Military Engineer Services Tender

... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Provision Of Sewage Treatment Plant (stp) At Bhaduriya Complex Under Ge (south) Pathankot in Pathankot, Punjab, with an estimated contract value of Rs. 2,32,00,000. The bid opening date for this tender is 03-11-2026 and the last date for bid submission is 09-12-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender - Punjab Tender

Opening Date3 Nov 2026
Closing Date9 Dec 2026
Tender Amount₹ 2,32,00,000 
Notes
Download

Costs

Description

Provision Of Sewage Treatment Plant (stp) At Bhaduriya Complex Under Ge (south) Pathankot

Contact

Unlock the Tender details

GEM & Bid Advisory Services

Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

Unlock the Tender details
... More
Item no. 3 (contd...) (iii) 6A TP MCCB 10KA ICS with automatic DOL Starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -1 nos: (For One number anoxic tank submerged mixer) (iv) 10A TP MCCB 10KA ICS with automatic star delta Starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos(One working+one standby) (For Two Numbers RAS pumps) (v) 6A TP MCCB 10KA ICS with automatic star delta Starter as per type -2 cordination with single phase preventer under/overvoltage protection, overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. - Two numbers (One Working+One Standby) ( For two number Centrifuge feed pumps). (vi) 6A TP MCCB 10KA ICS with automatic star delta Starter as per type -2 cordination with single phase preventer under/overvoltage protection, overload and short circuit protection,R.Y.B Phase indication lamp with fuse . -2 nos: (For One number Centrifuge Hydraulic press machine motor) (vii) 10A TP MCCB 10KA ICS with DOL starter as per type -2 cordination with single pahse preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers(One working +one standby) ( For two number MBR PERMEATE PUMPS) (viii) 10A TP MCCB 10KA ICS with DOL starter as per type -2 cordination with single pahse preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For two numbers Air compressor motor) (ix) 6A TP MCCB 10KA ICS with starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers (1 Working +One standby) MBR C.I.P Pumps and other fitting parts) (x) 6A DP MCB 10KA ICS with under/overvoltage protection,overload and short circuit protection, indication lamp with fuse 1 set. -2 nos: (For SIX numbers Pneumatic Valves with flange fitting parts each)

-

-

-

... More
Item no. 3 (contd...) (xi) 6A DP MCB under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers Citric Acid Dosing Pumps) (xii) 6A TP MCCB 15KA ICS with DOL starter as per type -2 cordination with single pahse preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers CITRIC ACID MIXER ,0.5 HP each) (xiii) 6A DP MCB under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers Hypo Dosing Pumps ) (xiv) 6A TP MCCB 10KA ICS with DOL starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers Hypo Mixer ,0.5 HP each) (xv) 6A DP 10 KA for ON line Monitoring System and two number flow meters (xvi) 16A DP 10 KA for Spare -03 No for PLC board. The above panel includes all kind of MCB , MCCB, MPCB, ENERGY METER , Indication Lights , Selector Switches ,Push Button.

-

-

-

... More
SEWAGE TREATMENT PLANT (50 KLD CAPACITY) (STP-2 1x50 KLD )Design, Supply, installation, testing and commissioning of STP of capacity 50 KLD based on any suitable technology/method as per Geographical location, temperature differential and rainfall complete with Mechanical, Electrical with tertiary treatment facilities to achieve designed Parameters of Sewage which should be maintained and provide treated sewage Parameters of Sewage. Complete sewage treatment plant to be provided as per the details given in Schedule 'A" Part-I from page No 41 to 44 of CA.

1

-

-

... More
"Design, supply, installation, testing and commissioning of PLC based SCADA system for 50 KLD STP including PLC panel, HMI, SCADA workstation, field instrumentation, control logic, interlocking, alarm, annunciation, trend logging, report generation, remote monitoring provision and integration with OCEMS/data logger complete as required as per the details given in Schedule 'A" Part-I from page No 45 of CA.

1

-

-

... More
LT PANEL FOR 50 KLD STP Supplying installation testing and commissioning of extendable, compartmentalised, front operated , back openable, LT cubicle STP panel having ingress protection of IP 54, suitable for operation on 415 Volt 3 phase 50 c/s power supply fabricated out of 2 mm thick CRCA sheet steel and base channel of MS section not less than 100mmX50mmX5mm, gland plate of 3 mm thick cleaned and treated in 7 tank process and powder coated with approved shade with TPN Electrolytic Aluminium busbar of 100A duly insulated in colour coding & suitable to withstand 25 MVA fault lavel complete with supplying & installation of following equipment including interconnection, control wiring etc as required. All MCCBs shall have microprocessor based release & shall have manually operated handle.It includes all wiring , cabling of required sizes from STP panel board to each electrical parts with on site control panel for individual motors . The panel will consists of following Items as per drawings attached.(Panel shall be of outdoor type installation with suitable IP Protection) (a) Incomming :-(i) 100Amp,4Pole,MCCB (25KA) with Microprocessor =01 No (ii) R.Y.B Phase indication lamp with fuse =1 set. (iii) 0-100 A Digital Ammeter 150/5A Class 10 , 1 set (iv) 0-500V Digital Voltometer with Control MCB 1 set (b) Out Going :- (i) 40 Amp, TP MCCB 15KA ICS with automatic star delta Starter as per type -2 cordination with single phase preventer under/ overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 sets (For Two Numbers Air blowers , 110m3/hr. ( 0.50 wc) 5.0HP motor each). (i) 10A TP MCCB 10KA ICS with automatic DOL Starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set of 2 numbers(One Working +One standby) (For Wet Well Submersible sewer pumps)

1

-

-

... More
Item no. 6(contd...) (ii) 10A TP MCCB 10KA ICS with automatic DOL Starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set of 2 numbers pumps (One working+one standby) (For Wet Well cutter Submercible sewer pumps) (iii) 6A TP MCCB 10KA ICS with automatic DOL Starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -1 nos: (For One number anoxic tank submerged mixer) (iv) 10A TP MCCB 10KA ICS with automatic star delta Starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos(One working+one standby) (For Two Numbers RAS pumps) (v) 6A TP MCCB 10KA ICS with automatic star delta Starter as per type -2 cordination with single phase preventer under/overvoltage protection, overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. - Two numbers (One Working+One Standby) (For two number Centrifuge feed pumps) (vi) 6A TP MCCB 10KA ICS with automatic star delta Starter as per type -2 cordination with single phase preventer under/overvoltage protection, overload and short circuit protection,R.Y.B Phase indication lamp with fuse . -2 nos: (For One number Centrifuge Hydraulic press machine motor) (vii) 10A TP MCCB 10KA ICS with DOL starter as per type -2 cordination with single pahse preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers(One working +one standby) ( For two number MBR PERMEATE PUMPS) (viii) 10A TP MCCB 10KA ICS with DOL starter as per type -2 cordination with single pahse preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For two numbers Air compressor motor )

-

-

-

... More
Item no. 6(contd...) (ix) 6A TP MCCB 10KA ICS with starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers (1 Working +One standby) MBR C.I.P Pumps and other fitting parts) (x) 6A DP MCB 10KA ICS with under/overvoltage protection, overload and short circuit protection,indication lamp with fuse 1 set. -2 nos: (For SIX numbers Pneumatic Valves with flange fitting parts each) (xi) 6A DP MCB under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers Citric Acid Dosing Pumps) (xii) 6A TP MCCB 15KA ICS with DOL starter as per type -2 cordination with single pahse preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers CITRIC ACID MIXER ,0.5 HP each) (xiii) 6A DP MCB under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. -2 nos: (For Two numbers Hypo Dosing Pumps) (xiv) 6A TP MCCB 10KA ICS with DOL starter as per type -2 cordination with single phase preventer under/overvoltage protection,overload and short circuit protection,R.Y.B Phase indication lamp with fuse 1 set. 2 nos: (For Two numbers Hypo Mixer ,0.5 HP each) (xv) 6A DP 10 KA for ON line Monitoring System and two number flow meters (xvi) 16A DP 10 KA for Spare -03 No for PLC board. The above panel includes all kind of MCB, MCCB, MPCB, ENERGY METER, Indication Lights, Selector Switches, Push Button.

-

-

-

... More
Lumpsum price worked out by the contractor for construction of building as listed in Schedule 'A' Part-II.

1

177830

-

... More
Lumpsum price worked out by the contractor for Internal Water Supply Works as listed in Schedule 'A' Part-III.

1

14237

-

... More
Lumpsum price worked out by the contractor for Plumbing Works as listed in Schedule 'A' Part-IV.

1

15295

-

... More
Lumpsum price worked out by the contractor for Internal Electric Supply Works as listed in Schedule 'A' Part-V.

1

43933

-

... More
Lumpsum price worked out by the contractor for Earth Works as listed in Schedule 'A' Part-VI.

1

1176698

-

... More
Lumpsum price worked out by the contractor for Road and Path Works as listed in Schedule 'A' Part-VII.

1

866812

-

... More
Lumpsum price worked out by the contractor for Fencing and Gate Works as listed in Schedule 'A' Part-VIII.

1

391178

-

... More
Lumpsum price worked out by the contractor for Area Drainage Works as listed in Schedule 'A' Part-IX.

1

141039

-

... More
Lumpsum price worked out by the contractor for External Electric Supply Works as listed in Schedule 'A' Part-X.

1

849271

-

... More
Lumpsum price worked out by the contractor for External Water Supply Works as listed in Schedule 'A' Part-XI.

1

778861

-

... More
Lumpsum price worked out by the contractor for Sewage Disposal Works as listed in Schedule 'A' Part-XII.

1

1623263

-

... More
Supply and fixing of DBOX x MCB protected socket with sheet steel enclosure single pole 25Amp with 3 pin plug top for AC connection from socket point to stabilizer ; complete all as specified and directed by the Engineer-in-Charge.

1

-

-

... More
Material and Labour for break down of pipe line bursting/cracks including exacavtion in hard/dense soil with the use of Earthmoving machinery/ labour and taking out old CI/GI/MS defective/misaligned water pipe of any size carefully after disconnection of joints to a length up to 8 metre and create bund with excavated earth and dewatering/bailing out water complete with diesel engine driven pump set and positioning the pipe line after repairs, returning filling and removal of surplus soil/excavated material with the help of excavator/proclainer; complete all as specified and directed by the Engineer-in-Charge. Note: (a) Material/Labour for lead joints/spares/CI/GI specials, CI/GI/MS pipe included in quoted rate (b) The rate is deemed to include cost for tool and plant and transportation required for attending the repair work. (c) Disconnecting/dismantling/cutting the existing pipe line is included in the quoted rate. (d) The rate is inclusive of earth work complete including returning & refilling in any type of strata complete. (e) The breakdown shall be attended within 4 hours of intimation round the clock and time of restroration shall be maximum of 8 hours. The additional manpower required to complete the job in quoted rate is deemed to be included in the quoted.

4

-

-

... More
Material and Labour for painting line, dashes, arrow, letters etc on road pavement of new/old black top surface road surface and applying one coat of retro reflective thermoplastic road marking paint 2 mm thick & width not exc 10 cm for longer durability with 8% glass beads using special applicator machine fitted with profile shoe heater driven by experianced operator on road surfaces on including preparation of new/old treated surfaces, cleaning surfaces of all dirt, scales, oils, grease & foreign materials etc complete all as specified and directed by Engineer in charge with heating arrangement upto 160 degree celcius. Paint material shall be conforming to ministry of surface transport (MOST) specification 803.4 Vol -I as laid down in specification of road / bridge work " third revision" ; complete all as specified and directed by the Engineer-in-Charge.

33

-

-

... More
Supply and fixing PPR Gate Valves (Brass Insert) of 90mm outer dia; complete all as specified and directed by the Engineer-in-Charge.

5

-

-

... More
Material and Labour for cutting existing GI/CI any size of pipe line making new connection for PPR pipe including short pieces , inserting tees, bends, sockets, union etc with existing water line ; complete all as specified and directed by the Engineer-in-Charge.

1

-

-

... More
Material and labour for construction of valve chamber of size 1000mm x 1000mm x 1050mm (Internal dimension) complete using under mentioned specifications ; and as directed by the Engineer-in-Charge :- (i) Earth work (Excavation, Return filling & Removal) in any type of Soil. (ii) PCC (1:4:8) type D2 in foundation using 40mm graded stone aggregate. (iii) Walls constructed with 15Cms thick solid concrete block made of PCC 1:3:6 type C-1 mix and wall built in cement mortar (1:4). (iv) 10mm thick rendering to internal surfaces of chamber full depth in cement mortar (1:4) surfaces finished even and smooth without using extra cement. (v) 15mm thick rendering to external surface of chamber up to 150mm below ground level in cement mortar (1:4) surfaces finished even and smooth without using extra cement. (vi) 50mm thick PCC (1:4:8) type D2 as in sub base of floor 40mm graded stone aggregate. (vii) 50mm thick floor in PCC 1:2:4 type B1 using 20mm graded stone aggregate surfaces finished even & smooth without using extra cement. (viii) Two Coats of white wash on all exposed internal & external surfaces. (ix) 15mm thick MS sheet cover including 40x40x6 mm MS angle frame embedded in 150 mm thick PCC 1:2:4 type B-1,with 25x6 mm flat iron hold fast, handles, hinges with locking arrangements (x) Painting to steel surfaces internally externally with two coats of synthetic enamel painting over a coat of the red oxide primer.

5

-

-

... More
Material and labour for construction of valve chamber of size 600mm x 600mm x 600mm (Internal dimension) complete using under mentioned specifications ; and as directed by the Engineer-in-Charge :- (i) Earth work (Excavation, Return filling & Removal) in any type of Soil. (ii) PCC (1:4:8) type D2 in foundation using 40mm graded stone aggregate. (iii) Walls constructed with 15Cms thick solid concrete block made of PCC 1:3:6 type C-1 mix and wall built in cement mortar (1:4). (iv) 10mm thick rendering to internal surfaces of chamber full depth in cement mortar (1:4) surfaces finished even and smooth without using extra cement. (v) 15mm thick rendering to external surface of chamber up to 150mm below ground level in cement mortar (1:4) surfaces finished even and smooth without using extra cement. (vi) 50mm thick PCC (1:4:8) type D2 as in sub base of floor 40mm graded stone aggregate. (vii) 50mm thick floor in PCC 1:2:4 type B1 using 20mm graded stone aggregate surfaces finished even & smooth without using extra cement. (viii) Two Coats of white wash on all exposed internal & external surfaces. (ix) 15mm thick MS sheet cover including 40x40x6 mm MS angle frame embedded in 150 mm thick PCC 1:2:4 type B-1,with 25x6 mm flat iron hold fast, handles, hinges with locking arrangements (x) Painting to steel surfaces internally externally with two coats of synthetic enamel painting over a coat of the red oxide primer.

16

-

-

... More
Supply ,install ,testing and commissioning of centrifugal pumpset of capacity 1.5 HP/1 KW,3 phase, 415 Volts,50 Hz,2900 RPM, min Head rang- 25 Mtrs at 312.50 L.P.M flow rate, horizontal type , inlet & outlet size -50 mm can withstand wide voltage fluctuation from 200-440 Volts, designed to prevent overloading and motor burntout, dynamically balanced rotating parts to ensure minimum vibratios during running, CED coated cast iron components for rust free & longer life. and motor body & delivery casing made of material- cast iron , shaft- stainless steel including, NRV of suitable size,cable; complete all as specified and directed by the Engineer-in-Charge. (01 set including 02 Nos of pumps one working & one standby)

2

-

-

... More
Supply ,install ,testing and commissioning of centrifugal pumpset of capacity 2 HP/3 KW,3 phase, 415 Volts,50 Hz,2900 RPM, min Head rang- 25 Mtrs at 350 L.P.M flow rate, horizontal type , inlet & outlet size -50 mm can withstand wide voltage fluctuation from 200-440 Volts, designed to prevent overloading and motor burntout, dynamically balanced rotating parts to ensure minimum vibratios during running, CED coated cast iron components for rust free & longer life. and motor body & delivery casing made of material- cast iron , shaft- stainless steel including,NRV of suitable size, cable); complete all as specified and directed by the Engineer-in-Charge. (01 set including 02 Nos of pumps one working & one standby

2

-

-

... More
Material, labour , testing & commissioning of straight through jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 10 to 70 Sqmm 3.5/4 core with working voltage 1100 volts; complete all as specified and directed by the Engineer-in-Charge.

2

-

-

... More
Material, labour , testing & commissioning of indoor End jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 10 to 70 Sqmm 3.5/4 core with working voltage 1100 volts; complete all as specified and directed by the Engineer-in-Charge.

8

-

-

... More
Supply and Fixing on pole street light bracket fabricated out of GI Tubing light grade 40 mm bore Bend to the shape as directed and of length 1.5 mtr complete with mounting MS clamp of flat iron of suitable size 02 Nos incl nut bolts etc of suitable size; complete all as specified and directed by the Engineer-in-Charge.

8

-

-

... More
Supply and Fixing for weather Proof PVC Junction Box made out of not less than 2 mm thick of size 250x200x100 mm (approx) complete with hinged door locking arrangement and consisting of 01 No panel mounted connector 4 pole 32 A - 01 No MCB SP 06 Amps 10 KA - 01 No, confirming to IP 65 complete including fixing on street light pole with MS Clamps, bolts, nuts and washers; complete all as specified and directed by the Engineer in Charge.

8

-

-

... More
Supply and Fixing for PVC insulated 3 core 2.5 Sq mm stranded Copper conductor cable for connecting junction box to street light fitting testing and commissioning; complete all as specified and directed by the Engineer-in-Charge.

60

-

-

... More
Material and Labour for breakdown of electric supply including excavation in hard / dense soil with use of Earthmoving/labour and taking out dameged Cable repair to jointing kit for 1100 V (Earthed) grade cable for Straight through joint cold shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 95 sqmm, after repairs, returning filling and removal of surplus soil; complete all as specified and directed by the Engineer in Charge.

4

-

-

... More
Material and Labour for breakdown of electric supply including excavation in hard / dense soil with use of Earthmoving/labour and taking out dameged Cable repair to jointing kit for 1100 V (Earthed) grade cable for Stright through joint cold shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, after repairs, returning filling and removal of surplus soil; complete all as specified and directed by the Engineer in Charge.

4

-

-

... More
Material and Labour for breakdown of electric supply including excavation in hard / dense soil with use of Earthmoving/labour and taking out dameged Cable repair to jointing kit for 11000 V (Earthed) grade cable for Straight through joint cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm, after repairs, returning filling and removal of surplus soil; complete all as specified and directed by the Engineer in Charge.

1

-

-

... More
Material and Labour for brakdown of electric supply including excavation in hard / dense soil with use of Earthmoving/labour and taking out dameged Cable repair to jointing kit for 11000 V (Earthed) grade cable for Stright through joint cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, after repairs, returning filling and removal of surplus soil; complete all as specified and directed by the Engineer in Charge.

1

-

-

... More
Material and Labour for breakdown of OFC cable,communication cable etc including excavation in hard / dense soil with use of Earthmoving/labour and taking out dameged Cable repair to suitable jointing kit for communication cable complete with jointing material and accessories suitable for network after repairs, returning filling and removal of surplus soil; complete all as specified and directed by the Engineer-in-Charge.

2

-

-

... More
Material & Labour for break down of pipe line bursting/cracks including excavation in hard / dense soil with the use of Earthmoving machinery/ labour and taking out old CI /GI/MS defective / misaligned water pipe line of any size carefully after discon-nection of joints to a length up to 8 mtr and create bund with excavated earth and dewatering / bailing out water complete with diesel engine driven pump set and positioning the pipe line after repairs, returning filling and removal of surplus soil / excavated material with the help of excavator / proclainer; complete all as specified and directed by the Engineer-in-Charge. NOTE : (a) M/L for Lead Joints/ spares/ CI/GI specials, CI / GI/MS pipe included in quoted rate (b) The rate is deemed to include Cost for tool and plant and transportation required for attending the repair work. (c) Disconnecting / dismantling/ cutting the existingpipe line is included in the quoted rate. (d) The rate is inclusive of earth work complete including returning & refilling in any type of strata complete. (e) The breakdown shall be attended within 4 Hrs of intimation round the clock and time of restoration shall be maximum of 8 Hours. The additional manpower required to complete the job in quoted rate is deemed to be included in the quoted.

4

-

-

... More
Material and Labour for Cutting existing roadwork for laying of sewage line/pipeline and making good including providing and laying 80mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern over 150mm thick PCC 1:3:6 type C-2 using 40mm graded aggregates, over compacted road metal retrieved during cutting of road over the necessary earth filling etc; complete all as specified and directed by the Engineer-in-Charge.

20

-

-

... More
Material and Labour for Cleaning and removing of blockage from manholes of any size and upto 1.5 metre depth with combined high pressure water jetting cum suction (vaccum) tupe machine mounted on LCV/HCV and having facilties of high pressure shaped nozzle pipe including removing the soil, roots,mud/sludge or any other materials from the manholes in working/running condition and flushing the entire stretch with water to make the stretch clean and functional. removal & depositing any type of sludge/debries to excavated area, spreading necessary insecticides where sludge is deposited; complete all as specified and directed by the Engineer-in-Charge.

50

-

-

... More
Supplying, aligning, Installation & testing of Precast circular reinforced concrete (M-30) manholes complete with and including 90mm thick S.F.R.C. cover (heavy duty, HD-20 grade designation),conical top (Top portion) of internal dia 0.56 metre at top,internal dia 1.0 metre at bottom,0.805 metre internal depth and bottom solid cylindrical portion 0.30 metre deep, with wall thickness of 125mm conforming to I.S. 12592, collector for AC pipe inlet 150/200, AC pipe outlet 150/200 pipes & future pipes connecting arrangements all as specified and shown on drawing no.SK-1054 Sheet 1/3 . The manholes shall be precast with M-30 concrete grade building in with end caps where shown or necessary, including cost of all materials, labours, T&P including providing the SFRC footrest as specified and shown on drawing suitable to with stand the bend test and chemical resistance test as per specifications and having manufactures permanent identification marks to be visible even after fixing including fixing in manhole; complete all as specified and directed by the Engineer-in-Charge.

175

-

-

... More
All as per item No.40 here-in-before but for circular precast reinforced manhole rings only for increase of manhole depth more than 0.805 metre and upto 2.0 metre complete including SFRC footrest required as per the height; complete all as specified and directed by the Engineer-in-Charge. Note:- Various manholes of different depths are to be provided at site as per site requirement. The tenderer shall quote rates for depth beyond 0.805 metre top portion for this item. Actual payment shall be made based on actual depth provided at site for increse in depth or for each manhole beyond 0.805 metre depth top portion. Tenderer should note this aspect while quoting rates against this item.

240

-

-

... More
Providing and laying Rodent Repelent SN-8 DWC ID (HDPE BLACK) 150mm diameter Pipe with full coupler and rubber ring conforming to IS:16098-2 including testing of joints, comissioning etc; complete all as specified and directed by the Engineer-in-Charge. Note:- Bedding of pipe shall not be provided in normal condition and CONSTRUCTION METHODS shall be strictly compiled as per clause no A-4 of ANNEX 'A' of IS 16098 (Part-2) : 2013.

3025

-

-

... More
Providing and laying Rodent Repelent SN-8 DWC ID (HDPE BLACK) 200mm diameter Pipe with full coupler and rubber ring conforming to IS:16098-2 including testing of joints, comissioning etc; complete all as specified and directed by the Engineer-in-Charge. Note:- Bedding of pipe shall not be provided in normal condition and CONSTRUCTION METHODS shall be strictly compiled as per clause no A-4 of ANNEX 'A' of IS 16098 (Part-2) : 2013.

310

-

-

... More
Supply, Install, testing and commissioning of Diesel Engine Driven Generating Set of 30KVA/24KW capacity with alternator out put Voltage 415 Volts +/- 1% at set value of 415Volts at a frequency 50HZ +/- 0.5% with suitable standard control panel, all mounted in acoustic enclosure and Control panel including AMF Panel as per manufacturers design and specification as per approved CPCB-IV Plus norms confirming to the detailed specifications appended below :- (i) ENGINE (a) General: Suitable four stroke compressed ignition, radiator water cooled,Turbocharged aspiration, continuous duty with 10% overload capacity for any one hour in 12 hours running, 50°C intake air temperature, CPCB-IV Plus Euro emission engine developing 268 BHP at 1500 RPM coupled to alternator mounted on Channel Iron base frame with in built fuel tank of minimum capacity suitable for 12 Hrs continous running. The prime mover provided should be as per IS specifications. (b) Air intake system : Should comprise of dry type intake air filter mounted on engine, one in number vacuum indicator mounted on intake piping. (c) Exhaust System: Should comprise of one exhaust manifold, dry type, mounted on engine, one exhaust residential type silencer which should be positioned in such a way that the exhaust gas is not sucked by the fan on the radiator, thereby affecting the cooling system. The silencer should cater to the noise level tolerance prescribed in the relevant IS/BS. The silencer should be provided with flaps with a provision so that it will open only when the generator is running. The complete exhaust system shall be properly supported so that entire lot of the exhaust system shall not fall on the DG Set. (d) Fuel System: Should comprise of disposal type element fuel filter, pressure type fuel pump mounted on engine, non return check valve in fuel supply and drain lines, wire braided hose between filter and pump, fuel system with suitable capacity electronic governor and engine mounted actuator. The fuel tank must have proper locking arrangement with level indicator and to be integrated with base frame.

1

-

-

... More
Item no. 44(contd...) (e) Cooling System: Should comprise of radiator designed and tested for 50oC ambient temperature with 7 PSI pressure cap mounted on base rail. The thermostat installed in the engine coolant outlet, fresh water pump mounted on engine, fan and fan hub mounted on engine. A reservoir of 50% of radiator capacity to replenish coolant by gravity (as and when required) is also to be provided. (f) Lubricating System: Should comprise of lubricating oil sump mounted on engine, gear driven lub oil pump mounted on engine, lubricating oil cooler-fresh water cooled integral with engine cool out circuit mounted on engine, oil filter lubricating with cap and lubricating oil dip stick for oil level check mounted on engine. The system should be capable of feeding lube oil to the main end & large end bearings, cam shaft, valve rocker gear and all moving parts. (g) Starting System: Should comprise of suitable voltage DC electrical starter mounted on engine, with suitable maintenance free batteries of capacity 12/24 V DC with suitable AH to be mounted in trays (having rubber insulation) on the main frame. It should have the provision to charge the battery from external sources during static condition and while running of the generator. (h) AC Generator : The generator shall be horizontal and foot mounted, 30 KVA, 415 Volts, 3 phase, 4 wire, 0.8 PF, 50 HZ, self excited, self regulated, brushless AC generator, suitable for an ambient temperature of 50° C with IP-23 enclosure class H insulation and temperature rise limited to class H as per following technical details (i) Type, Brush less AC Generators (ii) Output rating 30 KVA (iii) Output Voltage: 415 ± 1% under all loading conditions. (iv) Output frequency 50Hz ±0.5% up to 0.8 lagging. (v) No of Phases: 3 phase with 01 Neutral (4 wire) (vi) Mounting : Horizontal foot mounted. (vii) Enclosure : Minimum IP-23 / Drip proof and screen protected. (viii) Automatic voltage regulator. (ix) Class of insulation-'H'

-

-

-

... More
Item no. 44(contd...) NOTE : Following shall be deemed to be included in cost quoted :- (i) Suitable size RCC cement concrete foundation platform of canopy base with height as required at site to mount the generator as per manufacturer's instructions/ recommendations. The cost of foundation bed incl earth work etc is deemed to be included in the quoted rate. (ii) Connecting existing cables, from existing panels and connecting cables , cables glands, cable lugs to new panel complete with all necessary accessories. (iii) Install on the foundation, connecting fuel lines, cable etc. (iv) Test and commissioning complete (v) The cost of control cables from engine Control panel to AMF panel shall be deemed to be included in the cost quoted. (j) BASE FRAME: Shall be stand by and fabricated with CRCA sheet metal which shall be suitable to mount the engine, alternator and radiator, channel width of base frame shall be adequate to accommodate anti-vibration pads. (k) CONTROL PANEL: Shall be indoor type manufactured with 14/16 guage CRCA sheet and is powder coated for weather-proff and long lasting finish consisting of microprocessor power command controller, Aluminium busbars with suitable capacity with incoming/outgoing terminals, indicating lamps for 'Load ON' and 'Set Running', instrument fuses duly wired and ferruled, MCCB of suitable rating with overload and short circuit protections , Volt meter, ammeter with selector switches, Frequency meter, energy meter, CTs and 3 Phase indicating lamps, timers etc all as per latest engineering practices.etc. complete all as specified and directed. (m) Accessories :- (i) 01 No standard mechanical and electrical tool box. (ii) Internal covered tube lights.

-

-

-

... More
Item no. 44(contd...) (n) Acoustic enclosure: Specially designed to meet CPCB norms 75dBA @ 1 mtr at 75% load under free field conditions. The Acoustic enclosure is made of CRCA sheets and a structural/sheet metal base with high quality noise absorbent and fire-retardant grade acoustic insulation material (P.U.Foam) complying to IS 8183 with two point lifting handles (o) Internal Lighting: Tube lights with protective mesh around it to be fitted inside the container for proper illumination (p) Doors : The enclosure will be provided with suitable doors on the side and rear to enter the enclosure during operation and maintenance. All doors will be provided with lock and handles for opening/ closing the doors, retainers for holding the panel door (q) Painting Scheme ISS shade 220 olive green 1994 or all as per manufacturers specifications (r) Lifting/ Transportation arrangements :- Container with suitable corners will be provided to lift the DG set along with container. This is suitable for road/ rail/ sea transportation. (s) Trials:-Trials on site should be given as per load tests prescribed and all functional trials should be shown. Note : (i) The Engine, alternator, Control Panel, Acoustic enclosure shall be integrated unit sourced from OEM only as per Make. (i) Necessary foundation for installing the DG Set shall be as per manufacturers' recommendation and cost of the same deemed to be included in the quoted rate (ii) Accessories included in manufacturers standard modules are deemed to be included in the quoted rate.

-

-

-

... More
Supply & fixing of GI strip 32 mm x 6 mm burried in ground; complete all as specified and directed by the Engineer-in-Charge.

50

-

-

... More
Supply, Install, testing and commissioning of Diesel Engine Driven Generating Set of 20KVA/16KW capacity with alternator out put Voltage 415 Volts +/- 1% at set value of 415 V at a frequency 50HZ +/- 0.5% with suitable standard control panel, all mounted in acoustic enclosure and Control panel including AMF Panel as per manufacturers design and specification as per approved CPCB-IV Plus norms confirming to the detailed specifications appended below :- (I) ENGINE (a) General: Suitable four stroke compressed ignition, radiator water cooled,Turbocharged aspiration, continuous duty with 10% overload capacity for any one hour in 12 hours running, 50°C intake air temperature, CPCB-IV Plus Euro emission engine developing 268 BHP at 1500 RPM coupled to alternator mounted on Channel Iron base frame with in built fuel tank of minimum capacity suitable for 12 Hrs continous running. The prime mover provided should be as per IS specifications. (b) Air intake system : Should comprise of dry type intake air filter mounted on engine, one in number vacuum indicator mounted on intake piping. (c ) Exhaust System: Should comprise of one exhaust manifold, dry type, mounted on engine, one exhaust residential type silencer which should be positioned in such a way that the exhaust gas is not sucked by the fan on the radiator, thereby affecting the cooling system. The silencer should cater to the noise level tolerance prescribed in the relevant IS/BS. The silencer should be provided with flaps with a provision so that it will open only when the generator is running. The complete exhaust system shall be properly supported so that entire lot of the exhaust system shall not fall on the DG Set. (d) Fuel System: Should comprise of disposal type element fuel filter, pressure type fuel pump mounted on engine, non return check valve in fuel supply and drain lines, wire braided hose between filter and pump, fuel system with suitable capacity electronic governor and engine mounted actuator. The fuel tank must have proper locking arrangement with level indicator and to be integrated with base frame.

1

-

-

... More
Item no. 46(contd...) (c ) Exhaust System: Should comprise of one exhaust manifold, dry type, mounted on engine, one exhaust residential type silencer which should be positioned in such a way that the exhaust gas is not sucked by the fan on the radiator, thereby affecting the cooling system. The silencer should cater to the noise level tolerance prescribed in the relevant IS/BS. The silencer should be provided with flaps with a provision so that it will open only when the generator is running. The complete exhaust system shall be properly supported so that entire lot of the exhaust system shall not fall on the DG Set. (d) Fuel System: Should comprise of disposal type element fuel filter, pressure type fuel pump mounted on engine, non return check valve in fuel supply and drain lines, wire braided hose between filter and pump, fuel system with suitable capacity electronic governor and engine mounted actuator. The fuel tank must have proper locking arrangement with level indicator and to be integrated with base frame. (e) Cooling System: Should comprise of radiator designed and tested for 50oC ambient temperature with 7 PSI pressure cap mounted on base rail. The thermostat installed in the engine coolant outlet, fresh water pump mounted on engine, fan and fan hub mounted on engine. A reservoir of 50% of radiator capacity to replenish coolant by gravity (as and when required) is also to be provided. (f) Lubricating System: Should comprise of lubricating oil sump mounted on engine, gear driven lub oil pump mounted on engine, lubricating oil cooler-fresh water cooled integral with engine cool out circuit mounted on engine, oil filter lubricating with cap and lubricating oil dip stick for oil level check mounted on engine. The system should be capable of feeding lube oil to the main end & large end bearings, cam shaft, valve rocker gear and all moving parts. (g) Starting System: Should comprise of suitable voltage DC electrical starter mounted on engine, with suitable maintenance free batteries of capacity 12/24 V DC with suitable AH to be mounted in trays (having rubber insulation) on the main frame. It should have the provision to charge the battery from external sources during static condition and while running of the generator.

-

-

-

... More
Item no. 46(contd...) (h) AC Generator : The generator shall be horizontal and foot mounted, 20 KVA, 415 Volts, 3 phase, 4 wire, 0.8 PF, 50 HZ, self excited, self regulated, brushless AC generator, suitable for an ambient temperature of 50° C with IP-23 enclosure class H insulation and temperature rise limited to class H as per following technical details (i) Type, Brush less AC Generators (ii) Output rating 20 KVA (iii) Output Voltage: 415 ± 1% under all loading conditions. (iv) Output frequency 50Hz ±0.5% up to 0.8 lagging. (v) No of Phases: 3 phase with 01 Neutral (4 wire) (vi) Mounting : Horizontal foot mounted. (vii) Enclosure : Minimum IP-23 / Drip proof and screen protected. (viii) Automatic voltage regulator. (ix) Class of insulation-'H' NOTE : Following shall be deemed to be included in cost quoted :- (i) Suitable size RCC cement concrete foundation platform of canopy base with height as required at site to mount the generator as per manufacturer's instructions/ recommendations. The cost of foundation bed incl earth work etc is deemed to be included in the quoted rate. (ii) Connecting existing cables, from existing panels and connecting cables , cables glands, cable lugs to new panel complete with all necessary accessories. (iii) Install on the foundation, connecting fuel lines, cable etc. (iv) Test and commissioning complete (v) The cost of control cables from engine Control panel to AMF panel shall be deemed to be included in the cost quoted. (j) BASE FRAME: Shall be stand by and fabricated with CRCA sheet metal which shall be suitable to mount the engine, alternator and radiator, channel width of base frame shall be adequate to accommodate anti-vibration pads.

-

-

-

... More
Material and labour for earthing with steel earth plate electrode of size 60cmx60xcmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of Gl strip to earth electrode to the full length of earth plate, Gl medium grade pipe 40 mm bore protection pipe upto test point, 20 mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation, earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-l and all as specified or indicated including testing on completion. Note :- Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RAC cover, funnel with watering pipe, Gl earth strip upto 7.5 m long for connection to test point etc. all as required at site for complete earthing.

8

-

-

... More
Manning & Operation of the STP & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) for 11 months, after completion of Phase-I { Phase-II refer Sch "A" note no.2.1(b) } complete :- Operating and keeping the capacity in running / operational condition by deploying FGM / technical staff to produce the treated effluent of specified quality including Sundays and holidays including all connected LT cubicle STP panel , electrical & sewage pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc for a period of 11 (Eleven Months) including all sunday & holidays complete all as specified and directed by Engineer-in-Charge.

11

-

-

... More
Manning & Operation of the STP & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) for 11 months, after completion of Phase-II { Phase-III refer Sch "A" note no.2.1(c) } complete :- Operating and keeping the capacity in running / operational condition by deploying FGM / technical staff to produce the treated effluent of specified quality including Sundays and holidays including all connected LT cubicle STP panel , electrical & sewage pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc for a period of 11 (Eleven Months) including all sunday & holidays complete all as specified and directed by Engineer-in-Charge.

11

-

-

... More
Manning & Operation of the STP & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) for 11 months, after completion of Phase-III { Phase-IV refer Sch "A" note no.2.1(d) } complete :- Operating and keeping the capacity in running / operational condition by deploying FGM / technical staff to produce the treated effluent of specified quality including Sundays and holidays including all connected LT cubicle STP panel , electrical & sewage pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc for a period of 11 (Eleven Months) including all sunday & holidays complete all as specified and directed by Engineer-in-Charge.

11

-

-

... More
Manning & Operation of the STP & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) for 03 months, after completion of Phase- IV { Phase-V refer Sch "A" note no.2.1(e) } complete :- Operating and keeping the capacity in running / operational condition by deploying FGM / technical staff to produce the treated effluent of specified quality including Sundays and holidays including all connected LT cubicle STP panel , electrical & sewage pumps items such as main switch, starter, change over switch, MCCB, voltmeter, ammeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc for a period of 03 (Three Months) including all sunday & holidays complete all as specified and directed by Engineer-in-Charge.

3

-

-

... More
Notes for Serial Item No. 48 to 51 above :- Note : - (i) The Contractor shall deploy minumum labour for maintaince & operation as under:- General Shift of 08 hours per day - I :- One skilled operator (FGM) for both STP's. (ii) The timing of shift shall be decided by the Engr-in-Charge/GE (iii) The FGMs employed by the contractor shall be ITI qualified from recognised institute having sufficient knowledge and experience i.e. minimum 02 years in maintenance / operation of similar work. The operators must be competent to carry out the repairs / maintenance of plant as required. (iv) The operators shall maintain the desired quality treated water including tracing out and rectification of minor leakages in pipe line / valves during the period. (v) The operators shall operate elctrical equipements, pumps and maintain the STP in workable condition by checking daily leakages noise, cleaning the plant and its surrounding areas of plant as directed. (iv) The Contractor shall maintain all registers, log books, under various rules, and shall be produced to the Engineer-in-Charge as well as officers detailed by central labour department. (vi) The unit rate quoted shall be deemed to be included for cost of labour for daily for daily routine maintenance for trouble free functioning of installation. (vii) The quoted rate shall be deemed to be inclusive all consumables required for operation of STP. (viii) The payment to the staff employed shall be made within first week of every month through online mode in employees respective Bank Account. No payment to contractors / firms will be made unless proof of payment of wages / EPF / ESI etc through bank account is submitted by the contractor to all employees. Contractor shall produce details of payment made to the employees along with supporting documents for the verification of Engineer-in-Charge for processing the monthly / finall bills. In case of revision in pay slab by Government during the currency of contract, same shall be paid to the employee by the contractor and accordingly rates shall be quoted. (ix) Necessary spare & manpower will be provides by Contractor.

-

-

-

... More
Comprehensive maintenance of the STPs & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) { Phase - II refer Sch "A" note no.2.1(b)} for the period of 1st years after expiry of Defect Liability Period. The scope of comprehensive maintenance includes maintenance of complete infrastructure under this work and replacing all defective components and restoring any defect / deformity / wear and tear and comprehensive maintenance of all STP components under this job, (Sl item No. 1.00 to 6.00 of this BOQ) including all connected LT cubicle STP panel , all pumps and DG Sets in the scope of entire tender for further period of 11 Months after completion defect liability period. The scope shall also include comprehensive maintenance of all electrical & Sewage Pumps items such as main switch, starter, change over switch, MCCB, voltmeter, anmeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc, as per manufacturers instructions and as specified and directede by Engineer-in-Charge.

11

-

-

... More
Comprehensive maintenance of the STPs & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) { Phase - III refer Sch "A" note no.2.1(c)} for the period of 2nd years after expiry of Defect Liability Period. The scope of comprehensive maintenance includes maintenance of complete infrastructure under this work and replacing all defective components and restoring any defect / deformity / wear and tear and comprehensive maintenance of all STP components under this job, (Sl item No. 1.00 to 6.00 of this BOQ) including all connected LT cubicle STP panel , all pumps and DG Sets in the scope of entire tender for further period of 11 Months after completion defect liability period. The scope shall also include comprehensive maintenance of all electrical & Sewage Pumps items such as main switch, starter, change over switch, MCCB, voltmeter, anmeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc, as per manufacturers instructions and as specified and directede by Engineer-in-Charge.

11

-

-

... More
Comprehensive maintenance of the STPs & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) { Phase - IV refer Sch "A" note no.2.1(d)} for the period of 2nd years after expiry of Defect Liability Period. The scope of comprehensive maintenance includes maintenance of complete infrastructure under this work and replacing all defective components and restoring any defect / deformity / wear and tear and comprehensive maintenance of all STP components under this job, (Sl item No. 1.00 to 6.00 of this BOQ) including all connected LT cubicle STP panel , all pumps and DG Sets in the scope of entire tender for further period of 11 Months after completion defect liability period. The scope shall also include comprehensive maintenance of all electrical & Sewage Pumps items such as main switch, starter, change over switch, MCCB, voltmeter, anmeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc, as per manufacturers instructions and as specified and directede by Engineer-in-Charge.

11

-

-

... More
Comprehensive maintenance of the STPs & SCADA (of capacity 75 KLD and 50KLD as per srl item No 1 to 6 of this BOQ) { Phase - V refer Sch "A" note no.2.1(e)} for the period of 3rd years after expiry of Defect Liability Period. The scope of comprehensive maintenance includes maintenance of complete infrastructure under this work and replacing all defective components and restoring any defect / deformity / wear and tear and comprehensive maintenance of all STP components under this job, (Sl item No. 1.00 to 6.00 of this BOQ) including all connected LT cubicle STP panel , all pumps and DG Sets in the scope of entire tender for further period of 03 Months after completion defect liability period. The scope shall also include comprehensive maintenance of all electrical & Sewage Pumps items such as main switch, starter, change over switch, MCCB, voltmeter, anmeter, panel board etc, Sewage water pump, valve system, controlling syatem, daily checking, leakage, checking noise, cleaning of plant and its surrounding area etc, as per manufacturers instructions and as specified and directede by Engineer-in-Charge.

3

-

-

... More
Notes for Srl Item No. 52 to 55 above :- (a) Comprehensive maintenance includes replacement of all defective/ worn out / damaged parts including membrane with new parts and nothing extra shall be paid on this account except the payment specified in this item. (b) The contractor shall be responsible for periodic maintenance as per maintenance schedule and specified including renewal/ replacement of parts, lubricants, fittings / fixtures filling of bacteria etc required for smooth functioning of the plant as per manufacturers instructions. (c) The rate quoted shall be deemed to be inclusive of safety gear & required tools for maintenance. (d) The quoted rate is deemed to be inclusive of tool & testing instruments required for operation & maintenance of STP plant. (e) The sludge cakes procured after treatment shall become contractors property and shall be removed from premises of STP as early as possible. The rate shall be quoted accordingly.

-

-

-

... More
Supply and fixing of LED Lamp 9/10 watt B-22 holder base with polycarbonate body and aluminium heat sink warm white complete all as specified and directed by Engineer - in - Charge.

1

-

-

... More
Supply, installing, testing and commissioning of LT feeder pillar box factory made outdoor type, fabricated out of 3.15 mm thick CRCA sheet with angle iron base frame made of 65 x65 x 6mm, 45 cm height, dust and vermine proof, suitable for voltage 415 separate hinge door for each compartment for incoming and outgoing MCCB etc. with locking arrangement, with back door openable screwed, legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with aluminum busbar (TPN), including provn of following :- Note : (a) The panel shall be as per CPRI certificate (b) Rates inclusive of PCC complete i) Aluminium Bus bar 200-A- mounted on porcelain insulator - 01 Set ( Set of 4 Nos) with PVC sleeve insulation ii) MCCB 4 Pole , 160 Amp, 415 V, 25 KA (Thermal magnetic release) adjustable overload setting 80% to100%- 01 No (incommer) Iii) MCCB 4 Pole , 100 Amp, 415 V, 25 KA (Thermal magnetic release) adjustable overload setting 80% to100%- 01 Nos (ii) MCCB 63 Amps TPN 16 KA - 02 Nos v) Digital Voltmeter of size 96x96mm rating 0-500 volts with selector switch - 01 No vi) Digital Amp meter of size 96x96mm rating 0-1000 Amp with CT's & selection switch - 01 No vii) RYB LED indicator- one set

1

-

-

... More
Supply, installing, testing and commissioning of LT feeder pillar box factory made outdoor type, fabricated out of 3.15 mm thick CRCA sheet with angle iron base frame made of 65 x65 x 6mm, 45 cm height, dust and vermine proof, suitable for voltage 415 separate hinge door for each compartment for incoming and outgoing MCCB etc. with locking arrangement, with back door openable screwed, legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with aluminum busbar (TPN), including provn of following :- Note : (a) The panel shall be as per CPRI certificate (b) Rates inclusive of PCC complete i) Aluminium Bus bar 200-A- mounted on porcelain insulator - 01 Set ( Set of 4 Nos) with PVC sleeve insulation ii) MCCB 4 Pole , 125 Amp, 415 V, 25 KA (Thermal magnetic release) adjustable overload setting 80% to100%- 01 No (incommer) Iii) MCCB 4 Pole , 100 Amp, 415 V, 16 KA (Thermal magnetic release) adjustable overload setting 80% to100%- 01 Nos (ii) MCCB 63 Amps TPN 16 KA - 02 Nos v) Digital Voltmeter of size 96x96mm rating 0-500 volts with selector switch - 01 No vi) Digital Amp meter of size 96x96mm rating 0-1000 Amp with CT's & selection switch - 01 No vii) RYB LED indicator- one set

1

-

-



Evaluation Notes How It Works ?

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.