Bhubaneswar Development Authority Tender
Search from a pool of business opportunities related to Odisha tenders on the online platform of BidAssist. Be it an Odisha PWD tender or a civil aviation tender, one can find every tender Odisha government, as well as PSUs and other organizations, post online. Every tender, active or achieved, is sourced from the eProcurement Odisha website and thus carries full credibility.
Bhubaneswar Development Authority - BDA Tender
Civil And Construction
Eprocure
Opening Date12 Jan 2024
Closing Date29 Jan 2024
Tender Amount₹ 3,09,06,060
Costs
EMD
₹ 3,09,061Document Cost
₹ 11,800Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_BDABU_99658_2Bid Award Id
ViewTender No
64/EM/BDA/2023-24, Dated-10/01/2024Tender Authority
Bhubaneswar Development Authority ViewPurchaser Address
-Website
http://https://www.bda.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Exhaust piping and insulation.
-
-
-
Supplying and fixing of Exhaust extension of 150MM DIA MS Pipe with wall Support including Horizontal Support with MS Steel, SS Below, Thermal Insulation of 50MM Rockwool, Chicken mess, Aluminium Sheet and painting etc.
50
-
4000
DG PANELS
Supply, delivery, installation, testing & commissioning of L.T. indoor floor/ wall mounted type main distributiob board made out of 2 mm thick CR sheet metal cubicle with front side hinges glass door for every meter compartment, the cabinet have a common bus bar, duly acid treated for derusting, primered and painted with 2 coats of enamel paint of approved shade; dust, damp & vermin proof powder coated; having hinged door and compartmental arrangement for each equipment & busbar chamber on the top of the panel; having provision for cable/ conduit entry, earthing studs as per specification mentioned below duly factory wired conforming to the relevant ISS and as per special conditions of contract making good the damages caused complete as per the direction of Engineer-in-charge. All MCCB shall confirm to IEC- 60947 and IS-13947. MCCB shall comply with the isolation function requirement of IEC-60947-2 section 7.1.2 to be marked as suitable for isolation / disconnection to facilitate safety of person in use. All MCCB have ics=100% icu and the overload setting should be from 0.7 to 1 times of Ir for thermal magenetic release and for microprocessor release the overload Settings: 0.4 to 1 times of Ir. Manually closing mechanism should be accommodated in a Moulded housing of robust and vermin-proof construction. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open) . The tripping devices shall be ambient temperature compensated type. The insulating case shall be made of high strength heat resistant and flame retardant thermosetting insulating material.
-
-
-
Main Distribution Board
incoming :
Busbar : 1 SET, 4Nos 1300 Amp Copper Strips. (CD=1.25A/sqmm)
1 Set of LED type RYB phase indicating lamps with control fuses & 1no multi function meter with required CT's
Outgoing : 2 No 160A (36kA) 4P Thermal magnetic MCCB with ROM and spreader links for middle common area Main Panel having two fire Lift and spare, 4no 125A 2P (36kA) Thermal magnetic MCCB with ROM and spreader links for both end common area Main Panel, 7nos 80A (25kA) 4P Thermal magnetic MCCB with ROM and spreader links for flat DG Distribution panel & spare. (Make : Legrand/ L&T/ Havells) Complete duly factory wired as per SLD
1
-
400000
DG Distribution Board for flat
incoming :
MCCB: 1 No 80A (16kA) 4P thermal magnetic(TM) with ROM & spreader links.
Outgoing:
Busbar : 1 SET, 4 Nos 100 Amp Copper Strips. (CD=1A/sqmm) MCB : 55 no of 16A 10 kA 2P for each flat ACCL DB
Instruments: 1 Set of 0-500volt Digital voltmeter with inbuilt selector switch, 1 set of LED type RYB phase indicating lamps with control fuses & 1no 0-100A digital ammeter with inbuilt selector switch with required CT's
6
-
150000
Cabling
Supply, laying & testing of following size of PVC insulated, PVC sheathed, round armoured aluminium conductor power cable of 1100 volt grade laid on surface of wall / column / existing RCC / stone ware / masonry cable trench / cable trey / through G.I. pipe / hume pipe as the case may be, including cost of saddles / clamps / markers etc but excluding the cost of G. I. pipe / hume pipe complete with making good the damages caused and returning the balance unused cables to stores as required and as per direction of Engineer-in-charge.
-
-
-
3 &1/2c x 400 Sq. mm Aluminum armoured cable.
600
-
2114
3 &1/2c x 95 Sq. mm Aluminum armoured cable.
100
-
681
3 &1/2c x 50 Sq. mm Aluminum armoured cable.
100
-
454
3 &1/2c x 25 Sq. mm Aluminum armoured cable.
300
-
288
Internal wiring
Supply of all required materials, installation, testing and commissioning company made board of approved make on the wall and making good to all damages caused and complete with all respect as per direction of Engineer-in-charge. (Make - Legrand/ ABB/ L&T/ Seamens/ Hager)
Distribution Board (4 way SPN metal double door DB)
incoming/outgoing :
ACCL : 1 no 600 Watt (30A/3.0A)
288
-
3000
Recessed wiring to submain in 2 x 2.5 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in required dia non-metalic heavy duty flexible conduit 1.6 mm thick alongwith 1 x 1.5sq.mm FR PVC insulated single core multistrand copper conductor as earth wire.(Makeof wire Finolex/ L&T/ Anchor/ Havels/ V Guard)
21600
-
120
PART-B for 2 BHK (Front side & Rear side)
-
-
-
Supply of 320 KVA, 415 Volts DG Set comprising of Cummins make engine model QSL9-G15 developing 399BHP and 320 KVA Stamford make alternator mounted on a common base , complete with:
Fuel tank
Battery and leads
Residencial silencer
AMF control Panel
First fill of lube oil and colant
AVM pads
Acoustic Enclosure
2
-
3050000
Intallation & commissioning with civil foundation for 320.0 kVA DG Set, 4 nos earthing, unloading & shifting, statutary (Electrical) approval, standard testing, silencer extension as per PCB rule.
2
-
150000
Exhaust piping and insulation.
-
-
-
Supplyinh and fixing of Exhaust extension of 150MM DIA MS Pipe with wall Support including Horizontal Support with MS Steel, SS Below, Thermal Insulation of 50MM Rockwool, Chicken mess, Aluminium Sheet and painting etc.
100
-
4000
DG PANELS
Supply, delivery, installation, testing & commissioning of L.T. indoor floor/ wall mounted type main distributiob board made out of 2 mm thick CR sheet metal cubicle with front side hinges glass door for every meter compartment, the cabinet have a common bus bar, duly acid treated for derusting, primered and painted with 2 coats of enamel paint of approved shade; dust, damp & vermin proof powder coated; having hinged door and compartmental arrangement for each equipment & busbar chamber on the top of the panel; having provision for cable/ conduit entry, earthing studs as per specification mentioned below duly factory wired conforming to the relevant ISS and as per special conditions of contract making good the damages caused complete as per the direction of Engineer-in-charge. All MCCB shall confirm to IEC- 60947 and IS-13947. MCCB shall comply with the isolation function requirement of IEC-60947-2 section 7.1.2 to be marked as suitable for isolation / disconnection to facilitate safety of person in use. All MCCB have ics=100% icu and the overload setting should be from 0.7 to 1 times of Ir for thermal magenetic release and for microprocessor release the overload Settings: 0.4 to 1 times of Ir. Manually closing mechanism should be accommodated in a Moulded housing of robust and vermin-proof construction. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open) . The tripping devices shall be ambient temperature compensated type. The insulating case shall be made of high strength heat resistant and flame retardant thermosetting insulating material.
-
-
-
Main Distribution Board
incoming :
Incomer : ACB : 1 No 800A (50kA) 4P Electronic release MDO. (Make : Legrand/ L&T/ Havells)
Busbar : 1 SET, 4Nos 1000 Amp Copper Strips. (CD=1.25A/sqmm)
1 Set of LED type RYB phase indicating lamps with control fuses & 1no multi function meter with required CT's
Outgoing : 2 No 160A (36kA) 4P Thermal magnetic MCCB with ROM and spreader links for end & middle Lift common area Main Panel and spare, 1 No 125A (36kA) 4P Thermal magnetic MCCB with ROM and spreader links for end Lift common area Main Panel and spare, 5nos 63A (36kA) 4P Thermal magnetic MCCB with ROM and spreader links for flat DG Distribution panel & spare. (Make : Legrand/ L&T/ Havells)
Complete duly factory wired as per SLD
2
-
250000
DG Distribution Board for flat
incoming :
MCCB: 1 No 63A (16kA) 4P thermal magnetic(TM) with ROM & spreader links.
Busbar : 1 SET, 4Nos 80 Amp Copper Strips. (CD=1.25A/sqmm)
MCB : 60 no of 16A 10 kA 2P for each flat ACCL DB
Instruments: 1 Set of LED type RYB phase indicating lamps with control fuses & 1no multi function meter with required CT's
8
-
150000
Cabling :
Supply, laying & testing of following size of PVC insulated, PVC sheathed, round armoured aluminium conductor power cable of 1100 volt grade laid on surface of wall / column / existing RCC / stone ware / masonry cable trench / cable trey / through G.I. pipe / hume pipe as the case may be, including cost of saddles / clamps / markers etc but excluding the cost of G. I. pipe / hume pipe complete with making good the damages caused and returning the balance unused cables to stores as required and as per direction of Engineer-in-charge.
-
-
-
3 &1/2c x 400 Sq. mm Aluminum armoured cable.
400
-
2114
3 &1/2c x 95 Sq. mm Aluminum armoured cable.
100
-
681
3 &1/2c x 50 Sq. mm Aluminum armoured cable.
100
-
454
3 &1/2c x 25 Sq. mm Aluminum armoured cable.
400
-
288
Internal wiring
-
-
-
Supply of all required materials, installation, testing and commissioning company made board of approved make on the wall and making good to all damages caused and complete with all respect as per direction of Engineer-in-charge. (Make - Legrand/ ABB/ L&T/ Seamens/ Hager)
Distribution Board (4 way SPN metal double door DB)
incoming/outgoing :
ACCL : 1 no 500 Watt (30A/2.5A)
416
-
3000
Recessed wiring to submain in 2 x 2.5 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in required dia non-metalic heavy duty flexible conduit 1.6 mm thick alongwith 1 x 1.5sq.mm FR PVC insulated single core multistrand copper conductor as earth wire.(Makeof wire Finolex/ L&T/ Anchor/ Havels/ V Guard)
43200
-
120
PART-C (For Community Hall)
-
-
-
Supply of 62.5 KVA, 415 Volts (3-Phase) DG Set comprising of Cummins make engine model 4BTAA3.3-G11 developing 84 BHP and 62.5 KVA Stamford make alternator mounted on a common base, complete with:
Fuel tank
Battery and leads
Residencial silencer
AMF control Panel
First fill of lube oil and colant
AVM pads
Acoustic Enclosure
1
-
880000
Intallation & commissioning with civil foundation for 62.5 kVA DG Set, 4 nos earthing, unloading & shifting, statutary (Electrical) approval, standard testing, silencer extension as per PCB rule.
1
-
100000
Exhaust piping and insulation.
-
-
-
Supplyinh and fixing of Exhaust extension of 150MM DIA MS Pipe with wall Support including Horizontal Support with MS Steel, SS Below, Thermal Insulation of 50MM Rockwool, Chicken mess, Aluminium Sheet and painting etc.
50
-
4000
Cabling :
Supply, laying & testing of following size of PVC insulated, PVC sheathed, round armoured aluminium conductor power cable of 1100 volt grade laid on surface of wall / column / existing RCC / stone ware / masonry cable trench / cable trey / through G.I. pipe / hume pipe as the case may be, including cost of saddles / clamps / markers etc but excluding the cost of G. I. pipe / hume pipe complete with making good the damages caused and returning the balance unused cables to stores as required and as per direction of Engineer-in-charge.
-
-
-
3 &1/2c x 25 Sq. mm Aluminum armoured cable.
120
-
288
PART-D (For Others)
-
-
-
Supply of 160 KVA, 415 Volts (3-Phase) DG Set comprising of Cummins make engine model QSB5.9-G2 developing 206 BHP and 160 KVA Stamford make alternator mounted on a common base , complete with:
Fuel tank
Battery and leads
Residencial silencer
AMF control Panel
First fill of lube oil and colant
AVM pads
Acoustic Enclosure
1
-
1750000
Intallation & commissioning with civil foundation for 160.0 kVA DG Set, 4 nos earthing, unloading & shifting, statutary (Electrical) approval, standard testing, silencer extension as per PCB rule.
1
-
100000
Exhaust piping and insulation.
-
-
-
Supplyinh and fixing of Exhaust extension of 150MM DIA MS Pipe with wall Support including Horizontal Support with MS Steel, SS Below, Thermal Insulation of 50MM Rockwool, Chicken mess, Aluminium Sheet and painting etc.
50
-
4000
Cabling :
Supply, laying & testing of following size of PVC insulated, PVC sheathed, round armoured aluminium conductor power cable of 1100 volt grade laid on surface of wall / column / existing RCC / stone ware / masonry cable trench / cable trey / throu
-
-
-
3 &1/2c x 35 Sq. mm Aluminum armoured cable.
100
-
379
4c x 16 Sq. mm Aluminum armoured cable.
200
-
248
4c x 10 Sq. mm Aluminum armoured cable.
100
-
234
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements