel cage induction motor, DIDW backward curve fan(s), belt drive, vibration isolators and mixing box for return air, fresh air. Fan Motor shall be suitable for 415±10% volts, 50 Hz, 3 phase AC supply and shall be high efficiency. AHU shall be supplied with suitable rating VFD drive. VFD shall have extendable sensor for giving control through surgon control panel, AHU shall be selected for a maximum coil of 500 FPM and filter face velocity of 350 FPM. The AHU inner skin shall be 0.6 mm pre coated GI, outer skin shall be 0.6 mm pre coatd GI, The AHU panel shall be 48 mm thick 40 Kgf PUF insulation with thermal break profile, The AHU shall be complete with AHU kit of following capacities. (Make: Zeco/ Edgetech/Systemaire,Revo)

-

-

-

... More
3000 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER (for ICU/ Operation Theatre)

8

2640000

330000

... More
Supplying, installing, testing and commissioning of double skin construction Air Handling Units as per specification.All AHU's shall be draw thru type, complete with pre & fine filter section, minimum 6 row deep 2 nos ( one working + one standby) DX coil of copper tube & aluminium fins, flexible duct connection, squirrel cage induction motor, DIDW backward curve fan(s), belt drive, vibration isolators and mixing box for return air, fresh air. Fan Motor shall be suitable for 415±10% volts, 50 Hz, 3 phase AC supply and shall be high efficiency. AHU shall be supplied with suitable rating VFD drive. VFD shall have extendable sensor for giving control through surgon control panel, AHU shall be selected for a maximum coil of 500 FPM and filter face velocity of 350 FPM. The AHU inner skin shall be 0.6 mm pre coated GI, outer skin shall be 0.6 mm pre coatd GI, The AHU panel shall be 48 mm thick 40 Kgf PUF insulation with thermal break profile, The AHU shall be complete with AHU kit of following capacities.(Make: Zeco/ Revo/Edgetech/Systemaire)

-

-

-

... More
5000 CFM/ CEILING MOUNTED/ 125 MM STATIC/ 06 ROW DEEP COIL/PRE FILTER ,FINE FILTER HEPA FILTER (for ICU/ Operation Theatre)

2

1220000

610000

... More
Providing, fixing, testing and commissioning of AMCA Certified (For Air and Sound Performance) tube axial flow fan of different capacity as mentioned below in standard M.S.contruction. Entire fan model & AMCA Seal shall apear in techncial submittal of fan. All the fans are synthetic enamelled panited/hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet. The electric motor coupler shall be squirrel cage induction motor (IE-2 type) confirming to IS - 325 IP55 with class `H' insulation. Motor shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hrs. Fan shall be EN 12101-3 Certified & CE/UL Listed for high temprature. Fan efficiency should not be less than 70 %, noise level should not be more than 80 db @ 3 m distance when measured in hemisperical reverberant room conditions for Normal mode Fans and noise level should not be more than 90 db @ 3 m distance when measured in hemisperical reverberant room conditions for Emergency mode Fans. Fan shall have all provision for start on emergancy signal from fire alarm panel. Fans should be as per specification and drawings.Make :- Kurger/ Nikotra/ Airflow/ Greeneck

-

-

-

... More
7500 cfm at 20 mm static (for lift well pressurization)

2

131800

65900

... More
Supply, Installation, testing and Commissioning of accoustically insulated ceiling / floor mounted Rectangular box type/circular type Inline fan, for toilet exhaust , ward normal exhaust constructed of GSS duly powder coated as per detailed specifications, complete with forward curved SISW fan, motor and drive suitable for 220 ± 10% volts, 1 phase, 50 Hz A.C supply, with necessary canvas connection etc complete in all respects.Make :- Kurger/ Nikotra/ Airflow/ Greeneck/Otemberg/ sphere

-

-

-

... More
1000 cfm at 15 mm static

4

74400

18600

... More
500 cfm at 15 mm static

8

102720

12840

... More
SITC of Desert Cooler(Ashoka fitted) cooling capacity 5000 cum/Hr. Cooler Size 28"X28"X38" fitted and tank size 9" height with 20" 1400 RPM Cooler fan motor(cool home/CG make) with three speed control fan motor and submercible pump melborne or eq. make)made of 18 SWG GI sheet for tank,front and top of 20 SWG GI sheet,Filter panel of 22 or better SWG,Grill of 22 or better SWG and Grill size 22"X24" complete as required with suitable stand.

26

458900

17650

... More
LIFT WORK

-

-

-

... More
Electrical BSR 2022

-

-

-

... More
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Long point (up to 10 mtr.)

14

10808

772

... More
Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
On board

14

4998

357

... More
S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
25 mm

70

3920

56

... More
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
3x 1.5 sq.mm

80

5040

63

... More
2 x 2.5 sq. mm. + 1x1.5sqmm

80

6480

81

... More
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Single pole MCB (With B/C curve tripping Characteristics)

-

-

-

... More
6 A to 32 A rating

4

748

187

... More
Four pole MCB (With B/C curve tripping Characteristics)

-

-

-

... More
50/63 A rating

2

3490

1745

... More
Providing & Fixing of 240/415 V factory fitted RCBO with overload, short-circuit and earth leakage protection with ISI marked (IS12640-2)/ conforming to IEC 61009-1, breaking capacity 10 KA, provision for pad lock, min. Electrical operation 10,000 upto 63 A rating , minimum phase termination capacity of 35sq.mm. , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Four pole 100/300 mA sensitivity

-

-

-

... More
40 A rating

2

7658

3829

... More
Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp.  insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, Ferrules,  detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Metal door (single phase) IK-09 and IP-43 with Metal end box

-

-

-

... More
12 Way (12+2)

2

5180

2590

... More
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

750

101250

135

... More
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity 99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
35.0 Sq. mm

-

-

-

... More
3.5 core

200

69400

347

... More
Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-

-

-

-

... More
(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole

-

-

-

... More
(b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts

-

-

-

... More
© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt

-

-

-

... More
(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm.

-

-

-

... More
(d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.

-

-

-

... More
(e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25 mm thick and 3 Mtr. Long

4

31820

7955

... More
Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25mm x 6mm G.I. ( Hot Dipped ) Strip

40

7840

196

... More
Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity 95% thimble etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
8 SWG G.I. ( Hot Dipped ) Wire

100

2000

20

... More
NON BSR

-

-

-

... More
SITC of 26 Passenger Bed (1768 KG) (With m/c Room) Lift with speed of 1.5 M/Sec., travel of Ground to Sixth:7 Stop/7 Open,power operated doors, ACVVVF Control, and automatic rescue operation during power failure. (Hospital, dimensions and travelling as per drawings) etc. as per Terms & conditions & specifications attached and as per direction of engg- in charge with 5 year defect liability period. Make : Otis / Kone / Mitsubishi / Johnson / Thyssen Krupp / Omega / Schindler and Equivelent Make as per Annx.

2

6670560

3335280

... More
FIRE FIGHTING WORK

-

-

-

... More
FIRE FIGHTING PUMPS

-

-

-

... More
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H.

-

-

-

... More
(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head

-

-

-

... More
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal

-

-

-

... More
(C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head

-

-

-

... More
(D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .

-

-

-

... More
( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads.

-

-

-

... More
(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives.

-

-

-

... More
(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

-

-

-

... More
(H)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
2280 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type Two stage, 1500 RPM

2

1552140

776070

... More
Supplying, Installation, Testing & Commissioning of Diesel Engine Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H.

-

-

-

... More
(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head

-

-

-

... More
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal

-

-

-

... More
(C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head

-

-

-

... More
(D) Heat Exchanger cooled Diesel Engine as per NFPA 20 developing suitable BHP for the below mentioned discharge at 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity (made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel level Indicator, Suitable MS angle iron stand for placing tank, first Filling of Diesel tank.

-

-

-

... More
(E) Diesel Engine Control comprising Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication, Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter, All standard relays and accessories for automatic operation of diesel engine System Controller in Existing Fire Fighting Control panel

-

-

-

... More
(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives.

-

-

-

... More
(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

-

-

-

... More
(H) Pump to be placed on Suitable size Existing Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
2280 LPM suitable for 88 Mtr Head Horizontal Axially split casing volute type Two stage, 1500 RPM

1

1110656

1110656

... More
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty Jockey pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM suitable for automatic operation and consisting of following details given as A, B, C, D, E,F and G

-

-

-

... More
(A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head

-

-

-

... More
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal

-

-

-

... More
(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .

-

-

-

... More
(D) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads.

-

-

-

... More
(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives.

-

-

-

... More
(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

-

-

-

... More
(G)Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
180 LPM suitable for 88 Mtr Multi Stage

2

372110

186055

... More
Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty Terrace pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H.

-

-

-

... More
(A) Horizontal End suction Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head

-

-

-

... More
(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal

-

-

-

... More
(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 3000 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .

-

-

-

... More
(D) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads.

-

-

-

... More
(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives.

-

-

-

... More
(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM

-

-

-

... More
(G) Suitable size Reinforced cement concreat (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra )

-

-

-

... More
(H) Weather proof hood fabricated from 5mm thick UV stablised FRP sheet supported by 50 mm x 50 mm x 5 mm Angle Iron fram above pumpset to protect it from weather All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
900 LPM with 35 mtr head

1

157612

157612

... More
Supplying, Installation, Testing & Commissioning submersible type dewatering pump of stainless steel casing and Noryl impellor of discharge and head given below complete with all accessories suitable for operation on 230 V, single phase/415 V /3 phase, 50 Hz. AC supply complete with starter for automatic operation including water level sensing device / float switch inter connection with submersible cable etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
180 LPM with 10 mtr head

2

57130

28565

... More
SITC of pressure switches of pressure range 3 to 15 Bar for Main, Jockey, Terrace pump and Diesel pumps, Etc. as Required ( Control Cable from Pressure switch to Panel to be Paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

7

14168

2024

... More
FIRE FIGHTING, HYDRANT & SPRINKLER SYSTEM

-

-

-

... More
SITC of UL listed / FM Approved Brass Test and drain valve assembly for sprinkler system comprising of 3-position ( off, test and Drain ) ball valves with drain orifice having K-factor 5.6 and maximum working pressure 300 PSI and Inbuilt sight glass etc. as required of following size. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
50 mm Dia.

5

69995

13999

... More
SITC of UL listed and FM Approved Polyethelene vane type water flow switch with actuation & delay mechanism for sensitivity in the range of 4 to 10 GPM and suitable for installation in following sizes of Sprinkler pipe for a Static pressure rating up to 250 PSI in cluding making connections, making hole in pipe for inserting the vane etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
150 mm Dia.

7

63294

9042

... More
SITC of suitable Pressure release valve of 50 mm dia, of CI body, with pressure setting range 7-15 kg/sqcm, on discharge header / Air Vessel, complete in all respect etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

7

53389

7627

... More
Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of required shade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25 mm dia

1800

822600

457

... More
32 mm dia

1200

704400

587

... More
40 mm dia

450

306900

682

... More
50 mm dia

400

381600

954

... More
65 mm dia

400

487200

1218

... More
80 mm dia

350

527800

1508

... More
100 mm dia

300

651600

2172

... More
150 mm dia

270

864540

3202

... More
200 mm dia, 6.0 mm thick

35

169820

4852

... More
250 mm dia, 6.35 mm thick

20

120620

6031

... More
Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C' class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supports including cutting, welding etc & forged steel fittings like elbows, tees, tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
80 mm dia

10

15990

1599

... More
150 mm dia

500

1696000

3392

... More
Supplying and fixing cylindrical air vessel of continuous welded construction for pump room made of 450 mm dia,fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, 2000 mm in height with flanged connection, Provision for 25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

2

80954

40477

... More
Supplying and fixing cylindrical air vessel of continuous welded construction fixed at riser top made of 250 mm dia, fabricated out of 8 mm thick MS sheet, 1200 mm in height with flanged connection, Provision for 25 mm dia drain valve,air release valve,safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of post office red enamel paint including The tank shall be installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

2

18044

9022

... More
Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holes in existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
150 mm dia

6

143850

23975

... More
200 mm dia

3

125898

41966

... More
Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
100 mm dia

4

31216

7804

... More
150 mm dia

6

63246

10541

... More
200 mm dia

2

44770

22385

... More
Supplying and Fixing of PN 1.6 Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
50 mm dia

2

6362

3181

... More
80 mm dia

15

56340

3756

... More
100 mm dia

6

29346

4891

... More
150 mm dia

12

91776

7648

... More
200 mm dia Gear Operated

2

34640

17320

... More
Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball including teflon tape etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
20 mm dia.

4

4880

1220

... More
25 mm dia.

4

5956

1489

... More
32 mm dia

4

11364

2841

... More
40 mm dia

4

15772

3943

... More
50 mm dia

4

24656

6164

... More
Supplying and Fixing of Brass/GM gate valves with screwed end , Non rising stem and conforming to IS:778 Class-1 including teflon tape etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
20 mm dia.

4

5272

1318

... More
25 mm dia.

4

7908

1977

... More
32 mm dia

4

11132

2783

... More
40 mm dia

4

14756

3689

... More
50 mm dia

4

21512

5378

... More
SITC of installation control valve of cast iron body and brass/bronze working parts comprising of water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continous alarm when the wet riser/Sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
150 mm

2

106372

53186

... More
Supplying and fixing of SS 304 Single / Double headed oblique pattern hydrant landing valve (internal/external) with 75 / 100 mm dia flanged inlet & 63 mm dia instantaneous type female outlet coupling with cast iron wheel complete with ABS cap and chain and all accessories as per IS:5290-93 (Type-A) in cluding matching flange (14 mm thick), nuts, bolts, washers, gaskets, etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Single Headed with 75 mm Dia. Flanged Inlet

27

216594

8022

... More
Supplying and fixing orifice plate made of 6 mm thick stainless steel with orifice of required size in between flange & landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete with rubber gasket, GI bolts, nuts, washers etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

27

39339

1457

... More
Supplying and fixing of flexible hose made with 100% polyester, black EPDM internal rubber lining with External coat of synthetic elastomer (IS:636, type-A) 63 mm dia, 15 mtr. Long RRL hose pipe with instanteneous type 63 mm dia SS-304 male and female couplings (IS:903) duly bound and riveted to hose pipes with copper rivets and SS wire etc. as required.Appropriate Test Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.

54

410184

7596

... More
Supplying & fixing SS-304 Short Branch Pipe conforming to IS: 903:93 fitted with 20mm (nominal internal diameter) bore nozzle, for projecting water in form of solid jet. The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm² for 2.5 minutes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

27

69255

2565

... More
Supplying and fixing first -Aid Fire hose reel Drum wall mounted swinging type with MS construction powder painted in post office Red, conforming to IS 884-1985 with upto date amendments, complete with the following as required. (A) Thermoplastic / Rubber Hose (B)20 mm dia UL, FM Bronze / SS nozzle with 5mm orifice (C)Drum and brackets for fixing the equipments on wall. (D) Connections from riser with 20/25 mm dia Brass/GM gate valves with screwed end and conforming to IS:778 Class-1 through Forged steel Screwed Union & M.S. pipe. Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
With 30 m x 20 mm High Pressure Braided Rubber Hose as per IS:5132 - 1969 and Bursting pressure 42 Kg/sqcm

14

174706

12479

... More
Supplying and fixing Inlet Breeching Connection of CI body with Gun Metal male instantaneous inlet couplings with Inbuilt NRV, Drainage Connection with 50 mm Brass gate valve complete with PVC blank cap and chain as required for 150mm dia Outlet with 1 no. Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Ways. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
4 Way

1

13854

13854

... More
Providing and fixing of 100 mm Dia. Flanged Gun Metal Fire brigade Suction hose coupling (draw out connection) for female coupling as per IS:902-1974 complete with Matching Flange (Minimum 14 mm thick), nuts, bolts, washers, gaskets, etc as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

1

10548

10548

... More
Supplying and fixing of 750 mm x 600 mm x 250 mm Outdoor application Fire Hose Cabinet made of 1.6 mm thick MS sheet Duly powder coated in red color externally and white internally with 6 mm thick glazed doors with Expanded Metal 2 mm thick Jali including necessary locking arrangement suitable to accommodate 2 Nos 15 Mtr. Long RRL Hose and 1 No. branch pipe on Existing Wall / Angle Iron Frame as required. (Cost of MS structure for mounting Frame is to be Paid Extra) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

15

84015

5601

... More
Providing and fixing of Fire / Electrical Shaft Door made from powder coated (50 Micron) aluminium partialy glazed with 6 mm thick glass and Partialy / Fully Louvered with Outer frame of Aluminium Section of Size 100 mm x 45 mm x 1.5 mm and Shutter's Top, Middle & side Section of Size 82 mm x 45 mm x 1.5 mm, Bottom Section of Size 110 mm x 45 mm x 1.5 mm Complete with Hinges, Tower bolt, Handle, Aldrop, Locking Arrangement including dash fasteners of required dia and size, necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. as per drawings and the directions of Engineer-in-charge. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

18

177336

9852

... More
Providing and Fixing of 15 mm dia Bronze quartzoid bulb type sprinkler heads with Maximum working pressure 11.6 Kg / Sqcm and suitable for 68 degree centigrade rating standard response (UL Listed) chrome plated complete in all respect of the following type. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Pendant/ Upright type

1106

320740

290

... More
Sidewall Sprinklers (ordinary)

150

45450

303

... More
Extended Throw Sidewall type .

150

75900

506

... More
Providing & fixing of UL listed 1.5 mm thick chrome plated Dual type MS Escutcheon plates fixed at junction of Sprinkler piping with the false ceiling. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

800

86400

108

... More
Supply & Fixing of Fire Man's Axe with carbon steel head & rubber moulde handel usable upto 20 KV and confirming to IS :926 with length approx 0.4 M & weight 3.0 Kg. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

14

26852

1918

... More
Providing & fixing sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1000 mm Long

900

995400

1106

... More
Providing & fixing Stainless Steel pressure gauge with dial of 150 mm dia size and range 0 to 20 kg/sq.cm with 3 / 8 " BSP bottom entry , Ball valve , SS Syphon tube all fittings etc, duly calibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS Pipe Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

10

26320

2632

... More
Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Capacity 4.5 Kg.

10

85470

8547

... More
Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
6 kg

21

96096

4576

... More
Supply & Fixing of Water + AFFF 6% Mechanical Foam type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 25 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Capacity - 9 Ltrs.

14

63308

4522

... More
Supply & Fixing of Trolley mounted 22.5 Kg CO2 type Fire Extinguisher conforming to IS: 16018:2012, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.5 Mtr. long Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Double mounted handle as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

2

52884

26442

... More
Supply & Fixing of Ceiling mounted UL listed clean Agent (HFC-236fa), Modular type Fire Extinguisher , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Fixed Bulb with Temerature 68 deg C, QR code for Product Traceability including Fixing on Ceiling with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
5 Kg Capacity

2

48608

24304

... More
10 Kg Capacity

2

89252

44626

... More
NON BSR ITEMS

-

-

-

... More
SITC of floor mounted dust and vermin proof compartmentalised cubical type main fire pump house panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories ( Group -I ) as below:

-

-

-

... More
Incomer

-

-

-

... More
400 Amp. FP MCCB (adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, CT, Indicating Lamps, 600 Amps Alum. Bus bar with with heat shrinkable sleeves.

-

-

-

... More
Out going

-

-

-

... More
(a) 250 Amp. TPN MCCB (adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. DOL Starter of 100-125 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets

-

-

-

... More
(b) 63 Amp. TPN MCB, 25 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. DOL Starter of 7.5 - 10 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Set

-

-

-

... More
© One no. Diesel Engine Auto Starting kit with Auto . Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, Battery charger, suitable for 12 V / 24 V DC with trickle / boost selector switch, DC ammeter & voltmeter

-

-

-

... More
(d) System controller to control Operation Main Electric pumps (two no), Diesel pump, jockey pump & dewatering pump in sequence as per specs. Consisting of relays, timers, NO / NC contacts etc as required.

1

315000

315000

... More
Providing and Fixing of PN16 Resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe Flange it should be complete as per manufacturer's specification & as per directed by Engineer In-charge.

-

-

-

... More
200 mm Dia.

4

20700

5175



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.