Medical Health And Family Welfare Department Tender
If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.
Costs
EMD
₹ 1,63,320Document Cost
₹ 1,500Tender Fee
₹ 1,500
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MEDIC_431159_2Tender No
NIT-24 of 2024-25 (EE MH Ajmer) Sr. 03Tender Authority
Medical Health And Family Welfare Department ViewPurchaser Address
-Website
http://http://www.rajswasthya.nic.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Tender documents Agreement, RTPP Act, Steel, circulars, Term and conditions
Order Date extend due to modification in tender condition
BOQ Items
For 12 MM OD Pipe
210
-
-
FOR 15 MM OD Pipe
20
-
-
FOR 22 MM OD Pipe
8
-
-
FOR 28 MM OD Pipe
8
-
-
FOR 42 MM OD Pipe
4
-
-
SITC of Gas outlet points Oxy, N2O, (AR-4), (AR-7) and Vaccum (8.7 psig) for dispensing medical gases (oxygen/air/vaccum) at point of use confirming to BSEN ISO 9170-1:2008. The gas outlet are quick connect type , it should have color coding for different gas source and should accept only repective adapters as required.Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE Marked. All as per pre approved by Engineer in charge. For additional echnical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021
410
-
-
SITC of BPC (back pressure compensated) flow meter with humidifer made of nickel plated body, double jacketed with flow gradations CE Marked on it. Desired flow will be setteled through rotary knob. Flow range should be between 0 to 15 lpm & work should be executed as per direction of engineer in charge. Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
180
-
-
SITC of ward suction unit (Suction controller and collection Jar-600 ml capacity) with posibility to configure required capacity collection jar and should meets the requirements as per BSEN ISO 10079-3:2009. The unit must designed to operate with the vaccum line of MGPS. The collection jar must accumpained with Vaccum regulator suitable for 0-14.7 psig with flow rate 0-55 Lmp (min) for operating temperature- 18°C to 50°C with ON/OFF facility. The collection jar should be transparent, made of high quality polycarbonate that can be autoclaved at 121°C for 20 minutes for reuse and provided with auto stop to avoid over spill and contaminatin of the suction source when the jar collection reached optimized level. The complete unit supplied with filter to protect the source and pipe line from bacterial contamination. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
180
-
-
SITC of valve box made of CRCA sheet duly powder coated with transparent window which is installed in the MGPS for oxygen and vaccum line and should comply with BSEN ISO5211:2001 complete with ball type valves and gauges as required for oxygen compressed air and vaccum line. Appropriate Test certificate/report of product/accessories from OEM shall be submited. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
-
-
-
Two Gas Service
10
-
-
Three Gas Service
5
-
-
SITC of microprocessor based auto alarm (digital type) suitable for medical gas service provided with audible and visual alarm for MGPS zoning. It should monitors the current status of oxygen / compresssed air pressure in distribution pipeline of central medical supply system and trigger the alarm to alert. The system should comply BSEN ISO:7396-I:2007 Appropriate Test certificate/report of product /accessories from OEM Shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
-
-
-
Two Gas Service
10
-
-
Three Gas Service
5
-
-
Four Gas Service
5
-
-
SITC of color coded High pressure rubber tube for positive pressure gases/vaccum. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
360
-
-
SITC of Bed Head Panel of 900-1500 MM long made out from high strength extruded aluminium with powder coating with at least 4 Nos 6/16 Amp switch socket and provision for required number of gas outlet points as suggested by the client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
26
-
-
P&F of Bed Panel accessories like Monitor Tray, Utility Basket, Vacuum Slider, Infusion Pump Pole with IV hooks, with proper nut bolts and screw and with proper finishing. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
-
-
-
Monitor Tray
26
-
-
Utility Basket
26
-
-
Vacuum Slider
26
-
-
Infusion Pump Pole
26
-
-
SITC of automatic gas control panel/Change over Panel for oxygen/nitrous oxide control panel cover made for M.S duly powder coated. Compact and fully automatic manifold control system for oxygen services easy to maintain and use Designed with both safety and continuity of flow supply at a constant pressure via two banks of bottled gas cylinders with following status monitoring A- Bank in use (Green Indication) B- Empty bank (Red Indication) Control Panel should have built in LED display to indicate Normal, High & Low line pressure. It should have facility to test all above indicators working perfectly. The control Panel should include pressure gauge to indicate the gas pressure of each header and pipe line distribution pressure. Capable to provide a distribution flow rate in excess of 1200 LPM. The control panel should incorporate manual bypass system in case of failure of shifting mechanism. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-
SITC of Oxygen/Nitrous Oxide Manifold System (8,8) with tal pipes NRV-manifold system comprise of bank of 8+8 cylinders (Bulk cylinder of D type) capacity manifold high pressure copper pipe of size 1/2"ID x14 swg (approx 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 16 no's non return valves & 16 no's high pressure flexible tail pipe is made of copper pipe of 1/3"x16 swg (approx. 1.6256 mm) the manifold is hydraulically tested at 225 kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
2
-
-
SITC of Emergency Oxygen / Nitrous Oxide Manifold System (2+2) with tail pipes NRV and One DGSS Regulator of Minimum 600 LPM capacity- manifold system comprise of bank of 2+2 cylinders (Bulk cylinder of D type ) capacity manifold high pressure copper pipe of size 1/2"IDx14 swg (approx. 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 4 no's non return valves & 4 no's high pressure flexible tail pipe is made of copper pipe of 1/3"x16 swg (approx. 1.6256 mm) the manifold is hydraulically tested at 225 Kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag make CE approved /CE certified. Note: Providing of cylinders is in the scope of Hospital/End client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-
SITC of Dessicant Air Dryer Output capacity as below with certified microprocessor controller with dewpoint based changeover option Pre-filter rating 0.3 microns, shuttle valve for low pressure drop, All Aluminium resist oxidation & scale formation, dewpoint better than-40o C including fixing on wall with required T&P making connections etc. complete in all respect. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
-
-
-
30 CFM
1
-
-
SITC of compressed air syste should consist on 1 nos. air compressors with electric motors electrical switch gear and automatic control system of following Specification: A) Air Compressor 1 (One) Nos: Type Non-lubricated /Oil-free Minimum capacity 24.43 cfm (Piston Displacement) at 8.5 kg/cm2 cooling air cooled B) Drive electric motor 1 (one) Nos. Capacity 7.5 HP Speed 1440 rpm (syn) drive belt drive Electricity supply 440 volt, 50 hz 3 Phase. C) Starter Star/Delta Control & Switchgear with overload protection including making PCC foundation and fixing withbolts anti vibration pad and making connections complete as required.Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-
SITC of compressed air filtration system and regulating system: one set of 3- stage filter the filters should be made of die cast aluminums housing with epoxy power paint on the outside and anodized surface treatment inside to prevent corrosion and ensure extra long life. The filters should have maximum contaminant removal efficiency with minimum pressure drop. Total 3-stage of filters should be used as mentioned below:- Stage1:- coalescing filters for general purpose protection removind liquid water and oil aerosol to 0.1 mg/cum (0.1 pm) and and particles down to 5 micro. Stage :- 2 particular filter for dust protection removing particles down to 1 micron. Stage:- 3 high efficiency coalescing filters, removing liquid water and oil aerosol to 0.01 mg / cum (0.01 pip) and particles down to 0.01 micron. Janatics regulator 1/2" or 3/4" to be installed for regulating the output air pressure. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-
SITC of Vacuum pump of single stage capacity minimum 3141 lpm/111 cfm (piston displacement) The pump should be suited for maximum working pressure of 29 inch mercury (730 mm mercury) The pump should be fitted with MS channel frame complete having vibration isolators with 1 Nos. silencers at vacuum pump discharge end. The pump should be air cooled 1 sets of isolation valve on return valve and filter should be provided with pumps. Drive Assembly The electrical drive for vacuum pump should consist of suitable TEFC induction motor operating at 1440 RPM and connected through a V-belt. The motor should be suited for 415 V+10% 50 HZ.3 Phase AC supply capacity : 7.5 HP of a reputed make vacuum switch vacuum switch of 0-760 mm range should be provided it should have both NO/NC contracts and suitable for 230 V 50 Hz . AC supply. The vacuum switch should be housed in weather proof casing with 3/8"BSP gas service connection at the bottom of the assembly. Vacuum Filter 1 Nos vacuum filters with drain valve. This filter should be non-ferrous and in line. including making PCC foundaton and fixing with bolts, anti vibration pad and making connections complete as required.Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-
SITC of hot dipped galvanized ( inside and outside) and powder coated Air/vacuum receiver tank (as per IS: 7938-1976 and upto date amendment ) for compressed air system/vacuum system to dampen out pulsatin and condense and trap the moisture in the compressed air and also to let oil and other impurities settle down before air passes into the piping with safety valve Drain Valve Pressure gauge and fusible plugs of 1000 litres capacity complete as required including fixing with bolts and making connections complete as required. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
2
-
-
Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V, with operating handle source seperator and phase barrier included, conforming to IS/IEC 60947-3 : 1999 including connections, testing etc. as required. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%