Patiala Locomotive Works Tender
If you want to inquire about any e-tender the Punjab government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Punjab tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Punjab etender you're looking for. Read further to learn how to search and bid for etender Punjab.
Costs
EMD
₹ 7,200Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Electrical Work Required For "construction Of Drug Store And Toilets In Plw Hospital In Colony- ii, Plw, Patiala".
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
PLW-EL-412-24-PLW HQ-ELECTRICAL/PLWTender No
PLW-EL-412-24Tender Authority
Patiala Locomotive Works ViewPurchaser Address
-Website
http://ireps.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Excavation of Kachcha trench/Pucca trench/any other terrain (750 mm deep from ground level & 4 width 350 mm), laying, termination, testing and commissioning PVC/XLPE, armoured, Aluminium conductor LT cable of size 4CX70 sq. mm. in Kachcha trench/Pucca trench/any other terrain/through HDPE pipe/G.I. pipe/RCC pipe as per technical specification and site requirements.
200
100
20100
Supply, laying & fixing of ISI marked PVC conduit pipe 25 mm dia to be concealed in wall/on wall 5 surface where as required along with all accessories such as PVC pipe bends, junction boxes, junction box covers, steel saddle clamps, steel screws etc. complete in all respect as per technical specifications and site requirements.
100
57
5728
Supply, installation, testing and commissioning of TP&N, double door Main Distribution Board 6 comprising of the followings as per technical specifications and site requirements: (i) 4 pole MCCB 100 A as incomer -01 No. (ii) DP MCB 63 A 'C' series- 03 No. (iii) SP MCB 6-32 A 'C' series- 18 No. (iv) Neutral link - 01 No. (v) Danger Plate - 01 No. (vi) Busbar arrangement - 01 set
3
14682
44046.15
Supply, erection, testing and commissioning of GI Pipe Earthing complete with all accessories i.e. G.I. B class pipe, GI Earth wire 8 SWG for earth continuity, salt, charcoal, CC pit & RCC cover etc. as per drawing no. DMW/EL/PD/1428, technical specification and site requirements.
2
2251
4502.7
Supply and laying of GI Earth wire 8 SWG as per technical specifications and site requirements.
60
30
1842
Supply, Installation, connection, testing and commissioning of fan regulator as per technical specifications and site requirements.
6
220
1320
Supply, Installation, testing and commissioning of SDB 8 way provided with neutral links/bar, earth terminal and duly wired complete in all respect as per technical specifications and site requirements.
2
2000
4000
Supply, Installation, connection, testing, and commissioning of MCB DP 32 Amp 'C' Curve in SDB as per technical specifications and site requirements..
2
430
860
Supply, Installation, connection testing, and commissioning of MCB SP 16 Amp 'C' Curve in SDB as per technical specifications and site requirements.
12
148
1784.4
Installation, testing and commissioning of Energy efficient Ceiling fans 1200 mm sweep.
6
74
447
Installation, testing and commissioning of energy efficient LED based tube light fittings 20-22 watt complete with LED tube rod be installed at site with all accessories and hardwares required & as per technical specifications and site requirements.
10
54
549
Installation, testing and commissioning of Exhaust fan 380 mm. sweep complete in all respect with all accessories and hardwares required at site as per technical specifications and site requirements.
3
373
1120.2
Design, Supply, installation, testing and commissioning of LT Light Panel comprising of the followings as per technical specifications and site requirements: (i) Main switches SFU 400 Amp as incomer -01 17 No. (ii) SFU 250 Amp - 01 No. (iii) SFU 100 Amp - 06 No. (iv) SFU 63 Amp - 05 No. (v) LCD display (digital) KWh meter along with CTs. (vi) Voltmeter, Ammeter, Indicators, voltage seclector switch, Amp selector switch. (vii) Aluminium Bus bar arrangment for 3 phase & neutral system as per required size and capacity power distribution. (viii) Sheet metal fabrication work complete with MS sheet etc.
1
224916
224916
Supply, erection, testing & commissioning of G.I. Earthing station as per PLW's Drawing No. PLW/EL/PD/1512/Rev-I, site requirements and technical specification complete with the followings:- i) GI Earthing plate size 600x600x6 mm as an Earthing electrode ii) GI strip size 38x3/25x5 mm (minimum cross section 114 18 sq. mm.) to Earth pit iii) 'B' class GI pipe 6 mtr. long of 38 mm. dia iv) 220 Kg. Salt and 120 Kg charcoal filling v) GI pipe, funnel, CI cover etc. vi) Excavation of approximately 900 mm diameter, 7 meter deep pit in ground, assembling and lowering of Earthing GI plate, GI Pipe, GI Earthing strip and filling of pit with charcoal, salt & Earth, pouring of water into pit, making of C.C.masonary Earth pit with cover and writing Earthing value on nearest wall with paint.
2
9414
18829.64
Supply and laying of G. I. Earthing strip of size: 38X3/25X5 mm. (minimum cross section 114 sq. mm.) from Earthing station to proposed MDB/SDB and as per technical specifications and site requirements.
60
121
7275