Rajasthan State Road Development And Construction Corporation Limited Tender

If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.

Rajasthan State Road Development And Construction Corporation Limited - RSRDC Tender

Works
Civil And Construction
Drainage Work
Eprocure
Opening Date18 Oct 2024
Closing Date24 Oct 2024
Tender Amount₹ 88,66,000 
Notes
Download

Costs

  • EMD

    ₹ 1,77,320
  • Document Cost

    ₹ 1,180
  • Tender Fee

    ₹ 1,500

Summary

Construction, Supply, Installation, Testing And Commissioning Of Sewerage Treatment Plan Of Capacity 150 Kld (based On Bsr Technology) Including Civil, Electrical And Electromechanical Work At Medical College Campus Bundi (raj.)(excl.cost Of Cement)

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
M10 grade Nominal Mix 1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size).

11.73

1799

21102.27

... More
Centering and Shuttering with plywood or steel sheets including strutting, propping bracing both ways and removal of formwork for foundation , footings, strap beam, raft , bases of columns etc.

65.94

113

7451.22

... More
Walls (any thickness) including attached pilasters, buttresses plinth and string course.

631.77

218

137725.86

... More
Centering& Shuttering with plywood or steel sheets including strutting , propping bracing both ways with steel props and removal of formwork for upto floor three level for : Suspended floors, roofs, landings, staircases, balconies, girders, cantilevers, bands, coping bed plates, anchor blocks, sills, chhajjas, lintel, beam, plinth beam etc.

16

191

3056

... More
Providing and fabricating reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (including cost of binding wire) all complete up to floor Three level. Thermo-mechanically Treated bars (Conforming of relevent IS code)

26040

77

2005080

... More
Providing and laying in position Ready mix concrete manufactured in fully automatic Batching Plant and transported to site in transit mixer for having continous agitated mixer, manufactured as per approved mix design of specified grade of RCC work including pumping of R.M.C. from transit mixer to site of laying , exculding the cost of centering, shuttering and reinforcement with all lead and lift including cost of admixtures in recommended portion as per IS 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer in charge . All works upto floor Three floor M20 grade Design Mix by using min 400 Kg of cement per cum of concrete

186.77

3282

612979.14

... More
Flyash Flyash Brick work with flyash Flyash Bricks of class designation 75 in superstructure above plinth level upto floor Three Level in all shapes and sizes in : Cement mortar 1 : 6 (1 cement : 6 coarse sand)

9.28

1822

16908.16

... More
Half Flyash Brick masonry in Superstructure , above plinth level upto floor Three level using Flyash Bricks of designation 75 Cement mortar 1 : 6 (1 cement : 6 coarse sand)

85

345

29325

... More
Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in:

8

1698

13584

... More
Providing and fixing steel gate ,grating , and grills made of angles ,tees,square bars flats ,or black pipe with holdfast and fitting complete as per design and drawing including cutting welding and fabrication with priming coat of red oxide.

1500

81

121500

... More
Extra if square ,rectangular hollow tubular section are used or grill made by flats only

500

8

4050

... More
Providing and fixing M.S. sheet single leaf door shutter in angle iron frame 35x35x5mm suitabilly diagonally braced with 25x3mm flat iron above and below lock rail of size 50x5mm beading extra including all fittings, as per direction of Engg. incharge but excluding cost of chowkhats: including two coats of anit-corrosive red oxide primer paint

5

1671

8355

... More
Polished Blue Kota stone flooring skirting, laid over 20 mm thick base of C.M. 1 : 4 and jointed with grey cement slurry to match the shade of the slab including rubbing and polishing complete :For area of each slab from 2001 to 5000 Sq.Cm :25 mm thick slab.

33

553

18255.6

... More
Plaster on new surface on walls in cement sand mortar 1:4 incliuding racking of joints etc.complete fine finish:20 mm thick

600

99

59880

... More
Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade

721.35

74

53379.9

... More
Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water proofing cement compound consisting of applying : a) after surface preparation, first layer of slurry of cement @ 0.488 kg/sqm mixed with water proffing cement compound @ 0.253 kg/sqm.b) laying second layer of Fiber glass cloth when the first layer is still green . Overlaps of joints of fiber cloth should not be less than 10 cm c) Third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/sqm mixed with water proffing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire treatment will be taken upto 30cm on parapet wall and tucked into groove in parapet all around d) fourth and final layer of brick tiling ‘with cement mortar or any other approved protective coarse. (which will be paid for separately) For the purpose of measurement the entire treated surface will be measured

560

302

169120

... More
Part- B (Electrical Work)

-

-

-

... More
SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-

8

5975

47800

... More
(a)Thickness of CRCA sheet shall be 2.0 mm, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided.

-

-

-

... More
(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.

-

-

-

... More
[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )

-

-

-

... More
(d)Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.

-

-

-

... More
(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.

-

-

-

... More
(f)Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )

-

-

-

... More
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.

-

-

-

... More
(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator with standard short circuit withstand capacity , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Electrolytic grade Aluminium bus bar 6010 grade

16

542

8672

... More
Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy as per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS

1

3252

3252

... More
Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Ring type tape wound CT

-

-

-

... More
C T Class 1, Ratio upto 150/5, Burden 5 VA

3

614

1842

... More
Providing & Fixing of Cam operated rotary (Auto/manual) switches on existing panel with 2 way and off position using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc. as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
32 AMP

2

504

1008

... More
Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Red/yellow/Green colour

3

170

510

... More
Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms)

4

1498

5992

... More
P & F of Direct on line (DOL) / Star - Delta Starter as per IEC type-2 Co-ordination chart of OEM in Existing Panel with circuit breaker having inbuilt overload protection or separate thermal Overload relay , Short circuit, phase loss protection, suitable Contactors, including wiring between switchgears, Indicating lamps for R,Y,B,ON,OFF, Push button for ON, OFF, Volt meter, Ammeter, selector switch for local/remote, auto/manual/OFF operation. Cast resin CT's, provision for potential free contacts making connection, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Motor rating 1.5 KW

2

11499

22998

... More
Motor rating 4.0 KW

4

12288

49152

... More
Motor rating 5.5 KW

2

12757

25514

... More
SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690 V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections etc. as required.OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,

1

7112

7112

... More
P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
1.5 Sq.mm 3 core flat / Round

300

92

27600

... More
4.0 Sq.mm 3 core flat / Round

100

214

21400

... More
Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity 99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
70.0 Sq. mm

-

-

-

... More
3.5 core

200

610

122000

... More
Add Extra for Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade direct in ground including excavation of trench of size 75 cm (Depth) x 35 cm(Width) , with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth

180

185

33300

... More
Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same

180

24

4320

... More
P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of Earth & Back filling with compaction is to be Paid Extra)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
50 mm

150

85

12750

... More
110 mm

180

226

40680

... More
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

200

135

27000

... More
Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick or RCC walls/ slab and making good the same. complete with painting of one coats of Red Oxide and two or more coats of synthetic enamel paint of required shade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.). All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
50 mm dia

50

954

47700

... More
80 mm dia

30

1508

45240

... More
Supplying and Fixing of PN 1.6 Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
50 mm dia

26

3181

82706

... More
Supplying and Fixing of PN 16 Cast Iron Dual Plate Wafer Type Check Valve / Non return valve with SS / Bronze flap complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
80 mm dia

2

6181

12362

... More
Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25 mm

35

229

8015

... More
50 mm

70

431

30170

... More
Supply and installation of high tensile low carbon steel rod molecularly bonded with 99.9 % Copper thickness (250 microns) and confirming to UL 467, IS/IEC 62561-2 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-

-

-

-

... More
(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole

-

-

-

... More
(b) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts

-

-

-

... More
© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt

-

-

-

... More
(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm.

-

-

-

... More
(d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.

-

-

-

... More
(e) Test certificates for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25 mm thick and 3 Mtr. Long

4

7955

31820

... More
Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
25mm x 3mm Alum. Strip

50

133

6650

... More
Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
300mm x 50mm x 1.6mm

30

1053

31590

... More
Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy =125 lm/ wt and potted driver & has a unique BIS R number with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @=300 V AC and Auto resetting Safety , Power Factor 0.95 driver Efficiency 85% ,THD(I) 10% Humidity 10% to 90% RH Working Temp -5C to 45C . driver current 750mA. The luminaire shall be BIS certified and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI 70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs. Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
LED Street Light fixture with Minimum lumen output 11225 lm

4

6765

27060

... More
Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
40 mm Dia.

6

958

5748

... More
Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it's ISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Short point (up to 3 mtr.)

1

359

359

... More
Medium point (up to 6 mtr.)

4

578

2312

... More
Long point (up to 10 mtr.)

10

772

7720

... More
Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 10 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. For specification of copper Conductor, Phenolic Laminated sheet's & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
On board

5

357

1785

... More
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
2 x 4.0 sq. mm. + 1 x 2.5 sq. mm.

100

122

12200

... More
S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including cutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
25 mm

60

56

3360

... More
Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification of Wiring accessories refer Chapter E - 07 related item & For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

6

580

3480

... More
Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
6 A to 32 A rating

12

187

2244

... More
Four pole MCB (With B/C curve tripping Characteristics)

-

-

-

... More
50/63 A rating

1

1745

1745

... More
Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for MCB / RCCB and SP / TP MCB as outgoing ,made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3. powder painted with reversible door (for double door DB only ) complete with insulated 100 A rating  copper bus bar, neutral bars with shrouds,  earth bar , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, ferrules,  detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure 'A' attached with this BSR

-

-

-

... More
Double door  IK-09 & IP-43 with Metal end box

-

-

-

... More
4 Way(8+12)

1

8255

8255

... More
Providing & Fixing of IP20 SMD Mid Power LED batten with integrated box (min.1200mmx40mmx60mm including reflector) with replacable driver fixture made from Powder coated Extruded aluminium housing ,Min. lumen output 4400 lm, System lumen efficacy ≥ 110 lm/Watt output, internal surge protection of 4.0 KV with Short & Open circuit protection,THD 10% , P. F.≥0.95, CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , Maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing.

-

-

-

... More
OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

4

1620

6480

... More
Making of hole in wall (brick/stone) of required and placing NP-2 RCC pipe ring of required size for housing exhaust fan and making good the same, with cement plaster required of following size. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Up to 457 mm size

2

348

696

... More
Providing & Fixing of BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan Conforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1200 mm Sweep BEE 1 Star rated (service value =4.0 to 4.5 )

4

1890

7560

... More
Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
300 mm sweep(900/1400 RPM)

2

3175

6350

... More
Electromechanical Work Part "C"

-

-

-

... More
BAR SCREEN

-

-

-

... More
SITC of BAR SCREEN size 500mm*1000mm made of SS-304 having MS bars of 6 mm thick at 10mm spacing lifting arrangement etc. complete as required by engineer incharge. Capacity :- 18.75 m3/hr Peak Flow,10 mm

2

25268

50536.33

... More
OIL SKIMMER

-

-

-

... More
SITC of PU belt& outdoor type oil skimmer 1000mm with 3 phase/single phase FHP AC Induction Electric Motor (Class F) with speed reduction gear box including making connection & testing as required by engineer incharge. Removalcapacity20-25LPH. make premier/Cutedge Engineering/ Eqv.

1

64154

64154.89

... More
EQUALIZED WASTE WATER TRANSFER PUMPS :

-

-

-

... More
SITC of IP68 continuous duty fully submersible type sewage handling pump for raw sewage transfer from equalization tank to aeration tank. The pump shall have complete CI construction, TEFC induction motor including pressure gauge, lifting arrangement for the pump. Solid handling shall be 30-40 mm including making connection & testing as required by engineer inchage. Capacity: 25 m3/hr Head : 10-12 Mtr Make- Kirloskar/ Crompton/KSB/Eqv./wilo. ( 1 Working+1 Standby )

2

94082

188165.53

... More
AIR BLOWERS:

-

-

-

... More
SITC of continuous duty IP 65/66 Tri Lobe rotary type air blowers with acoustic inclosure to supply air coupled through TEFC induction motor of suitable HP rating 400- 415V ± 10% volts, 3 phase, 50 cycles a/c supply for aeration of SBR/ EQT and SHT including making connection & testing as required by engineer incharge. Capacity : 225-240 m3/hr Make: Beta/Akash/Eqv. ( 1 Working+1 Standby )

2

234117

468235

... More
Air piping Grid:- SITC of air piping grid of required size for equlization tank SBR tank & sludge holding tank made of shall comprise of UPVC pipes 10 kg / cm2 sch - 80 submerged complete with all fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc cutting chases & making good in Plant Room. Make: Tata/Jindal

1

108292

108292.14

... More
DIFFUSERS

-

-

-

... More
SITC of Fine /coarse Non clog type aeration bubble diffusers for air dispersion system in equlization tank SBR tank & sludge holding tank capable of handling 3-5 cfm of air with oxygen transfer efficiency of 3-4% per/meter water depth.complete in all respect required by engineer incharge. Make :- Scogen/Bharat Industries/Flowsys/Eqv.

36

5068

182450.6

... More
SBR Control panel

-

-

-

... More
SITC of IP54 fully automatic PLC based SBR controller panel front access totally enclosed free standing dust & vermin proof with required protection system & PLC programing to be autocontrol Motorised valves,transmeter as per SBR Cycle including making connection & testing all complete as required by engineer incharge. Make:- Wastech/PP Aqua/ Eqv.

1

210086

210086.75

... More
DECANTER

-

-

-

... More
SITC of DECANTER SS - 304 with scum and bottom support rotaty joint, actuator with gear box comprising drives eletric motor lifiting Mechanisms, Float Switches, etc. complete with connection & testing as required by engineer incharge. CAPACITY : 25 m3/hr, DECANTING TIME :40 – 50 MINUTES, NO OF BATCH: 6.0, Make :- Wastech/PP Aqua/ Eqv.

1

700289

700289.17

... More
SITC of Level Switch Float type of required rating making connection & testing as required by engineer incharge. Make :- Banner/Eqv.

1

26416

26416.72

... More
SITC of submerged type DO meter with sensor of required rating making connection & testing as required by engineer incharge.

1

111327

111327.6

... More
Return & Surplus Activated Sludge PUMP :

-

-

-

... More
SITC of IP 68 continuous duty Submersible type Surplus Activate and return activated Sludge pump 3phase 415watt with 20-30mm solid handling. The pumps shall have CI casing, CI Impeller & CS shaft & sleeve with mechanical seal. MSEP common base frame including making connection & testing as required by engineer incharge.. Capacity :25 m3/hr @ 8-10 m head Make- Wilo/Kirloskar/ Crompton/KSB/Eqv.

2

93938

187876.76

... More
FILTER FEED PUMPS :

-

-

-

... More
SITC of IP 65/66 continous duty Horizontal type filter feed pumps for filtration pressure of 2kg/cm2 & 3.5 kg/cm2. The pumps shall be made of CI casing, CI Impellar, CS shaft & sleeve, Mechanical Seal are connected to a TEFC induction motor of suitable rating 400/440 V, 3 Phase, 50 cycles AC power supply including making connection & testing as required by engineer incharge.. . Capacity 12.5 M3/Hr.@ 30M head Make- Wilo/Kirloskar/Crompton/KSB/Eqv. (1W+1S)

2

40429

80858.13

... More
MULTIGRADE SAND FILTER (PSF) :

-

-

-

... More
SITC of vertical down flow type multi grade sand filter capable of filtering 1 cum/hour. The filter shall comprise of MSEP shell, suitable for a minimum operating pressure of 10.0 kg/sq.cm., complete with 63 mm dia MS frontal piping with butterfly valve, pressure guage, first charge of filter media. etc as required by engineer incharge.. Flow rate : 12.5 M3/Hr Filter Diameter : 1000 mm.6 mm thick shell 8mm thick top & bottom dish Filter Height : 1500 mm Make- Wastech/Eqv.

1

274340

274340.09

... More
ACTIVATED CARBON FILTER (ACF):

-

-

-

... More
SITC of vertical down flow type activated carbon filter capable of filtering 1 cum/hour. The filter shall comprise of MSEP shell, suitable for a minimum operating pressure of 10.0 kg/sq.cm., complete with 63 mm dia MS frontal piping with butterfly valve, pressure guage, first charge of filter media with activated carbon etc as required by engineer incharge.. Flow rate : 12.5 M3/Hr Filter Diameter : 1000 mm.6 mm thick shell 8mm thick top & bottom dish Filter Height : 1500 mm Make- Wastech/Eqv.

1

347191

347191.16

... More
CHEMICAL DOSING SYSTEM

-

-

-

... More
Dosing Pumps

-

-

-

... More
SITC of hypochlorite/ polyelectrolite dosing pumps with outdoor type motor of suitable rating comprising of 100 Litres capacity dosing HDPE tank making connection & testing alongwith metering (0-10 lph) for dosing pump etc as required by engineer incharge... (2W+2S) make :- Edose /Positive Metering/Eqv.

4

62809

251237.76

... More
Sodium hypochlorite & polyelectrolite Dosing Tank

-

-

-

... More
SITC of 100 Ltr Dosing HDPE Tank with Sodium hypochlorite & polyelectrolite solution along with agitator of suitable rating making inlet/outlet connection etc as required by engineer incharge. Make:-Wastach/Eqv.

2

56607

113214.51

... More
U.V. SYSTEM

-

-

-

... More
Supplying, installing, testing & commissioning of ultravilot lamp System including making connection & testing etc as required by engineer incharge. Flow Rate 12.5.0 m3/hr UV Dose 60,000 uW-sec/cm2 UV Transmission (per cm) 65% Number of Lamps 6 MOC Stainless Steel 316L Max. Operating Pressure 80 psi Quartz Jacket MOC High Purity Quartz (UVT 95%) Maximum Power Consumption (W) 730 W make :- Alfa /Eqv.

1

412232

412232.08

... More
CENTRIFUGE

-

-

-

... More
Supply, erection & commissioning of Centrifuge With Compraise 24" Dia SS 304 Basket, MOC SS304 With Motor With PP Filter Beg Complete including making connection & testing etc as required by engineer incharge.. Make:- Skylab/Eqv.

1

462046

462046.46

... More
CENTRIFUGE FEED PUMP:

-

-

-

... More
SITC of out door continuous duty screw type centrifuse/ Sludge disposal pump for the disposal of sludge to tanker or to sludge dry beds. The pumps shall have CI casing, SS stator Impeller & SS shaft & sleeve with mechanical rotary shaft seal connected by a flexible tier type coupling to TEFC induction motor of suitable rating mounted on a common channel base-plate with coupling guard including making connection & testing etc as required by engineer incharge.. Capacity 2m3/hr @ 40 M Head. Make-Wilo/Roto/Rotomac/Eqv.

1

106270

106270.69

... More
Flow Meter

-

-

-

... More
Providing & fixing on line Electro magnetic type flow meter cum Totaliser for Monitoring the total flow, Flow rate. etc. Including electrical wiring from panel to flow meter. Complete with all type of Plumbing & Electrical connections, accessories, wiring, conduits & supports complete with all respect ncluding making connection & testing etc as required by engineer incharge. Make: Unitech/ Eqv.

1

68834

68834.42

... More
PH METER

-

-

-

... More
Supply Instllation & Commissioning of Online pH Meter ncluding making connection & testing etc as required by engineer incharge Make : Embark /Aster/Digital/ Eqv.

1

39247

39247.7

... More
ROTA METER

-

-

-

... More
Supply Instllation & Commissioning of Online Rotameter ncluding making connection & testing etc as required by engineer incharge Make : Aster/Digital/ Eqv

1

7207

7207.99



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.