If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.

Medical Health And Family Welfare Department - MHFW Tender

Works
Civil And Construction
Electrical and Electronics
Electrical Works
Eprocure
Opening Date9 Sep 2024
Closing Date11 Nov 2024
Tender Amount₹ 1,63,53,000 
Notes
Download

Costs

  • EMD

    ₹ 3,27,060
  • Document Cost

    ₹ 2,000
  • Tender Fee

    ₹ 2,000

Summary

Sitc Of Electrical Substation And Dg Set Work In The Construction Of District Hospital Gangapur City

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
(c) OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities for cables . Appropriate type test certificate / OEM test report shall be submitted . All above as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Armoured Cable

-

-

-

... More
630.0 Sq. mm

-

-

-

... More
1 core

800

564800

706

... More
400.0 Sq. mm

-

-

-

... More
1 core

800

350400

438

... More
Providing & Laying of 25 cm thick layer of river sand to cover of existing cable in 30cmx75cm size cable trench with levelling and making symmetric 25 mm thick layer in complete running length of trench as required.

600

32400

54

... More
Providing & covering of existing cable lying in existing trench by IInd class bricks/ Stone slab of minimum 32mm thick and 250 mm wide in complete running length of trench complete as required.

600

26400

44

... More
Labour charges for Excavation of 30cmx75cm size trench in loose soil including refilling of excavated earth,compaction of earth, making good the same complete as required .

600

35400

59

... More
Supplying and making end termination with heavy aluminium lugs Pin / ring type (as per IS 8309 -1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tape as per PWD specification for electrical Works etc of following size. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
630.0 Sq.mm

54

11664

216

... More
400.0 Sq.mm

24

2976

124

... More
Plate Earthing as per PWD specification for electrical Works as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

16

139104

8694

... More
Supply & Laying following size earth strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
32mm x6mm G.I. ( Hot Dipped ) Strip

120.03

13563

113

... More
50mm x 6mm copper strip

100

204200

2042

... More
Supply installation testing & Commissioning of star rated Copper wound distribution Transformer ( All the distribution transformer must be star rated as per notification of (BEE) ministry of power, Goverenment of India) of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooled & as per BEE star level- 2 & BIS approved as per IS 2026-1977 & losses as defined as per IS 1180 part I 2014. including standard accessories like conservator, silica gel breather,Bucholz relay, radiator, fins, HT cable box & LT cable boxes, Off -LTC (+5% to - 10% @ 2.5%) temperature rise of 40 degree C in oil / 45 degree C in winding , ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953 , Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer complete in all respect. NABL accredeated / CPRI/ ERDA lab testing reports with OEM certificate must submitted to engineer in charge .Transformer must be tested from CTL test lab of discom (if reqd.) before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, CTL testing charges & Inspection charges shall be reimbursed by the department to the contractor as per actual expenditure. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1000 KVA

2

2531554

1265777

... More
Supply , Installation, Testing and Comissioning of 11 KV, 630 A, 20kA / 3 sec, Out door, Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, earthing switch, mechanical ON / OFF / Earth indication, Voltage presence indicator, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, Shunt trip coil, Anti reflex operating handle, right angle boots etc. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA lab type test reports before execution as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

1

347690

347690

... More
Supply , Installation, Testing and Comissioning of 1 no. VCB / SF6 circuit breaker coupled with existing extensible type RMU with over load, Earth fault, short circuit relay, copper bus bar, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, mechanical ON / OFF / Earth indication, Voltage presence indicator, Anti reflex operating handle, right angle boots etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

1

316867

316867

... More
Providing & Laying XLPE insulated as per IS:7098/II/85 H.T.cable as per PWD specification for electrical Works for working voltage 11 K.V.(E) in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench , on existing cable trays or on surface etc. including making necessary connection, testing etc. as required of size as per points (a), (b), (c) mentioned below:-

-

-

-

... More
(a) Material :- H4- Grade aluminium conductor of purity 99.6 % & as per IS:1554 P-I / IS :7098 P - I

-

-

-

... More
(b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999 for armouring of cables , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures

-

-

-

... More
(c) OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities for cables . All above as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
3 core 185.0 Sq.mm

400

381200

953

... More
Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit as per PWD specification for electrical Works suitable for 11 KV / 33 KV cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streight through joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Cross linking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. OEM test lab should be as per ISO 9001:2015 & 14001 : 2015 & reports submitted to engineer in charge including testing etc. as required of following sizes. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
11 KV End Termination Kit Indoor type

-

-

-

... More
3 core 120/150/185 Sq.mm

14

56658

4047

... More
11 KV End Termination Kit Outdoor type

-

-

-

... More
3 core 120/150/185 Sq.mm

2

9840

4920

... More
Providing & laying of Double wall corrugated pipe confirming to IS : 14930 P - 1 & 2 with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required( Excavation of Earth to be paid Extra as required. ) of following Outer Dia. / Inner dia as per IS:4984:1995. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
200 / 175 mm

100

67200

672

... More
SITC of Draw out type 3/4 pole IP53, IK 08 door interlock Air Circuit Breaker (ACB) as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 in existing LT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, earth fault and with separate LED indication for each type of fault , Password protected relase (trip mechanisum) shall confirm to EMI/ EMC test , LCD/LED display , Thermal memory , pollution degree 4, trip free mechanisum , suitable for ambient 50 degree and utilization catagary B. In built electrical & mechanical anti pumping fearute , 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 25 ms. Provision for electrical & mechanical interlock between ACBs, Min.electrical operation 10,000 upto 2000 A rating and 5,000 for 2500 A. including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Microprocessor based release Draw out type (Manual spring charged) 4Pole

-

-

-

... More
800 A Rating , 50kA

6

807378

134563

... More
1000 A Rating , 50kA

2

284134

142067

... More
1600 A Rating ,65kA

3

521025

173675

... More
SITC of IP 40 3 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings as per PWD specification for electrical Works, conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 800 V, provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections with lugs & spreaders, etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
With Thermal Magnetic release

-

-

-

... More
up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu

12

42828

3569

... More
SITC of IP 40 quick make and quick break 4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings as per PWD specification for electrical Works, conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, line load interchangeability, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 800 V, provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections with lugs & spreaders, etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
With Thermal Magnetic release

-

-

-

... More
up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu

4

23068

5767

... More
160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu

4

34656

8664

... More
200 Amp , 35kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu

4

54644

13661

... More
250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu

8

140000

17500

... More
400 Amp ,50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu

6

166044

27674

... More
630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu

4

120360

30090

... More
SITC of wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as per PWD specification for electrical Works, made out of CRCA sheet . Other parameters required as per point (a) ,(b), (c),(d) below:-

-

-

-

... More
(a)Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors with / without detachable extension type structure

-

-

-

... More
(b)panel shall be duly treated for derusting in 7 tank process with dephosphating and with powder coating of minimum 70 microns on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware, separate detachable gland plate M.S. base channel (min75mm) , hinged door with locking arrangement for equipment/switchgear

-

-

-

... More
[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 125 amp ) and by solid bus bar (125 amp ) . All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar.

-

-

-

... More
(d) only outer area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator. All as per drawing pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

120

413160

3443

... More
Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar as per PWD specification for electrical Works, by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Electrolytic grade Aluminium bus bar 6010 grade

600

267000

445

... More
Providing & Fixing of BIS approved Current Transformer as per PWD specification for electrical Works ,ISI marked as per IS 2705-1992/ conforming to IEC 60044-1, with secondary terminal of CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as required Current transformer Resin Cast Wound Primary / Ring Type Tape Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA

3

1305

435

... More
C T Class 1, Ratio 400/5 to 1200/5, Burden 15 VA

3

1416

472

... More
C T Class 1, Ratio 1600/5 to 2000/5, Burden 15 VA

15

10455

697

... More
Providing & Fixing of IP 51 Multi function meter as per PWD specification for electrical Works, ISI marked (IS 16444)/ Confirming to IEC 61557 & IEC 62052 with LCD/ LED 3/4 line display capable of measuring electrical parameters like V, I, F, PF, KW, Kva, Kvar, Kwh, Kvah, Kvarh display with 1A/5A CT input for LV/ HV network, with /without RS 485 communication port etc. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA lab test reports before execution & complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Multifunction LCD meter with V,A,F,PF,KW,KVA, old energy memory, class 1 accuracy without RS485 port .

2

6966

3483

... More
SITC of chemical Gel earthing system of Dual Pipe Technology made of with "B" Class G I Pipe as per IS 1239 ( part-1):2004 of Medium duty of following sizes as per points mentioned (a), (b), [c), (d), (e) below :-

-

-

-

... More
(a) filled with anti corrosive conductive compounds with the permanent sealings at both the ends, CPRI/ ERDA tested with RMS capacity of minimum 35- 40 KA for withstanding 1 second .

-

-

-

... More
(b) To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated lab for low resistivity ( less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content as per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts

-

-

-

... More
©Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height 250 to 300 mm.

-

-

-

... More
(d) Testing of earth resistance for value of 5 ohms or less as required & must record by engineer in charge during site visit and ensure to enter in measurment book.

-

-

-

... More
(e) Self certificate for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
With Pipe in Pipe Technology (Outer pipe dia. / Inner pipe dia. ) Minimum 100 mm dia borewell

-

-

-

... More
GI pipe 2000 mm long, 50 / 25mm, Terminal 40mm x 6 mm GI Strip

10

40630

4063

... More
Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. ( Excavation of Earth to be paid Extra as required. ) All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
200 mm Dia.

50

20600

412

... More
Providing and fixing welded mesh/expanded metal mesh in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. including two coat of red oxide and two coat of enamel paint or more required complete with frame work with 50 X 50 X 6mm angle iron post 30 cm in ground embeded in cement concrete 1:3:6 (30X30X45cm) at corner and every three mtr including painting with one coat of primer and two coat of enamel paint work will be done as per direction of engineer incharge of size complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Welded mesh 25 mmx 25 mm x 2.1 mm

80

70240

878

... More
Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specification for electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating. Appropriate type test certificate / OEM test report shall be submitted . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Open execution type

-

-

-

... More
630 A

4

88600

22150

... More
Providing & Fixing of ISO certified company made UL listed , IP 65 110/220 V, unibody LED Indicating lamp IEC 60947 , CSA 22.2 with integral circuit, IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 29 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Red/yellow/Green colour

20

2540

127

... More
Blue / white Colour

3

627

209

... More
Providing & Fixing of Electrical insulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
3.3 KV, 2 mm thick with proof voltage 10 KV / 3 min. and Break Down Voltage 30 KV

10

14890

1489

... More
11 KV, 2.5 mm thick with proof voltage 22 KV / 3 min. and Break Down Voltage 45 KV

20

37900

1895

... More
Supply , Installation, Testing and Comissioning of Silent DG Set (As per latest CPCB emission norms) having specifications as per A, B, C, D, E, F,G,H

-

-

-

... More
A. 1500 RPM Diesel Engine conform to BS:649/5514 of suitable BHP Engine shall have residential silencer (isolated from main DG chamber), up to 3 M exhaust piping (with insulation & cladding ) as required .

-

-

-

... More
B. AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS 4722.-2001 . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled

-

-

-

... More
C. Standard canopy with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with side wall fabricated from 1.6 mm CRCA sheet & filled with glass wool (96Kg/m3)/ Foam. as per IS 8183 the doors of 28/40/50/85 mm thick as per rating and fabricated from 1.6mm CRCA sheet packed with accoustic material,All doors/ opening are sealed with neoprene/EPDN gaskets. The enclosure has built in fuel tank, with protection and tripping of DG set against temperature of more than 50 degree centigrade

-

-

-

... More
D. Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger, Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring & control system, MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :

-

-

-

... More
E. (A)Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (B).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA. (C)Accoustic glass wool wall thickness should not be less then 100mm for rating above 250 KVA.

-

-

-

... More
F. First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department.

-

-

-

... More
G. Servicing of the DG set (as per OEM guidelines) during the DLP period shall be done by contractor including all consumables,actual charges shall be reimbursed to the contractor by department/client complete in all respect.

-

-

-

... More
H. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA/ CPCB standards approved lab type test reports before execution as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Radiator Cooled & Turbo Charged /AC 500 KVA at 0.8 pf 415V 50Hz 3-ǿ

1

3536719

3536719

... More
Supply , Installation, Testing and Comissioning of Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stop commands, control Relays , Ammeter & Voltmeter with selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA lab type test reports before execution as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Electro-Mechanical Relay Based

-

-

-

... More
500 KVA

1

273781

273781

... More
Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applications including cutting, welding etc & fittings like elbows,flanges, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts . including the cost of thermal insulation with 50 mm thick layers of LRB rock wool as per IS : 8183-1993 (64 kg/m3 density) & 26 SWG aluminium sheet claddings etc complete as required complete in all respect. OEM Must have BIS certificate and & shall have submit NABL/ OEM lab appropriate type test reports before execution as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
150 mm dia

15

35610

2374

... More
Supply, installation and testing of metal flexible coupling (bellow) of following dia required for horizontal length more than 3 mtr.as per standard of guide line of D.G. set company complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
150 mm dia

1

14346

14346

... More
Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

600

53400

89

... More
Supply, Installation, Testing & Commissioning of HT metering cubical panel as approved By DISCOMs fabricated out of 14 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX6mm having provision for Following: (i)Provision for fixing Trivector Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set (To be supplied by DISCOMs), (iii)TT Block, (iv) 6mm Bakelite sheet on all sides, (V) 3/6 core copper cable for interconnections etc. as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

1

20663

20663

... More
Providing & Fixing of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per PWD specification for electrical Works, IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
up to 6 kVar

6

7194

1199

... More
10 kVar

6

9102

1517

... More
20.0 kVar

8

20744

2593

... More
50.0 kVar

8

63680

7960

... More
Providing & Fixing of 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C tripping characteristic as per type of load and site requirement) 4KV impulse withstand voltage, as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductorline load reversibility, label holding facility , IP 20 contact protection and fitted with existing distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A rating including making connections, testing etc. as required. . OEM shall have submit NABL / CPRI / ERDA accrediated lab test reports before execution & All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Triple pole MCB

-

-

-

... More
6 A to 32 A rating

6

3816

636

... More
40 A rating

6

5496

916

... More
50-63 A rating

8

7648

956

... More
Providing & Fixing of ISO certified company made Cam operated rotary (Auto/manual) switches on existing panel with 2 way and off position using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc. as required . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
10 AMP

6

1524

254

... More
32 AMP

6

1770

295

... More
63 AMP

8

3432

429

... More
Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) as per PWD specification for electrical Works, ISI marked IS:13340-41 / conforming to IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz and total wattage loss less than 0.35 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 250 times of rated current, including making connections, testing etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
Heavy duty Three phase 480 V, 50 Hz cylindrical capacitor (Bank)

700

234500

335

... More
Providing & Fixing of IP54 on front microprocessor based three phase sensing power factor correction relay , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, VTHD, ITHD, metering facility as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab test reports. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
12 to 14 stage

2

31146

15573

... More
Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from 99.99% purity copper, class 5 stranding in acc. to IEC 60228 for lower watt loss , oxygen free ( 10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4, , in existing surface or recessed PVC/ MS conduit/casing capping including all as per pre approved by Engineer in charge,making connections, etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
1 x 6.0 sq.mm

60

2460

41

... More
1 x 10.0 sq.mm

100

7000

70

... More
1 x 16.0 sq.mm

100

12000

120

... More
1 x 1.5 sq.mm

180

2160

12

... More
Supply, Fabricating & installing following sizes of powder coated perforated M.S. cable trays with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with MS suspenders including bolts & nuts , fastners, supports, painting suspenders etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
300mm x 50mm x 1.6mm

91

45136

496

... More
Supply , Installation, Testing and Comissioning of following capacity End Feed Unit Confirming to ANSI C37.23 standard & IS 8623 P-II suitable for Sandwich typy for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. OEM Must have BIS certificate and & shall have submit NABL / CPRI / ERDA lab type test reports before execution as required complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR .

-

-

-

... More
For 1600 Amp. (Without ACB)

37

3697447

99931



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.