The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Provn Of Addl Ac Plant With Integrated Ahu And Hepa For Ot Of Mh Under Ge (u) Bathinda in Bathinda, Punjab, with an estimated contract value of Rs. 3,25,64,000. The bid opening date for this tender is 30-04-2025 and the last date for bid submission is 11-06-2025. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
AI Insights
Technical
Technical
Financial
Class Of Bidder
... View More
Class 'A' and above, specifically for MES enlisted contractors.
Technical Capacity
... View More
The required prior work experience for the bidder includes satisfactorily completion of requisite value works with Central/State Government/ Central/ State PSUs/AWHO/AFNHB/ CGEWHO/ DGMAP. The contractor should meet the enlistment criteria of 'A' class MES contractors. Additionally, the contractor's average annual turnover is considered as part of the eligibility criteria. However, specific values like amount and percentage of similar works completed are not mentioned.
Costs
EMD
₹ 4,00,600Document Cost
₹ 2,000Tender Fee
Refer Documents
Summary
Provn Of Addl Ac Plant With Integrated Ahu And Hepa For Ot Of Mh Under Ge (u) Bathinda
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_706066_1Tender No
CE BTZ/BTD/TOKEN-07 OF 2025-26 84483/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Bus Coupler shall be configured as follows : (a) Accessories including Breaker Control Switch (T-N-C), space heater with thermostat, DC , AC control
circuit through MCB, Indicating Lamps for RYB, spring charge, DC healthy, Breaker ON/OFF/TRIP and TEST/ SERVICE position.
-
-
-
... More
Chiller Should be 4 Star rated. Bidder has to submit the BEE Star rating Certificate in support of Energy Efficiency rating for chiller model approval
-
-
-
... More
Supplying, installing, testing and commissioning of Dual Plate Check valve 80mm bore, PN-1.6 rating having Body Cast Iron, Disc SS-304 along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
2
-
-
... More
Design, Supply, installation, testing and commissioning of site/factory fabricated supply air duct (air supply to inside OT, square/rectangular ducting), fabricated from the 22 gauge galvanized steel sheet having zinc coating on both sides, including all fixtures and fitting accessories complete such as neoprene rubber gaskets, elbows, splitters, vanes, supports to installed /hanging the duct with suitable size of SS hole fastener, full threaded rod, screws, fastener, hook, nut bolt, washer etc, and including insulation with 32 mm thick class "o" closed cell EPDM insulation. Insulation exposed to sun shall also be wrapped with 2 layer of fiber glass cloth & 2 coat of UV paint complete all as specified and directed.
Note :- (i) The duct work shall be as per IS-655 and design of duct shall be approved by Accepting Officer before fabrication. (ii) The GI sheet for duct work shall conform to class viii with zinc coating of 120 gm/sq mtr as per IS-277(2003). (iii) Duct joint should be properly seal with Silicon gel. (iv) Cost for required scaffolding work to install the ducts at site shall also deemed to be included in the unit rate.
250
-
-
... More
Sch 'A' Sec - III (Part-II), EXTERNAL WATER SUPPLY WORKS
-
-
-
... More
Supplying, installing, testing and commissioning of electrical HW generator of capacity 18 KW - Multi Heater bank, equipped with sufficient number of electrical immersion heaters. The pressure vessel shall be constructed and insulated on all sides with 100 mm thick density 48 kg/cum fiber glass and cladded with 0.63 mm aluminum sheet in a neat and clean manner. The generator shall be equipped with all automatic and safety controls such as manual reset high temperature water outlet, step controller and recycling relay, 'ON' 'OFF' switch thermostats, pilot light, low water cutoff and other controls as per manufacturers recommendations. All controls and terminals shall be located in an integral control cabinet factory wired and tested. The generator shall be suitable for 415 (+)/(-) 10% volts, 50 cycle, 3 phase power supply. The entire generator shall be factory assembled and tested at 350 PSI pressure. The Hot Water Generator shall be of following capacity made of MS sheet and dish end made of MS with heaters arranged in banks and controlled by electronic controller and thermostats so that hot water is generated at 70º C with nominal variation including necessary controls including inlet and outlet connections for water as per specifications complete with water drain line with necessary fitting, air purging valve on top, pressure release valve, low level cut-out. Auto vent sight-glass, foundation for HWG as per manufacturer’s instructions complete all as specified and as directed.
1
-
-
... More
Chilled Water Pump : 2 Nos ( 1W+1S)
(ii) 20 A, 415 V, TP MCB for chilled water pumps including fully automatic starter suitable for upto 7.5 HP or higher capacity as per Chilled water motor rating complete with connector, Auto manual Selector switch, push button, On, Off, Trip Indicating light, over load protection, SPPR, Multifunction meter - 2 No (Both starter panel should integrated with motor protection relay and 1 Voltmeter and 1 Amp meter with suitable size of CT with Acc class 0.5 in both starter panel).
-
-
-
... More
Sch 'A' Sec - V (Part-II), AIR CONDITIONING WORKS
-
-
-
... More
Supplying, installing, testing and commissioning of balancing valve 50mm bore, PN-1.6 rating having Body: CI:IS:210 FG:220, Bonnet : SG Iron IS : 1865 GR 420/7, Seat: Nitrile/EPDM, Stem: AISI 410// Disc: EN3 along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
3
-
-
... More
(i) 125 A, 415 V, Ics = Icu = 36 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and Thermal Magnetic based trip - 01 No
(ii) LED phase indicators (Yellow, Blue, Red) - 01 Set
(iii) Multifunction meter with CTs with accuracy class 0.5 - 01 No
-
-
-
... More
The Incomer Panels shall contain Line PT arrangement. The Panel, Vacuum Circuit Breaker, Vacuum Bottle, Numerical relays shall be of same make as the Panel Manufacturer. Bus bar should be of electrolyte Copper. The panel shall be tested for IAC AFLR for 26.3kA/1s. The IED (Numerical relay) shall be Complied to 61850 protocol without any external protocol converter. GOOSE signals shall be freely configurable. WEB HMI feature should be present. Inter-operability test shall be preferably done. Proof w.r.t Interoperability shall be submitted by the Manufacturer. The relay shall have integral arc-protection based on simultaneous detection of current and light to ensure reduced cubicle damage and increase personal safety. (15 ms) The relay must support IEC 61850 Edition 1 and Edition 2 (with test reports) and shall supports HSR and PRP redundancy protocols. It shall comply with international standard of NERC CIP or BREW for cyber security. The Circuit Breaker shall be of floor rolling design with encapsulated Vacuum bottles, and shall have all fool-proof interlocks shall be provided to prevent a ‘Closed’ breaker to rack out from ‘Service’ to ‘Test’ /'Isolated’, position or insert a ‘closed’ breaker from ‘Test’ to ‘Service’ position. In either case the breaker contacts must remain in open position. Before racking out the breaker must be fully discharged from any static charge. Switchgear should be SCADA Compatible. Panel should be Alu zinc coated All Panels shall have integral earth Switch with making capacity.
-
-
-
... More
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
-
-
-
... More
Subtotal
-
-
-
... More
Supplying, installing, testing and commissioning of ball valve 25mm bore, PN-1.6 rating having Cast iron body, SG iron disc & AISI 410 shaft along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
1
-
-
... More
Sch 'A' Sec - IV (Part-II), EXTERNAL ELECTRIFICATION AND STANDBY POWER SUPPLY WORKS
-
-
-
... More
Supplying, installing, testing and commissioning of 3-Way valve 25mm bore, PN-1.6 rating along actuator, Thermostat & transformer with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed. Note: The valves controller shall be specially programmed to regulate humidity. The programming should ensure that the hot water flow opens when the relative humidity (RH) in the air-conditioned room rises above the set point and closes when the RH falls below the set point.
1
-
-
... More
Condenser
(i) Condenser Leaving Water Temperature : 97.5 º F
(ii) Condenser Entering Water Temperature : 90 º F
(iii) Condenser Water Flow Rate : 180 USGPM
(iv) Condenser Maximum Pressure Drop : 10.2 Feet
(v) Condenser Fauling Factor : 0.00100 h.ft 2 º F/Btu
(vi) Maximum KW/TR @ 100% load on above selection data ( Duty Point) shall not be more than 0.8837
(vii) COP should not be less than 5.0 ( On actual duty point )
-
-
-
... More
Supply only modular switch 16Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
Supplying, installing, testing and commissioning of Y-Strainer 80mm bore, PN-1.6 rating having Body: Cast Iron/MS fabricated, Screen: SS-304, End Connection: Flanged End Connection along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
2
-
-
... More
Material and labour for concealed Point wiring for one socket out let 15/16 Amps point controlled by one switch (on independant board) (using red, black and green colour wires as colour coding) complete with 4 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches / socket, including provn of 4 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switch, socket complete all as specified and as directed. (switch, socket shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate).
1
-
-
... More
Copper Busbar Rating of 1250 Amps, Short Circuit Capacity of 26.3kA .Bus-bars shall have full Voltage Sleeving on it and shall be self-supported type, i.e. without any support insulators.
-
-
-
... More
Evaporator
(i) Evaporator Leaving Water Temperature: 44º F
(ii) Evaporator Entering Water Temperature: 54 º F
(iii) Evaporator Water Flow Rate : 90 USGPM
(iv) Evaporator Maximum Pressure Drop : 8.9 Feet
(v) Evaporator Fouling Factor : 0.000500 h.ft 2 º F/Btu
-
-
-
... More
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing strip 25x4mm by means of GI bolts/nuts/washers and protected by 40 mm bore GI light grade pipe upto test point or upto 7.5mtr, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, Pit cover 40mm thick made with RCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including TMT reinforcement 8mm dia @ 75mm c/c both way, MS handle 12mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge.
Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing strip upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
16
-
-
... More
Material and labour for shifting of DG Set (complete fitted in acoustic enclosure) of any capacity (320KVA to 380KVA) including disconnecting all connection (input and output connection cable, earthing etc), handling and transporting of DG set from existing location to Proposed location upto a distance of 10 KM and installing on PCC foundation including connecting input and output connection cable with minor spares as required, commissioning and testing complete all as specified and as as directed. Note:- (i) Cost for taking down, loading/unloading, shifting transport/T&P (crane and vehicle) for shifting to proposed site and minor spares to complete the job and functional shall deemed to be included in the quoted unit rate, nothing shall be paid extra on this account.
(ii) Incase damage of DG set during to the shifting, which penalty recovery shall be made from the contractor payment as per directed. (iii) RCC/PCC platform and connection cable upto DG set shall be measured and paid separately.
3
-
-
... More
Supply and fixing MCB ‘B’ curve suitable for 240 volts AC supply, 06 to 32 Amps, SPN with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
1
-
-
... More
Supply and fixing energy efficient LED security light fitting of 45W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street luminaire, with driver, including electric connection with using 3 core flexible copper conductor cable 1.5Sqmm from ceiling rose to light fitting, fixing the light fitting with new bracket made out of GI tubing medium grade 25mm dia, 1.5 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron size 25x3 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Minimum 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
1
-
-
... More
Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIFICATION AND STANDBY POWER SUPPLY WORKS" as listed in Schedule ‘A’ Section - IV (Part-I)
1
4236772
-
... More
Supply and installing of cable laying protection U shape cable tray with perforation more than 17.5 % in convenient sections of size 50mm height and 300mm width made out of hot dip galvanized sheet 1.6 mm thick including fixing accessories like cross over, bolt in partition, snap in partition, supporting corner, horizontal bend, low elbow, rising elbow, T-pieces, tray cover, edge protection, full threaded rod, slotted U channel, round head square neck bolt, flange nut, hinged joiner, screws, fastener, hook, nut bolt, washer etc complete all as specified and as directed.
Note :- (i) Cost for accessories as per site requirement for installing of cable tray shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account.
40
-
-
... More
Supplying, installing, testing and commissioning of Y-Strainer 100mm bore, PN-1.6 rating having Body: Cast Iron/MS fabricated, Screen: SS-304, End Connection: Flanged End Connection along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
2
-
-
... More
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 4 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable 1100 volt drawn through and including PVC conduit 25mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed by Engineer-in-charge.
Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
20
-
-
... More
Supply only modular Socket outlet multipurpose type 6 Amp, flush type (2 module) complete all as specified and as directed by Engineer-in-charge.
2
-
-
... More
Exhaust fan unit Starter- 20 Amp TP, MCB 'C' Curve type along with DOL starter, VFD of suitable capacity inline with motor rating fixing, By pass arrangement for VFD & starter along with auto manual selection switch, Manual Frequency control switch, On/Off Push button & Indicating light - 2 Nos for Exhaust Fan unit. Note : Panel should integrated with motor protection relay and 1 Voltmeter and 1 Amp meter with suitable size of CT with Acc class 0.5 in both starter panel.
-
-
-
... More
Supplying, installing, testing and commissioning of Mono Block centrifugal chilled water pump ( 1 W+1 S), factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system. All pumps shall be provided with bronze impeller and mechanical seal aligned properly as required. The pump motor shall be suitable for 415 +/-10% volts, 50 cycles, 3 phase power supply. The quoted price shall include cost of thermal insulation and cladding of chilled water pumps complete all as specified and as directed and comprising with the following:-
(i) Flow : 90 USGPM
(ii) Head : 22-25 Mtr .
(iii) Casing : Cast Iron
(iv) Impeller : Bronze
(v) Shaft : Stainless Steel
2
-
-
... More
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing wire of size 4 mm dia by means of GI bolts/nuts/washers and protected by 15 mm bore GI light grade pipe upto test point or upto main switch board, HT/LT equipments, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, Pit cover 40mm thick made with RCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including TMT reinforcement 8mm dia @ 75mm c/c both way, MS handle 12mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge.
Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing wire upto test point or upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
1
-
-
... More
Supply and fixing automatic Air purge valve of 15 mm bore complete all as specified and as directed.
6
-
-
... More
Hot water Generator - 1 No (1 W)
(vi) 63 A, 415 V, 36 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and thermal Magnetic based trip unit for HWG.
Note : outgoing of HWG unit may be design as per OEM rating of unit. Design change shall be accepted as per OEM of HWG main incoming supply requirement.
-
-
-
... More
Supplying, installing, testing and commissioning of Mono block centrifugal condenser water pump ( 1 W+1 S), factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system. All pumps shall be provided with bronze impeller and mechanical seal aligned properly as required. The pump motor shall be suitable for 415 +1-10% volts, 50 cycles, 3 phase power supply. The quoted price shall include cost of thermal insulation and cladding of chilled water pumps complete all as specified and as directed and comprising with the following:-
(i) Flow : 180 USGPM
(ii) Head : 18-22 Mtr
(iii) Casing : Cast Iron
(iv) Impeller : Bronze
(v) Shaft : Stainless Steel
2
-
-
... More
Subtotal
-
-
-
... More
Supply and fixing Ceiling Rose, polycarbonate, isolated body, surface bakelite 3 terminal, 240 volts, 5/6 Amp, ISI Marked complete all as specified and as directed by Engineer-in-charge.
3
-
-
... More
Sch 'A' Sec - II, INTERNAL ELECTRIFICATION WORKS
-
-
-
... More
Chiller - 2 Nos (1W+1S)
(i) 125 A, 415 V, 36 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and thermal Magnetic based trip unit for chillers - 2 Nos. (with one voltmeter and one ampere meter with suitable size of CT acc class 0.5 in both feeder of CHILLER) Note : Outgoing of chiller unit may be design as per OEM rating of chiller. Design change shall be accepted as per OEM of chiller main incoming supply requirement.
-
-
-
... More
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (indoor type for 415 volts, 3 phase, 4 wire AC supply, free standing, floor mounting) cubical type suitable size made out of CRCA epoxy powder coated 2mm thick sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and stainless steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on pedestal frame made out of MS channel of size ISMC 50mm, both side properly welded and all vertical corner grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) including painting to pedestal frame with spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer. Danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
1
-
-
... More
Lump sum price worked out by the tenderer for “BUILDING /STRUCTURE WORKS" as listed in Schedule ‘A’ Section - I
1
1692000
-
... More
Supply and fixing MCB ‘B’ curve suitable for 240 volts AC supply, 6 to 32 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
2
-
-
... More
INCOMING
-
-
-
... More
Material and labour for mild steel Framed work for support and for expansion tank stand made as directed by using angle iron, flat iron, hollow square/rectangular/round pipe (ERW or induction butt welded tubes conforming to latest relevant IS) etc, including welding work as required and including two coats of synthetic enamel paint (1st quality) of approved tint/colour over a coat of red oxide primer complete all as specified and as directed by Engineer-in- charge.
600
-
-
... More
Lump sum price worked out by the tenderer for “EXTERNAL WATER SUPPLY WORKS" as listed in Schedule ‘A’ Section-III (Part-I)
1
23018
-
... More
Supplying, installing, testing and commissioning of Dual Plate Check valve 100mm bore, PN-1.6 rating having Body Cast Iron, Disc SS-304 along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
2
-
-
... More
Subtotal
-
-
-
... More
Supply and fixing 3 core 4 Sqmm flexible flat/round cable, copper conductor multistranded, PVC insulated and overall PVC sheathed, 1100 volt, laid in trenches/ducts/fixed to wall/pole/laid in floor/on cable tray/through pipe etc including necessary connections with suitable size of thimbling complete all as specified and as directed by Engineer-in-charge. Note :- (i) Excavation, earth work, sand cushioning, protection cover, cable tray, cutting of road and protection pipe shall be measured & paid separately under appropriate item of this Schedule/BOQ.)
250
-
-
... More
OUTGOING
-
-
-
... More
Supplying, installing, testing and commissioning of 10mm thick sound board Acoustic lining inside ducts/plenum using open cell nitrile rubber foam having microbial anti-microbial/antifungal product protection and of 160-180 kg /m³ density as per ASTM D3575, class 1 rating as per BS476,PART-7, cut to required sizes and to be stuck to the inside of duct surfaces with adhesive as approved by the manufacturer. (Rubber based solvent) complete all as specified and directed.
30
-
-
... More
Supplying, installing, testing and commissioning GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, complete all as specified and as directed.
Note :- Fire damper complete with smoke detector/thermistor, fusible link etc. and actuator as required for operation complete all as specified and as directed and shall meet the following design criteria ;-
(i) The fire dampers shall be spring activated on melting of fusible link having melting point 67.13º C. The fire damper shall be located in ducts. The control panel shall be located in such a way that the reset can easily be done. These combination smoke and fire dampers shall be interlocked with the building management system for the fire detection or HVAC and shall trip/close in the event of fire/smoke in the respective zone. Fire damper shall be tested as per ULL- 555 and certified by CBRI. The fire-damper shall be of at least 120minutes fire-rating as per the approved particular technical specifications.
(ii) Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers.
4
-
-
... More
Supply, laying, connecting, fixing and testing of Chilled/Hot water MS ERW class "C" pipe of size 80mm dia complete with all fitting duly 25mm thick insulation in two layers with closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminum cladding, pipe laid in floor/underground/along wall etc complete all as specified and as directed.
Note :- After fixing of valve insulation of pipe thickness along with 26 G aluminum cladding shall also be apply along valve/Y-Strainer and cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
150
-
-
... More
Supplying, installing, testing and commissioning in Weather Proof Outdoor Type AHU ( 4 Fresh Air changes per Hour), Supplying, installing, testing and commissioning of factory built Floor mounted double skin type air handling unit (AHU) 4000 CFM, 14 TR cooling capacity, 02 TR heating capacity (Motor Should be VFD compatible to control Speed of unit.) (2W+1S) with thermal break profile made of 46mm ± 2 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8 mm outside layer and 0.6 mm plain Aluminum inside layer with polyurethane foam (PUF) insulation of density 32kg/m3 factory injected between them by injection molding machine, complete with blower section with backward curved blower. The AHU shall have separate compartment as mixing chamber before filter section, AHU shall have weather proof canopy, Fresh air damper, supply air damper, return air damper. The gap between each coil shall be minimum 400 mm for cleaning & Space for Humidifier before blower and after coil. These blowers shall be VFD compatible & will be operated by a single VFD, coil section will have cooling coil, heating coil, section with aluminum finned copper tubes (tube thickness not less than 0.5mm), filter sections with 50 mm thick washable synthetic type Pre filters having efficiency 90% down to 10 micron, Fine filters having efficiency 99% down to 5 micron, drive package with TEFC drive motor suitable for 415V ± 10%, 50 Hz, 3 phase, A.C supply, complete with drain connections with drain valve, 18G stainless steel drain pan, thermometers and pressure gauge at the inlet and outlet of the coils, necessary vibration isolation arrangement etc, complete all as specified and as directed
3
-
-
... More
Incomers of 630A VCB 2 Nos
-
-
-
... More
Acoustic Enclosure : M & L for acoustic enclosure (canopy) for the 1010 KVA DG Set to reduce noise level to 75 dB (A) measured at 1.0 metre distance for audible frequencies as approved from CPCB IV+ for emission compliance as per Central Pollution Control Board norms of suitable size as per manufacturer's specification and comprising of following :-
(i) Acoustic Enclosure made CRCA sheets in munsell green shade and a structural / sheet metal base frame panted in black
(ii) High quality noise absorbent and fire -retardant grade acoustic Insulation material (P.U Foam) complying to IS 8183
(iii) Four point lifting for easy handling
(iv) Air inlet louvers
(v) Tank pretreatment process and UV resistant powder coating of all parts to with stand extreme environment
(vi) Fluid drains for lube oil & fuel
(vii) Fuel filling arrangement inside the enclosure.
-
-
-
... More
Design, Supply, installation, testing and commissioning of site/factory fabricated exhaust air duct (square/rectangular ducting) for return air, fabricated from the 22 gauge galvanized steel sheet having zinc coating on both sides, including all fixtures and fitting accessories complete such as neoprene rubber gaskets, elbows, splitters, vanes, supports to installed /hanging the duct with suitable size of SS hole fastener, full threaded rod, screws, fastener, hook, nut bolt, washer etc, complete all as specified and directed.
Note :- (i) The duct work shall be as per IS-655 and design of duct shall be approved by Accepting Officer before fabrication. (ii) The GI sheet for duct work shall conform to class viii with zinc coating of 120 gm/sq mtr as per IS-277(2003). (iii) Duct joint should be properly seal with Silicon gel. (iv) Cost for required scaffolding work to install the ducts at site shall also deemed to be included in the unit rate.
80
-
-
... More
Material and labour for Dismantling of existing VCB panel set of three from MH substation after removing of existing electric connections incoming/out going and deposited to MES store yard complete all as specified and directed.
1
-
-
... More
AHU Starter 20-32 Amp TP, MCB 'C' Curve type along with star delta starter, VFD of suitable capacity inline with motor rating fixing, By pass arrangement for VFD & starter along with auto manual selection switch, Manual Frequency control switch, On/Off Push button & Indicating light - 3 Nos for AHU. Note : Panel should integrated with motor protection relay and 1 Voltmeter and 1 Amp meter with suitable size of CT with Acc class 0.5 in both starter panel.
-
-
-
... More
Supplying, installing, testing and commissioning of balancing valve 80mm bore, PN-1.6 rating having Body: CI:IS:210 FG:220, Bonnet : SG Iron IS : 1865 GR 420/7, Seat: Nitrile/EPDM, Stem: AISI 410// Disc: EN3 along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
2
-
-
... More
Taking out old HT cable of any type and size from trenches/road/pipe/pole including taking out layer of protection cover any type and deposited to MES store yard complete all as specified and as directed by Engineer-in-Charge.
(Excavation, earth work, shall be measured and paid separately under appropriate item of BOQ).
70
-
-
... More
Supplying, installing, testing and commissioning of butterfly valve 100mm bore, PN-1.6 rating having Cast iron body, SG iron disc & AISI 410 shaft along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
10
-
-
... More
Supplying, installing, testing and commissioning of butterfly valve 80mm bore, PN-1.6 rating having Cast iron body, SG iron disc & AISI 410 shaft along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
8
-
-
... More
Material and labour for Cutting of existing GI pipe line 50mm bore for taping in trenches including threading/screwing work for insertion and including GI tee of size 50x50x50mm for new connection including union and jointing material complete all as specified and as directed.
NOTE:- Necessary earth work, GI fitting, jointing material etc reqd to complete the job deemed to be included in the quoted rate.
1
-
-
... More
Material and labour for Dismantling of existing chageover switch from sub station building of any size after removing of existing electric connections incoming/out going and deposited to MES store yard complete all as specified and directed.
2
-
-
... More
Each out going and bus coupler shall be configured as follows : (a) CTs : 200-100/1-1, 5VA, Cl-5P10, Cl-1.0
(b) Feeder Protection and Control Relay REF615 of ABB or Equivalent of L&T/ Siemens, Protections 50,51, 50N, 51N,46,49,67,67N,27,59,59N,95, Measurement for 31,10,3U,UO,Kw, KVA, PF, Hz, Kwh,16DI+10DO, One front RJ45 Port. Two Rear FO (LC) Port for IEC-61850 Protocol. Draw out Type with CT Shorting feature Separate TCS and Master trip relay to be provided.
(c) Accessories including Breaker Control Switch (T-N-C), space heater with thermostat, DC , AC control
circuit through MCB, Indicating Lamps for RYB, spring charge, DC healthy, Breaker ON/OFF/TRIP and TEST/ SERVICE position, Multifunction Meter with RS485 port for MODBUS communication (Acc.Cl.0.5), Digital Ammeter (Acc.Cl.0.5), Digital Voltmeter(Acc.Cl.0.5).
-
-
-
... More
Condenser Water Pump : 2 Nos ( 1W+1S)
(iii) 20 A, 415 V, TP MCB for condenser water pumps including fully automatic starter suitable for upto 7.5 HP or higher capacity as per Condenser water motor rating complete with connector, Auto manual Selector switch, push button, On, Off, Trip Indicating light, over load protection, SPPR, Multifunction meter - 2 No (Both starter panel should integrated with motor protection relay and 1 Voltmeter and 1 Amp meter with suitable size of CT with Acc class 0.5 in both starter panel).
-
-
-
... More
Supplying and laying synthetic rubber insulated mat electrical shock safety for voltage upto 11 KV, non-slippery, fire-resistant, for electrical purpose as per IS 15652-2006 of size 2 meter x 1 meter, 2.5 mm thick complete all as directed.
5
-
-
... More
Humidifier Starter - 16 Amp 4P, MCB ' C' Curve type along with DOL starter, auto manual selection switch , On/Off Push Button & indicating light - 2 Nos for Humidifier.
-
-
-
... More
Note :- Contractor has to submit the AHRI Selection sheet of OEM on actual condition (Duty point), AHRI Condition & BEE Energy rating certificate along with approval of chiller model
-
-
-
... More
Alternator : 1010 KVA at 0.8 PF ,415 Volt, 3 phase, 4 wire, 50 Hz , at 1500 RPM , Brushless type, Screen protected, revolving field, Self excited alternator conforming to IS/IEC 13364(II) standards, AVR , 3 Phase reconnectable winding with H class insulation, better motor starting capability, best in class efficiency, Compact design with sealed bearing for longer life and lesser maintenance & Impregnation on all wound components for better mechanical strength.
-
-
-
... More
Supplying, installing, testing and commissioning in Weather Proof Outdoor Type AHU ( 4 Fresh Air changes per Hour), Supplying, installing, testing and commissioning of factory built Floor mounted double skin type air handling unit (AHU) 1000 CFM, 3 TR cooling capacity, 02 TR heating capacity (Motor Should be VFD compatible to control Speed of unit.) with thermal break profile made of 46mm ± 2 mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8 mm outside layer and 0.6 mm plain Aluminum inside layer with polyurethane foam (PUF) insulation of density 32kg/m3 factory injected between them by injection molding machine, complete with blower section with backward curved blower. The AHU shall have separate compartment as mixing chamber before filter section, AHU shall have weather proof canopy, Fresh air damper, supply air damper, return air damper. The gap between each coil shall be minimum 400 mm for cleaning & Space for Humidifier before blower and after coil. These blowers shall be VFD compatible & will be operated by a single VFD, coil section will have cooling coil, heating coil, section with aluminum finned copper tubes (tube thickness not less than 0.5mm), filter sections with 50 mm thick washable synthetic type Pre filters having efficiency 90% down to 10 micron, Fine filters having efficiency 99% down to 5 micron, drive package with TEFC drive motor suitable for 415V ± 10%, 50 Hz, 3 phase, A.C supply, complete with drain connections with drain valve, 18G stainless steel drain pan, thermometers and pressure gauge at the inlet and outlet of the coils, necessary vibration isolation arrangement etc, complete all as specified and as directed
1
-
-
... More
Material and labour for boring of holes under main road pavement, hard standing or any other situation by manual mean for accommodate 80mm to 100mm bore pipe in the drilled holes, including returning, filling in the end working space including removal of surplus soil and making good the surface complete all as specified and as directed.
Note ; Pipe for inserting as required shall be measured and paid for separately.
75
-
-
... More
Material and labour for Dismantling of existing AMF panel from MH substation after removing of existing electric connections incoming/out going and refix the AMF panel at new location of MH substation including cable connection and control wiring complete all as specified and directed.
2
-
-
... More
Supply and fixing ON load chage over switch 1600 A four pole with sheet metal enclosure includig all fixing accessories complete all as specified and as directed.
1
-
-
... More
Supplying, installing, testing and commissioning of Ultrasonic Humidifiers of capacity 5 ltr/hr with piezo transducers to give instantaneous humidity with water droplets less than 5 micron along with Humidity controller complete all as specified and as directed and comprising with the following:-
(i) Complete package with all plumbing and electrical works done and factory tested.
(ii) Flying water fog having water particle as small as 1-5µ is produced.
(iii) Waiting time for humidity creation is maximum up to 3 Minutes.
(iv) Instantaneous humidity available with just a press on start button.
(v) Level of accuracy achieved in humidity control is 92-97%. Safety Feature
(vi) Reliable Piezo transducers duly interlocked with level sensors.
(vii) Level switches for upper and lower water level. Stops working when water level is too low.
(viii) Water overflow protection.
(ix) Water and air filter assembly.
(x) Solenoid operated water makeup connection.
2
-
-
... More
Lump sum price worked out by the tenderer for “EXCAVATION, EARTHWORK AND SITE DEVELOPMENT WORKS" as listed in Schedule ‘A’ Section - VI
1
441063
-
... More
Supplying, installing, commissioning and testing of factory assembled Diesel Engine driven generating set (CPCB-IV+ Norms ) fully wired alternator AC to give an output of 1010 KVA /808KW (CRDI), 1192 BHP continuously rating at a PF of 0.8 lagging, 415 volts , AC 3 phase 4 wire 50 HZ ,1500 RPM, directly coupled with diesel engine water cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of adequate capacity with fuel line & accessories, with Std. Auto mains failure Panel (Outdoor AMF Panel) , Residential type Silencer, Fuel Tank, Inbuilt AVM Pads, DG Set in Acoustic, First Fill of Lube oil, Battery with Leads, Remote Monitoring Unit as directed, flexible exhaust pipe, vibration damper pads & other accessories etc. incl necessary PCC foundation as per manufacturer instructions complete all as specified and as directed and comprising with the following:-
1
-
-
... More
Supply, laying, connecting, fixing and testing of Chilled/Hot water MS ERW class "C" pipe of size 25mm dia complete with all fitting duly 19mm thick insulation in two layers with closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminum cladding, pipe laid in floor/underground/along wall etc complete all as specified and as directed.
Note :- After fixing of valve insulation of pipe thickness along with 26 G aluminum cladding shall also be apply along valve/Y-Strainer and cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
36
-
-
... More
Supplying, installing, testing and commissioning of HDPE expansion tank of size 500 Lt complete with FR-XLPE/XPE 19 mm thick of minimum bulk density 28+4Kg/cum covered with vapour barrier and finished with 0.5 mm thick Al cladding and applied with Pidilite SR 998 complete with air vent and drain connection with float valve, quick fill and control valves complete all as specified and as directed.
1
-
-
... More
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
-
-
-
... More
02 Nos Outgoing Feeders with 630A VCB
-
-
-
... More
Supply and fixing Water Flow Switch complete all as specified and as directed.
4
-
-
... More
Supplying, installing, testing and commissioning of balancing valve 100mm bore, PN-1.6 rating having Body: CI:IS:210 FG:220, Bonnet : SG Iron IS : 1865 GR 420/7, Seat: Nitrile/EPDM, Stem: AISI 410// Disc: EN3 along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
2
-
-
... More
Taking out old LT cable of any type and size from trenches/road/pipe/pole including taking out layer of protection cover any type and deposited to MES store yard complete all as specified and as directed by Engineer-in-Charge.
(Excavation, earth work, shall be measured and paid separately under appropriate item of BOQ).
230
-
-
... More
Supplying, installing, testing and commissioning of 3-Way valve 50mm bore, PN-1.6 rating along actuator, Thermostat & transformer with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
3
-
-
... More
AHU Outgoings to AHU sub Panel - 1No
(vii) 125 A, 415 V, 36 kA, 50 Hz FP MCCB with adjustable overload settings, adjustable short-circuit settings and thermal Magnetic based rip unit for AHU Sub Panel including 1 voltmeter and 1 amp meter with suitable size of CT of acc class 0.5.
-
-
-
... More
Supply and fixing LED tube light fitting polycarbonate housing 1 x 18/20 Watt, appx 4 feet long, housing environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) LED Driver of the same make as of the luminaire. (h) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (j) Surge protection minimum 2.5 kV. (k) CCT : Minimum 6000K (l) CRI : Minimum 80 (m) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
2
-
-
... More
Supplying, installing, testing and commissioning Control panel actuator, including electrical spring type actuator, remote indication of the fire damper complete all as specified and as directed.
Note :- Fire damper complete with smoke detector/thermistor, fusible link etc. and actuator as required for operation complete all as specified and as directed and shall meet the following design criteria ;-
(i) The fire dampers shall be spring activated on melting of fusible link having melting point 67.13º C. The fire damper shall be located in ducts. The control panel shall be located in such a way that the reset can easily be done. These combination smoke and fire dampers shall be interlocked with the building management system for the fire detection or HVAC and shall trip/close in the event of fire/smoke in the respective zone. Fire damper shall be tested as per ULL- 555 and certified by CBRI. The fire-damper shall be of at least 120minutes fire-rating as per the approved particular technical specifications.
(ii) Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers.
2
-
-
... More
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
-
-
-
... More
Supply, laying, connecting, fixing and testing of Condenser water MS ERW class "C" pipe of 25mm bore complete with all fitting etc complete all as specified and as directed.
18
-
-
... More
Supplying, installing, testing and commissioning of butterfly valve 50mm bore, PN-1.6 rating having Cast iron body, SG iron disc & AISI 410 shaft along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
6
-
-
... More
Supplying, installing, testing and commissioning Return air grill made out of Stainless Steel Grade 304 sheet/aluminium powder coated, with damper for return air complete all as specified and as directed.
Note :- Fire damper complete with smoke detector/thermistor, fusible link etc. and actuator as required for operation complete all as specified and as directed and shall meet the following design criteria ;-
(i) The fire dampers shall be spring activated on melting of fusible link having melting point 67.13º C. The fire damper shall be located in ducts. The control panel shall be located in such a way that the reset can easily be done. These combination smoke and fire dampers shall be interlocked with the building management system for the fire detection or HVAC and shall trip/close in the event of fire/smoke in the respective zone. Fire damper shall be tested as per ULL- 555 and certified by CBRI. The fire-damper shall be of at least 120minutes fire-rating as per the approved particular technical specifications.
(ii) Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers.
4
-
-
... More
Supply, laying, connecting, fixing and testing of Condenser water MS ERW class "C" pipe of 32mm bore complete with all fitting etc complete all as specified and as directed.
6
-
-
... More
Supplying, installing, testing and commissioning of balancing valve 25mm bore, PN-1.6 rating having Body: CI:IS:210 FG:220, Bonnet : SG Iron IS : 1865 GR 420/7, Seat: Nitrile/EPDM, Stem: AISI 410// Disc: EN3 along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
1
-
-
... More
Supply, Installation, Testing and Commissioning of Water cooled Invertor scroll chiller of Nominal capacity is 36TR, Actual capacity not less than 40 TR (1W+1S) as per below given condition. Chiller having Eco friendly refrigerant R-410A with Inverter driver technology which are equipped with a variable frequency drive with microprocessor controller, with multiple scroll compressors, with suitable TEFC motor, Water Cooled condenser, evaporate, suction, discharge shut off valves, pressure switches, refrigerant piping, base frame, insulation, controls, vibration isolators, automatic capacity control systems if applicable, drive package and refrigerant throttling device to suit the chiller all as specified and/ or directed etc., complete. The capacity of water chilling package unit shall not be less than 40 TR at the following specified conditions (Chiller Selection Data) :-
2
-
-
... More
Material and labour for Dismantling of existing LT panel and power synchronous panel of any size and any type from MH substation after removing of existing electric connections incoming/out going and deposited to MES store yard complete all as specified and directed.
2
-
-
... More
Supply, installing, commissioning and testing of factory made LT panel board (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully compartment type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and stainless steel cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 300 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 450 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
1
-
-
... More
Four Pole, Copper busbar of rated capacity 1000 A - 01 Set (03 P+1 N busbars)
-
-
-
... More
Supply only modular switch 6Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
5
-
-
... More
Supply and fixing blanking plate of plastic suitable for any type of DB complete all as specified and as directed by Engineer-in-charge.
2
-
-
... More
Supply Installation testing and commissioning of outdoor type double skin Exhaust air fan of capacity 1500 CFM 40 mm static, sections comprising of DIDW forward curved blower, Pre-filter. Motor should be VFD compatible to control Speed of unit complete all as specified and as directed.
2
-
-
... More
All as per above Srl item No. 03 but for one socket out let 5 Amps point controlled by one switch (on independent board and not below the any other switch board) complete all as specified and as directed by Engineer-in-charge. (switch, socket shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate. ).
1
-
-
... More
Supply only modular Socket outlet multipurpose type 16 Amp, flush type (2 module) complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing strip 32x6mm by means of GI bolts/nuts/washers and protected by 40 mm bore GI light grade pipe upto test point or upto main switch board / electric equipment / DG set / HT/LT equipments etc, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, Pit cover 40mm thick made with RCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including TMT reinforcement 8mm dia @ 75mm c/c both way, MS handle 12mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge.
Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing strip upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
33
-
-
... More
Subtotal
-
-
-
... More
Supplying, installing, testing and commissioning of Mono block centrifugal Hot water pump (1 W+1S), factory mounted on a common base with electric motor for recirculation of water for the central air conditioning system. All pumps shall be provided with bronze impeller and mechanical seal aligned properly as required. The pump motor shall be suitable for 415 V ± 10% volts, 50 cycles, 3 phase power supply. The quoted price shall include cost of thermal insulation and cladding of chilled water pumps complete all as specified and as directed and comprising with the following:-
(i) Flow : 18 USGPM
(ii) Head : 16-18 Mtr
(iii) Casing : Cast Iron
(iv) Impeller : Bronze
(v) Shaft : Stainless Steel
2
-
-
... More
Supplying, installing, testing and commissioning Unidirectional Laminar Air Flow Plenum SITC OF Unidirectional Laminar Air Flow Plenum Ceiling constructed out of 1.2 mm thick SS 304 sheet of size 1500 X 1500 mm having 8 nos of Hepa filters (Hepa Filter qty can be change as per OEM Specification). The Hepa filters having dust spot efficiency of 99.97% 0.3 micron. For filtration H13/H14 HEPA filters with aluminum frames are used. Air Velocity should not be more than 90FPM through Laminar flow plenum. A laminisator made of special tautsilk fabric is used under the laminar flow unite, to achieve laminar flow. Laminisator is made of two parts with a special design that enable spendant lamp connection in the middle of the unit. Air & Light diffuser made of mono filament precision woven polyester for the plan air ceiling to give a ″LAMINAR FLOW ″ of filtered air. It also provides a diffused shadow less lighting system with Intensity control complete all as specified and as directed.
2
-
-
... More
Supplying, installing, testing and commissioning of FRP INDUCED DRAFT COOLING TOWERS of capacity 50 TR for air-conditioning system. Each tower shall be complete with fan, motor, basin, casing, distribution system, filling, louvers, float valve, quick fill / make-up drain connection, supports, G.I. ladder should be from floor level to top of cooling tower. Motor shall be TEFC (EFF 1/IE 2), weather proof and suitable for 415 V ±10%, 50 cycles 3 phase power supply. Isolator at cooling tower shall be provided, enclosed in weather proof (IP-55) panel. Tower for air-conditioning system shall be selected on the basis of water temperature 97.5-90 Deg F, ambient wet bulb 83 Deg F including cooling tower civil foundation as per manufacturer’s instructions complete all as specified and as directed.
2
-
-
... More
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator etc, as per IEC 61439-3, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge.
Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
1
-
-
... More
Supply, laying, connecting, fixing and testing of Condenser water MS ERW class "C" pipe of 100mm bore complete with all fitting etc complete all as specified and as directed.
100
-
-
... More
OUTGOING
-
-
-
... More
Supply and installing of cable laying protection U shape cable tray with perforation more than 17.5 % in convenient sections of size 50mm height and 150mm width made out of hot dip galvanized sheet 1.6 mm thick including fixing accessories like cross over, bolt in partition, snap in partition, supporting corner, horizontal bend, low elbow, rising elbow, T-pieces, tray cover, edge protection, full threaded rod, slotted U channel, round head square neck bolt, flange nut, hinged joiner, screws, fastener, hook, nut bolt, washer etc complete all as specified and as directed.
Note :- (i) Cost for accessories as per site requirement for installing of cable tray shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account.
75
-
-
... More
Supplying, installing, testing and commissioning Motorized, spring return type, combination fire and smoke damper complete all as specified and as directed.
Note :- Fire damper complete with smoke detector/thermistor, fusible link etc. and actuator as required for operation complete all as specified and as directed and shall meet the following design criteria ;-
(i) The fire dampers shall be spring activated on melting of fusible link having melting point 67.13º C. The fire damper shall be located in ducts. The control panel shall be located in such a way that the reset can easily be done. These combination smoke and fire dampers shall be interlocked with the building management system for the fire detection or HVAC and shall trip/close in the event of fire/smoke in the respective zone. Fire damper shall be tested as per ULL- 555 and certified by CBRI. The fire-damper shall be of at least 120minutes fire-rating as per the approved particular technical specifications.
(ii) Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers.
2
-
-
... More
Supplying, installing, testing and commissioning of Y-Strainer 50mm bore, PN-1.6 rating having Body: Cast Iron/MS fabricated, Screen: SS-304, End Connection: Flanged End Connection along with all necessary fittings like flange, nut bolts, Gasket etc. complete all as specified and as directed.
3
-
-
... More
Each Incomer shall be configured as follows : (a) CTs : 400-200/1-1, 5VA, Cl-5P10, Cl-0.5
(b) PT draw out type : 11000/V3/110/V3/110/3,50VA,Cl-1.0,3P (c) Feeder Protection and Control Relay, REF615 of ABB or Equivalent of L&T/ Siemens, Protections 50,51,50N,51N,46,49,95, Measurement for 3I, I0, 3U,UO,Kw, KVA, PF, Hz, Kwh, 16DI + 10 DO, One front RJ45 Port, Two Rear FO(LC) Port for IEC-61850 Protocol, Draw out Type with CT Shorting feature. Separate TCS and Master trip relay to be provided -01 Nos
(d) Auxiallry relay fro transformer OTI.
(e) WTI and Bucholz. Annunciator window.
(f) Accessories including Breaker Control Switch (T-N-C), space heater (g) Trivecto meter with thermostat, DC , AC control circuit through MCB, Indicating Lamps for RYB, spring charge, DC healthy, Breaker ON/ OFF/ TRIP and TEST/ SERVICE position, Multifunction Meter with RS485 port for MODBUS communication (Acc.Cl.0.5), Digital Ammeter (Acc.Cl.0.5), Digital Voltmeter(Acc.Cl.0.5).
-
-
-
... More
Control AMF Panel : AMF panel with copper bus bar of 2500A capacity should be outdoor type for automatic transfer of supply through microprocessor based ACB's 2000A four Pole manual draw out type as directed. AMF panel shall transfer the load to DG set when commercial supply fails and incase of commercial supply available, AMF panel shall transfer the load to commercial supply and DG set should stops automatically. AMF panel shall consist of PLC (AMF controller) DSE 8610 MKIII as per DG set OEM.
-
-
-
... More
Supply, Installation, testing , Commissioning of 11kV Air Insulated HT Indoor type Switchgear Panels with maximum system voltage rating of 12kV consisting of following and complete all as directed and as per following specification:-
1
-
-
... More
Sand cushioning, with dry and clean river sand (for under ground cable) 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and as directed. Note:- (i) Punned thickness shall be considered for payment purpose (ii) Approved sand free from vegetations, grass and other deleterious substances shall be used.
145
-
-
... More
Supply & fixing Thermometer complete all as specified and as directed.
30
-
-
... More
Diesel engine : Radiator cooled turbocharger to deliver not less than 1192 BHP at 1500 RPM under NTP conditions of BS 5514 ,ISO 3046 with an overload capacity of 10 % for one hour in any 12 continuous hours operation with the following accessories:-
12 cylinder in VEE configuration 4 stroke, radiator cooled engine, Full Authority Electronic Engine, Well designed air handling system with Dry type Replaceable paper element air cleaner with restriction indicator, Air to air after cooling, Optimized turbocharger for increased altitude capabilities, Best in class fuel economy with Bosch HPCR fuel system with A1 class electronic governing, Dual fuel filter system: Pre filter including water separator and Water In Fuel (WIF) sensor and main filter, Electrical lift pump for faster response, Standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, Full flow spin on lube oil filter, Plate type lube oil cooler, First fill of lube oil and coolant, Electrical starter motor with soft start engagement feature, Battery charging alternator, 2X 12 V DC battery.
-
-
-
... More
Hot Water Pump : 2 Nos ( 1W+1S)
(iv) 20 A, 415 V, TP MCB for hot water pumps including fully automatic starter suitable for 5HP or higher capacity as per Hot water motor rating complete with connector, Auto manual Selector switch, push button, On, Off, Trip Indicating light, over load protection, SPPR, Multifunction meter - 2 No (Both starter panel should integrated with motor protection relay and 1 Voltmeter and 1 Amp meter with suitable size of CT with Acc class 0.5 in both starter panel).
-
-
-
... More
Control Point For 3way Valve & Fire Damper - 6 Amp 4P, MCB ' C' Curve type along with Contactor, auto manual selection switch, Toggle Switch - 10 Nos for control.
-
-
-
... More
INCOMING
-
-
-
... More
Supply and fixing Lightning arresters pin type complete with all fittings, discharge capacity 65 kilo Amp suitable for 11000 volts complete all as specified and as directed.
3
-
-
... More
Supply and fixing 3 core 1.5 Sqmm flexible flat/round cable, copper conductor multistranded, PVC insulated and overall PVC sheathed, 1100 volt, laid in trenches/ducts/fixed to wall/pole/laid in floor/on cable tray/through pipe etc including necessary connections with suitable size of thimbling complete all as specified and as directed by Engineer-in-charge. Note :- (i) Excavation, earth work, sand cushioning, protection cover, cable tray, cutting of road and protection pipe shall be measured & paid separately under appropriate item of this Schedule/BOQ.)
350
-
-
... More
Supply, laying, connecting, fixing and testing of Condenser water MS ERW class "C" pipe of 50mm bore complete with all fitting etc complete all as specified and as directed.
6
-
-
... More
Cooling Tower : 1 No ( 1W)
(v) 20 A, 415 V, TP MCB for Cooling Tower including fully automatic starter suitable for 5 HP or higher capacity as per Cooling tower rating complete with connector, Auto manual Selector switch, push button, On, Off, Trip Indicating light, over load protection, SPPR, Multifunction meter - 1 No ( starter panel should integrated with motor protection relay and 1 Voltmeter and 1 Amp meter with suitable size of CT with Acc class 0.5 in both starter panel).
-
-
-
... More
Four Pole, aluminium busbar of rated capacity 200 A - 01 Set (03 P+1 N busbars)
-
-
-
... More
Supply, laying, connecting, fixing and testing of Chilled/Hot water MS ERW class "C" pipe of size 50mm dia complete with all fitting duly 25mm thick insulation in two layers with closed cell elastomeric insulation 30 to 40 kg /cum density & 26 G Aluminum cladding, pipe laid in floor/underground/along wall etc complete all as specified and as directed.
Note :- After fixing of valve insulation of pipe thickness along with 26 G aluminum cladding shall also be apply along valve/Y-Strainer and cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
150
-
-
... More
Material and labour for concealed Point wiring for one light point/fan point /bell point controlled by one switch (using red, black and green colour wires as colour coding) complete with 2.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches/ socket / regulator etc, including provn of 2.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) including fixing of switch/socket/regulator etc complete all as specified and as directed. (switch, socket, regulator shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate. ).
3
-
-
... More
All as per above Srl item No. 03 but for one socket out let 5 Amps point controlled by one switch (on same board) complete all as specified and as directed by Engineer-in-charge.(switch, socket shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate. ).
1
-
-
... More
1 Nos Bus coupler 11 KV of 630A VCB
-
-
-
... More
Supply and installing of cable laying protection U shape cable tray with perforation more than 17.5 % in convenient sections of size 50mm height and 450mm width made out of hot dip galvanized sheet 2 mm thick including fixing accessories like cross over, bolt in partition, snap in partition, supporting corner, horizontal bend, low elbow, rising elbow, T-pieces, tray cover, edge protection, full threaded rod, slotted U channel, round head square neck bolt, flange nut, hinged joiner, screws, fastener, hook, nut bolt, washer etc complete all as specified and as directed.
Note :- (i) Cost for accessories as per site requirement for installing of cable tray shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account.
20
-
-
... More
Material and labour for cable route indicator post 900mm long made of precast cement concrete (1:2:4) type B-1, using 20mm graded stone aggregate, rounded tops as directed and embeded in ground of size 350x150x450mm below ground and 300x100x450mm above ground, applying two coats of cement base paint on plastered surface including writing letters (like LT/HT UG cable, __ feeder etc.) with synthetic enamel paint in brown colour in suitable size including earth work and form work complete all as specified and as directed.
40
-
-
... More
(i) ACB 4 Pole cap-630 Amps, 415 volts, 50 kA (Ics=100% of Icu) Manual Draw Out Type Microprocessor Release Type - 01 No
(ii) LED phase indicators (Yellow, Blue, Red) - 01 Set
(iii) Multifunction meter with CTs with accuracy class 0.5 - 01 No
-
-
-
... More
Supplying, installing, testing and commissioning of HDPE make up tank of size 5000 Ltr. complete with air vent and drain connection & overflow pipe, make up connection with float valve complete all as specified and as directed.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%