Public Works Department Tender
View complete overview of Puducherry PWD Tender
Public Works Department - PWD Tender
Eprocure
Opening Date20 Dec 2021
Closing Date31 Dec 2021
Tender Amount₹ 1,06,67,260 This is an estimated amount, exact amount may vary.
Costs
EMD
Refer DocumentsDocument Cost
₹ 1,050Tender Fee
Refer Documents
Summary
Electrical Work For Engineering College
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_PWDC2_8910_1Bid Award Id
ViewTender No
87/EEY/2021-22Tender Authority
Public Works Department ViewPurchaser Address
-Website
http://https://pwd.py.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
1.14.1 Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 1.5 sq.mm + 1 x 1.5 sq.mm earth. (If required)
100
-
-
... More
1.17.12 Supplying and drawing following sizes of FRLS PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit as required -3 x 2.5 sq.mm
4100
-
-
... More
1.17.21 Supplying and drawing following sizes of FRLS PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit as required -3 x 4 sq.mm
3000
-
-
... More
1.14.4 Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required - 2 X 6 sq.mm + 1 x 6 sq.mm earth wire
655.2
-
-
... More
1.14.5 Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required - 2 X 10 sq.mm + 1 x 6 sq.mm earth wire
598.4
-
-
... More
1.14.9 Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required - 4 X 6 sq.mm + 2 x 6 sq.mm earth wire
1200
-
-
... More
1.14.10 Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 4 X 10 sq.mm + 2 x 6 sq.mm earth wire
900
-
-
... More
1.4.11 Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 4 X 16 sq.mm + 2 x 6 sq.mm earth wire(if required)
10
-
-
... More
PVC CONDUITS AND ACCESSORIES
1.21.1 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required - 20mm
1500
-
-
... More
1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required - 25mm (For Communication conduit - (TV/TELE/DATA/CAMERA)
3000
-
-
... More
1.21.3 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required - 32mm (For Projector points & Street light cable)
200
-
-
... More
1.21.5 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required - 50mm
75
-
-
... More
1.20.2 Supplying and fixing of following sizes of steel conduit along with accessories in surface / recess including painting in case of surface conduit , or cutting the wall and making good the same in case of recessed conduit as required - 25 mm
25
-
-
... More
1.27.1 Supplying and fixing following size / modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required - 1 or 2 module (75mm x 75mm)
84
-
-
... More
1.27.2 Supplying and fixing following size / modules, GI box along with modular base & cover plate for modular switches in recess etc. as required - 3 module (100mm x 75mm)
11
-
-
... More
1.27.3 Supplying and fixing following size / modules , GI boxalongwith modular base & cover plate for modular switches in recess etc. as required - 4 module (125 mm x 75 mm) - (If required)
29
-
-
... More
1.27.4 Supplying and fixing following size / modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required - 6 module (200 mm x 75 mm) - (If required)
3
-
-
... More
1.27.5 Supplying and fixing following size / modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required - 8 module (125 mm x 125 mm)
110
-
-
... More
1.27.6 Supplying and fixing following size / modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required - 12 module (125 mm x 125 mm)
102
-
-
... More
1.22.8 Supplying and fixing metal box of following sizes (nominal size) on surface or inrecess with suitable size of phenolic laminated sheet cover in front including painting etc.as required - 200 mm x 150 mm x 75 mm - ( Required for Junction box)
20
-
-
... More
1.22.16 Supplying and fixing metal box of following sizes (nominal size) on surface or inrecess with suitable size of phenolic laminated sheet cover in front including painting etc.as required - 250 mm x 300 mm x 100 mm - ( Required for Junction box)
20
-
-
... More
1.24.1 Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 5/6 A switch
1579
-
-
... More
1.24.2 Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 2 way 5/6 A switch
10
-
-
... More
1.24.3 Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 15/16 A switch
10
-
-
... More
1.24.4 Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 3 pin 5/6 A socket outlet
25
-
-
... More
1.24.5 Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 6 pin 15/16 A socket outlet
10
-
-
... More
1.31 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess , including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch , connections etc , as required
320
-
-
... More
1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess , including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/6 A modular switch , connections etc , as required
250
-
-
... More
1.56 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess , including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlets and 2 nos. 5/6 A modular switches , connection etc.as required.
200
-
-
... More
1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plates(if required)
10
-
-
... More
1.57 Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB , "C" curve including connections , painting etc .as required.
55
-
-
... More
2.20 Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth , metal enclosed plug top alongwith 30A "C" curve, TPMCB in sheet steel enclosure , on surface or in recess , with chained metal cover for the socket out let and complete with connections , testing and commissioning ets as required
45
-
-
... More
DISTRIBUTION BOARD
NPSR Supplying and fixing of following ways surface/recess mounting, vertical type, 415V, TPN MCB distribuition board of sheet steel , dust protected, duly powder painted , inclusive of 200 A tinned copper bus bar , common netural link, earth bar , din bar for mounting MCB'S (but without MCB's and incomer) as required. (note : Vertical type MCCB TPDB is normally used where 3 phase outlets are required -12 way , double door
5
-
-
... More
NPSR Supplying and fixing of following ways surface/recess mounting, vertical type, 415V, TPN MCB distribuition board of sherrt steel , dust protected, duly powder painted , inlusive of 200 A tinned copper bus bar , common netural link, earth bar , din bar for mounting MCB'S (but without MCB,S (but without MCB's and incomer) as required. (note : Vertical type MCCB TPDB is normally used where 3 phase outlets are required -8 way , double door
1
-
-
... More
2.5.1 Supplying and fixing of following ways surface/recess mounting, vertical type, 415V, TPN MCB distribuition board of sherrt steel , dust protected, duly powder painted , inlusive of 200 A tinned copper bus bar , common netural link, earth bar , din bar for mounting MCB'S (but without MCB,S (but without MCB's and incomer) as required. (note : Vertical type MCB TPDB is normally used where 3 phase outlets are required -4 way , double door
2
-
-
... More
2.5.3 Supplying and fixing following way , horizontal type three pole and neutral , sheet steel , MCB disribution board , 415 V, on surface / recess, complete with tinned copper bus bar , neutral bus bar , earth bar , din bar , interconnections , powder painted including earthing etc. as required (But without MCB / RCCB / Isolator) -12 way (4+36) , double door
8
-
-
... More
2.4.3 Supplying and fixing following way , horizontal type three pole and neutral , sheet steel , MCB distribution board , 415 V, on surface / recess , complete with tinned copper bus bar , neutral bus bar , earth bar , din bar, Interconnections , powder painted including earthing etc. as required (but without MCB / RCCB / Isolator ) 8way (4+24) , double door
22
-
-
... More
2.4.2 Supplying and fixing following way , horizontal type three pole and neutral , sheet steel , MCB distribution board , 415 V, on surface / recess , complete with tinned copper bus bar , neutral bus bar , earth bar , din bar, Interconnections , powder painted including earthing etc. as required (but without MCB / RCCB / Isolator ) 6way (4+18) , double door
12
-
-
... More
2.3.3 Supplying and fixing following way, single pole and neutral , sheet steel , MCB disribution board , 240 V, on surface / recess, complete with tinned copper bus bar , neutral bus bar , earth bar , din bar , interconnections , powder painted including earthing etc. as required (But without MCB / RCCB / Isolator) - 12 way , double door
3
-
-
... More
2.3.2 Supplying and fixing following way , single pole and neutral , sheet steel , MCB disribution board , 240 V, on surface / recess, complete with tinned copper bus bar , neutral bus bar , earth bar , din bar , interconnections , powder painted including earthing etc. as required (But without MCB / RCCB / Isolator) - 8 way ,double door
16
-
-
... More
2.3.1 Supplying and fixing following way , single pole and neutral , sheet steel , MCB disribution board , 240 V, on surface / recess, complete with tinned copper bus bar , neutral bus bar , earth bar , din bar , interconnections , powder painted including earthing etc. as required (But without MCB / RCCB / Isolator) - 6 way ,double door
7
-
-
... More
2.17 Supplying and fixing TP sheet steel enclosure on surface / recess along with 16/25/32 A, 415 V "C" curve TP MCB complete with connections , testing and commissioning etc as required
7
-
-
... More
2.16 Supplying and fixing DP sheet steel enclosure on surface / recess along with 25 / 32 A 240 V "C" curve DP MCB complete with connections , testing and commissioning etc.as required
6
-
-
... More
2.10.1 Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc. as required. - Single Pole
697
-
-
... More
2.10.4 Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Triple Pole
75
-
-
... More
2.14.1 Supplying and fixing following rating, double pole , (single phase and neutral), 240V , residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections , testing and commissioning etc as required - 25 A
19
-
-
... More
2.14.2 Supplying and fixing following rating, double pole , (single phase and neutral), 240V , residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections , testing and commissioning etc as required - 40 A
56
-
-
... More
2.14.3 Supplying and fixing following rating, double pole , (single phase and neutral), 240V , residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections , testing and commissioning etc as required - 63 A
67
-
-
... More
2.12.1 Supplying and fixing following rating, double pole ,240V, isolator in the existing MCB DB complete with connections , testing and commissioning etc.as required - 40 A
2
-
-
... More
2.13.1 Supplying and fixing following rating , four pole ,415 V , isolator in the existing MCB DB complete with connections , testing and commissioning etc.as required - 40 A
18
-
-
... More
2.13.2 Supplying and fixing following rating , four pole ,415 V , isolator in the existing MCB DB complete with connections , testing and commissioning etc.as required - 63 A
31
-
-
... More
2.2.1 Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel baorad including drilling holes in cubicls panels , making connections , etc. as required - 100 A . 16 kA 4 Pole
6
-
-
... More
2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc.as required
331
-
-
... More
LIGHT FITTINGS / FAN / EXHUAST FAN
1.34 Supplying and fixing brass batten / angle holder including connection etc.as required
81
-
-
... More
3119-O Supplying of 13W / 15W / 18W CFL lamp for Pin type Make: Philips
53
-
-
... More
1.35 Installation , testing and commissioning of wall bracket / ceiling fittings of all sizes and shapes containing upto two GLS / CFL /LED lamps per fitting. Complete with all accessories including connections etc as required.
53
-
-
... More
NPSR approved rate Supply and fixing of ceiling fan for sweep 1200 mm Fusion -ES50 energy saving fan five star. Make : Havells ( Approval No. 605/PW/Se-I/W/AE(P)II/F.No. 221/14-15, dt. 02.02.15.
375
-
-
... More
1408 supply of Stepped type Modular Fan regulator (2 module)
375
-
-
... More
1.47 Supplying and fixing extra down rod of 10 cm length G.I.pipe , 15 mm dia , heavy gauge including painting etc . As required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
375
-
-
... More
3129-O Supply of 300mm 1400 rpm heavy duty exhaust fan Make:Almonard/Orient/Usha
52
-
-
... More
1.50.1 Installation of exhaust fan in the existing opening , including making good the damage , connection , testing ,commissioning etc. as required - Upto 450 mm sweep
52
-
-
... More
EDP approved rate Supply and Fixting of 20W LED tube light fitting Make: Philips / Bajaj / Havells
1100
-
-
... More
1200 Supplying and fixing of LED 4000K 2 x 2 Square Type Recessed Fitting. (Philips / Havells )
60
-
-
... More
1202 Supplying and fixing of 18W LED 3000K Square Type Recessed Fitting. (Philips / Havells )
72
-
-
... More
NPSR app. Rate Supplying and fixing of 230V, 1 x 35W LED Wall bracket mounted type light fitting with suitable 20W LED lamp and necessary fixing accessories as required. Make: Philips/Bajaj
16
-
-
... More
CABLE
EDP. Cost Data Supply of 4C x 25 sqmm PVC sheathed armoured aluminium U.G cable- 1.1 KV grade. Make:Finolex/Polycab
600
-
-
... More
EDP. Cost Data Supply of 4C x 50 sqmm PVC sheathed armoured aluminium U.G cable- 1.1 KV grade. Make:Finolex/Polycab
300
-
-
... More
EDP. Cost Data Supply of 3 1/2 x 95sqmm PVC/XLPE sheathed armoured aluminium U.G cable-1.1 KV grade. Make:Finolex/Polycab
200
-
-
... More
EDP. Cost Data Supply of 3 1/2 x 240sqmm PVC/XLPE sheathed armoured aluminium U.G cable-1.1 KV grade. Make:Finolex/Polycab
200
-
-
... More
9.1.34 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required - 4 X25 sq.mm (28 mm)
12
-
-
... More
9.1.36 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required - 4 X50 sq.mm (35 mm)
18
-
-
... More
9.1.24 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required - 31/2 X95 sq.mm (45 mm)
8
-
-
... More
9.1.29 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required - 31/2 X240 sq.mm (62mm)
20
-
-
... More
7.1.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation , sand cushioning, protective covering and refilling the trench etc.as required - Upto 35 sq.mm
540
-
-
... More
7.1.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation , sand cushioning, protective covering and refilling the trench etc.as required - above 35 sq.mm and upto 95 sq.mm
420
-
-
... More
7.1.4 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation , sand cushioning, protective covering and refilling the trench etc.as required - above 185 sq.mm and upto 400 sq.mm
200
-
-
... More
CABLE TRAY AND TRENCH
4.6.2 Supplying and installing following size of perforated Hot dipped Galvanised iron cable tray (galvanization thickness not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors, suspended from the ceiling with G.I.suspenders including G.I.bolts & nuts , etc .as required - 150 mm width x 50 mm depth x 1.6mm thickness
42
-
-
... More
4.6.4 Supplying and installing following size of perforated Hot dipped Galvanised iron cable tray (galvanization thickness not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I.suspenders including G.I.bolts & nuts , etc .as required - 300 mm width x 50 mm depth x
132
-
-
... More
4.6.6 Supplying and installing following size of perforated Hot dipped Galvanised iron cable tray (galvanization thickness not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I.suspenders including G.I.bolts & nuts , etc .as required - 450 mm width x 50 mm depth x 2.0
30
-
-
... More
4.7.2 Supplying and installing following size of perforated Hot dipped galvanised iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I.suspenders including G.I. bolts & nuts , etc.as required - 150 mm width x 50 mm depth x 1.6 mm thickness
2
-
-
... More
4.7.4 Supplying and installing following size of perforated Hot dipped galvanised iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I.suspenders including G.I. bolts & nuts , etc.as required - 300 mm width x 50 mm depth x 1.6 mm thickness
8
-
-
... More
4.7.6 Supplying and installing following size of perforated Hot dipped galvanised iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I.suspenders including G.I. bolts & nuts , etc.as required - 450 mm width x 50 mm depth x 2.0 mm thickness
4
-
-
... More
4.8.2 Supplying and installing following size of perforated Hot dipped galvanised iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I.suspenders including G.I.bolts & nuts . As required - 150 mm width x 50 mm depth x 1.6 mm thickness
5
-
-
... More
4.8.4 Supplying and installing following size of perforated Hot dipped galvanised iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts . As required - 300 mm width x 50 mm depth x 1.6 mm thickness
7
-
-
... More
4.8.6 Supplying and installing following size of perforated Hot dipped galvanised iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5% , in convenient sections , joined with connectors , suspended from the ceiling with G.I.suspenders including G.I.bolts & nuts . As required - 450 mm width x 50 mm depth x 2.0 mm thickness
2
-
-
... More
4.10.4 Supplying and installing following size of perforated Hot dipped galvanised iron cable tray "Reducer" (galvanisation not less than 50 microns) with perforation not more than 17.5% ,in convenient sections , joined with connectiors , suspended from the ceiling with G.I.suspenders including G.I.bolts & nuts , etc.as required - 300 mm width x 50 mm depth x 1.6 mm thickness
4
-
-
... More
14.4 Excavation for cable trenches in soft soil , depth upto 1.2 m including dressing of sides lift upto 1.5m , including getting out the excavated soil , refilling with sand and good soil after laying of cable / pipe etc. in layers of 20cm , ramming, watering and disposal of surplus excavated soil as directed , within a lead of 50 meters
25
-
-
... More
EARTHING
5.20 Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal / coke and salt as required
20
-
-
... More
5.50 Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. (but without charcoal / coke and salt) as required (if required)
1
-
-
... More
5.14 Providing and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc as required
12
-
-
... More
5.15 Providing and fixing 25mm x 5mm GI.strip on surface or in recess for connections etc . as required
564
-
-
... More
5.17 Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required
348
-
-
... More
5.80 Supplying and laying 25 mm x 5 mm copper strip at 0.50 meter below ground as strip earth electrode , including connection / terminating with nut , bolt, spring , washer etc.as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spached at 50mm)
24
-
-
... More
5.90 Supplying and laying 25 mm x 5 mm G.I strip at 0.50 meter below ground as strip earth electrode , including connection / terminating with G.I. nut , bolt, spring , washer etc.as required. (Jointing shall be done by overlapping and with 2 sets of G.I.nut bolt & spring washer spached at 50mm)
48
-
-
... More
DATA NETWORKING
NPSR App.Rate Supplying and fixing Data socket outlet modular type and modular plate in cadmium / GI plated MS box including making connections etc as required. Make: MK / Crabtree
178
-
-
... More
1.53.1 Supplying and drawing of UTP 4 pair CAT 6 Lan cable in the existing surface / recessed Steel / PVC Conduit as required - 1 run of cable.
4200
-
-
... More
NPSR App.Rate Supply, installation, testing and commissioning of 16 port Data switches with rack, the rate shall be inclusive of all required civil works. (Make: Netgear / Digilink)
8
-
-
... More
NPSR App.Rate Supply, installation, testing and commissioning of 24 port Data switches with rack, the rate shall be inclusive of all required civil works. (Make: Netgear / Digilink)
5
-
-
... More
NPSR App.rate Supply of wall Mounted network rack - 9U door of glass, completely covered and have security lockers, proper ventilated with one fan one cable manager, power distribution units of 6nos (5A) sockets with surge protection, mounting accessories and 5A top Ventilation switch.
5
-
-
... More
NPSR App.Rate Installation of wall Mounted network rack - 9U door of glass, complety covered and have security lockes, proper ventilated with one fan one cable manager, power distribution units of 6nos(5A) sockets with surge preotection, mounting accessories and 5A top Ventilation switch.
5
-
-
... More
LT CT METER PANEL
31.254.1
Civil PSR (20-21) Supply and erection of compartmentalised CT metering panel (3 Compartment type) for receiving the EB supply consisting of :- 250A 4 Pole copper bus bars suitable to accommodate 3 Nos. CT's. The meter chamber will have provision to fix 3 phase 4 wire 50 HZ CT operated Kwhr meter to be supplied by supply authorities and the front meter door shall be fitted with glass /Acrylic cover infront of meter dial to read the meter recording the meter door shall have provision for sealing arrangement by supply authorities The TTB chamber will have 3 phase 4 wire 50 HZ TTB. All chambers should have sealing arrangement provision. 3 Nos 250 Amps Porcelain cutouts and 315 Amps Neutral link with cable chamber suitable for receiving 1 no. 3 1/2 core 240 sq mm PVC insulated Aluminium conductor armoured cable. The board should be manufactured such that should be approved by Local supply authorities.
1
-
-
... More
NON PSR Design and Supply of 250A TPN SDF DIN Type fuse link with suitable sorting links as complete with enclosure.
1
-
-
... More
PANEL
Supply of 415V cubical type, fully compartmentalised, floor mounted type main switch board fabricated with 16G CRCA sheet, powder coated with Siemens grey (RAL 7032) after seven tank process and complete with welded & bolted design and all incoming & outgoing switch gears as per the following."
Suitable aluminuim busbars, control wiring, control fuses, seperate metering compartment with multi function meter and phase indications.
Electrical and mechanical interlocking facility between EB incomers, EB incomers & bus coupler.
Safety features and items including necessary earthing throughout the bottom length, 6 sq.mm FRLS copper wire interconnections for compartment earthing, complete copper control wiring with crimping type ferrules, copper lugs, proper engravation on each compartment etc.
The switch boards shall be CPRI approved of factory assembled and tested.
All complete compatible with EMS & RS485 integration
All busbars shall be fixed with standard space clearance and with colour coated heat shrinkable PVC sleeves with DMC/SMC bus bar supports and suitable copper earth bus.
The cable entry shall be from the bottom/top as per site requirement.
The item including cost of MS base frame of 75mm height, 3.15mm sheet steel or 40x40x6mm MS angle for load bearing members, lifting hooks, steel support structure required for erection and its painting, minor civil works, vendor drawings, necessary safety clearance from statutory authorities, panel approval from CPWD/PED till obtaining final power supply, all complete as per specifications, drawings and / or as directed by the Engineer.
The contractor shall submit general arrangement & control wiring drawings along with the CPRI test certificates, and get approval from Engineer in-charge before commence the fabrication works.
-
-
-
... More
MAIN PANEL
Incomer
i) 630A, TPN, 36KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No."
Phase indication lamps(R,Y,B) - 1 sets.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 630/5A,CL:1.0 tape insulated bar primary type with suitable sorting links - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH & Phase sequence. - 1 Set.
"Busbar:
i) 630A, TPN, 36KA, for 1 sec Aluminium bus bar"
ii) Phase: current density not more than 0.8A/sq.mm
iii) Neutral: half of the phase current (0.5 x phase)
iv) Earth: 25x3mm copper flat throught the panel length
"Outgoing:
i) 400A, TPN, 36KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 2 Nos."
ii) 250A, TPN, 36KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No.
iii) 200A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 2 Nos.
iv) 160A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 3 Nos.
v) 125A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 2 Nos.
vi) NON PSR 100A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No.
1
-
-
... More
SSB-1
Incomer
i) 400A, TPN, 36KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No."
Phase indication lamps(R,Y,B) - 1 sets.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 400/5A,CL:1.0 tape insulated bar primary type with suitable sorting links - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH & Phase sequence. - 1 Set.
Busbar:
i) 400A, TPN, 36KA, for 1 sec Aluminium bus bar
ii) Phase: current density not more than 0.8A/sq.mm
iii) Neutral: half of the phase current (0.5 x phase)
iv) Earth: 25x3mm copper flat throught the panel length
Outgoing:
i) 160A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 3 Nos.
ii) 125A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 Nos.
iii) 100A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 3 Nos.
iv) NON PSR 63A, TPN, 18KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 3 Nos.
1
-
-
... More
WORKSHOP PANEL
Incomer
i) 100A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 sets.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 100/5A,CL:1.0 tape insulated bar primary type with suitable sorting links - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH & Phase sequence. - 1 Set.
Busbar:
i) 100A, TPN, 25KA, for 1 sec Aluminium bus bar
ii) Phase: current density not more than 0.8A/sq.mm
iii) Neutral: half of the phase current (0.5 x phase)
iv) Earth: 25x3mm copper flat throught the panel length
Outgoing:
i) NON PSR 32A, TPN, 18KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 8 Nos.
1
-
-
... More
UTILITY PANEL
Incomer
i) 125A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No."
Phase indication lamps(R,Y,B) - 1 sets.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 125/5A,CL:1.0 tape insulated bar primary type with suitable sorting links - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH & Phase sequence. - 1 Set.
Busbar:
i) 125A, TPN, 25KA, for 1 sec Aluminium bus bar
ii) Phase: current density not more than 0.8A/sq.mm
iii) Neutral: half of the phase current (0.5 x phase)
iv) Earth: 25x3mm copper flat throught the panel length
Outgoing:
i) NON PSR 63A, TPN, 18KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 5 Nos.
1
-
-
... More
PSB-2 (RIGHT WING)
Incomer
i) 160A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 sets.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 160/5A,CL:1.0 tape insulated bar primary type with suitable sorting links - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH & Phase sequence. - 1 Set.
Busbar:
i) 160A, TPN, 25KA, for 1 sec Aluminium bus bar
ii) Phase: current density not more than 0.8A/sq.mm
iii) Neutral: half of the phase current (0.5 x phase)
Iv) Earth: 25x3mm copper flat throught the panel length
Outgoing:
i) NON PSR 63A, TPN, 18KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 12 Nos.
1
-
-
... More
LSB-2 (RIGHT WING)
Incomer
i) 100A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 sets.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 100/5A,CL:1.0 tape insulated bar primary type with suitable sorting links - 1 Set.
Metering: Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH & Phase sequence. - 1 Set.
Busbar:
i) 100A, TPN, 25KA, for 1 sec Aluminium bus bar
ii) Phase: current density not more than 0.8A/sq.mm
iii) Neutral: half of the phase current (0.5 x phase)
iv) Earth: 25x3mm copper flat throught the panel length
Outgoing:
i) NON PSR 40A, TPN, 18KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 9 Nos.
1
-
-
... More
USB-1(LEFT WING)
Incomer :
63A FP MCB (C - curve 10KA) - 1 No
Outgoings :
i) NON PSR 25A DP MCB (C - curve 10KA) - 8 Nos
1
-
-
... More
USB-2(RIGHT WING)
Incomer :
63A FP MCB (C - curve 10KA) - 1 No
Outgoings :
i) 40A FP MCB (C - curve 10KA) - 4 Nos
ii) NON PSR 25A DP MCB (C - curve 10KA) - 4 Nos
1
-
-
... More
ELSB-1(LEFT WING)
Incomer :
32A DP MCB (C - curve 10KA) - 1 No
Outgoings :
i) NON PSR 25A DP MCB (C - curve 10KA) - 5 Nos
1
-
-
... More
50KVAR APFC Panel
Incomer :
200A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism & spreader - 1 Nos.
Phase indication lamps(R,Y,B) - 1 set.
CT ratio 200/1A,CL:1.0 tape insulated type with suitable sorting links
Metering:Multifunction meters cl:1.0 measured with following parameters:V,I,PF,KW,KWh.
Outgoing:- Each bank provide with stage incomers,and on indication lamp
Microprocessor based APFC relay with 8 stages
Type of control:Capcitor duty contactors
Capacitors:Type-cylindrical gas filled and consider upto 5kvar heavy duty type,voltage:440V
i) 15KVAR with 63A TP MCB - 1 No.
ii) 10KVAR with 63A TP MCB - 2 Nos.
iii) 5KVAR with 32A TP MCB - 1 No.
iv) 4KVAR with 32A TP MCB - 1 No.
v) 3KVAR with 32A TP MCB - 1 No.
vi) 2KVAR with 32A TP MCB - 1 No.
vii) 1KVAR with 32A TP MCB - 1 No.
viii) NON PSR APFC controller with 8 stages - 1 No.
1
-
-
... More
SSB-2 (Lab Block)
Incomer
i) 250A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 sets.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 250/5A,CL:1.0 tape insulated bar primary type with suitable sorting links - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH & Phase sequence. - 1 Set.
Busbar:
i) 250A, TPN, 25KA, for 1 sec Aluminium bus bar
ii) Phase: current density not more than 0.8A/sq.mm
iii) Neutral: half of the phase current (0.5 x phase)
iv) Earth: 25x3mm copper flat throught the panel length
Outgoing:
i) 100A, TPN, 25KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 8 Nos.
ii) 63A, TPN, 18KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 5 Nos.
iii) NON PSR 40A, TPN, 18KA, MCCB with adjustable thermal magnetic releases and rotary handle mechanism & spreader - 2 Nos.
1
-
-
... More
ONLINE UPS / INVERTER
NON PSR Supply and erection of 1 Phase, 230 V, 2 kVA 1P -n 1P out /INVERTER with suitable BCB (battery circuit breaker), filters, 6 nos. 12V 28Ah SMF battery bank, with 30minutes backup. The items including necessary safety features, protections/relays, necessary battery racks, cables/wires and fixing accessories etc.
2
-
-
... More
NON PSR Supply and erection of 1 Phase, 230 V, 3 kVA 1P -n 1P out UPS with suitable BCB (battery circuit breaker), filters, 6 nos. 12V 42Ah SMF battery bank, with 30minutes backup. The items including necessary safety features, protections/relays, necessary battery racks, cables/wires and fixing accessories etc.
1
-
-
... More
NON PSR Supply and erection of 3 Phase, 415 V, 15kVA 3P -in 3P out online UPS with suitable BCB (battery circuit breaker), filters, 24 nos. 12V 42Ah SMF batteries with 30minutes backup with necessary fixing accessories etc. Make: Numeric / Consul / Luminous Battery make: Exide/Quanta
1
-
-