The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Repair And Maint Of 33kv Network And Other Allied Work Incl Improvement Of Infrastructure And Repair/ Maint/ Assessment/ Calibration Of Ht Switch Gears At Sector A, B And C At Army Area Jodhpur Under Ge (army) No.01 in Jodhpur, Rajasthan, with an estimated contract value of Rs. 60,00,000. The bid opening date for this tender is 11-06-2026 and the last date for bid submission is 23-12-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender - Rajasthan Tender

Opening Date11 Jun 2026
Closing Date23 Dec 2026
Tender Amount₹ 60,00,000 
Notes
Download

Costs

Description

Repair And Maint Of 33kv Network And Other Allied Work Incl Improvement Of Infrastructure And Repair/ Maint/ Assessment/ Calibration Of Ht Switch Gears At Sector A, B And C At Army Area Jodhpur Under Ge (army) No.01

Contact

Unlock the Tender details

GEM & Bid Advisory Services

Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

Unlock the Tender details
... More
Supply and fix in replacement of microprocessor based relay of IDMT relay including testing, setting of relay for proper tripping according to load all as specified and directed by Engineer-in-Charge. Note : 1. Calibration certificate from competent protection team will be submitted by contractor. 2. Rates are deemed to include synchronisation of protection relay with main incoming 33 KV electric supply from JVVNL i.e. Co- ordination of power system incl setting of 11 KV in coming and out going circuits enabling the system to respond quickly for arresting the tripping to particular outgoing circuit. the job may include liaison with JVVNL for acquiring the tech data relative to relay/CT setting to achieve desired Co-ordination of the system all as directed at site and to the entire satisfaction of Engr in charge. Rates are also deemed to include synchronisation of 33 KV and 11 KV VCB's again after 3 months of job completed. A certificate in this regard to be submitted by the contractor in each case. 3. All Test equepments/T&P reqd for carry out calibration of relays etc should be deemed to be included in quoted rates.

3

3100000

-

... More
Supply and fix in replacement of terminal bushing assembly (spout bushing) 11 KV VCB complete all as specified and directed by Engineer-in-Charge.

6

3100000

-

... More
Supply and fix in replacement of Tulip contact (isolating contact 630 A) 11 KV VCB/RMU complete all as specified and directed by Engineer-in-Charge.

5

3100000

-

... More
Supply and fix in replacement of circuit spout RYB (bus bar insulators) 61 mm for 11 KV VCB complete all as specified and directed by Engr-in-Charge.

5

3100000

-

... More
Supply and fix in replacement of loading spring and main link for 11 KV VCB complete all as specified and directed by Engr-in-Charge.

10

3100000

-

... More
Supply and fix in replacement of spring charging gear for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

10

3100000

-

... More
Supply and fix in replacement of common operating shaft for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

5

3100000

-

... More
Supply and fix in replacement of trip shaft for 11 KV VCB/RMU complete all as specified and directed by Engineer-in-Charge.

6

3100000

-

... More
Supply and fix in replacement of Tripping coil assembly 110 V DC for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

10

3100000

-

... More
Supply and fix in replacement of Closing coil assembly 110 V DC for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

10

3100000

-

... More
Supply and fix in replacement of trip roller for 11 KV VCB/RMU complete all as specified and directed by Engineer-in-Charge.

8

3100000

-

... More
Supply and fix in replacement of vaccum interupter bottles for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

5

3100000

-

... More
Supply and fix in replacement of anti pumping relay for 11 KV VCB complete all as specified and directed by Engr-in-Charge.

5

3100000

-

... More
Supply and fix in replacement of Auxiliary Contactor 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

10

3100000

-

... More
Supply and fix in replacement of in replacement of Auxiliary switch 4 pole for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

10

3100000

-

... More
Supply and fix in replacement of spring charging motor for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

7

3100000

-

... More
Supply and fix in replacement of terminal protector or push-on-boot for 11 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

8

3100000

-

... More
Supply and fix in replacement of current Transformer including testing, calibration of 11 KV single phase indoor, (metering & protection ) for 11 KV VCB/RMU ratio 150/75 / 5-5 Amp complete, IS2705/1992 and IEC 60044-2 and all as specified and directed by Engr-in-Charge.

5

3100000

-

... More
Supply and fix in replacement of Potential Transformer including testing calibration of 11 KV single phase indoor, Epoxy cast PT of ratio 11KV/√3/110/√3 class 1.0, burden 100 VA/Phase insulation level 28/75 KV, voltage factor 1.2 Cont and 1.5 for 30 Sec, confirming to IS-3156 incl suporting insulator complete all as specified and directed by Engineer-in-charge.

5

3100000

-

... More
Supply and fix in replacement of T2 Functional card of same Make and modle of existing VCB/RMU and all as specified and directed by Engr-in-Charge.

7

3100000

-

... More
Maintenance and complete Repair/Calibration of 33 KV VCB/RMU rating upto 800 Amp suitable for repturing capacity 350 MVA and remote control switch including dismantling of operating mechanism parts, well cleaning with petrol & CRC-226 and replacing moving parts including reassembling of parts after well cleaning of complete panel board, main bus bar, de-carbonizing all joints bus bar, CTs & PTs and spouts metal parts and making VCB perfect operating in manual and electric mode including all routine and preventive maintenance complete all as specified and directed by Engineer-in-Charge. Notes: (i) Spare parts required for replacement obtained approved OEM suitable capacity shall be measured and paid separately under respective items (Srl No.25 to 39) of costed schedule of works. (ii) Calibration shall be done by authorised service technician/engineer and test report shall be submit accordingly. (iii) Single RMU each breaker/VCB shall be considered as one Job

7

3100000

-

... More
Supply and fix in replacement of terminal bushing (spout bushing) 33 KV VCB complete all as specified and directed by Engineer-in-Charge.

2

3100000

-

... More
Supply and fix in replacement of Tulip contact (isolating contact 630 A) 33 KV VCB/RMU complete all as specified and directed by Engineer-in-Charge.

6

3100000

-

... More
Supply and fix in replacement of Circuit spout RYB (bus bar insulators) 61 mm for 33 KV VCB complete all as specified and directed by Engr-in-Charge.

8

3100000

-

... More
Supply and fix in replacement of loading spring and main link for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

3

3100000

-

... More
Supply and fix in replacement of spring charging gear for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

2

3100000

-

... More
Supply and fix in replacement of operating gear mech 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

3

3100000

-

... More
Supply and fix in replacement of trip shaft for 33 KV VCB/RMU complete all as specified and directed by Engineer-in-Charge.

4

3100000

-

... More
Supply and fix in replacement of Tripping coil with assembly 110 V DC for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

4

3100000

-

... More
Supply and fix in replacement of Closing coil with assembly 110 V DC for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

3

3100000

-

... More
Supply and fix in replacement of trip roller for 33 KV VCB/RMU complete all as specified and directed by Engineer-in-Charge.

2

3100000

-

... More
Supply and fix in replacement of vaccum interupter bottles for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

3

3100000

-

... More
Supply and fix in replacement of anti pumping relay for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

2

3100000

-

... More
Supply and fix in replacement of Auxiliary Contactor 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

2

3100000

-

... More
Supply and fix in replacement of Auxiliary switch 4 pole for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

4

3100000

-

... More
Supply and fix in replacement of spring charging motor for 33 KV VCB/RMU complete all as specified and directed by Engr-in-Charge.

2

3100000

-

... More
Material and labour for repair/ replacement of defective compete control wiring of current transformers, ampere meter, voltmeter, potential transformers, circuits of indoor/Outdoor type 33/11 KV VCB'S using 2.5 sqmm copper flexible PVC insulated wire and suitable size of copper lugs and thimbles and connector all as directed at site by Engr-in-Charge.

1

3100000

-

... More
Repair & replacement of unserviceable of male, incoming contact (moving ) 06 sets & female out going 06 sets of VCB 11KV including dismantling of existing & fixing new upto satisfactory complete all as specified and directed by Engineer-in-Charge. Note :- Contractor should visit the site to know the exact scope of the job for above items of BOQ before quoting rates. No claim arising out of any error or inaccuracy in understanding the scope of work shall be enterained.

3

3100000

-

... More
S&F in Replacement of existing u/s under ground control copper cable PVC insulated and PVC sheathed 1100 Volt grade of size 2.5 Sqmm 2 core including necessary excavation and earth work complete all as specified and directed by Engineer-in-Charge.

15

3100000

-

... More
S&F in Replacement of existing u/s under ground control copper cable PVC insulated and PVC sheathed 1100 Volt grade of size 2.5 Sqmm 4 core including necessary excavation and earth work complete all as specified and directed by Engineer-in-Charge.

100

3100000

-

... More
S&F in Replacement of existing u/s under ground control copper cable PVC insulated and PVC sheathed 1100 Volt grade of size 2.5 Sqmm 12 core including necessary excavation and earth work complete all as specified and directed by Engineer-in-Charge.

100

3100000

-

... More
Supply and fixing in replacement of HT 11 KV RMU operating mechanism suitable to open/close/grounding the breaker including all fixing arrangements and made serviceable upto the satisfaction of complete all as specified and directed by Engineer-in-Charge.

5

3100000

-

... More
Supply and fixing in replacement of HT 33 KV VCB/RMU operating mechanism suitable to open/close/grounding the breaker including all fixing arrangements and made serviceable upto the satisfaction of complete all as specified and directed by Engineer-in-Charge.

2

3100000

-

... More
Supply, installation, testing and commissioning in replacement of outdoor type oil cooled single phase HT Potential Transformer (PT) suitable for 33 KV / 110 Volt outdoor type, 3 Phase system, 15 VA burden for protection (accuracy class 1) as per IS: 2705-1992 complete with necessary connections etc as required complete all as specified and directed by Engineer-in-Charge.

1

3100000

-

... More
Supply and fix in replacement of 11 KV RMU PT fuse 0.5 Amps complete all as directed by Engr-in-Charge.

8

3100000

-

... More
Supply and fix in replacement of over current and earth fault relay operated on self-energize for 11/33 KV RMU suitable to HT swichgear complete with complete wiring and testing complete all as specified and directed by Engineer-in-Charge. Note :- Operational Test @ 70%, 85%, 100% and 110% of 110V DC 2. Power Frequency HV Tests for 1 minute Main circuits 3. Dielectric Tests on auxiliary & control circuits for 1sec 4. Design and Visual Checks 5. Measurement of contact resistance of main circuit in µ 6. Closing & Tripping Timing 7. Checking wiring of circuits and their contacts 8. Insulation resistance of complete wiring circuit with all Equipment mounted on the panels 9. Checking of operational protective schedule, instruments & meters 10. Checking of phase faults between R&Y, Y&B and B

2

3100000

-

... More
Supply and fix in replacement of over current and earth fault relay operated on 20 to 110 Volts DC supply, for 11/33 KV VCB/RMU suitable to HT swichgear complete with complete wiring and testing complete all as specified and directed by Engineer-in-Charge. Note :- Operational Test @ 70%, 85%, 100% and 110% of 110V DC 2. Power Frequency HV Tests for 1 minute Main circuits 3. Dielectric Tests on auxiliary & control circuits for 1sec 4. Design and Visual Checks 5. Measurement of contact resistance of main circuit in µ 6. Closing & Tripping Timing 7. Checking wiring of circuits and their contacts 8. Insulation resistance of complete wiring circuit with all Equipment mounted on the panels 9. Checking of operational protective schedule, instruments & meters 10. Checking of phase faults between R&Y, Y&B and B

2

3100000

-

... More
Supply and fix in repair L1, L2, and L3 Digital phase indicator ,input current-1Amp or 5 Amp, Acc Class : CL 1.0 complete all as specified and directed by Engineer-in-charge. Model Conserv EM 6436 of schneider or its equivalent

4

3100000

-

... More
Supply and fix Master Trip relay suitable for 33/11 KV VCB Panel complete all as specified and directed by Engr-in-Charge.

4

3100000

-

... More
Supply and fix panel alarm announciator as per existing make and capacity complete all as specified and directed by Engr-in-Charge.

1

3100000

-

... More
M&L for checking, tightening & replacement of jumpers, clamps connectors of bus bar for the transformer in the 33kv tower /11kv on poles etc complete all as specified and directed by Engr-in-charge. Nopte :- Quoted Rates shall be deemed to include of minor consumable items, i.e Nuts bolts, Control wires, PVC tapes, Welding Job, cotton waste & cleaning clothes, petroleum jelly, grease, lubricating oil, emery paper, T & P items etc.

10

3100000

-

... More
M&L for removal of bird nest and foreign material from the 33/11 kv overhead line complete all as specified and directed by Engineer-in-charge.

15

3100000

-

... More
Supply fix in replacement of HT 33 KV, terminal protector, right angle, insulation boot including accessories suitable for XLPE insulated earthed cable of size 120-185 sqmm complete all as specified and directed by Engr-in-Charge.

3

3100000

-

... More
Supply fix in replacement of VCB Pole assessbly outdoor type 33000 Volts suitable for existing as per site and same make complete all as specified and directed by Engr-in-Charge. Note: Contractor may be visit the site before quoting the rate and work has to be completed upto entire satishfaction of Engr-in-Charge.

2

3100000

-

... More
Repair and maintenance, cleaning, servicing, and calibration of battery charger at main receiving station including replacement of faulty spares such as 220/110V AC transformer having current rating 5 Amps, PCB for main supply, PCB for float and boosting charging, variac variable transformer of suitable size, HRC fuses with fuse base, MCBs, indicator, voltmeter, ammeter etc. or any other spare required to made serviceable the battery charger complete all as specified and directed by Engineer-in-Charge. Note: Contractor may be visit the site before quoting the rate and work has to be completed upto entire satishfaction of Engr-in-Charge.

2

3100000

-

... More
Material and labour for SF6 gas filling into RMU of any way indoor/outdoor type complete all as specified and as directed by Engr-in-Charge.

10

3100000

-

... More
Supply and fixing in replacement of U/S breaker control (TNC) switch suitable for HT switchgears complete all as specified and directed by Engineer-in-Charge.

5

3100000

-

... More
Supply and fixing in replacement of unserviceable LED type lamp indicator (Red/Yellow/Blue) suitable for 110 Volt DC in HT switchgear complete all as specified and directed by Engineer-in-Charge.

11

3100000

-

... More
Supply and fixing in replacement of DC power pack incl charger unit 230V AC input and 24V DC out put, 5Amp including connecting wire/accessories complete all as specified and directed by Engineer-in-Charge.

5

3100000

-

... More
M&L in replacement of 33 KV rated horizontal mounting 400 / 600 Amp Gang operated Air break off load, disconnecting switch, Tripple pole, each pole consists of galvanized steel base, HT Insulators as per BSS./I.S non-ferrous knife and spring loaded contacts, arcing horns of adequate section to break magnetizing current of the transformers horizontal GI pipe of adequate lenghth for phase separation, adequate length of GI pipefor operation from ground level and operating handle complete in both OFF and ON position complete all as specified. conform to IS : 9385 complete all as specified and directed by Engineer-in-Charge.

3

3100000

-

... More
Material and labour in replacement of old unserviceable HT 33 KV lightening arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp complete all as specified and directed by Engineer-in-Charge.

3

3100000

-

... More
Supplying, fabricating & fixing structural mild steel channel, angle iron, flat iron and brackets etc for fabrication of cross arms, bracings, supports, D-clamps, stiffeners, eye hooks, bolts, pole clamps and plates including nuts, bolts and washers, welding cold or hot drilling holes for insulators bolts in any shape or size, and febrication of 33 KV tower as per existing height as indicated or directed and inclusive of one red oxide prime coat, one under coat and one finishing coat of aluminium paint complete (Insulators to be measured and paid for separately under respective items).complete all as specified and directed by Engineer-in-Charge.

4

3100000

-

... More
Testing / fault detection of under ground cable by authorised agency with Computerised Fault Detection Van complete to find the fault location for 33/11/0.433 KV rated UG cables complete all as specified and directed by Engineer-in-Charge. at site. Note :- Any excavation and earth work and cable joint work involved shall be measured and paid separately against respective item.

18

3100000

-

... More
Supply and fix HT 33 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 9 polymer/porcelain insulators of rating upto 200 Amps complete all as specified and directed by Engineer-in-Charge.

3

3100000

-

... More
M&L for replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with multistranded aluminium conductor, 33000 volts Earthed, grade cross sectional area 185 sq. mm, 3 core conforming to IS 7098 (Part-II) 2011 with upto date amendments complete all as specified and directed by Engineer-in-Charge.

155

3100000

-

... More
Material and labour for replacement of unserviceable end jointing kit, outdoor type heat shinkable, 185 - 300 Sqmm, 3.0 Core suitable for 33 KV 3 Core, XLPE armoured aluminium conductor electric cable complete all as specified and directed by Engineer-in-Charge.

20

3100000

-

... More
All as per above item No 69 but indoor type.complete all as specified and directed by Engineer-in-Charge.

5

3100000

-

... More
All as per above item No.69 but straight through type Note :- Contractor quoting the rate incl disconneting and re-connecting of existing cable, excavation & refilling of soil and work has to be completed upto entire satishfaction of Engr-in-Charge.

14

3100000

-

... More
Excavation in trenches not exceeding 1.5m wide and n.exc. 1.5m in depth for laying of cable and foundation in soft/loose soil complete all as specified and directed by Engineer-in-Charge.

74.4

3100000

-

... More
Removing excavated material and depositing at a distance not exceeding 50m where directed at a level n exc. 1.5m above starting point complete all as specified and directed by Engineer-in-Charge.

23.99

3100000

-

... More
Returning, filling in and well ramming in layers n. exc. 25cm including spreading, levelling and watering complete all as specified and directed by Engineer-in-Charge.

50.41

3100000

-

... More
M&L for tibba sand cushioning to underground cable for cushioning 8cm below the cable and 15 cm above cable complete all as specified and directed by Engineer-in-Charge. Note :- For the purpose of payment only punned thickness will be measured.

13.39

3100000

-

... More
Supplying and laying reinforced precast concrete cable cover, class EHV, type 1 with peak, size 450mm x 230mm x 50mm complete laid over the cable perpendicular to the cable for protection complete all as specified and as directed.

610

3100000

-

... More
M&L for Auguring/ Drilling /Boring of holes under road, pavement, hard standing by trenchless technology by mannual /machine, including fixing of pipe of 150 mm bore dia complete all as specified and directed by Engineer-in-Charge.

6

3100000

-

... More
M&L in replacement of GI tubing light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall including claps, nut bolt etc all as specified and directed of size 150 mm.complete all as specified and directed by Engineer-in-Charge.

7

3100000

-

... More
Supply and fix in replacement of Touch Proof Cable Termination Kits with Boots for 33KV RMU Complete all as directed by Engr-in-Charge.

1

3100000

-

... More
Material and Labour for painting of 33/11 KV main receiving stations yard which includes maximum 12 Nos of steel tubular pole's, complete structure of VCBs, CT & PTs structures, complete busbar structure, channels of 11 mtr poles structure, GOD structures, with stay wire, clamps, nuts and bolts with two coats of aluminium paints of max height up to 10 mtr from ground level incl painting of PCC platforms/coping with two coats of synthetic enamel paint after cleaning the surface thoroughly of colour complete all as specified and directed by Engr-in-Charge at site.

2

3100000

-

... More
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground earth (earth pit not less 2.25 m deep below ground level) with top edge of the plate not less then 1.5 mtr below normal ground level connected to galvanised iron earthing strip 32mm x6mm thick as earthing lead by means of bolt nuts check nuts and washers of galvanized iron or steel all as specified & shown in electrical plate No.3 of MES SSR part-I 2009 connected to earth test point as specified and testing on completion including provision of 40 mm dia light grade pipe up to 7.5 mtr length as protection & watering pipe shall be 20 mm bore medium grade including all excavation & earth work in any type of soil incl PCC pit (1:3:6) type C-1 with RCC cover including charcoal , salt, funnel, complete all as specified and directed by Engineer-in-Charge at site. NOTE:- Rate included for excavation & earth work in any type of strata as shown in electrical plate No 3 and dismantling of old earthing.

4

3100000

-

... More
Taking out old unserviceable PG Clamp of 33 kv and supply, fix and replacement of new PG clamp in repair complete all as specified and directed by Engineer-in-charge.

150

3100000

-

... More
M&L for Earthing complete with copper earth plate elctrodes 60×60cm×3.15mm thick and 20×3 mm copper strip as earthing lead buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 3 meter (BGL) connected to Copper strip of size 20x3 mm earth lead by means of bolts, nuts, check nut and washer of copper including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 25 mm bore “light grade” galvanized iron protection pipe for earth lead copper strip upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion. Note : 1) Rate included for excavation & earth work in any type of strata as shown in electric plate no-3 in SSR Part-I. 2)

4

3100000

-

... More
Supply and spraying anti weeding spray of superior quality by mixing in water with optimum ratio as per manufacturer norms and complete all as specified and directed by Engineer-in-Charge.

12

3100000

-

... More
Material and Labour for painting of 33 KV Steel tower / GOD/DO complete busbar structure, channels with stay wire, channels, clamps, nuts and bolts with two coats of aluminium paints of complete hight from bottom to top incl painting of PCC platforms/copping with two coats of synthetic enamel paint after cleaning the surface thoroughly of colour complete all as specified and directed by Engr-in-Charge at site.

50

3100000

-

... More
Material and labour in replacement of old unserviceable 12 Volt 150 AH sealed lead Acid tubular Battery type all fittings complete all as specified and directed by Engineer-in-Charge.

2

3100000

-

... More
Material and labour in replacement of old unserviceable 12 Volt 7 AH sealed lead Acid Battery SMF type all fittings complete all as specified and directed by Engineer-in-Charge.

2

3100000

-

... More
Supply and fixing in replacement of Post/Pin type, porcelain , vitreous, white , green & brown insulator including one galvanised iron long steel spindle, two galvanised iron washer and one galvanised iron nut, working pressure 33000 Volts and of size 290 mm dia x 290 mm height ISI marked complete all as specified and directed by Engineer-in-Charge.

40

3100000

-

... More
Supply and fixing in replacement of disc type porcelain vitreous, white brown or green 145mm height and 255mm dia ball and socket type three disk assembly for tension with tension clamp for conductor working pressure 33000 volt grade, conforming to IS-13134, for 7.5 KN max failing load complete all as specified and directed by Engineer-in-Charge.

18

3100000

-

... More
Supply, fixing & stringing of ACSR conductor on poles with jumpring and binding with aluminium conductors and in yards with and incl aluminum connectors of required shape and suitable for conductor size and including dismantling of old ACSR conductor etc all as directed and specified by Engr-in-Charge.

3.5

3100000

-

... More
Supply and fixing of stringing, and tensioning of guard wire Cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia for 33 kV overhead lines, including all materials, labour, tools, and equipment required for proper installation as per approved drawings and relevant standards (IS/REC specifications). The work includes fixing guard wire on guard brackets, binding, jumpering, and proper earthing at each pole/structure and complete all as specified and directed by Engineer-in-Charge.

0.7

3100000

-

... More
Supply & finxing of Replacement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25X20cm size all as directed and specified by Engr-in-Charge.

60

3100000

-

... More
Servicing of transformer dry type,11000 Volt / 433 Volts step down, indoor/out door,type of capacity upto 200 KVA comprising following work services :- (a) Disconnection of cable termination of HT & LT ends. (b) Visula inspection of the transformer and cleaning dust and debris from cover louvers, screens, internal coil cooling ducts, doors, removing dust and debris from transformer core and windings using blower and Vacuum cleaning of windings and core (low-pressure) all as directed (c) checking of HT/LT insulators including internal inspection (d) Replacement of corroded nuts/bolts with double washers, burned lugs, etc by new one and tightening of all accessible hardware inclusing bushings, bolts and other connections. (e) Servicing of tap changing gears by cleaning and polishing tapping contact points.(f) Removing, cleaning, polishing of bushings and studs of both HT/LT side by using soft cotton cloth including checking for cracking and refixing the same. (g) Refixing all cable terminals HV & LV sides and transformer top cover, other fitments in position. (k) Connecting HT & LT side with existing incoming and outgoing cables including re-connection of earth strip/lead. (l) HT side cable connection shall be made with new HT tape & M Seal Monoplast as required at site. (m) All marshalling boxes to be cleaned. (n) All the terminal connection of control and relay wiring to be checked and tighten. (o) Examine the rollers carefully includes greasing them properly. (p) Measurement of winding resistances on both HV and LV sides (q) performing the Magnetic balance test (r) The servicing report of the transformer should be provided mentioning all the recommendations, determining the serviceability of transformer, assesing the further life of the transformer (s) Insulation resistance test (primary to secondary, secondary to earth), Winding resistance measurement, Turns ratio (TTR) test, Thermographic scanning for hotspots, Record all readings, test results, and photographs, Submit maintenance report and recommendations (t) 11 KV VCB Cleaning, servicing, calibration and testing complete, de-carbonisation of all terminals, lubricating the all moving mechanical parts and calibrate according the load after re-fixing at the same position complete all as directed by the Engineer-in-charge. Note :- Quoted Rates shall be deemed to include of minor consumable items, i.e Nuts bolts, PG Clamps, thimbles, wires, PVC tapes, Welding Job, cotton waste & cleaning clothes, petroleum jelly, grease, lubricating oil, emery paper, T & P items etc

11

3100000

-

... More
Repairing of damaged/unserviceable gang operate devices 33 KV male & female contacts, flexible jumpers, MS jumper carrier and back connector plate incl cleaning and greasing of complete contacts of GOD unit, and reluging of aluminium/ copper conductors connected to top & bottom contacts of GOD and welding and threading of operating rod mechanism complete making serviceable complete all as specified and directed by Engineer-in-Charge. Note:- (i) Quoted Rates shall be deemed to include of minor consumable items, i.e necessary parts like copper rod, male/female contacts and aluminium conductor for jumpering, GI pipe and handle, Welding machine, threading arrangements, grease, jumper and binding wire. (ii) Contractor may be visit the site before quoting the rate and work has to be completed upto entire satisfaction of Engr-in-Charge.

12

3100000

-

... More
M&L for cutting, trimming of trees and branches to clear the over head line in the arc of HT 33 KV over head line feeders and removal of the trimmed branches of trees complete all as specified and directed by Engineer-in-Charge. Notes : 1. Any ACSR conductor damaged during the cuttings of trees / branches shall be repaired and jointed / fixed by the contractor, to the entire satisfaction of Engr-in-Charge, without any extra cost and nothing extra shall be admissible from the department on this account what-so-ever. 2. The cutting / trimming of tree branches shall be done to atleast 2.00 metre radius of OH line. 3. The unit of measurement is 'SPAN' i.e. distance covered between two poles. 4. Proper shut down will be taken by the authorised rep only. 5. The necessary man power, tool & plant, cutting tools and JCB required for cutting/pruning of branches is deemed to incl in the rate quoted for the job

24

3100000

-

... More
Restringing only of HT 33 KV over head ACSR conductor straightening properly on insulators and binding with aluminum taps /binding wire /conductor jumper etc complete all as specified and directed by Engineer-in-Charge. Note: Contractor may be visit the site before quoting the rate and work has to be completed upto entire satisfaction of Engr-in-Charge.

800

3100000

-



Evaluation Notes How It Works ?

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.