Technical Education Department Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Technical Education Department - DTE Tender
Eprocure
Opening Date14 Oct 2024
Closing Date31 Oct 2024
Tender AmountRefer Documents
Costs
EMD
₹ 1,50,000Document Cost
₹ 2,360Tender Fee
₹ 500
Summary
Supply Installation Testing And Commissioning Of Hvac System
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_DTEDM_1115317_1Tender No
COEP TECH/BWC/LIBCOMPIT/24/10Tender Authority
Technical Education Department ViewPurchaser Address
-Website
http://http://www.dtemaharashtra.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Supply Installation Testing and Commissioning of HVAC System for Library and Computer IT Building at COEP Tech Pune
BOQ Items
Supplying, erecting, testing and commissioning of 16HP, VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100% capacity at 47° C, non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00, modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete.
2
-
-
Supplying, erecting, testing and commissioning of 18HP, VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100% capacity at 47° C, non stop cooling even at 56° C and coefficient of performance (COP) 3.00 to 4.00, modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/ digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete.
2
-
-
Supplying, erecting, testing and commissioning of 20HP, VRF/VRV air conditioning system out door unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100% capacity at 47° C, non stop cooling even at 56°C and coefficient of performance (COP) 3.00 to 4.00, modular type vertical hot air discharge suitable for longer piping range upto 1000 metre operation in cooling mode with inverter/digital VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete.
7
-
-
Supply, installation, testing and commissioning of VRF/VRV based Hi-wall type indoor unit (IDU) of nominal cooling capacity 1.8TR (594 cfm) to 2.2TR (655 cfm) having EER as per BEE standards and specifications with multiple speed evaporator fan with motor, copper tube aluminium fin evaporator coil, washable air filter, insulated drain tray, expansion device, cordless remote control with necessary controls, with 3-core copper flexible cord of required length and electrical terminal to receive power supply, etc. IDU shall have anticorrosive coating suitable for coastal area. Unit shall be suitable for indoor wall mounting, having an electronic control console, provided with suitable mounting brackets with any additional refrigerant and oil charge as per the requirement during installation, connected to the system complete.
18
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact/standard size) of nominal cooling capacity 1.0TR ( 441 cfm ) to 1.3TR (512 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for costal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
3
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact/standard size) of nominal cooling capacity 2.0TR (618 cfm) to 2.3TR (671 cfm) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for costal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
8
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact / standard size) of nominal cooling capacity 3.0TR (1100 cfm) to 3.2TR (1165 cfm) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for costal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation
6
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette room/indoor unit (IDU-compact / standard size) of nominal cooling capacity 3.3TR (1165 cfm) to 4.0TR (1218 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for costal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
11
-
-
Supply, installation, testing and commissioning of VRV / VRF based ductable type, high static room/indoor unit (IDU) having nominal cooling capacity of 4.1TR (1640 cfm) to 5.0TR (2000 cfm) having EER as per BEE standards and specifications with evaporator fan with motor, copper tube aluminium fin evaporator coil, washable air filter, insulated drain tray, in built drain pump, expansion device, cordless remote control with necessary controls and electrical terminal to receive power supply, etc. having anti-corrosive coating suitable for costal area and decorative slim dimension suitable for ceiling suspended arrangement with an electronic control console and any additional refrigerant and oil charge as per requirement during installation complete.
18
-
-
Supply, installation, testing and commissioning of VRV / VRF based ceiling suspended 8.0TR (6600 cfm) to 10.0TR (8200 cfm) Treated Fresh Air (TFA) (5380 cfm) room/IDU with evaporator fan with motor, copper tube, aluminium fin evaporator coil, washable air filter, insulated drain tray, in built drain pump, expansion device, cordless remote control with necessary controls and electrical terminal to receive power . having anti-corrosive coating suitable for costal area with decorative slim dimension suitable ceiling suspended arrangement and an electronic control console with any additional refrigerant and oil charge as per requirement during installation complete.
2
-
-
Supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 41.3mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
125
-
-
Supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 34.9mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
110
-
-
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 28.6mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
170
-
-
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 22.2mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiation with OEM standards of VRV/VRF air conditioning system complete.
140
-
-
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 19.1mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
220
-
-
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 15.9 mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
790
-
-
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 12.7mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
1603
-
-
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 9.5 mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
760
-
-
supplying, laying/fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 6.4mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
60
-
-
Supplying and installation of high pressure grade required size copper connection Y or T- Joints/refnut complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV/VRF air conditioning system
66
-
-
Supply, Installation, Testing & Commissioning of Drain Piping shall be HARD PVC PIPE . 25mm dia.Drain Piping shall be insulated 13mm Armaflex rubber nitrile closed cell insulation. The drain shall be released as per tender layout. 'U'-Traps to be provided at each individual units. G.I Threaded rod supports with Clevis clamps.
310
-
-
Supply, Installation, Testing & Commissioning of Drain Piping shall be HARD PVC PIPE . 32mm dia.Drain Piping shall be insulated 13mm Armaflex rubber nitrile closed cell insulation. The drain shall be released as per tender layout. 'U'-Traps to be provided at each individual units. G.I Threaded rod supports with Clevis clamps.
320
-
-
Supply, Installation, Testing & Commissioning of Drain Piping shall be HARD PVC PIPE . 50mm dia.Drain Piping shall be insulated 13mm Armaflex rubber nitrile closed cell insulation. The drain shall be released as per tender layout. 'U'-Traps to be provided at each individual units. G.I Threaded rod supports with Clevis clamps.
200
-
-
Supply, Installation, Testing & Commissioning of 3 core,1.5 sqmm, Interconnecting copper shielded control cabling between IDU's & ODU's. The cabling shall be well supported / tied up with the ref line. In PVC conduits of Black colour with Junction boxes required as per the indoor unit locations.
2050
-
-
Supplying, erecting, testing and commissioning of AIR DISTRIBUTION SYSTEM consists of factory fabricated sheet metal ducting. complete tdc flanges, GI slotted channels and GI fully threaded rod supports, gaskets, TDF flange and box sections to be provided Smoke test shall be required for 100% of ductingDuct shall be with all necessary support arrangement.factory fabricated 120 GSM GSS ducting, TDC/TDF flanges, Guide vanes,reinforcement/stiffeners .All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure Class.
24 G - 0 TO 750 mm
1010
-
-
Supplying, erecting, testing and commissioning of AIR DISTRIBUTION SYSTEM consists of factory fabricated sheet metal ducting. complete tdc flanges, GI slotted channels and GI fully threaded rod supports, gaskets, TDF flange and box sections to be provided Smoke test shall be required for 100% of ductingDuct shall be with all necessary support arrangement.factory fabricated 120 GSM GSS ducting, TDC/TDF flanges, Guide vanes,reinforcement/stiffeners .All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure Class.
22 G - 751mm TO 1250mm
160
-
-
Supplying, erecting, testing and commissioning of AIR DISTRIBUTION SYSTEM consists of factory fabricated sheet metal ducting. complete tdc flanges, GI slotted channels and GI fully threaded rod supports, gaskets, TDF flange and box sections to be provided Smoke test shall be required for 100% of ductingDuct shall be with all necessary support arrangement.factory fabricated 120 GSM GSS ducting, TDC/TDF flanges, Guide vanes,reinforcement/stiffeners .All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure Class.
20 G - 1251mm TO 2100mm
85
-
-
Providing adhesive thermal insulation for supply return air duct with 19mm nitrile rubber insulation having R-value as per the prevailing provisions in ECBC2007
67
-
-
Providing and applying of acoustic insulation for air ducts with 25mm thick, 48kg/cu.m fiber glass faced with RP tissue and covered with 26SWG perforated aluminium sheets complete.
78
-
-
supplying and installing of collar damper of galvanised iron material of upto 120microns for anti corrosive resistance for supply air grill of suitable size
18
-
-
Supplying and erecting aluminium powder coated linear grill of suitable size for width length without collar dampers having matching colour with the existing false ceiling and suitable for deflection of 15/30/45°- 100/150/200/250mm width Grill.
56
-
-
UNDERDECK INSULATION -
Supply and installation of thermal insulation for underdeck application under the RCC slab. Insulation shall be anti-microbial closed cell Elastomeric Nitrile Rubber with thermal conductivity not exceeding 0.032 W/moK at an average temperature of 25oC. Density of the material shall be 25-30 Kg/m3 and shall be single layer up to 19mm thickness in the factory. The insulation material shall be fire rated for Class O as per BS-476 Part 6 with non-toxic smoke and shall be provided with flame laminated aluminum foil. Quoted price shall be inclusive of adhesive, tapes, dash fasteners, etc. as per specification.
19 mm thick insulation.
1950
-
-
Supply, installation, testing and comissioning of Circular 100 mm Dia Disc Valve suitable for Toilet Exhaust
160
-
-
Supply, installation, testing and comissioning of Circular 100 mm Dia FLEXIBLE DUCT suitable for Disc valve to duct cannection.
450
-
-
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
10
-
-
Supplying, erecting, testing and commissioning centralised programmable remote control panel (HMI) touch manager controls minimum 16 system of 64 ODU's can be controlled and up to 992 IDU's can be individually mounted and controlled indoor units having colour min 200mm size LCD touch panel, yearly schedule, power proportional distribution function, temperature limitation, history function complete erected on wall integrated with provided fire alarm system
1
-
-
Supply, fabrication, installation an testing of flexible canvass connections constructed between ductable unit/dampers/ducting of suitable size with fire resist flexible double canvas sleeve complete
42
-
-
Supply and installation of readymade 16SWG, GI perforated TYPE cable tray of 100mm Width size of 75mm depth unless otherwise specified including readymade accessories e.g. Vertical, horizontal bends, tee's, right-angle etc. Vendor to consider readymade GI clamps / supports for fixing the cable trays. Along with Supply and installation of readymade GI tray covers 16/18 SWG including readymade shape of Vertical & Horizontal Bend, Tee's, Right angles etc. to suit tray for all vertical & Horizontal runs.
60
-
-
Supply and installation of readymade 16SWG, GI perforated TYPE cable tray of 150mm Width size of 75mm depth unless otherwise specified including readymade accessories e.g. Vertical, horizontal bends, tee's, right-angle etc. Vendor to consider readymade GI clamps / supports for fixing the cable trays. Along with Supply and installation of readymade GI tray covers 16/18 SWG including readymade shape of Vertical & Horizontal Bend, Tee's, Right angles etc. to suit tray for all vertical & Horizontal runs.
20
-
-
Supply and installation of readymade 16SWG, GI perforated TYPE cable tray of 200mm Width size of 75mm depth unless otherwise specified including readymade accessories e.g. Vertical, horizontal bends, tee's, right-angle etc. Vendor to consider readymade GI clamps / supports for fixing the cable trays. Along with Supply and installation of readymade GI tray covers 16/18 SWG including readymade shape of Vertical & Horizontal Bend, Tee's, Right angles etc. to suit tray for all vertical & Horizontal runs.
30
-
-
Supply and installation of readymade 16SWG, GI perforated TYPE cable tray of 300mm Width size of 75mm depth unless otherwise specified including readymade accessories e.g. Vertical, horizontal bends, tee's, right-angle etc. Vendor to consider readymade GI clamps / supports for fixing the cable trays. Along with Supply and installation of readymade GI tray covers 16/18 SWG including readymade shape of Vertical & Horizontal Bend, Tee's, Right angles etc. to suit tray for all vertical & Horizontal runs.
160
-
-
Wall mounted propeller fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, Ggravity louver, Switch socket will be provided at a distance of 1 M from the fan.
150 CFM Wall mounted propeller-
28
-
-
Axial fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, GI gravity louver, outlet cowl piece with protective wire mesh etc. . Power cabling from this switch socket to fans shall be included in the unit rates.Capacities shall be as under. Fans Are AMCA Certified for the sound and Air
All necessory supports and accessories, vibration /spring isolator, pads etc shall be included
Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans
Motor shall be - IE3 motor (As per IS 12615) Mechanical and motor efficiency shall be 65%
All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor
Lift Well Pressurization Fan @ Terrace floor
Capacity- 8000 cfm External Static pressure -32-40mm wc
2
-
-
Axial fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, GI gravity louver, outlet cowl piece with protective wire mesh etc. . Power cabling from this switch socket to fans shall be included in the unit rates.Capacities shall be as under.Fans Are AMCA Certified for the sound and Air
All necessory supports and accessories, vibration /spring isolator, pads etc shall be included
Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans
Motor shall be - IE3 motor (As per IS 12615) Mechanical and motor efficiency shall be 65%
All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor
Pump Room @ Basement Capacity- 3000 cfm External Static pressure -25mm wc
1
-
-
Axial fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, GI gravity louver, outlet cowl piece with protective wire mesh etc. Power cabling from this switch socket to fans shall be included in the unit rates.Capacities shall be as under. Fans Are AMCA Certified for the sound and Air All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Motor shall be - IE3 motor (As per IS 12615)
Mechanical and motor efficiency shall be 65% All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C Smoke Extraction fans motor shall be Fire rated motor
Electrical Panel room @ Basement Capacity- 1600 cfm External Static pressure -20mm wc
1
-
-
Axial fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, GI with protective wire mesh etc. Power cabling from this switch socket to fans shall be included in the unit rates.Capacities shall be as under.All necessory supports and accessories, vibration /spring isolator, pads etc shall be included Mechanical and motor efficiency shall be 65%
Toilet Exhaust @ Ground Floor To Seventh Floor.
Capacity- 1100 cfm External Static pressure -10mm wc
16
-
-
Axial fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, GI gravity louver, outlet cowl piece with protective wire mesh etc. . Power cabling from this switch socket to fans shall be included in the unit rates.Capacities shall be as under.
Fans Are AMCA Certified for the sound and Air
All necessory supports and accessories, vibration /spring isolator, pads etc shall be included
Pressure relief dampers to be considered for Stairwell & Lift well pressurisation fans
Motor shall be - IE3 motor (As per IS 12615)
Mechanical and motor efficiency shall be 65%
All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C
Smoke Extraction fans motor shall be Fire rated motor
Lift Well Pressurization Fan @ Terrace floor
Capacity- 8000 cfm External Static pressure -30- 35mm wc
2
-
-
Axial fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, with protective wire mesh etc. Power cabling from this switch socket to fans shall be included in the unit rates.Capacities shall be as under.
Fans Are AMCA Certified for the sound and Air
All necessory supports and accessories, vibration /spring isolator, pads etc shall be included
Motor shall be - IE3 motor (As per IS 12615) vith VFD .
Mechanical and motor efficiency shall be 65%
All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C
Smoke Extraction fans motor shall be Fire rated motor
Ventilation Compactor Room @ Basement Capacity- 18000cfm For Exhaust
External Static pressure -40mm wc
1
-
-
Axial fans ( with necessory supports arrangement) complete with 1Ph/3 Ph motor, frame for fixing, impeller, with protective wire mesh etc. Power cabling from this switch socket to fans shall be included in the unit rates.Capacities shall be as under.
Fans Are AMCA Certified for the sound and Air
All necessory supports and accessories, vibration /spring isolator, pads etc shall be included
Motor shall be - IE3 motor (As per IS 12615) vith VFD .
Mechanical and motor efficiency shall be 65%
All basement fans and smoke extraction fans ,emergency fans are fire rated fans for 2 hours at 250 deg C
Smoke Extraction fans motor shall be Fire rated motor
Ventilation Compactor Room @ Basement Capacity- 18000cfm For Supply
External Static pressure -40mm wc
1
-
-
RH Control Heater duct type.
Supplying, erecting, testing and commissioning of RH Control Heater duct type 2.0 Kw, Disply remot control , with sencer.
2
-
-
Frame Work, Supply, fabrication and installation of MS base frame for outdoor,units complete with painting, vibration isolation pads, support hangers,brackets, etc. - Platform / Floor Mounting / Double Decker Type. 14 HP TO 20 HP VRV ODU
12
-
-
Frame Work, Supply, fabrication and installation of MS base frame for outdoor,units complete with painting, vibration isolation pads, support hangers,brackets, etc. - Platform / Floor Mounting / Double Decker Type. 06HP TO 12HP VRV ODU
2
-
-
Gas Charging - R410A.
Supply ,installation and testing for R 410A Gas in system.
208
-
-
Supplying, erecting & terminating FR XLPE insulated, galvanised steel wire armoured (round) cable 1100 V, 4 core 6 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
130
-
-
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
120
-
-
Supplying, erecting, testing and commissioning of flat flexible 3 core 2.5 sq.mm PVC sheathed submersible type copper cable suitably clamped at fixed intervals with column pipe assembly complete.
178
-
-
Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for 4 pole incoming 400A, 12 ways 4 pole outgoing, up to 100A MCCBs on iron frame, as per specification no. SW-MCCBPB. (Excluding MCCBs)
1
-
-
Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-MCCB
1
-
-
Supplying, fixing and commissioning 4 pole RCBO 32/40A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCBO.
20
-
-
Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for 4 pole incoming 250A, 8 ways 4 pole outgoing, up to 100A MCCBs on iron frame, as per specification no SW-MCCBPB. (Excluding MCCBs)
1
-
-
Providing & erecting 3 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB
1
-
-
Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for 4 pole incoming 250A, 6 ways 4 pole outgoing, up to 100A MCCBs on iron frame, as per specification no SW-MCCBPB. (Excluding MCCBs)
1
-
-
Providing & erecting 3 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-MCCB.
1
-
-
Supply and installation Structural steel Supports MS painted Structural Steel for supports. Two coats of red oxide and enamel paint to be applied.
1000
-
-