Department Of Power Tender
View complete overview of Nagaland Department Of Power Tender
Costs
EMD
₹ 20,00,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2018_DP_125_1Bid Award Id
ViewTender No
NO.CEL/DanR/DOPN/IPDS/PKG8Tender Authority
Department Of Power ViewPurchaser Address
-Website
http://https://powermin.nic.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
33KV SIDE EQUIPMENT
-
-
-
33 KV SF6 circuit breaker /Autorecloser (out-door type ) complete with control cabinet, communication capabilities for remote control and compatible to DSA/SCADA, maintenance free DC battery with charger, mounting structure etc.
4
-
-
33kv, single pole, single phase,outdoor type with ratio 400-200A/1-1A, 15 VA burden, class accuracy 0.5 Line CT for metering complete with bimetallic terminals, weather proof secondary terminals including all accessories.
6
-
-
33kv, single pole, single phase,outdoor type with ratio 200-100A/1-1A, 15 VA burden, class accuracy 0.5 Transformer CT for metering and TRF differential protection complete with bimetallic terminals, weather proof secondary terminals, including all accessories.
6
-
-
Outdoor, single pole Potential transformer with voltage ratio (33/√3 kV)/(110V/√3), output 100 VA burden with class accuracy 0.5 complete with bimetallic terminals, weather proof secondary terminals, including all accessories.
6
-
-
Isolator suitable for a system voltage of 33 KV, rated current of 400 A and fault withstand of 16 KA for 1 sec and shall be manual operated, single break type, triple pole, outdoor type, pole mounted suitable for horizontal mounting with EARTH SWITCH
2
-
-
Isolator suitable for a system voltage of 33 KV, rated current of 400 A and fault withstand of 16 KA for 1 sec and shall be manual operated, single break type, triple pole, outdoor type,pole mounted suitable for horizontal mounting WITHOUT EARTH SWITCH
5
-
-
33KV, 400A, 3-ph, Gang switch (Rocking Type Air Break Isolator) along with support insulators operating mechanism, Base Channel down Pipe, terminal connectors and other accessories complete as per IS : 9921 (Pt. I to IV) or its latest amendment and TS Vol II - for 33/0.4KV Station Transformer
1
-
-
33 KV Drop Out fuse of rated current 100 A/ 200 A/400A, complete with fuse carrier assembly, fuse base & tube and mounting arrangement as per IS:9385 (Part-I to III) as amended from time to time and tech spec Vol-II. For 33/0.4 KVStation Transformer
1
-
-
30kV, 10 kA single pole, class2,station type, heavy duty,
Lightning Arrestor complete with suitable bimetallic connectors. for ACSR wire connections, parallel groove clamps, weather proof secondary terminals, with-out counter, including all accessories.
12
-
-
Discharge rod with clamp having screw type arrangment for
fixing tightly on conductor(ASCR) for panther with boalt nut and saddle for earthwire. The operating rod fixed with clamp shall be made of telestone fiber glass tube suitable for 33/11 KV
2
-
-
11KV SIDE EQUIPMENT
-
-
-
11 KV Auto Recloser (out-door type) in-coming and out-going feeders complete with control cabinet, communication capabilities for remote control and compatible to DSA/SCADA), mounting structure etc.
6
-
-
11kv, single pole, single phase, outdoor type with ratio 600-300A/1-1A, 15 VA burden,PS class accuracy 0.5 Transformer CT for metering and differnetial protection complete with bimetallic terminals, weather proof secondary terminals, including all accessories.
6
-
-
11kv, single pole, single phase,outdoor type with ratio 600-300A/1-1A, 15 VA burden,PS class accuracy 0.5 Neutral CT for protection complete with bimetallic terminals, weather proof secondary terminals, including all accessories.
2
-
-
11kv, single pole, single phase,outdoor type with ratio 200-100/1A, 15 VA burden, class accuracy 0.5 Line CT for metering complete with bimetallic terminals, weather proof secondary terminals, including all accessories.
12
-
-
Outdoor, single pole Potential transformer with voltage ratio (11/√3 kV)/ (110V/√3), output 100 VA burden with class accuracy 0.5 complete with bimetallic terminals, weather proof secondary terminals, including all accessories.
6
-
-
Isolator suitable for a system voltage of 11 KV, rated current of 800 A and fault withstand of 16 KA for 1 sec and shall be manual operated, single break type, triple pole, outdoor type,pole mounted suitable for horizontal mounting WITHOUT EARTH SWITCH
3
-
-
Isolator suitable for a system voltage of 11 KV, rated current of 800 A and fault withstand of 16 KA for 1 sec and shall be manual operated, single break type, triple pole, outdoor type,pole mounted suitable for horizontal mounting WITH EARTH SWITCH (for Line)
4
-
-
9kV, 10 kA single pole, class 2, station type, heavy duty, Lightning Arrestor complete with suitable bimetallic connectors for ACSR wire connections, parallel groove clamps, weather proof secondary terminals, with-out counter, including all accessories.
12
-
-
INSULATORS
-
-
-
33 KV Pin/Post Insulators with Pin
2
-
-
11 KV Pin/Post insulators with Pin
2
-
-
Disc Insulators (Polymer) 70 KN BS type
2
-
-
Steel Fabricated items, additional requirement.
3
-
-
TRF- CONTROL RELAY PANEL
-
-
-
Outdoor type, front operated floor mounted, free standing, relay control panel.Auxillary voltage 240V AC ,1 Phase from stn. Trf. The panel will have the following features and items (Separate for Individual Transformer)
2
-
-
Protection Relays
-
-
-
1No. Transformer Differential Relay - Static type
-
-
-
1 No. Standby E/F Relay
-
-
-
1 No. Master Trip Relay
-
-
-
1 No. Aux.Relay for Transformer
-
-
-
1 No. DC Supervision relay
-
-
-
Metering
-
-
-
4 Nos. Trivector Meter Acc. Cl-0.5 Accuracy (Secure Make AMR, DLMS complaint Meters)
-
-
-
Indication Lamps
-
-
-
Phase Indication Lamps R,Y,B 110V AC
-
-
-
Breaker On/Off Lamps
-
-
-
Controls
-
-
-
Breaker Control Switch(TNC)
-
-
-
Control MCB
-
-
-
Space Heater with Thermostate & Toggle Switch
-
-
-
Emergency Push Button
-
-
-
3 Pin Socket 230V, 6A
-
-
-
CFL
-
-
-
Door Switch 2A, 1C/O
-
-
-
Hooter/ Buzzer
-
-
-
Annunciator-6W
-
-
-
Metering Panel for 33KV and 11KV ARCBs.
1
-
-
OVERHEAD CONDUCTOR
-
-
-
PANTHER ACSR Conductor
300
-
-
40mm dia GI pipe
100
-
-
80mm dia GI pipe
100
-
-
Control Cables
-
-
-
Control cable, 5 C X 2.5 mm sq.
600
-
-
Control cable, 10 C X 2.5 mm sq.
600
-
-
Control cable, 12 C X 2.5 mm sq.
600
-
-
HT Power Cables
-
-
-
33 KV 1 x C 400sqmm XLPE Al. (Only for connecting 33kV Auto recloser to Power Transformer Primary and from Incomer 33KV feeder to Bus)
1100
-
-
11 KV 1 x C 630 sqmm XLPE Al.(Only for Connecting Secondary of Power Transformer to 11kV Incomer Auto Recloser and for 11KV Bus to Outgoing Feeders - 4 Nos)
500
-
-
11 KV 3C X185 sq. mm. XLPE Al. (For DT)
180
-
-
LT XLPE Power Cables
-
-
-
1.1kV XLPE Armoured Power cable: 2 x C, 25 sqmm
100
-
-
1.1kV XLPE Armoured Power cable: 3½ x C, 35 sqmm
50
-
-
1.1kV XLPE Armoured Power cable: 3½ x C, 70 sqmm
50
-
-
1.1kV XLPE Armoured Power cable: 3.5 C X 95 sqmm
50
-
-
1.1kV XLPE Armoured Power cable: 3.5C X 120 sqmm
50
-
-
1.1kV XLPE Unarmoured Power cable: 1C x 25 sqmm
15
-
-
1.1kV XLPE Unarmoured Power cable: 1C x 70 sqmm
150
-
-
Termination Kits
-
-
-
33 KV Termination Kit for 1 C X 400 mm sq. XLPE cable( for connecting 33kV Auto recloser to Power Transformer Primary and for Incomer 33KV feeder to Bus)
32
-
-
11 KV Termination Kit for 1 C X 630 mm sq. XLPE cable ( for Connecting Secondary of Power Transformer to 11kV Incomer Auto Reclosers and for Autorecloser to outgoing feeder - 4 outgoing 11KV Feeders).
30
-
-
11 KV Termination Kit for 1 C X 185 mm sq. XLPE cable ( for DTs etc).
10
-
-
Earthing & Lightning Protection
-
-
-
3.0 mtr 40mm dia GI Pipe Earthing
50
-
-
Copper Plate Earthing for Transformer Neutral
(600x600x3.15)
10
-
-
Earthing Strip
-
-
-
75X6mm GI Strip
700
-
-
50X10mm GI Strip
400
-
-
50X6mm GI Strip
400
-
-
25X3mm GI Strip
200
-
-
50X6mm Copper Strip
200
-
-
CT & PT Jnc Box (12 way)
20
-
-
Lightining spike
30
-
-
Down conductor for Lightining spike (25x3mm GI Strip)
420
-
-
Communication
-
-
-
For Sub-station
-
-
-
Industrial grade Router with adequate Ports/ slots for connectivity with 3G SIM cards, OFC backbone cables, RS-232/485 on Modbus protocol for Energy Meters, and Ethernet Port for Reclosers ( IEC 104 Protocol). The router shall be able to establish mulitple connections(redundant) with the control room for SCADA system
1
-
-
Cat 6 e Ethernet cable / patch cords with connectors of reputed make
1
-
-
Computer System / laptop including UPS, Printers computer furniture for local configuration, manitenence and operations
1
-
-
any other networking accesory
1
-
-
Control Room Auxiiaries
-
-
-
24V, 65AH, Lead Acid type Battery Set at 10 Hr Discharge Rate consisting of 11 Nos., each of 2.2V Cell having float level indicators, terminal connectors along with suitable wooden rack, required quantity of acid, distilled water & all other accessories and connectors required for installation, testing & commissioning as per technical specifications.
1
-
-
Transistorised Battery Charger Set with full wave rectification, 1-ph, 200/240V, 50Hz Input Voltage for charging 24V, 65AH Battery along with required cable, connectors etc. for conection with 24 V 64AH Battery Set & 220V AC Source and 24V DCDB
1
-
-
415 Volt LTAC Panel as per specification with 250A TPN MCCB as incomer ,2x 100A MCCB,2x32A TP ,5x16A TP, 4x16A DP,1x32A DP MCB.
1
-
-
24V DCDB as per TS & the Electrical Layout
1
-
-
Supply, of following Transformers
-
-
-
33/11KV, 10 MVA Oil Type Transformer
2
-
-
33/0.433KV, 63KVA, oil type Station transformer
1
-
-
Optional Items
-
-
-
Relay/Meter Monitoring Software
1
-
-
Evaluation Notes How It Works ?