Military Engineer Services Tender

... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Comprehensive Maintenance Vcbs Rmus, Go/dos Ht Cable Transformer And Connected Items Under Ge Bharatpur At Bharatpur Mil Stn in Bharatpur, Rajasthan, with an estimated contract value of Rs. 45,00,000. The bid opening date for this tender is 26-10-2026 and the last date for bid submission is 23-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender - Rajasthan Tender

Opening Date26 Oct 2026
Closing Soon23 Nov 2026
Tender Amount₹ 45,00,000 
Notes
Download

Costs

Description

Comprehensive Maintenance Vcbs Rmus, Go/dos Ht Cable Transformer And Connected Items Under Ge Bharatpur At Bharatpur Mil Stn

Contact

Unlock the Tender details

GEM & Bid Advisory Services

Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

Unlock the Tender details
... More
Removing of excavated material (soil) to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.50metre above the starting point complete all as specified.

-

-

-

... More
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified.

-

-

-

... More
M & L Sand cushioning to XLPE under ground cable with screened and washed sand and punning to provide a required cover complete all as specified.

-

-

-

... More
Taking down ACSR over head Aluminium conductor steel reinforced of any size all as specified and directed including stringing/ dismatling through RCC/Steel tubular poles, fixing on insulators, jumpering with aluminium binding wire etc complete all as specified.

-

-

-

... More
Taking out old u/s HT cable from trench/pole/wall/pipe etc as per site complete all as specified.

-

-

-

... More
Supply, laying and commissioning XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 11000 volts grade IS-7098 marked, suitable for HT 11 KV (E) System laid in trenches/ ducts/ encased in GI pipe/ fixed to poles including jointing & testing complete all as specified of following cross sectional area :-

-

-

-

... More
(a) 95 Sqmm, 3 core cable

-

-

-

... More
(b) 120 Sqmm, 3 core cable Note: Excavation & earth work, Sand cushioning, Bricks, GI tubing & Clamps shall be measured & paid seperately under relevent items of BOQ.

-

-

-

... More
M/L ACSR over head Aluminium conductor steel reinforced of any size all as specified and directed including stringing/ dismatling through RCC/Steel tubular poles, fixing on insulators, jumpering with aluminium binding wire etc complete all as specified.

-

-

-

... More
M&L for PCC (1:3:6) type C1 (using 20mm grade stone aggregate) in base & foundation of pole including necessary form work complete all as specified.

-

-

-

... More
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate in coping of existing/new poles / foundation for poles, struts, posts etc including necessary form work, finished the exposed surfaces fair and even without using extra cement complete all as specified.

-

-

-

... More
Dismantling and taking out old unserviceable HT PCC pole 11 Mtr long complete all as specified.

-

-

-

... More
Supplying, Erecting and fixing in replacement Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" wide, complete all as specified.

-

-

-

... More
Dismantling of cross arms, bracing, support, clamps, nut & bolt of mild steel channel or angle sections etc complete all as specified.

-

-

-

... More
M&L cross arms,bracing ,support clamps and back plate fabricated from structural steel section including nuts bolts washers welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat one under coat and one finishing coat of paint complete all as specified.

-

-

-

... More
Dismantling and taking down existing HT insulators of any type and size complete all as specified.

-

-

-

... More
M&L Disc type insulator, Porcelain, vitreous brown, white or green single disc assembly, 145mm high & 255mm dia ball & socket type, for tension clamps for conductors, working pressure 11000 volts complete all as specified.

-

-

-

... More
M&L pin type, porcelain, vitreous brown, white or green insulator (HT), 150mm height and 150 mm dia, 11000 volts grade including one galvanised MS spindle, two GI washers and one GI nut complete all as specified.

-

-

-

... More
Supply of post insulator single pole with GI post for holding fixed/moving contact assemby including fixing arrangment suitable for Air break gang oprated switch 400 Amps, 11000 volts grade complete all as specified.

-

-

-

... More
M&L for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and fixed with MS clamps, bolts and nuts of approved size, for HT, 25X20 cm size complete all as specified.

-

-

-

... More
Supply & fixing or laying galvanised steel tubing medium grade (ISI marked) for protection of under ground cable on poles / walls under road crossing etc of 100mm bore sizes including taking down existing pipe complete all as specified.

-

-

-

... More
Boring of holes under road, pavement, hard standing by manually boring for laying under ground pipe up to 100mm dia complete all as specified. Note :- GI pipe shall be measured and paid in concern Item.

-

-

-

... More
M&L for cable end termination, jointing kit, HT 11 KV grade, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade incl taking down complete all as specified of following sizes :-

-

-

-

... More
(a) 50 sqmm to 95 Sqmm x 3 core

-

-

-

... More
(b) 120 sqmm to 185 Sqmm x 3 core

-

-

-

... More
M&L for cable end termination, jointing kit, HT 11 KV grade,heat shrinkable, indoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade incl taking down complete all as specified of following sizes :-

-

-

-

... More
(a) 50 sqmm to 95 Sqmm x 3 core

-

-

-

... More
(b) 120 sqmm to 185 Sqmm x 3 core

-

-

-

... More
M&L for cable, jointing kit, HT 11 KV grade, heat shrinkable, straight through type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade incl taking down complete all as specifi\ed and directed of following sizes :-

-

-

-

... More
(a) 50 sqmm to 95 Sqmm x 3 core

-

-

-

... More
(b) 120 sqmm to 185 Sqmm x 3 core

-

-

-

... More
Dismantalling of Air break, gang operated, , outdoor, horizonal mounting type complete all as specified.

-

-

-

... More
Supply, installing, testing and commissioning of Air break, gang operated, triple pole switch, outdoor, horizonal mounting type (ISI marked) , mechanically operated, mounted on 15 insulators with 9 insulator for moving contact of GOD and 6 insulator for fuse unit with operating mechanism worked from ground level with locking arrangments including Godrej pattem 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections complete including taking down old U/S all as specified of following rating :-

-

-

-

... More
(a) 200 amp rating complete with fuse carriers and HT fuse elements.

-

-

-

... More
(b) 400 amp rating complete with fuse carriers and HT fuse elements.

-

-

-

... More
Supply and fix lightening arrestor expulsion type complete with all fittings Distribution class discharge capacity 65 KA as per IS 3070 Pt-3 1993 suitable for 11000 volts incl taking down complete all as specified.

-

-

-

... More
Dehydration / filtration of transformer oil existing transformer installed at site with portable plant to improve the dielectric strength 40 to 60 KV during filling after initial filtration including testing of dielectric strength after dehydration at site with testing and completion complete all as specified.

-

-

-

... More
Supply & filling of transformer oil in transformer at site for toping up the level of oil having dielectric strength 60 KV at 2.5 mm gap during filling after initial filtration complete all as specified.

-

-

-

... More
M&L for disconnecting of defective transformer (in door/out door type ) 11 KV/433 volts copper wound from power mains and dismantling the same from 2/4 pole structure/ platform mounted, uploading and transporting by using crane and vehicles the same to authorised workshop and opening the transformer cover, draining out of tranformer oil and keep safely for reuse after filtration, assembling, removing of the burnt parts i.e tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all partsincluding taking out HT/LT leg coil core tank and cooling tubes, painting the inner side tank by zinc chromate paint, spray painting outside by enemelled smoke gray coloure paint and preparing the same for re-assembling after ovening of core with coil and carrying out required repair and Transporting and re-installation on existing 2/4 pole structure/ platform with neccessary fixing arrangment including connecting up electrically, commissioning and testing complete all as specified of the following capacity complete (HT/LT limb case measured and paid seperately)

-

-

-

... More
(a) 50 KVA to 200 KVA capacity

-

-

-

... More
(b) 250 KVA to 500 KVA capacity

-

-

-

... More
Supply only following parts for indoor/out door transformer :-

-

-

-

... More
(a) LT limb copper coil with triple papper coated and varnish insulated complete all as specified.

-

-

-

... More
(b) HT limb copper coil with triple papper coated and varnish insulated complete all as specified.

-

-

-

... More
Supply only HT porecelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-

-

-

-

... More
(a) 50 KVA to 250 KVA capacity

-

-

-

... More
(b) 315 KVA to 500 KVA capacity

-

-

-

... More
Supply only LT porecelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for following cap transformer :-

-

-

-

... More
(a) 50 KVA to 250 KVA capacity complete all as specified.

-

-

-

... More
(b) 315 KVA to 500 KVA capacity complete all as specified.

-

-

-

... More
Supply only tap changer switch 11 KV complete with rod and gasket for following cap transformer :-

-

-

-

... More
(a) 50 KVA to 250 KVA capacity

-

-

-

... More
(b) 315 KVA to 500 KVA capacity

-

-

-

... More
Opening of transformer cover at site for carrying out repairs such as replacment of bushing rods gasket, insulators and minor spare parts etc and re-assembling after carrying out required repair in the transformers complete all as specified. (Note :- Bushing rods shall be measured and paid separately)

-

-

-

... More
Taking out old unservisiable silica gel and fill the new silicate into the breather complete all as specified.

-

-

-

... More
S & F in replacement of neon type indicating lamp (R Y & B) - 01 Set complete all as specified.

-

-

-

... More
M&L for uprooting up to 30 cm depth grass/weeds/plant by scrapping soil in order to made free ground from all sort of vegetation including supply & spray chemical (glycel 41% Sl or equivalent) for prevention of growth of weed and grass in electrical sub station with spray gun as per the manufacturer's instructioned complete all as specified.

-

-

-

... More
Supply and spread and leveling Grading 3 coarse Aggregate in loose filling over the surface of guage 20 mm nominal size in the installation yard complete all as specified.

-

-

-

... More
Supply and spread and leveling Grading 2 coarse Aggregate in loose filling over the surface of guage 40 mm nominal size in the installation yard complete all as specified.

-

-

-

... More
M&L Earthing complete as per electrical plate No 3 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0mm, burried directly vertically in ground in a pit of depth not less than 2.25 metres below ground level with the top edge of earth plate at a depth not less than 1.5m below normal ground level connected to and including galvanised iron or steel earth streep lead 32X6mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel earthing wire protected by galvanised iron or steel pipe 40mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20mm bore GI medium grade including excavation and earth work in any type of soil, PCC pit and RCC cover complete all as specified and tested complete all as specified. Notes :- (i) The concrete pit shall be PCC (1: 3:6), 20mm thick precast cover slab of RCC (1:2:4) type B1 using 20mm graded stone aggregate with suitable mild steel handle in lieu of cast iron cover shown in electrical plate No-03 of MES SSR Part-I. Reinforcement in RCC cover shall be 8 mm dia TMT steel bar @ 150mm c/c both ways. (ii) Item includes the cost of 7.5 mtr GI pipe for protection of earth lead/strip. Any varriation in length shall be measured and paid through relevent item of schedule 'A'.(iii) Item includes the cost of 7.5 mtr earth lead strip. Any varriation in length shall be measured and paid through relevent item of schedule 'A'.(iv) Earth eletrode shall be surrounded by adequate quantity of charcoal dust and salt to packedthickness of 150mm on all sides as specified.

-

-

-

... More
Material and labour for replacement of unserviciable existing earthing with bore well earthing with the help of mechanical boring machine of 150 mm dia-30 mtr depth supply and fix 160 mm dia (O.D), UPVC pipe 6 kg/sqcm rating -06 mtr long with the help of suitable size clamp with nut bolt and washer -01 No including charcoal dust ,salt fill in bore well for earth conductivity M&L for covering of bore well with PCC (1:2:4) type B-1 / Brick masonry pit of size 45x45x45 cm complete and give the minimum earth test result below 1 ohm complete all as specified. Note :- (i) The earth pit shall be refilled by boulders free from vegetable soil.(ii) Earthing shall be tested by contractor in presence of Engr-in-charge.Record shall be maintained.Payment shall be admissible only after satisfactory test results.

-

-

-

... More
Supply & fixing in replacement of GI tubng 50 mm dia medium grade in incl necessary fittings for lowering in borewell of depth upto 30 mtr complete all as specified.

-

-

-

... More
Earth continuty conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required by using galvanised iron 32x6 mm strip as earthing lead complete all as specified.

-

-

-

... More
M & L for Repir / Maintenance of drawout type / trolly mounted HT VCB/RMUs 11 KV by cleaning the VCB/RMU by using air blower, tightening of connections / controls , checking of all fuses/,spray painting outside by enemelled smoke gray coloure paint/ sealing of VCB/RMU at bottom, repairing of mechanical parts, oiling / greesing of all moving parts and carrying out following checks for smooth functioning complete all as specified. (a) Visual Inspection. (b) Checking of functional locks, interlocks, signalling devices and auxillery devices. (c) Checking of suitability and correct operations of protections, control instruments and electrical connection of the circuit breaker operating mechnasim. (d) Checking of Tripping Mechanism Operation. (e) Spring Charging Limit Switch Operation. (f) Checking with stand voltage on the auxillary circumstances. (g) Checking of with stand voltage at power frequency. (h) Checking of Breaker ON/OFF Operation manually & electrically. (i) Testing of vacuum Bottle Integrity. (j) Relay Testing. (k) Checking of the resistance of the main circumstances. (l) Verification of wiring. Note:- (i)Work shall be executed by the authorised service center of manufacturer. (ii) Spare part if found deffective will be measured & paid seperatly as supply & fix in repair under respective item of this BOQ

-

-

-

... More
Supply and fix in repair battery 12V DC fixed to Metering module of RMU for auto charging of spring with compatible existing system all as specified & directed by Engg in Charge.Make:- C&S/Crompton/CG

-

-

-

... More
Supply and fix in repair contactor for 24 V DC fixed to SF 6 type VCB/RMU of any capacity & connecting complete with compatible existing system complete all as specified. Make:- C&S/Crompton/CG/C Sec

-

-

-

... More
Supply and fix in repair open push button fixed to SF6 type VCB/RMU of any capacity & connecting complete with compatible existing system complete all as specified. Make:- C&S/Crompton/CG/C Sec

-

-

-

... More
Supply and fix in repair close push button fixed to SF6 type VCB/RMU of any capacity & connecting complete with compatible existing system complete all as specified. Make:- C&S/Crompton/CG/C Sec

-

-

-

... More
Supply and fix in repair VPIS Unit, 9-15 kV fixed to SF6 type VCB/RMU of any capacity & connecting complete with compatible existing system complete all as specified. Make:- C&S/Crompton/CG/C Sec

-

-

-

... More
Supply and fix in repair Trivector meter for VCB/RMU including disconnecting the existing and connecting the new one with necessary wiring complete with compatible existing system complete all as specified. Note : Old meter to be deposit to MES Yard for BER Process

-

-

-

... More
Supply and fix in repair trip coil of PR 512 type relay for SF6 type VCB/RMU of any capacity & connecting complete with compatible existing system complete all as specified. MakC&S/Crompton/CG/C Sec

-

-

-

... More
S&F in repair complete intenal wiring for PR 512 type relay with copper conductor, PVC insulate cable for SF6 type VCB of any capacity as per manufacturer instruction with compatible existing system complete all as specified.

-

-

-

... More
Supply and fix in repair locking device kit for door assembly of outdoor type Ring Main Unit with compatible existing system complete all as specified.

-

-

-

... More
Supply & fix in reapir complete GASKET rubber tube type of outdoor type Ring Main Unit any type with compatible existing system complete all as specified. Make:- C&S/Crompton/CG/C Sec

-

-

-

... More
Supply and fix in reapir 'K' Mechanism of SF6 type Ring Main Unit with compatible existing system complete all as specified. Make:- C&S/Crompton/CG/C Sec

-

-

-

... More
Supply and fix in reapir '3PAE' Mechanism of SF6 type Ring Main Unit with compatible existing system complete all as specified. Make:- C&S/Crompton/CG/C Sec

-

-

-

... More
Supply and fix in reapir 'A' Mechanism for breaker assembly of SF6 type Ring Main Unit with compatible existing system complete all as specified. Make:- C&S/Crompton/CG

-

-

-

... More
Supply and fix in repair Current Transformer 250 / 1A, 2.5 VA, 5P10 for metering module of Ring Main Unit with compatible existing system complete all as specified. Make:- C&S/Crompton/CG

-

-

-

... More
Supply and fix in repair Current Transformer 150/ 1A, 2.5 VA, 5P10 for metering module of Ring Main Unit with compatible existing system complete all as specified. Make:- C&S/Crompton/CG

-

-

-

... More
Supply, installation, testing and setting of Digital Protection relay with Instant trip for phase and earth fault, relay to be fixed in existing 11 KV VCB drawout type, including taking down old relay complete all as specified.

-

-

-

... More
Tracing out the Fault in existing U/G HT cables network under any depth below or above the existing earth surface by earth work, fault locator machine, expertise staff incl taking down and repair the same by required spares materials in existing position whenever informed by Engr -in-charge or JE E/M in the AOR at Bharatpur incl testing on completion. Note : 1. The all T&P and earth work shall be included in quoted rates and no extra cost shall be claim by the contractor. 2. The neccessary Materials any type required to repair the fault will be measured and paid seperatly under relevent item of BOQ.

-

-

-

... More
M&L for HT cable route indicator made out of PCC(1:2:4) type B-0(12.5mm graded aggregate of size 1000mm (H) x 120mm (W) x 80mm (thick), painted with orange colur lettering synthetic enamel paint and embedded in PCC block (1:3:6) type C2 (using 40mm grade aggregate ) of size 150mm x 150mm x 200mm including necessary excavation for PCC block, placed at interval of 30Mtr complete all as specified.

-

-

-

... More
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 KV for electrical purpose as suitable forelectrical shock safety of size 2x1m complete all as specified.

-

-

-

... More
M&L for Replacement of broken earth chamber cover by providing RCC cover of 1:2:4, Type B-1, using 20mm graded stone aggregate of size 550mmx550mmx40mm thick, reinforced with 8mm dia MS TMT bars @100 mm C/C both ways with MS handle 12mm dia complete all as specified.

-

-

-

... More
S & F Fibre insulation boards, of thickness of 18 mm ,ordinary type,. and fixed to timber frame / cross arm work with proper nut & bolts complete all as specified.

-

-

-

... More
Supplying, fabricating and fixing sign board of aluminium composite panel made out of 3 mm thick aluminium composite panel material consisting of 2.5 mm thick mineral core sandwiched between two Aluminium sheets (each 0.25 mm thick), high intensity reflective maintenance free sheet of size 1500mmx1200mm, including writing letters / site map as per requirement / location with high reflective sheet / tape, colour & design as approved fixed on square of size 2.5 to 3.0 mtr (02 Nos) vertical and 150mm x 150mm (02 Nos) horizontal steel frame work complete all as specified. Note:- Steel Frame and earth work for grouting of steel frame in PCC will be included in quote rate.

-

-

-

... More
M&L for chequred cement concrete tiles 200x200x250mm thick set jointed and pointed in neat cement slurry over and including 15mm thick screened bed in CM 1:6 and dismantling existing tiles complete all as specified.

-

-

-

... More
M & L for Repir / Maintenance of existing two/four pole GODs of any any type and capacity by Providing grease , tightening of connections, checking of all fuses/, repairing of mechanical parts, oiling / greesing of all moving parts and carrying out checks of all type of insulators for smooth functioning complete all as specified. Note : Necessary parts required for replacement will be measured and paid seperately under appropriate items of BOQ.

-

-

-

... More
M&L for painting of transformer of any capacity and size by using sand papers and applying one coat suitable primer and applying of synthetic enameled paint through spray gun by arranging compressor at site with adequate power generating set complete all as specified.

-

-

-

... More
M&L for painting steel tubular poles 11 Mtr height with two coats of synthetic enamel paint alternatively with black and yellow colour , after copping and remaining portion with aluminium paint but including brckets, clamp & cross arms (i.e single poles, 2/3/4/6 pole structure) etc complete all as specified.

-

-

-

... More
M&L for calibration of IDMT microprocessor based nemuric relay fixed in 11 KV HT VCBV/RMU panel by primary and secondary injection method and setting the relay tripping timing in advance to match the outgoing load on the incoming and outgoing feeders complete all as specified. NOTE : (i) individual Breaker VCB/RMU shall be considered as one unit and above job is to be carried out unitwise. Above job woll be carried out by licenced technician as approved by GE. (ii) Any accident/mishappening occurred during the execution of work shall be responsibility of Contractor. (iii) All necessary tools & plants required to carry out above job will be provided by contractor and the cost of the same deemed to be included in quoted reate.

-

-

-

... More
S&F silica gel breather assembly with fresh silica gel for 63 KVA to 500 KVA transformers complete with end fitting complete all as specified.

-

-

-

... More
Brick work for construction of platform with steps for transformer with sub class B bricks straight or curvced on plan exc 6mm radius built in CM 1:4 complete all as specified.

-

-

-

... More
M&L rendering 15mm thick in CM (1:4) on fair faces or concretre surface finsihed even & smooth without using extra cement including 02 x coats of white wash complete all as specified.

-

-

-

... More
Demolition of brick brick work or stone/bolder masonry built in line mortar including all arches pillars and PCC articles etc complete all as specified.

-

-

-



Evaluation Notes How It Works ?

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.