Public Works Department Tender

If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.

Public Works Department - PWD Tender

Works
Electrical and Electronics
Eprocure
Opening Date3 Dec 2024
Closing Date31 Dec 2025
Tender Amount₹ 6,05,67,151 
Notes
Download

Costs

  • EMD

    ₹ 12,11,350
  • Document Cost

    ₹ 30,000
  • Tender Fee

    ₹ 5,900

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Wiring light point

56

762

42698.32

... More
Wiring 6Amp. wall socket point

15

618

9283.95

... More
Wiring 16/20Amp. power plug control point

29

478

13862.87

... More
PVC INSULATED FR COPPER CONDUCTOR CABLES:

-

-

-

... More
Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-

-

-

-

... More
Overall size 1sq.mm (Un-sheathed)

310

19

5942.7

... More
Overall size 1.5sq.mm (Un-sheathed)

110

24

2711.5

... More
Overall size 4sq.mm (Un-sheathed)

620

53

33114.2

... More
XLPE INSULATED ARMOURED CABLES (LOOSE):

-

-

-

... More
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specidications:-

-

-

-

... More
Overall size 16sq.mm (2Core) Armoured (Loose)

120

131

15802.8

... More
Overall size 240sq.mm (3½ Core) Armoured (Loose)

1300

1136

1477398

... More
Overall size 300sq.mm (3½ Core) Armoured (Loose)

441

1376

606873.33

... More
Overall size 400sq.mm (3½ Core) Armoured (Loose)

2243

1729

3878281.58

... More
XLPE INSULATED ARMOURED CABLES (ON SURFACE):

-

-

-

... More
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed armoured and served cable 1100 volts grade as per IS:7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:-

-

-

-

... More
Overall size 16sq.mm (2Core) Armoured (On-Surface)

400

154

61628

... More
Overall size 95sq.mm (3½ Core) Armoured (On- Surface)

552

512

282767.52

... More
Overall size 150sq.mm (3½ Core) Armoured (On- Surface)

550

761

418632.5

... More
Overall size 240sq.mm (3½ Core) Armoured (On- Surface)

650

1182

768657.5

... More
PVC, HDPE PIPES & PVC FLEXIBLE PIPES:

-

-

-

... More
Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, MS saddle clamps and other petty materials etc., as per PWD General Specifications:-

-

-

-

... More
Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed)

290

70

20532

... More
G.I. EARTHING:

-

-

-

... More
Earthing with G.I. wire/ rope in G.I. pipe partly recessed and partly on surface complete with 150cm long 50mm dia. G.I. earth pipe (Cutting threads and 36 Nos. holes, 1cm dia. to make a mesh around the GI Pipe) with G.I. reducing socket including erection of the same, 4.50 metre (14.76 feet) below ground level with 20Kg. charcoal & salt mixture etc., up to 8 metre in length (including boring & refilling).

-

-

-

... More
Earthing with 7/12 S.W.G. (7/2.80mm dia.) G.I. rope in 20mm dia G.I. pipe with G.I. reducing socket 50mm x 20mm (upto 8Metre in length)

54

3770

203591.34

... More
COPPER EARTHING (Upto 23 metre in Length):

-

-

-

... More
Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 19.50 metre (63.96 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 23metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 18metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm around the hole of excavation:-

-

-

-

... More
Earthing with 25mm x 5mm Copper Tape (upto 23Metre in Length)

18

37996

683934.66

... More
Earthing with 40mm x 5mm Copper Tape (upto 23Metre in Length)

36

51617

1858214.88

... More
MINIATURE CIRCUIT BREAKERS/ RCBO's/ RCCB's:

-

-

-

... More
Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- Make: Havell's, Legrand( DX3), Schneider (ACTi-9), L&T ( Exora), Hager (NCN), or equivalent.

-

-

-

... More
MCB Single Pole 6-32amp. (10kA, Curve-C)

50

190

9529

... More
MCB Double Pole 50, 63amp. (10kA, Curve-C)

5

930

4650.7

... More
SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB/ RCBO/ RCCB's:

-

-

-

... More
Supply and erection of sheet metal Double Door Distribution Boards IP 43-IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB/ RCCB/ RCBO as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB/ RCCB/ RCBO as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:-

-

-

-

... More
SP&N Double Door Distribution Board 12 way each

5

1797

8989.5

... More
XLPE INSULATED HT ARMOURED CABLES (LOOSE):

-

-

-

... More
Supply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanised steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be laid loose in the existing trench or pipe:-

-

-

-

... More
HT Cable Overall size 35sq.mm (3Core)

500

562

281285

... More
HT Cable Overall size 70sq.mm (3Core)

350

759

265923

... More
HT Cable Overall size 150sq.mm (3Core)

612

1154

706376.52

... More
HT Cable Overall size 240sq.mm (3Core)

1400

1605

2247742

... More
HT Cable Overall size 300sq.mm (3Core)

2010

1860

3740409

... More
S/E of Heat shrinkable cable end termination/ Straigt through joint kit for 11 KVA /6.6 KV (E) XLPE Cables as approved & desired by Enginer in charge:-

-

-

-

... More
Heat Shrinkable End Termination for cable size 240- 400 sq. mm, 3Core (Indoor Type)

10

4635

46356.1

... More
Heat Shrinkable type Straight Through Joint Kit for cable size 240-300 sq. mm, 3Core

10

12915

129157

... More
DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:

-

-

-

... More
Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-

-

-

-

... More
Doubled Walled corrugated HDPE pipe 120/103.5mm (outer.inner) Dia

4200

290

1221234

... More
MS CHANNELS/ FLATS:

-

-

-

... More
Supply and Erection of MS angle iron (Channel)/ MS Flats of suitable size with cutting, bending and necessary holes as desired by Engineer-in-charge at site:-

-

-

-

... More
MS angle iron size 100mm x 50mm x 6mm thick

250

635

158972.5

... More
TRANSFORMER:-

-

-

-

... More
Supply, Erection, Testing at site and Commissioning of 11/0.433KV 800KVA 50 Hz OFF Load Tap Changer (+5% to -10% @ 2.5%), Three phase, ESTER Oil type transformer. i) Standard: IS: 2026 and IS 1180 2021 (Part-1) Level 2 with all latest amendmentsii) Losses and Temp. Rise shall be as per IS1180 2021 level 2. i.e. Losses at 50% Load: 2.147KW (Max), and Losses at 100% Load: 5.838KW (Max) iii) Outdoor/Indoor Installation, iv) Vector group: Dyn11 v) Rating: 800 KVA vi) Cooling System: ONAN, vii) Winding: Copper, viii) Magnetic Core: Prime grade of M4 or better ix) High voltage: 11KV-50 Z, x) Low voltage: 433V-50HZ xi) System highest voltage: 12kV at the HV side xii) Manufacturer testing labotatory to be NABL certified with in house core cutting facility for proper control & monitoring of quality & to avoid mixing of Prime core with Second grade/defective core materials xiii) Insulation Level-H.V. Power Frequency (KV rms): 28 kV-H.V. Impulse withstand voltage (KV peak): 75 kVp Tapping: +5% to -10%OFF Load Tap Changer in steps of 2.5%.Temperature rise of Oil/Winding Over design ambient temperature of 50 deg C: 40/45 deg. C xiv) HT Termination - Cable Box xv) LT Termination - Bus Duct and with all accessories ie. first filling of filtered dehydrated oil and confirming to IS & standard accessories required. Note: 1. Following points are to be considered for selection of transformer manufacturer: (i) Te core shall be constructed from high grade, non ageing, prime grade CRGO with M4 grade or better, silicon steel laminations. The core material shall be purchased directly from manufacturer (Posco/Nippon/Novex/AK steels) or from their accredited marketing organisation. (ii) Manufacturer shall have in house automated core cutting facility to ascertain that there is no mixing of second grade core. (iii) The core andcore assembly should be dried through a high a high efficent vacuum drying autoclave for heating and drying. (iv) Manufacturer shall test transformer from NABL accredited lab to ascertain the authenticity of test results and Purchaser may test the transformer from CPRI/ERDA officials with their testing equipments.Complete in all repsects as desired by the Engineer in charge of work at site.

-

-

-

... More
Transformer designed for 110% continuous overfluxing withstand capability as per IS:6600. Noise Level for Transformer shall be as per NEMA TR1-2013. All Routine Test shall be carried out as per IS: 2026:- Note: Manufacturer testing labotatory to be NABL certified with in house core cutting facility for proper control & monitoring of quality & to avoid mixing of Prime core with Second grade/defective core materials. The warranty period will be start after complete commissioning. The Supervision, Inspection & testing at Manufactuers site (By department in contractor scope). The Concerened contactor shall be provide the detailed drawing of Transformer from OEM designed attested and submitted to department for approval with complete specification in all respects as approved and desired by the Engineer-in-charge at site

5

2895419

14477095

... More
Supply, Erection, Testing and Commissioning of 11/0.433KV 1000KVA 50 Hz OFF Load Tap Changer (+5% to -10% @ 2.5%), Three phase, ESTER Oil type transformer.i) Standard: IS: 2026 and IS 1180 2021 (Part-1) Level 2 with all latest amendments ii) Losses and Temp. Rise shall be as per IS1180 2021 level 2. i.e. Losses at 50% Load: 2.62KW (Max), and Losses at 100% Load: 7KW (Max) iii) Outdoor/Indoor Installation iv) Vector group: Dyn11 v) Rating: 1000 KVA vi) Cooling System: ONAN, vii) Winding: Copper, viii) Magnetic Core: Prime grade of M4 or better (ix) High voltage: 11KV-50 HZ, x) Low voltage: 433V-50HZ xi) System highest voltage: 12kV at the HV side xii) Manufacturer testing labotatory to be NABL certified with in house core cutting facility for proper control & monitoring of quality & to avoid mixing of Prime core with Second grade/defective core materials xiii) Insulation Level-H.V. Power Frequency (KV rms): 28 kV-H.V. Impulse withstand voltage (KV peak): 75 kVp Tapping: +5% to -10%OFF Load Tap Changer in steps of 2.5%.Temperature rise of Oil/Winding Over design ambient temperature of 50 deg C: 40/45 deg. C xiv) HT Termination - Cable Box xv) LT Termination - Bus Duct and with all accessories ie. first filling of filtered dehydrated oil and confirming to IS & standard accessories required. Note: 1. Following points are to be considered for selection of transformer manufacturer: (i) Te core shall be constructed from high grade, non ageing, prime grade CRGO with M4 grade or better, silicon steel laminations. The core material shall be purchased directly from manufacturer (Posco/Nippon/Novex/AK steels) or from their accredited marketing organisation. (ii) Manufacturer shall have in house automated core cutting facility to ascertain that there is no mixing of second grade core. (iii) The core and core assembly should be dried through a high efficent vacuum drying autoclave for heating and drying. (iv) Manufacturer shall test transformer from NABL accredited lab to ascertain the authenticity of test results and Purchaser may test the transformer from CPRI/ERDA officials with their testing equipments.Complete in all repsects as desired by the Engineer in charge of work at site.

-

-

-

... More
Transformer designed for 110% continuous overfluxing withstand capability as per IS:6600. Noise Level for Transformer shall be as per NEMA TR1-2013. All Routine Test shall be carried out as per IS: 2026:- Note: Manufacturer testing labotatory to be NABL certified with in house core cutting facility for proper control & monitoring of quality & to avoid mixing of Prime core with Second grade/defective core materials. The warranty period will be start after complete commissioning. The Supervision, Inspection & testing at Manufactuers site (By department in contractor scope). The Concerened contactor shall be provide the detailed drawing of Transformer from OEM designed attested and submitted to department for approval with complete specification in all respects as approved and desired by the Engineer-in-charge at site

4

3193071

12772284

... More
Vacuum Circuit Breaker

-

-

-

... More
Supply, Erection, Testing and Commisioning of 11kV, 3Phase, 50Hz, Indoor metal clad, floor mounted, ‘Horizontal draw out’ type VCB (Vacuum Circuit Breaker) switch board unit 630/800 Amp. which includes 630/800 Amp. Vacuum Circuit Breaker for Incoming/ Out going feeder with Electrolytic Copper bus bars of suitable rating, Horizontal Isolation type as per IEC 62271-100-200. The Switchgear panels shall be sheet steel construction with ALUZINC not less than 2.5mm thickness for load bearing sections and not less than 2mm thickness for non-load bearing, dust, moisture and vermin proof to provide a degree of protection IP-4X in accordance with IS:13947. VCBs are type tested according to International Standards IEC-62271 at renowned laboratories. They are compact, safe and reliable. The Panels shall be tested for IAC level of 25kA/1 Sec. No. of operations of Vacuum interrupter bottles for better performance (i) At rated current: 10,000 operation (ii) No. of short circuit dead operation at rated short circuit current: 100 opeartion.

-

-

-

... More
VCB parameters are as below: (a). Rated Voltage: 12kV (b). Rated short circuit breaking current withstand : Min. 25kA for 3sec. (c). Rated insulation voltage lightning (Impulse withstand) : At 75kV Peak (d). Rated insulation voltage( Power frequency withstand) : Min. 28kV (e). Rated operating sequence : O-0.3 sec - CO - 3 min-CO (f). Spring charging mechanism : Manually as well as motor operated (230V, AC, 50Hz) (g). Operation type: Manually and electrically open (Electrical-230V, AC,50Hz) (h). Earthing Switch : Mechanically interlocked device to prevent personnel from getting electric shock during breaker maintenance. VCB incorporating mechanical as well as electrical ON/OFF indiaction "OFF" push button, test/ serviceposition limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position, Manual charging of breaker should be done without opening the front door.

-

-

-

... More
Incomer shall consist of: (a). Cast Resin CT's 11kV : 600-300/1-1A, Core1: Class1, 10VA for 3phase, Core2: 5P10, 10VA (b). Cast Resin PT's 11kV : PT Ratio 11kV/√3 / 110V/√3 / 110V/√3, Class 1, Class 0.5 Burden 50VA (c). Protections : Numerical instantaneous IDMTL mimic dispaly relay (230V, AC, 50Hz) : U/V, O/V, E/F, O/C, S/C & TCS with RS 485 Modbus protocol for communication & drawout type (d). Master Trip/ Anti pumping relay (e). Digital Voltmeter : Range 0-12kV with necessary voltmeter with built in selector switch & suitable for 230V AC 96x96 sq.mm dial with shrouded terminal. (f). Digital Ammeter : Applicable Range with necessary ammeter with built in selector switch & suitable for 230V AC 96x96 sq.mm dial with shrouded terminal. (g). Multi-function meter with suitable communication to Central Software dta control & SCADA system, Converter having facility of real time data monitoring, historical trend and web dashboard (h). Necessary AC supply, healthy indication lamp & switch, TNC (Trip, Neutral & Close) breaker control switch with indicating arrangement, Local/ remote selector switch for breaker open/close operations All the relays shall belong to a common platform and shall be of single make with Electro-mechanical type relays in draw-out casing. PCB shall be with conformal coating to withstand heavily polluted environments.

-

-

-

... More
Outgoing shall consist of: (a). Cast Resin CT's 11kV : 600-300/1-1A, Core1: Class1, 10VA for 3phase, Core2: 5P10, 10VA (b). Protections : Numerical instantaneous IDMTL mimic dispaly relay : E/F, O/C, S/C & TCS with RS485 Modbus protocol for communication & drawout type for line feeder protection (c). Master Trip/ Anti pumping relay (d). Transformer Protection : 3 elements auxiliary relay (230V, AC, 50Hz) for transformer fault, Alarm for Buchholz, winding temperature & oil temperature (e). Digital Ammeter : Applicable Range with necessary ammeter with built in selector switch & suitable for 110V AC 96x96 sq.mm dial with shroded terminal (f). Multi-function meter with suitable communication to Central Software dta control & SCADA system, Converter having facility of real time data monitoring, historical trend and web dashboard (g). Necessary AC supply, healthy indication lamp & switch, TNC (Trip, Neutral & Close) breaker control switch with indicating arrangement, Local/ remote selector switch for breaker open/close operations All the relays shall belong to a common platform and shall be of single make with Electro-mechanical type relays in draw-out casing. PCB shall be with conformal coating to withstand heavily polluted environments:-

-

-

-

... More
11kV, 3Phase, 50Hz, Indoor metal clad, floor mounted, ‘Horizontal draw out’ type VCB (Vacuum Circuit Breaker) Switch board unit 630/800 Amp. which includes 1 No. 630 /800Amp. Vacuum Circuit Breaker as Incomer, 2Nos. Vacuum Circuit Breaker as Outgoing feeder with in built power packs interconnected with Electrolytic Copper bus bars of suitable rating.

3

1765664

5296992

... More
Supply, Erection, Testing and Commisioning of 11kV, 3Phase, 50Hz, Indoor metal clad, floor mounted, ‘Horizontal draw out’ type VCB (Vacuum Circuit Breaker) switch board unit 630/800 Amp. which includes 630/800 Amp. Vacuum Circuit Breaker for Incoming/ Out going feeder with Electrolytic Copper bus bars of suitable rating, Horizontal Isolation type as per IEC 62271-100-200. The Switchgear panels shall be sheet steel construction with ALUZINC not less than 2.5mm thickness for load bearing sections and not less than 2mm thickness for non-load bearing, dust, moisture and vermin proof to provide a degree of protection IP-4X in accordance with IS:13947. VCBs are type tested according to International Standards IEC-62271 at renowned laboratories. They are compact, safe and reliable. The Panels shall be tested for IAC level of 25kA/1 Sec. No. of operations of Vacuum interrupter bottles for better performance (i) At rated current: 10,000 operation (ii) No. of short circuit dead operation at rated short circuit current: 100 opeartion.

-

-

-

... More
VCB parameters are as below: (a). Rated Voltage: 12kV (b). Rated short circuit breaking current withstand : Min. 25kA for 3sec. (c). Rated insulation voltage lightning (Impulse withstand) : At 75kV Peak (d). Rated insulation voltage( Power frequency withstand) : Min. 28kV (e). Rated operating sequence : O-0.3 sec - CO - 3 min-CO (f). Spring charging mechanism : Manually as well as motor operated (230V, AC, 50Hz) (g). Operation type: Manually and electrically open (Electrical-230V, AC,50Hz) (h). Earthing Switch : Mechanically interlocked device to prevent personnel from getting electric shock during breaker maintenance. VCB incorporating mechanical as well as electrical ON/OFF indiaction "OFF" push button, test/ serviceposition limit switches, with minimum 6NO+6NC breaker auxiliary contacts in service position, Manual charging of breaker should be done without opening the front door.

-

-

-

... More
Incomer shall consist of: (a). Cast Resin CT's 11kV : 600-300/1-1A, Core1: Class1, 10VA for 3phase, Core2: 5P10, 10VA (b). Cast Resin PT's 11kV : PT Ratio 11kV/√3 / 110V/√3 / 110V/√3, Class 1, Class 0.5 Burden 50VA (c). Protections : Numerical instantaneous IDMTL mimic dispaly relay (230V, AC, 50Hz) : U/V, O/V, E/F, O/C, S/C & TCS with RS 485 Modbus protocol for communication & drawout type (d). Master Trip/ Anti pumping relay (e). Digital Voltmeter : Range 0-12kV with necessary voltmeter with built in selector switch & suitable for 230V AC 96x96 sq.mm dial with shrouded terminal. (f). Digital Ammeter : Applicable Range with necessary ammeter with built in selector switch & suitable for 230V AC 96x96 sq.mm dial with shrouded terminal. (g). Multi-function meter with suitable communication to Central Software dta control & SCADA system, Converter having facility of real time data monitoring, historical trend and web dashboard (h). Necessary AC supply, healthy indication lamp & switch, TNC (Trip, Neutral & Close) breaker control switch with indicating arrangement, Local/ remote selector switch for breaker open/close operations All the relays shall belong to a common platform and shall be of single make with Electro-mechanical type relays in draw-out casing. PCB shall be with conformal coating to withstand heavily polluted environments.

-

-

-

... More
Outgoing shall consist of: (a). Cast Resin CT's 11kV : 600-300/1-1A, Core1: Class1, 10VA for 3phase, Core2: 5P10, 10VA (b). Protections : Numerical instantaneous IDMTL mimic dispaly relay : E/F, O/C, S/C & TCS with RS485 Modbus protocol for communication & drawout type for line feeder protection (c). Master Trip/ Anti pumping relay (d). Transformer Protection : 3 elements auxiliary relay (230V, AC, 50Hz) for transformer fault, Alarm for Buchholz, winding temperature & oil temperature (e). Digital Ammeter : Applicable Range with necessary ammeter with built in selector switch & suitable for 110V AC 96x96 sq.mm dial with shroded terminal (f). Multi-function meter with suitable communication to Central Software dta control & SCADA system, Converter having facility of real time data monitoring, historical trend and web dashboard (g). Necessary AC supply, healthy indication lamp & switch, TNC (Trip, Neutral & Close) breaker control switch with indicating arrangement, Local/ remote selector switch for breaker open/close operations All the relays shall belong to a common platform and shall be of single make with Electro-mechanical type relays in draw-out casing. PCB shall be with conformal coating to withstand heavily polluted environments:-

-

-

-

... More
11kV, 3Phase, 50Hz, Indoor metal clad, floor mounted, ‘Horizontal draw out’ type VCB (Vacuum Circuit Breaker) Switch board unit 630/800 Amp. which includes 1 No. 630 /800Amp. Vacuum Circuit Breaker as Incomer, 3Nos. Vacuum Circuit Breaker as Outgoing feeder with in built power packs interconnected with Electrolytic Copper bus bars of suitable rating.

1

2313344

2313344

... More
LT PANEL:-

-

-

-

... More
Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel (TTA-IEC 61439) enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, Rated Impulse Voltage- 12 KV, 3 phase 4 wire & earth system. Panel has to be certified for Internal Arc test for 50 KA at Horizontal Busbar, Vertical Busbar and Cable chamber and Mechanical Impact IK10.The assembly manufacture should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP42). Fabrication: Panel shall be made from 14/16 SWG CRCA sheet, conforming to IEC61439 (Part 1&2). The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B IP2 X (touch proof) protection (even after opening the feeder compartment door. ) fully compartmentalized type i.e. bus bar channel as well as the cable chamber should be totally isolated from the feeder chamber,The compartmentalization to be achieved by using metal separators, use of PVC sheet/ Hylem sheets shall not be allowed. Where the crossing of the wire or bus link should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. The base channel will be made out of 75mm x 40mm x 5mm rolled channel. "The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc. Painting: The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work. Busbars: The panel shall be provided with TPN Aluminium Bus-Bar of E91E Grade. of suitable size according to the size of MCCB's. All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports.

-

-

-

... More
Metering: The panel shall be completed with digital metering unit (with selector switches, voltmeter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc. Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO 9001: 2015 standard). LV Switchboards shall be certified by 3rd party Certification body as per IEC 61439-(Part1-2).Test reports without certificate shall not be considered admissible proof of compliance.The Certifying Authority shall be qualified under ISO/IEC 17065 as per IEC 61439-1.Certified design of switchboards shall be proven design from OEM(Original Equipment/ Switchgear Manufacturer). OEM name should be mentioned on top of each column of switchboard. Also, OEM Partnership Certificate shall be furnished by Panelbuilder.Switchboard configurations offered shall be CPRI/ Independent international test house tested for all the 12 type tests as per IEC61439-1-2 and to provide certificate against each panel rating and internal arc tests. Copies of the test certificates shall be submitted with the tender.The authorization certificate of principal /switchgear manufacturer should be attached by concerned contactor/ panel builder, The Concerned contactor shall be approved the detailed drawing of panel with complete specification from the Engineer in charge at site. Detail of capacities of ACB/MCCB's to be installed in the cubical panel Enclosure (including the cost of ACB/MCCB's+E.R.H.) as per following.

-

-

-

... More
Incomer: Air circuit-breaker of suitable ampere rating at 415V, 50Hz, 4 Pole Electrical draw-out type with inbuilt microprocessor based trip sytem with thermal memory, zone selective interlocking, pre trip alarm, individual fault indicating LED, O/C, S/C, Instantaneous & E/F internal protection, Impulse withstand voltage 12kV, rated insulation voltage 1000V, rated operational voltage 690V, fully rated neutral, protection against overload & shortcircuit with setting at 50%-100%-OFF, suitability for isolation as per IEC 60947-2. The ACB should be capable for recording 10 fault history, LCD Display of current & voltage, Icu = Ics = Icw (1 Sec.) = 50kA with no derating upto 50 degree celcius on the existing industrial panel (With terminal adapter on load and line side of breaker), including bonding to the existing earth and making necessary connections with suitable size of thimbles as required by the Engineer-in-Charge at site and as per PWD General Specifications.

-

-

-

... More
Public Health (Panel Size 3550mmX1825mmX1000mm):- Incommer Feeder :- 1250 Amp.415volts 50KA, 4P EDO ACB = 2No. MCB Single Pole 6-32amp. (10kA, Curve-C) = 8No. Under Voltage Release 220VAC for ACB Interlocking Bus Coupler: 1250 Amp.415volts 50KA, 4P EDO ACB = 1No. Under Voltage Release 220VAC for ACB Interlocking Outgoing Feeder:- MCCB FP 400amp.,415volts,≥36kA Microprocessor Based Adj. Thermal and Magnetic Setting = 3No.

1

1552538

1552538

... More
Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel (TTA-IEC 61439) enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, Rated Impulse Voltage- 12 KV, 3 phase 4 wire & earth system. Panel has to be certified for Internal Arc test for 50 KA at Horizontal Busbar, Vertical Busbar and Cable chamber and Mechanical Impact IK10.The assembly manufacture should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP42). Fabrication: Panel shall be made from 14/16 SWG CRCA sheet, conforming to IEC61439 (Part 1&2). The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B IP2 X (touch proof) protection (even after opening the feeder compartment door. ) fully compartmentalized type i.e. bus bar channel as well as the cable chamber should be totally isolated from the feeder chamber,The compartmentalization to be achieved by using metal separators, use of PVC sheet/ Hylem sheets shall not be allowed. Where the crossing of the wire or bus link should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. The base channel will be made out of 75mm x 40mm x 5mm rolled channel. "The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc. Painting: The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work. Busbars: The panel shall be provided with TPN Aluminium Bus-Bar of E91E Grade. of suitable size according to the size of MCCB's. All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports.

-

-

-

... More
Metering: The panel shall be completed with digital metering unit (with selector switches, voltmeter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc. Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO 9001: 2015 standard). LV Switchboards shall be certified by 3rd party Certification body as per IEC 61439-(Part1-2).Test reports without certificate shall not be considered admissible proof of compliance.The Certifying Authority shall be qualified under ISO/IEC 17065 as per IEC 61439-1.Certified design of switchboards shall be proven design from OEM(Original Equipment/ Switchgear Manufacturer). OEM name should be mentioned on top of each column of switchboard. Also, OEM Partnership Certificate shall be furnished by Panelbuilder.Switchboard configurations offered shall be CPRI/ Independent international test house tested for all the 12 type tests as per IEC61439-1-2 and to provide certificate against each panel rating and internal arc tests. Copies of the test certificates shall be submitted with the tender.The authorization certificate of principal /switchgear manufacturer should be attached by concerned contactor/ panel builder, The Concerned contactor shall be approved the detailed drawing of panel with complete specification from the Engineer in charge at site. Detail of capacities of ACB/MCCB's to be installed in the cubical panel Enclosure (including the cost of ACB/MCCB's+E.R.H.) as per following.

-

-

-

... More
Incomer: Air circuit-breaker of suitable ampere rating at 415V, 50Hz, 4 Pole Electrical draw-out type with inbuilt microprocessor based trip sytem with thermal memory, zone selective interlocking, pre trip alarm, individual fault indicating LED, O/C, S/C, Instantaneous & E/F internal protection, Impulse withstand voltage 12kV, rated insulation voltage 1000V, rated operational voltage 690V, fully rated neutral, protection against overload & shortcircuit with setting at 50%-100%-OFF, suitability for isolation as per IEC 60947-2. The ACB should be capable for recording 10 fault history, LCD Display of current & voltage, Icu = Ics = Icw (1 Sec.) = 50kA with no derating upto 50 degree celcius on the existing industrial panel (With terminal adapter on load and line side of breaker), including bonding to the existing earth and making necessary connections with suitable size of thimbles as required by the Engineer-in-Charge at site and as per PWD General Specifications.

-

-

-

... More
Radiotherapy (Panel Size 3550mmX2275mmX1000mm) :- Incommer Feeder :- 1250 Amp.415volts 50KA, 4P EDO ACB = 2No., MCB Single Pole 6-32amp. (10kA, Curve-C) = 8No. , Under Voltage Release 220VAC for ACB Interlocking Bus Coupler: 1250 Amp.415volts 50KA, 4P EDO ACB = 1No., Under Voltage Release 220VAC for ACB Interlocking Outgoing Feeder:- MCCB FP 400amp.,415volts,≥36kA Microprocessor Based Adj. Thermal and Magnetic Setting = 3No. MCCB FP 200amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting= 5 No.

1

1622448

1622448

... More
Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel (TTA-IEC 61439) enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, Rated Impulse Voltage- 12 KV, 3 phase 4 wire & earth system. Panel has to be certified for Internal Arc test for 50 KA at Horizontal Busbar, Vertical Busbar and Cable chamber and Mechanical Impact IK10.The assembly manufacture should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP42). Fabrication: Panel shall be made from 14/16 SWG CRCA sheet, conforming to IEC61439 (Part 1&2). The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B IP2 X (touch proof) protection (even after opening the feeder compartment door. ) fully compartmentalized type i.e. bus bar channel as well as the cable chamber should be totally isolated from the feeder chamber,The compartmentalization to be achieved by using metal separators, use of PVC sheet/ Hylem sheets shall not be allowed. Where the crossing of the wire or bus link should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. The base channel will be made out of 75mm x 40mm x 5mm rolled channel. "The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc. Painting: The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work. Busbars: The panel shall be provided with TPN Aluminium Bus-Bar of E91E Grade. of suitable size according to the size of MCCB's. All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports.

-

-

-

... More
Metering: The panel shall be completed with digital metering unit (with selector switches, voltmeter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc. Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO 9001: 2015 standard). LV Switchboards shall be certified by 3rd party Certification body as per IEC 61439-(Part1-2).Test reports without certificate shall not be considered admissible proof of compliance.The Certifying Authority shall be qualified under ISO/IEC 17065 as per IEC 61439-1.Certified design of switchboards shall be proven design from OEM(Original Equipment/ Switchgear Manufacturer). OEM name should be mentioned on top of each column of switchboard. Also, OEM Partnership Certificate shall be furnished by Panelbuilder.Switchboard configurations offered shall be CPRI/ Independent international test house tested for all the 12 type tests as per IEC61439-1-2 and to provide certificate against each panel rating and internal arc tests. Copies of the test certificates shall be submitted with the tender.The authorization certificate of principal /switchgear manufacturer should be attached by concerned contactor/ panel builder, The Concerned contactor shall be approved the detailed drawing of panel with complete specification from the Engineer in charge at site. Detail of capacities of ACB/MCCB's to be installed in the cubical panel Enclosure (including the cost of ACB/MCCB's+E.R.H.) as per following.

-

-

-

... More
Incomer: Air circuit-breaker of suitable ampere rating at 415V, 50Hz, 4 Pole Electrical draw-out type with inbuilt microprocessor based trip sytem with thermal memory, zone selective interlocking, pre trip alarm, individual fault indicating LED, O/C, S/C, Instantaneous & E/F internal protection, Impulse withstand voltage 12kV, rated insulation voltage 1000V, rated operational voltage 690V, fully rated neutral, protection against overload & shortcircuit with setting at 50%-100%-OFF, suitability for isolation as per IEC 60947-2. The ACB should be capable for recording 10 fault history, LCD Display of current & voltage, Icu = Ics = Icw (1 Sec.) = 50kA with no derating upto 50 degree celcius on the existing industrial panel (With terminal adapter on load and line side of breaker), including bonding to the existing earth and making necessary connections with suitable size of thimbles as required by the Engineer-in-Charge at site and as per PWD General Specifications.

-

-

-

... More
Nuclear Plant (Panel Size 1450mmX2275mmX1000mm) Incommer Feeder :- 1250 Amp.415volts 50KA, 4P EDO ACB = 1No., MCB Single Pole 6-32amp. (10kA, Curve-C) = 3No. Under Voltage Release 220VAC for ACB Interlocking, Outgoing Feeder:- MCCB FP 63/80/100amp.,415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting (2 MCCB 63Amp+2MCCB 100 Amp)= 4 No.., MCCB FP 200amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting= 1 No., MCCB FP 630amp., 415volts, ≥36kA Microprocessor Based Adj.Thermal and Magnetic Setting = 1No Under Voltage Release 220VAC for ACB Interlocking

1

709127

709127

... More
Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel (TTA-IEC 61439) enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, Rated Impulse Voltage- 12 KV, 3 phase 4 wire & earth system. Panel has to be certified for Internal Arc test for 50 KA at Horizontal Busbar, Vertical Busbar and Cable chamber and Mechanical Impact IK10.The assembly manufacture should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP42). Fabrication: Panel shall be made from 14/16 SWG CRCA sheet, conforming to IEC61439 (Part 1&2). The fabrication should be such that all the member i.e. vertical/horizontal should be detachable type i.e. total bolted. In case of any changes required at site should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B IP2 X (touch proof) protection (even after opening the feeder compartment door. ) fully compartmentalized type i.e. bus bar channel as well as the cable chamber should be totally isolated from the feeder chamber,The compartmentalization to be achieved by using metal separators, use of PVC sheet/ Hylem sheets shall not be allowed. Where the crossing of the wire or bus link should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition. The base channel will be made out of 75mm x 40mm x 5mm rolled channel. "The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc. Painting: The sheet metal is sprayed with corrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work. Busbars: The panel shall be provided with TPN Aluminium Bus-Bar of E91E Grade. of suitable size according to the size of MCCB's. All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports.

-

-

-

... More
Metering: The panel shall be completed with digital metering unit (with selector switches, voltmeter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc. Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO 9001: 2015 standard). LV Switchboards shall be certified by 3rd party Certification body as per IEC 61439-(Part1-2).Test reports without certificate shall not be considered admissible proof of compliance.The Certifying Authority shall be qualified under ISO/IEC 17065 as per IEC 61439-1.Certified design of switchboards shall be proven design from OEM(Original Equipment/ Switchgear Manufacturer). OEM name should be mentioned on top of each column of switchboard. Also, OEM Partnership Certificate shall be furnished by Panelbuilder.Switchboard configurations offered shall be CPRI/ Independent international test house tested for all the 12 type tests as per IEC61439-1-2 and to provide certificate against each panel rating and internal arc tests. Copies of the test certificates shall be submitted with the tender.The authorization certificate of principal /switchgear manufacturer should be attached by concerned contactor/ panel builder, The Concerned contactor shall be approved the detailed drawing of panel with complete specification from the Engineer in charge at site. Detail of capacities of ACB/MCCB's to be installed in the cubical panel Enclosure (including the cost of ACB/MCCB's+E.R.H.) as per following.

-

-

-

... More
Cancer Hospital (LT Panel Size 3550mmX2275mmX1000mm) :- Incommer Feeder :- 1250 Amp.415volts 50KA, 4P EDO ACB = 2No. MCB Single Pole 6-32amp. (10kA, Curve-C) = 8No. Under Voltage Release 220VAC for ACB Interlocking Bus Coupler: 1250 Amp.415volts 50KA, 4P EDO ACB = 1No. Under Voltage Release 220VAC for ACB Interlocking Outgoing Feeder:- MCCB FP 400amp.,415volts,≥36kA Microprocessor Based Adj. Thermal and Magnetic Setting= 4No. MCCB FP 200amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting= 6 No.

1

1671682

1671682

... More
Supply of Rubber hand gloves suitable for 11KV.

8

899

7192

... More
Supply & fixing of shock treatment chart both in Hindi & English for treating person suffering due to electric shock mounted on wall hooks.

4

181

724

... More
Providing and fixing H.T. danger notice plate of 250 mm x 200mm, made of mild steel at least 2mm thick and vitreous enamelled white on both sides and with inscription in single red colour on front side as required.

4

157

628

... More
Providing of set of 4 Nos. 9.5 Litre capacity GI bucket painted in post office red colour with prior coat of red - oxide paint and written with white paint 'Fire' and mounted on MS angle iron frame with bracket of appropriate size and capacity including filling sand etc.

4

5596

22384

... More
Supply and fixing of foam fire extinguishers, Portable ABC type 6Kg capacity hanged on wall with bracket component as required.

13

3999

51987

... More
Supply of First Aid box as approved by St. John Ambulance Brigade / Indian red Cross conforming to IS 2217 -1963

4

2262

9048

... More
Supply & fixing of fire retardant/ extinguishing Electrical insulated synthatic mat 1Mt. x 2Mt. of 2.0 mm thick +/- 10% confirming to BIS: DOC NO. ET-02 (5440) meeting requirments of IS: 15652 :2006 (with upto date amendment), suitable for all voltages not exceeding 3.3 KV and having minimum width of 1000 mm +/- 20mm and including supply of required quantity of adhensive/ compound and fixing the same at size as per site requirments.

4

2322

9288

... More
Supply & fixing of fire retardant/ extinguishing Electrical insulated synthatic mat 1Mt. x 2Mt. of minimum 3.0 mm thick +/- 10% confirming to BIS: DOC NO. ET-02 (5440) meeting requirments of IS: 15652 :2006 (with upto date amendment),, suitable for all voltages not exceeding 33 KV and having minimum width of 1000 mm +/- 20mm and including supply of required quantity of adhensive/ compound and fixing the same at size as per site requirments.

4

3393

13572

... More
Supply and erection of LED batten 20 Watt LED (including constant LED driver) with High quality extruded aluminium with efficacy of LED fixture minimunm 100 lumens per watt and operating voltage between 140 to 270 volt, THD 10% ingress protection IP20 (as per latest BIS standards) surge protection - 2.5 KV and above (as per IS/IEC standards) wattage of each low power LED less than 1 watt input AC frequency 50 Hz ± 3 % with 5 year warranty including there drivers complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site. LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide Letter ION No: AT/2021/GL/1410-1422, Dated: 06.05.2021. Besides this the lighting fixtures manufactures should have in house NABL accredited laboratory.

44

751

33044

... More
Supply and erection of LED Flood Light 120 watt, AC supply voltage 140-270 volts, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD10%, CRI minimum 70, High power LED (with wattage 1 to 5 watt) with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No: AT/2021/GL/1410-1422 Dated: 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab

20

10220

204400

... More
Supply and Erection of 5 Star Rating BLDC Ceiling fan Suitable size 48" (1200mm), No of blades:3Down d length: 26 cm, Motor type: BLDC, Star Rating: 5 Star Bidde, Power Consumption: 26-28W, Rated frequency: 50Hz, Rated Voltage 220-240V, Net contents: 1 N Fan Motor with PCB Controller, 1 N Safety Wire1 N Canopy Set, 2 N AAA Batteries (1.5 V)1 N Downrod, 1 N Instruction Manual1 N Set of 3 N Fan Blades & 1 N Shackle Assembly, Guarantee: 2 Years including erection, testing of ceiling fan, having connections with PVC insulated & sheathed two single core copper conductor (FR) having cable size of 0.75 Sq.mm. The work should complete in all respect as desire by the Engineer in charge of work at site.

34

4472

152048

... More
Supply and erection of Heavy duty Exhaust Fan 300mm, 900RPM with aluminium louver shutter, double ball bearing longer life including flexible wire & petty material etc. for connections and testing complete in all respect as approved and desired by the Engineer in- charges at site.

12

4842

58104

... More
PCC POLES: Supply and erection of pre-stressed cement concrete pole of suitable length with a given planting depth confirming to IS-1678/ 1960/1978 below ground level in excavated pit of suitable dimension complete in all respect as per satisfaction of Engineer-in-charge:-

-

-

-

... More
PCC Pole Overall Length 9 metre, Planting depth 1.5 metre, W/L 200 kg.

54

4485

242193.78

... More
STAY SETS: Supply and erection of Stay Set consisiting of 19/20mm dia.of suitable length G.I. stay rod duly threaded upto 300mm at one end and shaped on the other end. MS plate size 30cm x 30cm x 6mm with 20mm dia. hole drilled in the centre of the plate G.I. stay wire size 7/10 SWG, G.I. thimble for stay binding, Egg/Strain insulator, MS elbow made out of 16mm plain sheet and a 20cm long piece of 50mm x 50mm x 6mm angle iron made to the shape as approved by Engineer-in-charge. Stay set complete shall be fixed to the pole by providing suitable size full clamps made out 50mm x 6mm size MS flat with required number of nut and bolts 16mm dia. on one end and shall be embedded in the on the other end. The stay plate shall be covered with cement concrete having total volume of the concrete not less that 0.042Cum. The job shall include excavation of pit and back filling and after pouring concrete with excavated soil etc. as approved/desired by the the Engineer-in-charge:-

-

-

-

... More
Stay Set consisiting of 19/20mm dia., 2.4 metre Long G.I. Stay Rod

20

3110

62219.8

... More
Supply stringing and sagging of aluminium conductor steel reinforced (ACSR) on poles including binding with insulators using aluminium wires complete as desired by the Engineer in charge of the site:-

-

-

-

... More
ACSR-RACOON conductor (80 sq. mm) Size (6/4.09 Al.+1/4.09mm GI)

450

86

39109.5



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.