Odisha Lift Irrigation Corporation Limited Tender
Search from a pool of business opportunities related to Odisha tenders on the online platform of BidAssist. Be it an Odisha PWD tender or a civil aviation tender, one can find every tender Odisha government, as well as PSUs and other organizations, post online. Every tender, active or achieved, is sourced from the eProcurement Odisha website and thus carries full credibility.
Costs
EMD
₹ 18,225Document Cost
₹ 6,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_OLIC_85416_8Bid Award Id
ViewTender No
3_2022_23_18_01_2023Tender Authority
Odisha Lift Irrigation Corporation Limited ViewPurchaser Address
-Website
http://http://www.odishalift.co.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Cement concrete (1:4:8) with 4cm size h.g.b. hand broken metal of approved quality from approved quarry with ramming watering and curring etc. complete including cost, taxes, royalty convence charge of all material to worksite, supply of cement T&P required etc. complete as per the direction of the Engineer-incharge.
4.15
20775
5006.19
Brick work with Fly ash Brick 25cm x 12cm x 8cm size having crushing strength not less than 75kg / cm2 with dimensional tolerrance + 8% in cement mortar (1:6) in foundation & plinth etc. complete as per the Engineer-incharge.
4.9
24187
4936.2
Brick work with Fly ash bricks 25cm x 12cm x 8cm size having crushing strength not less than 75 Kg/cm2 with dimensional tolerance ±8 percent in cement mortar (1:6) in superstructure per cum etc. complete as per the Engineer-incharge.
6.37
31655
4969.53
12mm cement plaster in cement mortar (1:6) finished smooth to brick work after racking out joints including waterring and curring with cost, taxes, royalty and conveyance charges of all material to the worksite and supply of all labour and T&P required for the work etc complete as directed by the Engineer-incharge.
61.04
9423
154.38
R.C.C. work in C.C. (1:2:4) including hoisting & laying & curring for 28 days using 12mm. Size clean black hard granite crusher broken chips of approve quality and from approve quarry including cost taxes conveyance charges of all materials to the worksite with supply of all labour and T&P required for the work etc complete as directed by the Engineer-incharge.
8.94
62944
7040.73
2.5 cm A.S. Flooring with C.C. (1:2:4) using 12mm size black hard granite crusher broken chips of approve quality for approve quorry including water and curring with cost taxes royalty and conveyance charges of all material to the worksite and supply of all labour and T&P required for the work etc complete as directed by the Engineer-incharge.
6.25
2114
338.36
Rigid smooths centering and shuttering for RCC works including false work and dismentgalling then after casting including cot os materials complete.
(a) RCC walls and fins including attached pillasters
55.08
35497
644.48
b) Chajja/Roof slab
10.34
4541
439.25
c) Lintel
0.68
183
269.17
d) RCC Beams, culumns, grider & Bressers etc
24.8
18650
752.05
e) RCC foundation an footing beases of columns etc.
5.85
776
132.71
Dry brick rammed Khoa (10 cm) thick well watered and rammed inluding all cost as per specification in complete.
5.62
1799
320.19
Labour charge for M.S. reinforcement for R.C.C. work including cutting, bending & typing the grills & placing in position including cost of binding wire 18 to 20 guage per Qntl. Including cost of HYSD Still Bar (FE 415/ FE 500)
5.82
68034
11689.82
Filling the foundation and plinth with excavated material as directed by the Engineer-incharge.
779.48
84573
108.5
White washing 3 coat with approve good stone lime including cost conveyance charges of materials including supply of labour, gum, indigo etc. required for the work complete as directed by the Engineer-incharge.
31.95
413
12.93
Colour washing three coat with stone lime and colouring materials per 1 Sqm
35.54
502
14.14
Writing charge of required information and data on both side of the transperancy pillar including supplying of approved paints and required material for writing etc. complete as per the direction of the Engineer-incharge.
1
1000
1000
MS Pannel Door double leafed with MS frame overall size including frame of height 1.2mt x 1.98mt. width for door and shutter of 20 gauge CR sheet pannel as per approved size & specification etc. complete including cost of all materials fitting and fixing the door etc. complete as per the direction of the Engineer-incharge.
1
5500
5500
Supplying of 200mm dia unplasticised rigid UPVC pipe ivory gray in colour having specific gravity of 1.40 to 1.46 gms/cc of straight length of 6 (six) meter for portable water supplies conforming to IS - 4985 / 2000 of BIS - Amendment - 2 read with Table - 1 of IS - specification bearing ISI marks for working pressure CI - I UPVC pipe to withstand pressure of 2.5 kgf/sqcm & the specification and manufacturer name should be prominently marked on body of each pipe as per the latest Amendment of IS - 4985. It includes the cost of sockets in case of plain ended pipe. PDI test are to be condcuted and should be marked on body of each pipe and report is to be obtained from CIPET, Bhubaneswar necessary approval of authority including transportation to work site in complete shape.
350
194250
555
Fitting of un plasticised 200mm dia PVC Pipe for following inside dia mtr. for all classes of pipe including jointing the pipe with solvent cement by non-head application method including fitting and fixing of required no. of PVC Tee for outlet and PVC Shaddle and PVC Riser nipple for fitting air valve, equal Tee etc. complete including conveyance pipe from village to worksite and testing of pipe line etc. complete as per the direction of the Engineer-incharge.
350
33225
94.93
Supplying of 160 mm dia unplasticised rigid UPVC pipe ivory gray in colour having specific gravity of 1.40 to 1.46 gms/cc of straight length of 6 (six) meter for portable water supplies conforming to IS - 4985 / 2000 of BIS - Amendment - 2 read with Table - 1 of IS - specification bearing ISI marks for working pressure CI - I UPVC pipe to withstand pressure of 2.5 kgf/sqcm & the specification and manufacturer name should be prominently marked on body of each pipe as per the latest Amendment of IS - 4985. It includes the cost of sockets in case of plain ended pipe. PDI test ( Both Pre & Post inspection ) are to be condcuted and should be marked on body of each pipe and report is to be obtained from CIPET, Bhubaneswar necessary approval of authority including transportation to work site in complete shape.
656
236160
360
Fitting of un plasticised 160mm dia PVC Pipe for following inside dia mtr. for all classes of pipe including jointing the pipe with solvent cement by non-head application method including fitting and fixing of required no. of PVC Tee for outlet and PVC Shaddle and PVC Riser nipple for fitting air valve, equal Tee etc. complete including conveyance pipe from village to worksite and testing of pipe line etc. complete as per the direction of the Engineer-incharge.
656
53136
81
10.00HP/7.5 KW Submersible motor pump of 25 mtr head with 1200 LPM discharge of reputed brand with BEE Star rated energy efficiency suitable for 200 mm dia tube well as per IS specification with 2 pair U-Clamp & 30 mtr of 4.00 sqmm flat cable as per IS specification
1
46325
46325
Labour charges for installation of 10HP Motor including fitting & fixing of base frame, fitting & fixing suction and delivery pipe to motor, NR Valve, Foot Valve, Sluice Valve and other fitting materials including cutting, welding and construction of supporting pillar etc. complete as per the direction of the Engineer-incharge.
1
8876
8876
100 mm Ø nominal bore G.I. pipe having wall thickness 4.5 mm electrical resistance welded of medium class confirming to IS - 1239 (pt-1 of 2004) with socketed at one end and the other end protected with plastic thread protector. The socket confirming to IS-1239 (pt-II/1992) with latest amendmewnts in random length of 4 to 7 mtrs. Each pipe should bear ISI certification & manufacturers name / Trade mark.
36
51300
1425
100 mm dia G.I. bend IS No.1239(Part-II/1992)
3
3075
1025
100 mm dia G.I. flange IS No.6392 / 1971
8
3704
463
100mm dia GI Socket IS 1239 (Part-II/1992 )
4
1016
254
100mm dia GI nipple IS 1239 (Part-II/1992 )
1
152
152
100 mm dia MS T/W Clamp
1
585
585
100 mm Ø Sluice Valve Flanged type of Manufacturing Standard - BS 5163 / IS14846 Pressure Ratings PN10.
1
5530
5530
50 mm Ø Air release valve with saddle & Raiser pipe. The air release valve shall confirm to IS 14845 with ISI mark.
2
5000
2500
200 mm x200 mm x200 mm Ø PVC Equal Tee (W.P. 4 kgf/cm2) confirming to IS-4995/1988 with latest ammendment
1
943
943
200 mm x 200 mm x 160 mm Ø PVC Tee (W.P. 4 kgf/cm2) confirming to IS-4995/1988 with latest ammendment
5
4535
907
160 mm x 160 mm x 160 mm Ø PVC Equal Tee (W.P. 4 kgf/cm2) confirming to IS-4995/1988 with latest ammendment
2
1510
755
200 mm Ø PVC Bend (900 W.P. 10 kgf/cm2) confirming to IS-4995/1988 with latest ammendment
1
1680
1680
200 mm Ø PVC End Cap (W.P. 10 kgf/cm2) confirming to IS-4995/1988 with latest ammendment
2
618
309
160 mm Ø PVC End Cap (W.P. 10 kgf/cm2) confirming to IS-4995/1988 with latest ammendment
7
1169
167
160 mm Ø PVC Flange
8
4320
540
160 mm Ø PVC Coupler
8
1896
237
5/8 x3" Nut bolt & Foundation Nut bolt as per IS specification
5
470
94
1/8" thick Rubber Insertion as per IS specification
5
290
58
Cost of 160mm x160mm x 110 mm M.S.Riser Tee made of M.S.Pipe 300 mm long fitted with one mtr long 100 mmQ M.S.Pipe(ISI mark) welded with 2 nos 100 mm Q m.S.flange in between 1 mtr M.S.pipe and 0.25 mtr long 100 mmQ m.S.pipe fitted horizontalley with 2 nos of 100 mmQ M.S.elbow with locking arrengments.
10
40000
4000
cost of 200mm×110mm dia PVC reducing socket.
1
434
434
Cost of 110mm dia PVC FTA
1
153
153
Cost of Butterflay valve with extended operating system and all accessaries for utilising in 6'' dia PVC dristibution system pipe line.
4
22000
5500
Cost of 2.5 mm 2 Submerssible ( 3 Core ) Flat Cable
60
6660
111
Control Pannel with Automatic Star delta Starter, sheet steel enclosure suitable for operation of Squirrel cage induction motor up to 10 HP with 16 Amp (AC -3) duty contractor at 415 Volt+6%-15%, 3 phase, 50 Hz AC supply with over load relay range 6.00 to 9.50 Amp & no volt coil with electronic timer suitable for operation at voltage range of 300 to 440 V. The Starter should provide dependable protection against over load and single phasing fitted with Volt meter,Ameter,MCB in complete shape including Indicator Lamp
1
14979
14979
63 Amp Main Switch Triple pole & neutral of voltage range 440 volt of re-wirable fuse and shall confirm to IS 4064 part I & with ISI mark.
1
3189
3189
3 x 10 sqmm Tarpodar cable XLPE (Cross link polyethylin) conforming to IS: 7098 (Part-II) including laying below .9mtr. of the ground and filling the excavated materials including watering and ramming.
30
4020
134
Schedule B
-
-
-
Construction of 3 phase 11 KV line as per REC standard confirming to IE Rules 1956 with 300 kg 9 M long PSC Pole with 55 Sqmm AAAC , 11 KV "V" Cross arm, with required No.of 11 KV T & C Disc. Insulators in tension point & 11 KV Pin insulators, Couping & Padding of Poles. Danger Board at each Pole, Anti Climbing Devices, Stay Set at Bending point & double stay at end point with 18 mm G.I.H.T.Stay, concreting of Stay with Anchor plate, guarding at Road crossings etc. including cost of all materials, labour transportation,inspection & commissioning etc. complete.
0.6
221767
369612.21
Construction and erection of 11 /0.4 KV , 25 KVA Double Pole mounted Substation Star rated confirming to RE Rules 1956, mounted on 2.44 Mtr. Long structure, supported in 300 kg 9 mtr long PSC pole,transformer hard channel & top channel made of 2.8 M long 100 X 50 X 6 mm M.S.Channel, Transformer belting on 2.80 M long 50 X 50 X 5 mm M.S.Angle, (all REC SPN Std.F-3) with all accessories like 3 pole 11 KV HG Fuse(F-5)& A.B.Switches(F-9) both mounted on 2.8 M long 75 X 40 X 6 mm M.S.Channel and supported by 1.0 M long 50 X 50 X 5 mm M.S.Angle, with 3 No. 11 KV Lightening Arrestors & Distribution box for 25 KVA S/S, G.I.pipe earthing with 25X5mm G.I.Flats including cost of 25 KVA 11/0.4 K.V.Transformer , 35 Sqmm 3 1/2 Core PVC Cable - 40 mtr couping & padding of Poles, Danger board at each Pole, Anti climbing Devices & all other necessary fittings i.e required size Nuts & Bolts, Brackets, Cable, Cable Sockets, barbed fencing ( size (15'x10') with constn. of retaining wall, erection of RCC fencing post , sand filling and metal spreading ,fixing of iron grill gate etc as per cesu specification etc. including cost of all materials, labour , transportation complete with liasioning for testing inspection & commissioning.
1
296827
296827.34
Electrical installation with electrical materials such as PVC tape, ampere tape, 7/20 PVC copper wire, 3/20 PVC copper wire, G.I. flexible conduite pipe, No.6 G.I. wire, copper cable socket, G.I. socket and flange and petty materials required for electrical installation. All materials should be as per IS.
1
3000
3000
Electrical Earthing with digging earth pit of size (2 ft X 2 ft X 3 ft ) and using 1/2 '' G.I pipe ,No -6 G.I wire ,cable socket ,Flange , carcoal, salt etc. as per the direction of the Engineer-incharge.
2
5000
2500
4 KVR power shunt capasitor
1
1772
1772
Evaluation Notes How It Works ?
Potential Partner