If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date21 May 2025
Closing Date11 Jun 2025
Tender Amount₹ 45,00,000
Costs
EMD
₹ 90,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_708508_1Tender No
GE (A) SOG Token No-14/25-26Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
S&F in replacement shackle type insulators, vitreous porcelain white, brown or green for working pressure 1100 volts grade of 100 mm height and 115 mm dia including galvanized mild steel straps of 31mm x 5mm size,14mm dia insulator bolts, washers and nuts complete all as specified and directed by Engineer-in-Charge.
60
-
-
... More
S&F in replacement pin type insulator of size 100mm height, 65 mm dia porcelain, vitreous white, brown or green insulator suitable for 1100 volts grade including one galvanized mild steel spindle, two GI washer and one GI nut complete all as specified and directed by Engineer-in-Charge.
60
-
-
... More
M&L for fixing in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections conforming to Fe-410-0 or Fe-310-0 grade including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces after preparation of surfaces, supplied and fixed in repair complete all as specified and as directed by Engineer-in-Charge.
(Note: - (i) Sizes & types of members and shape of the cross arms etc shall be as required at site all as directed by the Engineer-in-Charge.(ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only. Cost of the same is included in unit rate of the item and nothing extra shall be paid on this account.)
2.5
-
-
... More
S&F in replacement stay assembly complete with accessories as shown in electrical plate No 1 using stay rod 20 mm dia x 1800mm long, stay bow 14mm dia and stay plate 30 cm x 30 cm x 6 mm including stay wire 8 SWG x 7 strands, loop type insulator with over all dimensions 90x140mm and clearence of hole 25.5mm, stay clamps and painting to exposed surfaces of mild steel work with two coats of aluminum paint over a coat of red oxide primer, complete all as specified and directed by Engineer-in-Charge.
Note : Excavation, earthwork and PCC in foundation shall be measured and paid seperately under respective items of BOQ.
12
-
-
... More
M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Steel Tubular Poles (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying one Coat of Red Oxide Zinc Chrome Primer, alternate Yellow & Black Strips Painting (5 No. Each Strip 300 mm wide) and remaining portion of Pole also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint and Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paint complete all as specified and as directed.
400
-
-
... More
M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Pre-stressed Concrete cement Pole (above the Planting Depth and PCC Copings) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (5 No. Each Strip 300 mm wide) and remaining portion of Pole treated with Two Coats of Exterior Weather Proof Paint also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. treated with Two Coats of Aluminium Paint complete all as specified and as directed.
400
-
-
... More
Disconnecting over head conductors and insulators any Nos on existing damaged Pre -stressed Concrete Cement LT poles, dismantling MS work such as cross arms /clamps/hooks etc, stay and street light (where exists), excavating and taking out damaged pole making good hole to receive new pole and M&L for Ereting Pre-stressed concrete poles 9 meter long, 102mm x 172mm at top and 102 mm x 279 mm at bottom, class 10, complying with requirements of IS-1678, including painting with two coats of synthetic enamel paint (in alternate black & white/yellow strips of 30 cm height) upto 1.5 meter height from top of PCC coping and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint, including dismantling of old unserviceable one complete all as specified and as directed by the Engineer-in-Charge.
Note : Earthwork, Cement Concrete, etc. will be measured and paid under approprite Items.
18
-
-
... More
Disconnecting over head conductors and insulators any Nos on existing damaged steel tubular swaged LT poles, dismantling MS work such as cross arms /clamps/hooks etc, stay and street light (where exists), excavating and taking out damaged pole making good hole to receive new pole and M&L for Ereting Steel Tubular Swaged Pole Type 410-SP-31 (9.0 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws including applying two coats of Black Bituminous Paint Internally and Externally from bottom End of Pole upto PCC Coping and applying with two coats of Aluminium Painting over a coat of red oxide Primer (Externally from Top of Coping)and applying Two Coats of Synthetic Enamel Painting in alternate Yellow & Black Strips Painting (4 No. Each Strip 300 mm wide) and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint, including dismantling of old unserviceable one complete all as specified and as directed.
Note : Earthwork, Cement Concrete, etc. will be measured and paid under approprite Items.
10
-
-
... More
Disconnect the electric supply from Main GO/DO and taking down old existing Loose ACSR conductor mounted on Steel/PCC pole 3 to 5 Conductor and Re-stringing of existing over head line ACSR conductor/GI wire of any size/type including repair of conductor broken due to wind storm/expansion, contraction etc, on existing LT steel and/or PCC pole including replacement of aluminium binding wire of suitable size and refixing of all old accessories carefully without damaging of insulator etc complete all as specified and directed by Engineer-in-Charge.
Note:- Length of each conductor shall be measured as one length.
250
-
-
... More
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in new / old coping of poles etc including weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge
13
-
-
... More
M & L for PCC (1:3:6) typeC-2 using 40mm graded stone aggregate as in foundation for stays & mass concrete including necessary form work and fair finishing complete all as specified and directed by Engineer-in-charge
15.12
-
-
... More
M & L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation for poles, struts & mass concrete including necessary form work and fair finishing to exposed surfaces complete all as specified and directed by Engineer-in-charge
1.51
-
-
... More
M&L as in replacement for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth not less than 1.5 meter below ground level, earth plate surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 32mm x 6mm thick as earth lead by means of bolts, nuts and washers of galvanised iron or steel and thimbles and other end of the earth strip connected to earthing test point/equipment and protected by galvanised iron pipe light grade 40mm dia upto earthing test point/equipment fixed with required number of mild steel clamp made out of 25mm x 3mm flat iron and perforated water pipe 20mm dia GI medium grade of length 2.25 metre and top with socket & plug and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mmthick pre-cast RCC (1:2:4) type B-0 cover with 40mm x 40mm x 3mm MS angle iron frame, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009. complete all as specified and directed by Engr-in-charge.
Notes :- (i) GI strip upto earth test point/equipment is included in this item. (ii) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber.
(iii) Minimum weight of reinforcement shall be 1 kg for each earth pit cover
25
-
-
... More
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays, joints or laying underground cable etc. in soft/loose soil, & getting out including taking out old brick or precast cable cover complete all as specified and directed by Engineer-in-Charge.
1431
-
-
... More
All as per Item No. 16 above but not exc 3 mtr in depth complete all as specified and directed by Engineer-in-Charge.
2.6
-
-
... More
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge
825.83
-
-
... More
Removal of excavated soil/ material to a distance not exc 50 metre and depositing where directed at a level n. exc 1.50 metre above the starting point complete all as specified and directed by Engineer-in-Charge.
605.17
-
-
... More
M&L for dry sand (Tibba sand) and punning for cushioning to underground cable complete all as specified and directed by Engineer-in-charge. Note: - For payment purpose thickness after punning shall be measured.
429.3
-
-
... More
Taking out old bricks laid in trenches and M & L for brick protection with old size sub class 'B' bricks laid flat, abutting each other with gap between adjacent bricks not exc. 10mm, length of bricks across the route of underground cable complete all as specified and directed by Engineer-in-Charge.
25.44
-
-
... More
Taking Out old Bricks laid in trenches & Relaying the same old serviceable bricks in trenches, complete all as specified and as directed by Engineer-in-Charge.
16.96
-
-
... More
Taking out old underground LT Cable of size 10 sqmm to 240 Sqmm of 3.5 core from LT Panels trenches/floors /road/wall/ pipe/pole/including taking out loop from trenches upto 1.5 mtrs depth, cutting the faulty end of cable and refixing the cable in original position by using flat aluminium sockets/ thimble/ and insulating the all nacked wires of any size including making connection with MCCB's/ Switches complete all as directed by Engineer-in-Charge. Note : Exacavation for taking out LT cable from will measured and paid separatly.
500
-
-
... More
Supplying, jointing and testing in replacement heat shrinkable type indoor / outdoor end termination jointing kit, suitable for different size of cable 35 sq MM to 120 sq mm aluminium conductor 1100 Volts including making connections complete all as per following.
35
-
-
... More
All as per item No 24 above but suitable for cable of size 185 sqmm to 300 sqmm.
10
-
-
... More
Supplying, jointing and testing in replacement heat shrinkable type following straight through jointing kit, suitable for different size of cable aluminium conductor 1100 Volts including making connections complete all as per following and directed by Engineer-in-Charge.
-
-
-
... More
All as per item No 25 above but suitable for cable of size 16 sq mm to 50 sqmm.
40
-
-
... More
All as per item No 25 above but suitable for cable of size 70 sqmm to 120 sqmm.
10
-
-
... More
All as per item No 25 above but suitable for cable of size 185 sqmm to 300 sqmm.
8
-
-
... More
Trimming/pruning of the tree branches comming cross electric power head line LT feeder cleaning the span and making it free from touching the tree branches complete all as specified and as diredted by Engineer-In-Charge. (Note :-(i) All item of LT overhead lines taken together shall be measured as one unit for the payment purpose under this item.
(ii) Only such length shall be measured where trees are required to be cut/trimmed as directed by Engineer-In-Charge.
(ii) Removing branches from road and diposition at a distance of more than 500 meter)
300
-
-
... More
Supply and fixing 32 mm dia 1.2 metre long GI pipe light grade bracket for fixing street light made to shape at including MS clamps (FI Plate 25X4mm as per site requirement) 02 Nos and nut and bolts duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete as required at site complete all as specified.
35
-
-
... More
S&F as in replacement power contactor two pole of capacity 40 Amps, coil voltage 220/ 240 volts, type MU-2P, wide band coil complete all as specified and directed by Engineer-in-Charge. Make:- L&T cat part No CS90119 or equivalent in Havells / GE / Legrand / Schneider
20
-
-
... More
S&F as in replacement MCCB 4 Pole 63 Amps, thermal magnetic release having, breaking capacity 16 KA, 415 Volt in the existing feeder pillar box including any addition / alteration to the panel to accommodate the new MCCB & making connections with 25x3 mm copper strip as required from main bus bars, making necessary welding work, metal work for fixing base plate etc and connections complete all as specified and as directed by Engineer-in-Charge.
10
-
-
... More
All as per item No. 29 here-in-before but MCCB 4 Pole, 160 Amps rating, breaking capacity 36 KA, 415 Volt .
12
-
-
... More
All as per item No. 29 here-in-before but MCCB 4 Pole, 250 Amps rating, breaking capacity 36 KA, 415 Volt.
10
-
-
... More
All as per item No. 29 here-in-before but MCCB 4 Pole, 400 Amps rating, breaking capacity 36 KA, 415 Volt.
6
-
-
... More
All as per item No. 29 here-in-before but MCCB 4 Pole, 630 Amps rating, breaking capacity 50 kA, 415 Volt.,
2
-
-
... More
Taking down complete high mast light fitting including 150-200 watt flood light for finding out faults and refixing the same in existing position after carrying out necessary repair and wiring with 4 sqmm 3 core copper PVC cable, tightning of loose connection and cleaning of glass complete all as specified and directed by Engineer-in-Charge.
Notes :- (i) Ladder wheel shall be arranged by the Contractor.
(iii) Detection and rectification of fault in over head/under ground line shall be done by the contractor.
25
-
-
... More
Supply and fixing as in replacement weather proof PVC insulated, sheathed three core stranded aluminium conductor cable of size 2.5 Sqmm, 1100 Volts grade conforming to IS:9968 (Part-I) 1988 or IS:694-1990 complete all as specified and directed by Engineer-in-Charge.
800
-
-
... More
Locating the fault in LT cable of any size for any type of fault like open cable short between phases/Neutral ,grounded cable with help of cable fault locator and pin pointing location with the help of audio signal ,excavation at the fault and openning cable to suitable distence and depth for making a cable joint and including complete Earth work all as specified and as directed .
Note:-1. The joint kit will be paid separately. 2:-contractor will have to arranged the cable fault locator or other testing Eqpt /tools as required &same shall be deemed to be includede in the item rate Quoted)
9
-
-
... More
S&F as in replacement LT Line polypropylene composite phase separator, moulded or bolted type, overall length 1250mm, width 25mm, thickness 12mm, suitable for 5-lines, 4 lines,3 lines wire complete reqd at site all as specified and as directed by Engineer-in-charge.
150
-
-
... More
Supplying, laying, jointing, commissioning and testing as in replacement XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade of cross sectional area 240 sq mm 3.5 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc complete all as specified and directed by Engineer-in-charge.
200
-
-
... More
All as per item No 34 above but cable of cross sectional area 185 sq mm 3.5 core.
150
-
-
... More
All as per item No 34 above but cable of cross sectional area 120 sq mm 3.5 core.
300
-
-
... More
All as per item No 34 above but cable of cross sectional area 95 sq mm 3.5 core.
300
-
-
... More
All as per item No 34 above but cable of cross sectional area 70 sq mm 3.5 core.
150
-
-
... More
All as per Item No 34 above but Cable of Cross Sectional Area 50 sq mm 3.5 Core
300
-
-
... More
All as per item No 34 above but cable of cross sectional area 35 sq mm 3.5 core.
500
-
-
... More
All as per item No 34 above but cable of cross sectional area 25 sq mm 4 core.
1000
-
-
... More
All as per item No 34 above but cable of cross sectional area 16 sq mm 4 core.
1200
-
-
... More
All as per item No 34 above but cable of cross sectional area 16 sq mm 2 core.
1200
-
-
... More
Suppyling, installing, testing and commissioning factory made outdoor type bus bar chamber having MCCB 4 Pole, 415 Volts, 160 Amps of suitable size for operation on 415 volts, 3 phase, 4 wire, 50 Hz, outer shell made out of 3.15mm thick CRCA sheet duly powder coated coated siemens gray shade and completely weather, vermin & dust proof, adequate air ventilation at sides & back, door shall be provided with double door fix with hinges and locking arrangements etc suitables to accomodate the 250 Amps aluminium bus bar fixed Horizontally in staggred manner minimum length 450mm, 3 phases and neutral duly insulated with heat shrinkable PVC sleeves and colour coded mounted on heavy duty DMC insulators duly connected with 160Amps MCCB including provision for taking out incoming and outgoing cables detachable plate at bottom for cable entry and making six Nos hole in each bus bar including with bottom frame made out of angle iron 50mm x 50mm x 5mm and 600mm long 4 legs duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer on exposed surfaces grouted in PCC 1:2:4 type B1 using 20mm graded stone aggregate blocks of size 30cm x 30cm x 60cm complete all as specified and as directed by Engineer-in-charge.
2
-
-
... More
S&F as in repair cable junction box of size not less then 300x200x105mm, made of high quality thermo plastic polystyrene, weather proof, dust, jet water proof, chemical, acid corrosion, impact, insulated & shock proof IP 66 / 67 for outdoor Installation with internallly embedded gasket (PUR) including the box fitted with connector 8 way 40 Amps 01 No including Emlex stud type TB 4 Nos incoming / outcoming cable at controlled with MCB SP 6 Amps 01 No & enclosed along pole with MS flat iron clamp of suitable size complete all as specified and directed by Engineer-in-Charge
Note :- Cost of flat iron clamp is deemed to include in unit rate of this items.
150
-
-
... More
Supply and fixing as in replacement electronic MPPCB for street light (Make as per site requirement) 220/240 V suitable for existing LED light fitting , 45 Watts ,60WATT /complete all as specified and directed by Engineer-in-Charge.
50
-
-
... More
Inspection/checking/tightening of connections for LED Security/Street light fitting such as 30/45/72/90 watts etc for tighting the connection with replacement of twin core multi strand 2.5 Sqmm aluminium wire complete all as specified and directed by Engi
950
-
-
... More
S&F as in replacement Galvanized iron tubing, 80 mm bore light grade, ISI marked, including all fittings and laid in trenches / under road / drains, fixed to poles / walls with required numbers of clamps made out of 25x3mm flat iron, bolts, nuts and washers for protection of LT electric cable complete all as specified and as directed by Engineer-in-charge.
Notes :- (i) Excavation & earthwork shall be measured & paid separately under respective items of BOQ
15
-
-
... More
All as per serial item No. 39 here-in-before but 50 mm bore
27
-
-
... More
Supply, fixing and testing LED Street light fitting of 45 Watt including LED lamps complete with body robust,corrosion resistant,superior finish and without any cracks or through holes,made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -65 / 66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 300 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD(I) less than 15% ,cool white colour and lamp starting time should not be more than 10 second fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 60 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 100 lumens per watt and must be certified by the LM-79 test report and including provision of connection for street light from pole box with 2.5 Sqmm PVC insulated stranded copper conductor FRLSH cable, 1100 Volts grade ISI marked including taking down old unsv streeet light of any size and any capacity complete all as specified and directed by Engineer-in- charge.
50
-
-
... More
Supply and fix heavy duty TPN bus bar chamber 100 Amps, 4ways, fixed with hinges and locking arrangements, surface mounting type,in replacement and arrangements for 04 Nos incoming / outgoing connections in each busbar, fixed on wall complete all as specified and as directed by Engineer-in-Charge
3
-
-
... More
Supply and fixing as in replacement electronic driver (Make as per site requirement) 220/240 V suitable for existing LED light any type fitting Watts complete all as specified and directed by Engineer-in-Charge.
150
-
-
... More
Supply & Fixing 10 KV surge protector suitable for any type of LED fitting & make complete all as specified and directed by Engineer-in-Charge.
85
-
-
... More
Taking down complete steam boiler capacity 200 kg/hr from existing place and servicing / repairing, maintnance of steam boiler and also ensure that safe, effeceint, uninterrupted operation of boiler by skilled technician from manufacturer (OEM) and refixinhg the same after checking of proper functioning of steam boilder complete all as specified.
The following are also ensure that :-
(a) Inspection & Diagnosis : Detailed examination of boiler components to defect faults, leaks and inefficiencies. Complete assesement to identify faults or wear and tear.
(b) Boiler tube repair / replacement & welding : Re-tubing, welding cracks and repairing leakage to restore stem generation capacity.
(c) Pressure part repairs :- Fixing cracks or worn-out areas in the Shell, Drum and header repairs to restore pressure holding capacity.
(d) Burner & ignition servicing : Dignosing and repairing or replacing faulty burners and ensure proper combustion.
(e) Electrical & control panel checks : Repairing sensors, thermostats, controllers and wiring system.
(f) Valve and steam line servicing : Overhauling safety valves, pressure reducing valve (PRVs), NRVs and steam traps.
(g) Refractory & insulation work : Replacing damaged insulation or refractory lining to improve heat effeciency.
(h) Hydrostatic pressure testing & certification : Conducting, performing hydrostatic pressure test as per industry standards (IBR norms if applicable) to verify the boiler's intigrity post-repair.
Note :- (i) The above servicing shall be done dy skilled technician from authorised manufacturer (OEM).
(ii) All unserviceable items shall be replaced and cost of the same are included in this items. Nothing shall be extra paid on this account.
(ii) A test certificate for servicing and proper functioning to verify the boiler intigrity by authorised OEM shall be subitted at the time of RAR / Final bill.
2
-
-
... More
Inspection & Checking,calibration settings, servicing and repair/replacement of burnt/unserviceable wiring duly lugged of existing ACB Capacity 630 AMP to 2500 AMP of any make including setting of over current, erathfault, etc complete all as specified and as directed by Engineer in charge. Note - old Unserviceable item retrieved from the above is deposited to AGE E/M Yard
6
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%