If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 37,200Document Cost
₹ 1,000Tender Fee
₹ 500
Summary
Mgps Work Of 50 Bedded Ward At Dh Baran Distt. Baran-300.00
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MEDIC_415020_2Bid Award Id
ViewTender No
EE M and H Kota NIT No. 07/2024-25Tender Authority
Medical Health And Family Welfare Department ViewPurchaser Address
-Website
http://http://www.rajswasthya.nic.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
FOR 22 MM OD Pipe
3
-
-
FOR 28 MM OD Pipe
3
-
-
SITC of Gas outlet points Oxy, N2O, (AR-4), (AR-7) and Vaccum (8.7 psig) for dispensing medical gases (oxygen/air/vaccum) at point of use confirming to BSEN ISO 9170-1:2008. The gas outlet are quick connect type , it should have color coding for different gas source and should accept only repective adapters as required.Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE Marked. All as per pre approved by Engineer in charge. For additional echnical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021
112
-
-
SITC of BPC (back pressure compensated) flow meter with humidifer made of nickel plated body, double jacketed with flow gradations CE Marked on it. Desired flow will be setteled through rotary knob. Flow range should be between 0 to 15 lpm & work should be executed as per direction of engineer in charge. Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
50
-
-
SITC of ward suction unit (Suction controller and collection Jar-600 ml capacity) with posibility to configure required capacity collection jar and should meets the requirements as per BSEN ISO 10079-3:2009. The unit must designed to operate with the vaccum line of MGPS. The collection jar must accumpained with Vaccum regulator suitable for 0-14.7 psig with flow rate 0-55 Lmp (min) for operating temperature- 18°C to 50°C with ON/OFF facility. The collection jar should be transparent, made of high quality polycarbonate that can be autoclaved at 121°C for 20 minutes for reuse and provided with auto stop to avoid over spill and contaminatin of the suction source when the jar collection reached optimized level. The complete unit supplied with filter to protect the source and pipe line from bacterial contamination. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
50
-
-
SITC of valve box made of CRCA sheet duly powder coated with transparent window which is installed in the MGPS for oxygen and vaccum line and should comply with BSEN ISO5211:2001 complete with ball type valves and gauges as required for oxygen compressed air and vaccum line. Appropriate Test certificate/report of product/accessories from OEM shall be submited. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021. Three Gas Service
4
-
-
SITC of microprocessor based auto alarm (digital type) suitable for medical gas service provided with audible and visual alarm for MGPS zoning. It should monitors the current status of oxygen / compresssed air pressure in distribution pipeline of central medical supply system and trigger the alarm to alert. The system should comply BSEN ISO:7396-I:2007 Appropriate Test certificate/report of product /accessories from OEM Shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021. Three Gas Service
4
-
-
SITC of Bed Head Panel of 900-1500 MM long made out from high strength extruded aluminium with powder coating with at least 4 Nos 6/16 Amp switch socket and provision for required number of gas outlet points as suggested by the client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
6
-
-
SITC of Emergency Oxygen / Nitrous Oxide Manifold System (2+2) with tail pipes NRV and One DGSS Regulator of Minimum 600 LPM capacity- manifold system comprise of bank of 2+2 cylinders (Bulk cylinder of D type ) capacity manifold high pressure copper pipe of size 1/2"IDx14 swg (approx. 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 4 no's non return valves & 4 no's high pressure flexible tail pipe is made of copper pipe of 1/3"x16 swg (approx. 1.6256 mm) the manifold is hydraulically tested at 225 Kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag make CE approved /CE certified. Note: Providing of cylinders is in the scope of Hospital/End client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-
SITC of automatic gas control panel/Change over Panel for oxygen/nitrous oxide control panel cover made for M.S duly powder coated. Compact and fully automatic manifold control system for oxygen services easy to maintain and use Designed with both safety and continuity of flow supply at a constant pressure via two banks of bottled gas cylinders with following status monitoring A- Bank in use (Green Indication) B- Empty bank (Red Indication) Control Panel should have built in LED display to indicate Normal, High & Low line pressure. It should have facility to test all above indicators working perfectly. The control Panel should include pressure gauge to indicate the gas pressure of each header and pipe line distribution pressure. Capable to provide a distribution flow rate in excess of 1200 LPM. The control panel should incorporate manual bypass system in case of failure of shifting mechanism. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-