Jaipur Vidyut Vitran Nigam Limited Tender

If you're looking for Rajasthan tenders online and are tired of typing tender ID over and again or going through the cumbersome government websites for it, you are in luck. We have collated every Eproc Rajasthan tender on BidAssist. And for any queries related to an e-tender Rajasthan, like bidding process, registration process, etc., are explained below. Read on.

Jaipur Vidyut Vitran Nigam Limited - JVVNL Tender

Works
Electrical Cables And Wires
Electrical and Electronics
Electrical Works
Eprocure
Opening Date27 Sep 2024
Closing Date9 Oct 2024
Tender Amount₹ 13,55,378 
Notes
Download

Costs

  • EMD

    ₹ 27,108
  • Document Cost

    ₹ 2,950
  • Tender Fee

    ₹ 1,180

Summary

Work Of Construction Of 33/11 Kv Gss At Nindola, Dist. - Jaipur And Erection Of 33 Kv Line And 11 Kv Line For Interconnection Work Under Aen (htm), Jpd, Chomu On Arc Under Tn-77 In The Jurisdiction Of Jaipur District Circle-north Of Jaipur Discom.

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
(2) Excavation of pit in ordinary rock which does not require blasting/murrad (in Jodhpur discom) to erect various supports and stay sets including stacking of excavated muck from the edge of excavation/pit.

-

-

-

... More
(2.1) Height of poles/R.S.Joist/M.S. Rail /Size of pit

-

-

-

... More
(i) 9 Mtr/ 1.2mx0.6mx1.50 m deep

56

14320

255.72

... More
(3) Earth work excavation and foundation of platfrom of transformers and brakers including dressing of sides and ramming of bottoms liftup to 1.5 meter including taking out the excavated soil and depositing and refilling of jhiri, watering and ramming and disposal of surplus excavated soil as directed with in a lead of 50 meter.

-

-

-

... More
(3.1) Hard /dense soil

160

12326

77.04

... More
(4) Providing and laying cement concrete including compaction etc, complete using stone aggregate 40 mm nominal size (hand broken) in foundation plinth excluding the cost of shuttering using 1 cement : 5 sand : 10 aggregate mix. Note : 1. The rates are all lead of cement, lime, ballast, sand, surkhi and grit etc. at site of work. 2. For all concrete work coarse sand shall be used no extra will be paid . 3. Concrete mix prepared by power driven mechanical mixer shall be used . 4. Under exceptional coditions, where mechanical mixer and vibrator are not used (with the approval of Engineer Incharge reduced by 3% for mechanical mixer and 2% for Vibrator. 5. Thickness of the cement concrete should not exceeed 100 mm.

10

23711

2371.19

... More
(5) Plaster on new surface on walls in cement, sand mortar 1:6 including racking of joint etc. complete fine finsh 25 mm thick. Note : 1. The rates for complete work including racking of joints, curing, grinding, mixing and finishing T&P and scaffolding material and cost of material with all lead and lift. 2. The rates cover protection of all place and things, requiring protection and cleaing such places and thing of all droppings and splashes of mortar etc.

53.6

6877

128.32

... More
(6) Cement concrete flooring grade 1:2:4 (1-cement :2- coarse sand :4-graded stone aggregate ) rounding off edges etc.but excluding cost of nosing of steps etc. complete. Note : 1. The rates for all items inculde all form of work, laying, curing and finishing etc. The rates are for complete work at site, inclusive of all leads. 2. The rates cover the preparation and cleaing of all places

-

-

-

... More
(6.1) 25 mm thick with 12.5 mm thick nominal size aggregate.

20

3347

167.39

... More
(6.2) 75 mm thick with 20 mm thick nominal size aggregate.

20

7978

398.92

... More
(7) Masonry for foundation and plinth

-

-

-

... More
(7.1) Randon Rubble stone masonry for foundation and plinth in cement sand mortar 1:6(1 Cement : 6 Sand) including labour charges.

21

40421

1924.83

... More
(8) Safe carriage of PCC poles including loading / un-loading

-

-

-

... More
(8.1) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole

-

-

-

... More
(i) Within 10 Kms.

56

12977

231.74

... More
(ii) Above 10 Kms. & upto 30 Kms. Add for each Km. or part thereof.

56

5320

95

... More
(9) Safe carriage of steel (fabricated and unfabricated) I.e. M.S. Rails, R.S. Joists, M.S. Channels, M.S. Angles, M.S. Flat, G.I. Stay Sets, G.I. Stay Wire, G.I. Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site.

-

-

-

... More
(9.1) Within 10 Kms.

4

1302

325.65

... More
(9.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

4

368

92.2

... More
(10) Safe Carriage of insulator, hardware, cable etc.including loading/unloading and stacking in Nigam.stores etc.

-

-

-

... More
(10.1) Within 10 Kms.

3

1170

390.29

... More
(10.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

3

334

111.4

... More
(11) Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading from store to site (these Charges will be 1.5 times for both sides)

-

-

-

... More
(11.1) 25 & 40 KVA

-

-

-

... More
(i) Within 10 Kms.

1

238

238.51

... More
(ii) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

1

135

135.6

... More
(12) Safe Carriage of 33/11 KV Power Transformer

-

-

-

... More
(12.1) 5.0 MVA

-

-

-

... More
(i) Within 10 Kms

1

5081

5081.77

... More
(ii) Above 10 Kms & upto 30 Kms . Add for each Km or part thereof

1

1016

1016.2

... More
(iii) Above 30 Kms & upto 50 Kms . Add for each Km or part thereof

1

672

672.2

... More
(iv) Above 50 Kms . Add for each Km or part thereof

1

488

488.1

... More
(13) Safe carriage of breakers/kiosks etc. including loading/ unloading and stacking in Nigam stores

-

-

-

... More
(13.1) Within 10 KMs.

6

5337

889.63

... More
(13.2) Above 10 Kms. and upto 30 Kms.Add per each km,or part thereof

6

1382

230.4

... More
(14) Safe loading of power/ distribution transformer.

-

-

-

... More
(14.1) 33/11 KV power transformer.

-

-

-

... More
(i) 5 MVA

1

5035

5035.67

... More
(15) Safe unloading of power/distribution transformers

-

-

-

... More
(15.1) 33/11 KV power transformer.

-

-

-

... More
(i) Above 3.15 MVA

1

4265

4265.88

... More
(16) Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base.

38

107307

2823.89

... More
(17) Fixing of all type of fabricated material on erected supports with nut & bolts as per approved design & drawing of sub-station.

3

9480

3160.02

... More
(18) Fixing of 11kv B&S / T&C type disc insulator for 33kv lines (each unit consiting of 3 nos. disc & 1set of H/W) on terminal point including fixing of hardware and strips.

30

1408

46.96

... More
(19) Fixing of 11kv B&S/T&C type disc insulator of 11kv lines (each unit consiting of 2 nos.disc.& 1set of H/ W ) on terminal point including fixing of hardware and strips.

117

3934

33.63

... More
(20) Assembly, Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories complete in all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(20.1) G.O. switch without earthing blade.

-

-

-

... More
(i) 33kv G.O.switch

3

3336

1112.29

... More
(ii) 11kv G.O.switch

5

4325

865.1

... More
(21) Assembly and installation of Horn Gap fuse set (set of 3nos) on erected structure as per design, complete in all respect with post insulator including jumpering on both ends for connection with the system. The nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(21.1) 33kv Horn Gap fuse set.

1

512

512.84

... More
(21.2) 11kv Horn Gap fuse set.

4

1779

444.96

... More
(22) Installation of lightening arrestors on erected structure / support (1 nos) including connection with earth by wire /strip as required and jumpering etc. The nuts & boltswill be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(22.1) Sub-Station type

-

-

-

... More
(i) 33 KV L.A. each

3

512

170.95

... More
(ii) 11 KV L.A. each

15

2224

148.32

... More
(23) Installation testing as per Nigams norm & commissioning of 11/0.4KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire /strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(23.1) 25 and 40 KVA

1

621

621.01

... More
(24) Fixing of PG clamp of Panther Conductor

162

1281

7.91

... More
(25) Assembly, installation & commisioning of 11Kv Roster switch on erected structure with stting for accurate operaion including fixing of allied accessories completed in all respect with post insulators and jumperingon both ends for connection with systm. The nuts & bolts will ve supplied by contractor for which payment will be made as per prevailing Discom store issue rates.

3

4858

1619.54

... More
(26) Laying, jointing, stringing, tensioning and clamping of conductor with proper sag as directed, using bolted type hardware including binding on pin insulators, jumpering on section points with binding wire / P.G.clamps. Aluminium jointing sleeves will be used for jointing the conductor. The line must stand at proper voltage on charging. The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate.

-

-

-

... More
(26.1) IN URBAN AREA

-

-

-

... More
(i) ACSR DOG

1.5

4372

2915.03

... More
(27) 3 Nos. of earthing of 11/0.4 KV distribution transformer /sub-station with 3 pieces of M.S.Rod 20mm dia each 3 meter long and driving them into earth by mechanical means at a distance as per approved design & drawing & specification.The work includes flattening of top ends of M.S.rod drilling a hole of 9/16" dia.at flattened top and tightening of M.S.flat 50x6mm/25x3mm (having 3 hole 2ends and 1mm middle) with nuts and bolts with M.S.rods top end hole.The flat will also be welded with M.S.rod.The end will be connected to equipments as under in sequence.

3

673

224.62

... More
(28) Mesh earthing for 33/11 kv sub-station as per approved map &design usingMS flat 50X6mm/MS road 20mm dia includinglaying of flat/rod at the depth of 0.65 Mtrs.,welding & jointing at joints , structures & equipments etc.asunder:

-

-

-

... More
(28.1) Excavation of trench of 0.65 Mtrs.depth and 0.5 Mtr.width

-

-

-

... More
(i) Hard Soil

133

20303

152.66

... More
(29) Laying of MS flat /MS rod in 0.65Mtr.deep excavated trench and welding of MS flat/rod continuosly with 100 mm overlaping for straight joint including coating of MS flat joints with molten bitumen and covering joint with bitumen impregnated tape to protect from rust.

400

10292

25.73

... More
(30) Shaping of MS flat for connecting the equipments with earthmesh .The work includes the welding of MS flat with equipments/structure and also with earth mesh.The work also includes coating of MS flat joint with molten bitumen and covering jointwith bitumen impregnated tape to protect from rust.

235

9103

38.74

... More
(31) Preparation of spikes made of M.S Rod of 20 mm dia and 3 Mtr. length as per design and requirment to be driven in earth by mechanical means and Providing & fastening of suitable clamps with the M.S. Rod, connection of earth wire/stay wire/MS flat in clamp depending on type of soil:

-

-

-

... More
(31.1) Where drilling is not required

40

7612

190.31

... More
(32) Painting of exposed portion of MS flat/rod with two coats of red-oxide primer and two coats of green enamel paint.including material.

235

1675

7.13

... More
(33) Pipe Erection for power Transformer at 33/11 KV S/S:- Supply & erection of earthing electrode shall consist of G.I. Pipe 100 mm,of 3 Mtr Length. The electrode shall be buried as far as practicable 3 meters below ground level. Wherever possible, earth electrodes shall be located as near the water tap, water drain or near down take pipe. Earth electrodes shall not be installed in proximity to a metal fence. It shall be kept clear of the buildings foundations and in no case it shall be nearer than 2 meters from the outer face of the wall. The electrode shall be surrounded with layer of charcoal dust and salt mixture through out the length. The 100 mm GI pipe shall be provided with holes of 12 mm dia. drilled at 75 mm interval upto 2.5 meters length from bottom. The top of the pipe shall be provided with a G.I. threaded cap for watering the earth through a pipe. A Clamp with Pati of 12" of M.S. Flat of size 50X6 mm shall be fixed (Bolted) on the top edge of the pipe which in turn shall be connected to Neutral / Body of the Power Transformer through M.S. Flat size 50X6 mm. The G.I. cap over the GI pipe shall be housed in a masonry chamber, approximately 300 mm x 300 mm x 300 mm deep. The masonry chamber shall be provided with a RCC inspection cover resting over a RCC frame, embedded in masonry.

4

20468

5117.12

... More
(34) Erection of PCC poles in excavated pit in alignment after checking the same with plumb line as per approved design & drawing of 33/11kv sub-station.The pit should be back filled with the soil with proper ramming below 30cm ground level and then muffed above 15cm average ground level with cement concrete ratio1:3:6.The charges for muffing will be paid extra as per chapter code no 5.7 The nuts & bolts will be supplied by the contractor for which payment will be made at the prevailing store issue rates.

-

-

-

... More
(34.1) IN RURAL AREA

-

-

-

... More
(i) PCC Poles 9 Mtr. Long

56

22903

408.99

... More
(35) Erection of OCB/Kiosk/VCB complete with accessories including use of special tools & conducting all pre-commissioning test before energization,filling oil etc. complete in all respect with erection & grouting of structure (excluding civil works). The relays will be tested by Discom.

-

-

-

... More
(35.1) 33 KV VCB/SF-6 Breaker

1

5013

5013.96

... More
(35.2) 11 KV VCB (Outdoor )

5

25069

5013.96

... More
(36) Installation of control panel including checking of wiring and conducting all pre-commissioning tests before energization, satisfactory operation of all equipment existing thereof. ( The relay will be tested by Discom ).

-

-

-

... More
(36.1) 33 KV Control Panel

1

1236

1236.88

... More
(37) Installation of current/potential transformers on supporting structure including checking of wiring & conducting all pre-commissioning tests before energization & satisfactory operation in all respect (The CT/PT set will be tested by Discom).

-

-

-

... More
(37.1) 11 KV CT(1 set of 3 Nos.) OR PT Set

4

4947

1236.88

... More
(38) Laying, testing termination of control cable 1100 volts PVC insulated including supply and installation of ferrules to designate various cores of control cables by terminal Nos. of identification including utilization of cable gland. The control cable should be clearly arranged in trenches avoiding crossings including clamping of control cable at regular interval and providing identify tags.

-

-

-

... More
(38.1) 12x2.5 Sq.mm.

15

369

24.65

... More
(39) Installation of metering points on 11 KV Outgoing feeder at 33/11 KV S/S. The installation work to be carried out as per drawing/design, under the supervision of concerned Assistant Engineer (A) Mounting structure The requisite steel members will be supplied by contractor including the hardware. Contractor shall joint/weld the members to form the mounting structure as per drawing. Necessary tools, welding, machines, lifting devices etc. shall be arranged by contractor. (B) Civil works Erection of lattices in alignment including excavation and concreting of structure foundation including cement, sand and grit 20 mm size (crusher broken) having ratio 1:3:6 and grit 40 mm size for ratio 1:5:10 and curing for period as required (21 days). Area of concreting will be as per the drawing.

4

79101

19775.39

... More
(39) (Continue) (C) Metering Equipments: The requisite metering equipments (CTPT set, meter,meter box & suitable conductors for jumpers), will be provided by the concerned Assistant Engineer in healthy condition at site. The cables from CTPT set to meter box laid down in 50 mm GI pipe with suitable bends & nipples, shall be provided by contractor alongwith the consumable items such as PVC tapes, petroleum jelly etc. The cable should be PVC multi strand copper 4 core 2.5/4 Sq. mm ISI marked and firm & tight connections shall be made by suitable connector e.g. at CTPT sets by using clamps and at meter/TTB by suitable lugs etc. The CTPT sets so installed shall be earthed by means of the MS Flat (size 50x6 mm) by joining it with the nearest earthing available at the sub-station. Requisite earthing material shall be made available by the contractor. (D) Meter: Meters should be fixed firmly inside the tamper proof box, as per drawing. All the meter fixture will be provided by contractor including all consumables.

-

-

-

... More
(39) (Continue) (E) Meter Box The meter box shall be provided by the concerned Assistant Engineer. However, hardware or any other items required to fix the meter inside the meter box will be provided by contractor. The meter box will be fixed firmly with sufficient strength at a place as per drawing. The test terminal block(TTB) link type shall be provided by contractor in the meter box. (F) Painting: All surfaces interior and exterior of lattice structure shall be white aluminum painted. (G) Commissioning of Metering Equipments: Installed meters inside the box and metering equipments duly mounted on the mounting structure will be powered up by connecting load in the presence of the concerned Assistant Engineer who will arrange the necessary shut down. The completion certificate shall be furnised by contractor.be filled accordingly. Since the work involves higher A.C. voltage level, the contractor shall take full care regarding safety norms, so as to avoid any accidental hazards.

-

-

-

... More
(40) Painting with priming coats or ready mixed red-oxide paint 2 coats of approved make on steel works after cleaning with wire brush / sand paper.(including cost of red oxide)

-

-

-

... More
(40.1) On new surface

30

974

32.47

... More
(41) Painting with aluminium paint of approved brand and manufacturer to give an even surface.(including cost aluminium paint)

-

-

-

... More
(41.1) On new works with two coats.

30

1461

48.7

... More
(42) Fabrication of steel structures of M.S angle ,M.S.channel & M.S.Flat including cutting ,drilling and continunous welding joint as per design and drawing.

-

-

-

... More
(42.1) Other steel items

2

8855

4427.99

... More
PART - 2

-

-

-

... More
(1) Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations.

2.2

439

199.79

... More
(2) Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line.

300

8994

29.98

... More
(3) Excavation of pit in ordinary rock which does not require blasting/murrad (in Jodhpur discom) to erect various supports and stay sets including stacking of excavated muck from the edge of excavation/pit.

-

-

-

... More
(3.1) Height of poles/R.S.Joist/M.S. Rail /Size of pit

-

-

-

... More
(i) 9 Mtr/ 1.2mx0.6mx1.50 m deep

8

2045

255.72

... More
(3.2) Lattice Tower /Size of pit

-

-

-

... More
(i) 12.8/12.6 Mtr/ 1.5mx1.5m x2.10 m deep

41

64215

1566.22

... More
(3.3) Stay set/Depth of pit

-

-

-

... More
(i) 8'x 3/4" -0.75x0.5x1.6 m

40

9298

232.47

... More
(4) Safe carriage of PCC poles including loading / un-loading

-

-

-

... More
(4.1) 9 Mtr. Long-400 Kg /11 Mtr. PCC pole

-

-

-

... More
(i) Within 10 Kms.

8

1853

231.74

... More
(ii) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

8

760

95

... More
(5) Safe carriage of steel (fabricated and unfabricated) I.e. M.S. Rails, R.S. Joists, M.S. Channels, M.S. Angles, M.S. Flat, G.I. Stay Sets, G.I. Stay Wire, G.I. Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site.

-

-

-

... More
(5.1) Within 10 Kms.

7

2279

325.65

... More
(5.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

7

645

92.2

... More
(6) Safe Carriage of insulator, hardware, cable etc. including loading / unloading and stacking in Nigam stores etc.

-

-

-

... More
(6.1) Within 10 Kms.

10

3902

390.29

... More
(6.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

10

1114

111.4

... More
(7) Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading/unloading and stacking in the Nigam. Stores / at work site.

-

-

-

... More
(7.1) Within 10 Kms.

22.55

10704

474.71

... More
(7.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

22.55

2079

92.2

... More
(8) Erection of all type of steel supports in the excavated pit in alignment after checking the same with plumb line including fixing of cross arms and top hamper before erecting the supports. The support should be grouted and muffed in cement concrete of ratio 1:3:6 as per item No. 5.7 the remaining portion of the pit will be back filled with soil. The nuts & bolts will be provided by the contractor as per Nigam's specification for which payment will be made at the prevailing store issue rates. The cost muffing and grouting will be paid extra.

-

-

-

... More
(8.1) Lattice Structure

22.55

110236

4888.53

... More
(9) Erection &assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line.Including fixing of top bracing of M.S.Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming.The nuts &bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates.

-

-

-

... More
(9.1) PCC Poles 9 Mtr. Long(400 Kg.)/11Mtr.long

4

5191

1297.81

... More
(10) Erection & fixing of G.I. Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming. The work includes fixing of stay clamps. Stay insulator with stay wire at both ends with proper tension. Size of stay set/stay wire

-

-

-

... More
(10.1) 8"x3/4" with 7/8 SWG stay wire

40

11152

278.81

... More
(11) Providing and laying of cement concrete in ratio 1:3:6 using 43 grade cement,river sand and 12 mm to 20 mm graded blast crusher broken in pit/foundation according to the size/type of supports/stay set including compaction/curing for 21days in steel plates shuttering /farmer base.

131.2

370494

2823.89

... More
(12) Fixing and assembly of disc.point channel pair with pilot plates&clamps on erected double pole structure as per design. The nuts &bolts are to be provided by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(12.1) 33 KV line

26

3533

135.91

... More
(13) Fixing of 11kv B&S / T&C type disc insulator for 33kv lines (each unit consiting of 3 nos. disc & 1set of H/W) on terminal point including fixing of hardware and strips.

60

2817

46.96

... More
(14) Fixing of 33kv pin insulator with pins.

150

2230

14.87

... More
(15) Assembly, Installation & commissioning of gang operated isolating switch on erected structure with setting for accurate operation including fixing of allied accessories complete in all respect with post insulator and jumpering on both ends for connection with the system. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(15.1) G.O. switch without earthing blade.

-

-

-

... More
(i) 33kv G.O.switch

1

1112

1112.29

... More
(16) Fixing of PG clamp of Panther Conductor

40

316

7.91

... More
(17) Laying, jointing, stringing, tensioning and clamping of conductor with proper sag as directed, using bolted type hardware including binding on pin insulators, jumpering on section points with binding wire / P.G.clamps. Aluminium jointing sleeves will be used for jointing the conductor. The line must stand at proper voltage on charging. The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate.

-

-

-

... More
(17.1) IN RURAL AREA

-

-

-

... More
(i) ACSR DOG

6.51

16823

2584.3

... More
(18) Laying, jointing, stringing, tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc. including proper binding at each end. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(18.1) IN RURAL AREA

-

-

-

... More
(i) G.I.Earth wire 6 SWG

2.1

1877

894.23

... More
(19) Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod 20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discomstore issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom)

20

6704

335.22

... More
(20) Providing and fixing of G.I. Pipe B-Class (IS:1239 marks) at the starting and finishing point of 33 & 11 KV under ground cables and to lay & clamp vertically with the existing support including labour charges.

-

-

-

... More
(20.1) Providing and fixing of G.I. Pipe of 150 mm diameter. B-Class (IS:1239 mark),at the starting and finishing point of 33 KV under ground cables and to lay & clamp vertically with the existing support including labour charges.

12

18714

1559.54

... More
(21) Intallation of 33 KV Cable (XLPE) termination / straight through joints ( Heat shrinkable type) as per manufacturer's kit guidance and direction including preparation of cable and testing refilling etc as required.(Including crimping of lugs)

-

-

-

... More
(21.1) Outdoor end terminal

-

-

-

... More
(i) 3x240 Sq mm to 3x400 Sq mm

4

6311

1577.99

... More
(ii) NOTE: If the Cable Jointing Kits of HT / LT are not available with Nigam, then the unit officer will obtain NAC from ACOS & the contractor will supply the same as per latest SIR plus 10% (profit) of approved vendors.

2

7946

3973.28

... More
(iii) 10% Above

2

794

397.33

... More
(22) Laying of 33 KV & 11KV XLPE cable without Road cutting i.e. through burrowing machine "VERMIER" (120 cm deep) Use of this technology must be restricted to the situation like:- (i) When the passages available for laying the proposed cable is totally a metal or cement concrete road. (ii) When the road cutting is not permitted by the local administration.

-

-

-

... More
(22.1) 33 / 11 KV 3C x 300 Sq.mm cable

100

30228

302.28

... More
(23) For Extra Loop (Ghera) to be provided near the pole on termination point and the length of cable along the pole for mounting of cable jointing kit.

-

-

-

... More
(23.1) 33 KV Cable:-

-

-

-

... More
(i) 3X240 Sq.mm to 3X400 Sq.mm

52

11619

223.46

... More
PART - 3

-

-

-

... More
(1) Conducting route survey as per approved route map and pegging of route with tee off point section point & double pole locations.

1.3

259

199.79

... More
(2) Trimming of tree branches/plants manually/ by machine and preparing route approchases for proposed line.

100

2998

29.98

... More
(3) Excavation of pit in ordinary rock which does not require blasting/murrad (in Jodhpur discom) to erect various supports and stay sets including stacking of excavated muck from the edge of excavation/pit.

-

-

-

... More
(3.1) Height of poles/R.S.Joist/M.S. Rail /Size of pit

-

-

-

... More
(i) 9 Mtr/ 1.2mx0.6mx1.50 m deep

39

9973

255.72

... More
(3.2) Lattice Tower /Size of pit

-

-

-

... More
(i) 11.4/10.8 Mtr/ 1.5mx1.5m x1.80 m deep

2

2621

1310.5

... More
(3.3) Stay set/Depth of pit

-

-

-

... More
(i) 6'x 5/8" -0.75x0.5x1.35 m

36

7531

209.21

... More
(4) Safe carriage of PCC poles including loading / un-loading

-

-

-

... More
(4.1) 9 Mtr.long 200 Kg. PCC pole

-

-

-

... More
(i) Within 10 Kms.

39

7583

194.46

... More
(ii) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

39

3705

95

... More
(5) Safe carriage of steel (fabricated and unfabricated) I.e. M.S. Rails, R.S. Joists, M.S. Channels, M.S. Angles, M.S. Flat, G.I. Stay Sets, G.I. Stay Wire, G.I. Wire Nut & Bolts etc. and ACSR Conductor including loading and unloading and stacking in Nigam store /at work site.

-

-

-

... More
(5.1) Within 10 Kms.

3

976

325.65

... More
(5.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

3

276

92.2

... More
(6) Safe Carriage of insulator, hardware, cable etc. including loading / unloading and stacking in Nigam stores etc.

-

-

-

... More
(6.1) Within 10 Kms.

2

780

390.29

... More
(6.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

2

222

111.4

... More
(7) Safe carriage of fabricated lattice towers structures and sub-station structures type AB, AB beams, isolators structures etc. including loading / unloading and stacking in the Nigam Stores / at work site.

-

-

-

... More
(7.1) Within 10 Kms.

1.1

522

474.71

... More
(7.2) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

1.1

101

92.2

... More
(8) Safe carriage of 11/.4 KV 3 Phase distribution transformer including loading/unloading from store to site (these Charges will be 1.5 times for both sides)

-

-

-

... More
(8.1) 25 & 40 KVA

-

-

-

... More
(i) Within 10 Kms.

1

238

238.51

... More
(ii) Above 10 Kms. & upto 30 Kms. Add for each Km.or part thereof.

1

135

135.6

... More
(9) Erection of all type of steel supports in the excavated pit in alignment after checking the same with plumb line including fixing of cross arms and top hamper before erecting the supports. The support should be grouted and muffed in cement concrete of ratio 1:3:6 as per item No. 5.7 the remaining portion of the pit will be back filled with soil. The nuts & bolts will be provided by the contractor as per Nigam's specification for which payment will be made at the prevailing store issue rates. The cost muffing and grouting will be paid extra.

-

-

-

... More
(9.1) Lattice Structure

1.1

5377

4888.53

... More
(10) Erection of PCC poles in excavated pit with fixing of brackets,cross arms & top hampers as required in alignment after checking the same with plumb line. The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigam's specification for which the payment will be made at the prevailing Discom store issue rates.

-

-

-

... More
(10.1) IN RURAL AREA

-

-

-

... More
(i) PCC Poles 9 Mtr. Long (400 Kg)

21

9447

449.9

... More
(11) Erection & assembly of 2 Pole structures of steel supports or PCC poles in excavated pit in alignment after checking the same with plumb line. Including fixing of top bracing of M.S. Channels with pilot plates and clamps.The support is to be back filled with soil with proper ramming. The nuts & bolts are to be provided by the contractor as per Nigams specfication for which the payment will be made at the prevailing Discom store issue rates.

-

-

-

... More
(11.1) PCC Poles 9 Mtr. Long (200 Kg.)

18

19890

1105

... More
(12) Erection & fixing of G.I. Stay sets with anchor plates in excavated pit in required position and back filling with soil with proper ramming. The work includes fixing of stay clamps. Stay insulator with stay wire at both ends with proper tension. Size of stay set/stay wire

-

-

-

... More
(12.1) 6"x5/8" with 7/10 SWG stay wire

36

8687

241.31

... More
(13) Fixing of all type of fabricated material on erected supports with nut & bolts as per approved design & drawing of sub-station.

1

3160

3160.02

... More
(14) Fixing and assembly of disc.point channel pair with pilot plates top hampers & clamps on erected single pole structure as per design. The nuts &bolts are to be provided by the contractor as per Nigams specification for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(14.1) 11 KV line

70

4155

59.37

... More
(15) Fixing of 11kv B&S / T&C type disc insulator for 33kv lines (each unit consiting of 3 nos. disc & 1set of H/W) on terminal point including fixing of hardware and strips.

162

7607

46.96

... More
(16) Fixing of 11kv pin insulator with pins.

123

1220

9.92

... More
(17) Installation testing as per Nigams norm & commissioning of 11/0.4KV distribution transformer on erected supports including fixing of base channels as per requirment jumpering on HV&LV side, crimping of lugs/ clamping earth connections of body and neutral of transformer with wire /strip (as already provided with earthing ) complete in all respect. The PG clamps nuts & bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(17.1) 25 and 40 KVA

1

621

621.01

... More
(18) Laying, jointing, stringing, tensioning and clamping of conductor with proper sag as directed, using bolted type hardware including binding on pin insulators, jumpering on section points with binding wire / P.G.clamps. Aluminium jointing sleeves will be used for jointing the conductor. The line must stand at proper voltage on charging. The contractor will be provide P.G.clamps for which payment will be made as per prevailing Discom issue rate.

-

-

-

... More
(18.1) IN RURAL AREA

-

-

-

... More
(i) ACSR RABBIT

4.1

9044

2205.98

... More
(19) Laying, jointing, stringing, tensioning and clamping of G.I.Earthwire continuosly on single/double pole by using earth clamps /nuts & bolts with washers and earth reel etc. including proper binding at each end. The nuts and bolts will be supplied by the contractor for which payment will be made as per prevailing Discom store issue rates.

-

-

-

... More
(19.1) IN RURAL AREA

-

-

-

... More
(i) G.I.Earth wire 6 SWG

1.3

1162

894.23

... More
(20) Drawing of overhead ABC conductor (Areal bunched cable)on existing erected pole/support including laying. Jointing,stringing complete in all respect.

-

-

-

... More
(20.1) 3cx25 + 25 Sq mm

0.3

1085

3618

... More
(21) Earthing of line for all type of supports as per REC construction standards using Stay wire/GI wire with one pcs.of M.S.rod 20mm dia each 3 meter long and driving into earth by mechanical means as per approved design.Drawing &specification.All material except MS rod,MS flat & stay wirewill be supplied by the contractor.If material is supplied by the contractor ,the payment will be made as per prevailing Discomstore issue rates.(In case of PCC poles earthing must be connected with earthwire already available on PCC pole at bottom)

10

3352

335.22



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.