Tata Memorial Centre Tender
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.
Costs
EMD
₹ 27,741Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_TMC_812966_1Bid Award Id
ViewTender No
Upgradation of MGPS SangrurTender Authority
Tata Memorial Centre ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply Installation Testing Commissioning of 3 stage filteration system
3
-
-
... More
Supply Installation Testing Commissioning of 7.5HP Reciprocating Vacuum Pump (Make Anesta Iwata / Ingersoll Rand )
1
-
-
... More
Supply Installation Testing Commissioning of Vacuum Receiver tank MS 1000 ltr
1
-
-
... More
Supply Installation Testing Commissioning of Vacuum Bacteria Filter T851 (Make Trident & Eqivalent)
1
-
-
... More
Supply Installation Testing Commissioning of Medical Grade Copper Pipe 28mm (0.9)with copper fitting ( Make Mexflow/mandv)
30
-
-
... More
Supply Installation Testing Commissioning of Medical Grade Copper Pipe 22mm (0.9)with copper fitting ( Make Mexflow/ Maindv)
50
-
-
... More
Supply Installation Testing Commissioning of Medical Grade Copper Pipe 15mm (0.9)with copper fitting ( Make Mexflow/Mandev)
25
-
-
... More
Supply Installation Testing Commissioning of Isolation Valve 22mm (make RN/Pax)
5
-
-
... More
Supply Installation Testing Commissioning of Isolation Valve 28mm (make RN/Pax)
2
-
-
... More
Supply Installation Testing Commissioning of Safety Valve 15mm
3
-
-
... More
Supply Installation Testing Commissioning of Alarm 4-Line Oxygen, Air, Vacuum, Nitrous
1
-
-
... More
Supply Installation Testing Commissioning of Alarm 3-Line Oxygen, Air, Vacuum
2
-
-
... More
Supply Installation Testing Commissioning of Alarm 2-Line Oxygen,Vacuum
1
-
-
... More
Supply Installation Testing Commissioning of Alarm 1-Line Oxygen
1
-
-
... More
Supply Installation Testing Commissioning of Vacuum Clamp
1
-
-
... More
Supply Installation Testing Commissioning of Butterfly Valve (12mm)
60
-
-
... More
Supply Installation Testing Commissioning of Brass Point
20
-
-
... More
Supply Installation Testing Commissioning of Brass Point
60
-
-
... More
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed armoured and served cable 1100 volts grade as per IS:7098 (Part-1)1988 to be laid (On Surface) wit proper clamps as per site and CPWD General Specifications:-
Overall size 70sq.mm (3½ Core) Armoured (On-Surface)
100
-
-
... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required in all aspect.
Make: COMMET/ BELIGA/PEECO/GRIPWELL/DOWELLS
3½ X 70 sq. mm (38mm)
2
-
-
... More
Supply and erection of sheet metal double door vertical distribution boards IP 43-IK09 metal door (dust protected) as per IS:8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars for each phase, 2 Nos. shrouded neutral bars, 2Nos. earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting MCCB's as incomer and outgoings SP/TP miniature circuit breakers in the distribution board as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc.:- TP&N Double Door Vertical DB's 8 way each (With provision of FP MCCB 160amp.)
1
-
-
... More
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having
Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary
handle and relevant PWD general specifications complete with G.I. Bolts,
Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:- MCCB Four Pole 100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
1
-
-
... More
Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:
-
-
-
... More
63 A TP&N
a. Air Compressor 3-Ф b. Vacuum - 3-Ф, c. spare d. Spare
4
-
-
... More
a. For Power load 32 A TPN b. For light load 20 amp TPN c. Spare 20 amp
4
-
-
... More
Supplying and fixing TP sheet steel enclosure on surface/ recess along with following rating 415 volts “C” curve TP MCB complete with connections, testing and commissioning etc. as required.
Make: L&T/Schneider/ABB/Legrand
4
-
-
... More
Triple pole and neutral 32A (Equipment side) a. Air comprassor - 3-Ф, b. Vaccume Pump c. existing Pump d. Spare
4
-
-
... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick
including accessories, and providing masonry enclosure with
cover plate having locking arrangement and watering pipe of
2.7 metre long etc. with charcoal/ coke and salt as required.
2
-
-
... More
Supplying and laying 6 SWG G.I. wire at 0.50 metre below
ground level for conductor earth electrode, including
connection/ termination with GI thimble etc. as required
60
-
-
... More
Supply and erection of PVC insulated PVC sheathed (4 core) round flexible cable with copper conductor (FR) cable (ISI marked) confirm to IS:694/1990 left bare in DWC or casing of suitable size complete in all espects as desired by the Engineer-in-charge:-
-
-
-
... More
4c X 6 sq. mm Annealed Copper Cable flexible copper cable (For equpiments )
15
-
-
... More
Supplying and making end termination with brass compression
gland and aluminium lugs for following size of PVC insulated
and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV
grade as required.
4 X 6 sq. mm (19mm) for quipment
4
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the
following sizes of FRLS PVC insulated copper conductor, single
core cable in surface/ recessed medium class PVC conduit as
required.
-
-
-
... More
2 X 4 sq. mm + 1 X 4 sq. mm earth wire for Power Points & ACs
15
-
-
... More
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire for Lighting circuit
45
-
-
... More
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recesse medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
-
-
-
... More
Group C (Primary Point)
8
-
-
... More
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc as required.
-
-
-
... More
Group C (Secondary Point)
8
-
-
... More
Supplying and fixing suitable size GI box with modular plate and cover in FRLSont on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. (3Module for Power Points)
Make: Panasonic/Legrand/Goldmedal/Havells/L&T
8
-
-
... More
Supplying and fixing following size/ modules, GI box alongwith
modular base & cover plate for modular switches in recess etc.
as required.
6 Module (200mmX75mm)
4
-
-
... More
Supplying and fixing following modular switch/ socket on the
existing modular plate & switch box including connections but
excluding modular plate etc. as required.
-
-
-
... More
5/6 amps switch
8
-
-
... More
3 pin 5/6 A socket outlet
8
-
-
... More
Supplying and fixing two module stepped type electronic fan
regulator on the existing modular plate switch box including
connections but excluding modular plate etc. as required.
4
-
-
... More
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete
with fitting and cutting, jointing etc. in the existing trench, complete as required.
90 mm dia (OD-90 mm & ID-76 mm nominal)
25
-
-
... More
Supply, Installation, Testing and Commissioning of 1200 mm sweep,
BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC)
Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2
nos. canopies, shackle kit, safety rope, copper winding, Power Factor
not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery
minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019),
THD less than 10%, remote or electronic regulator unit for speed
control and all remaining accessories including safety pin, nut bolts,
washers, temperature rise=75 degree C (max.), insulation resistance
more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC
Supply, earthing etc. complete as required.
4
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements