Tata Memorial Centre Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Tata Memorial Centre Tender
Machinery and Tools
Eprocure
Opening Date26 Jul 2024
Closing Date14 Aug 2024
Tender Amount₹ 1,17,50,000
Costs
EMD
₹ 2,35,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_TMC_818325_1Bid Award Id
ViewTender No
SmokeExtraction/24-25/07Tender Authority
Tata Memorial Centre ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Minimum 7500 CFM with 25 mm WC SP
1
-
-
Minimum 8500 CFM with 25 mm WC SP
1
-
-
Minimum 9500 CFM with 25 mm WC SP
2
-
-
Minimum 10000 CFM with 25 mm WC SP
2
-
-
Minimum 12500 CFM with 25 mm WC SP
3
-
-
Minimum 10000 CFM with 25 mm WC SP (Fresh Air)
1
-
-
Supply,installation, testing and commissioning of electrical starter panel for smoke exhaust and fresh air fans with appropriate motor, protection circuit breaker, overload relay, control wiring with auto and manual functions potential free contacts to be provided to interlock with local emergency fire panel, Starter panel shall be Comprising of all electrical accessories for smooth operation of fan including suitable starter for thesame. MCB, DOL/Star-delta Starters, neccessary safety controls, RYB indication, ON/OFF indications, start/stop and emergency stop push button. Panel should be with control relay logics for operation of AHU damper, Exhaust fan damper, Exhaust fan and AHU based on input from fire panel.
Makes- Elecrical Panel - Shivam Electricals/ Arrow Engineering / Adarsh Electricals
MCB- LT / Schneider
Starter- LT/ Shneider
RYB Indications - Vaishnoy/ LT
On/Off Indications - Vaishnoy/ LT
-
-
-
Starter 1.5 KW 3PH
2
-
-
Starter 2.2 KW 3PH
5
-
-
Starter 3 KW 3PH
4
-
-
Starter 4 KW 3PH
3
-
-
Starter 5.5KW 3PH
3
-
-
Supply, delivery, Installation & testing of FACTORY FABRICATED Galvanized Sheet (GI) Ducting class VIII with M.S. Angle Flange , turning vanes, with proper duct sealing etc with RTV duct Sealant, complete with supports etc all as per specification. GI sheet make - Jindal, Tata
-
-
-
22 gauge
575
-
-
20 gauge
275
-
-
SITC of motorised combined smoke and fire damper (UL listed, leackage S1 class) complete with control panel and all control wiring with necessary accessories to ensure proper functioning of damper as per standards. Make- Caryaire/Trox/Ravistar/Balaji Airvent.
-
-
-
SITC of Smoke and Fire Damper.
Make- Caryaire/Trox/Ravistar/Balaji Airvent.
48
-
-
SITC of Actuators for above dampers. Make- Belimo/Siemens
70
-
-
SITC of 1100 V a.c. grade FRLS PVC armoured CU cable along with appropriate size of saddles,spacers, glands, lugs etc. complete with terminations in approved manner. Make- Polycab/RRK/Finolex/Caliplast / Century
-
-
-
4 Core x 16 Sqmm CU Cable
80
-
-
4 Core x 10 Sqmm CU Cable
80
-
-
4 Core x 6 Sqmm CU Cable
600
-
-
4 Core x 4 Sqmm CU Cable
300
-
-
2 Core x 1.5 Sqmm CU Cable
1200
-
-
Supply and laying of 2C x 1.5 Sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring and LSZH outer sheath comlete as required. Colour - Red.
Make -Polycab / Caliplast / Century
4950
-
-
Supply,Installation, Testing & Commissioning of addressable, UL listed, Photoelectric smoke detector with Heat element(57Deg C), 0.5% to 2.35% per foot obscuration,loop powered, class A wired, low profile, temper resistant, low quiescent current, 360Deg View LED, Rotary/DIP decimal address setting switch,24V DC(15-32V), suitable for below & above false ceiling, complete with Base, wiring box, In/Out cable glands. Make- Siemens Cerberus FIT / Bosch / Honeywell Esser
140
-
-
SITC of UL listed Conventional Sounder with Strobe having light-emitting diode (LED) strobe technology - thereby having reduced current draw & supporting multi-candela settings (15 | 30 | 75 | 95cd) on a single appliance && having HIGH & LOW audible outputs & two (2) audible settings in each appliance & supporting 85db to 92 dB output levels - UL Listed & FM Approved with back box Make -Siemens Cerberus / Bosch / Honeywell Esser
16
-
-
Supplying, installation, testing and commissioning of micro processor basedintelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2km, network communication card, minimum 320 character graphics/ LCD displaywith touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-upwith 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system ( which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol Bacnet/ Modbus over IP complete as per specifications. MAKE- Siemens Cerberus FIT/ Bosch/Honeywell esser
1
-
-
Supply,Installation, Testing & Commissioning of addressable, UL listed, Manual Call Point, loop powered, class A wired, low profile, temper resistant, low quiescent current, Polling LED, Rotary/DIP decimal address setting switch,24V DC(15-32V), suitable for surface / recess installation, wiring box, In/Out cable glands Make -Siemens Cerberus FIT / Bosch / Honeywell Esser
16
-
-
SITC of Addressable Input-Output control module having monitorable contact input for reporting technical status &/or activating of alarm & having Control output with potential free relay contact for activating alarm devices/fans/HVAC/Lift etc.. & having inbuilt isolation - & having integral LED indicator for indicating Input/Output statuses for alarm/Fault - capable of addressing automatically & supporting 2 wire installation - supporting operating temperature of -25 to 70 degree centigrade with up to 95% relative humidity - having IP65 with housing - conforming to EN 54 standard & LPCB approved with back box
Make -Siemens Cerberus FIT / Bosch / Honeywell Esser
30
-
-
SITC of UL listed and FM approved addressable Intelligent The Thermal (Heat) Detector,HI921 is UL 268 7th Ed. listed and incorporates advanced built-in isolation is an intelligent,addressable multi-criteria detector that incorporates optical and thermal sensors, and uses signals in a neural network to create an intelligent multi-criteria detector (BFC) in AHU Room
Make -Siemens Cerberus / Bosch / Honeywell Esser
16
-
-
SITC of AHU triping Box with 4 change over Relay for AHU, Addressable UL listed and FM approved Intelligent addressable Control Relay Module Class X type [Style 7) Integral single-pole, double- throw (SPDT) relay with 4 Amps at 30VDC with single monitor module with built in dual isolator/ polarity insensitive for monitoring purpose with Tri color LED for status (Green for Normal,Yellow for Faulty and RED for activation)The Single - Input version are each designed to monitor a normally open (N.O) or (N.C) normally closed dry contact .This moduel can be used to Integarte Abort and Manual Release button. Environmental operating conditions for each interface module is 32 deg F ( 0 deg C) to 120 deg F(49 deg C) with a relative humidity of no greater than 95% non-condensing with Back Box (For Control Panel / Tripping for Motorized damper ON/OFF / AHU triping). Exhaust fan Tripping and Motorized damper ON/OFF.
Make -Siemens Cerberus / Bosch / Honeywell Esser
16
-
-
SITC of Addressable UL listed and FM approved Dual Optical Detector Make -Siemens Cerberus / Bosch / Honeywell Esser
16
-
-
SITC of Addressable Duct Smoke Detector with housing, sampling tubes, inbuilt fault isolation module (Short circuit & open circuit) Make -Siemens Cerberus / Bosch / Honeywell Esser
16
-
-
SITC of Differential pressure switch for AHU & exhaust air fan
Make - Greystone
16
-
-
SITC of PVC Trunking
-
-
-
100 mm x 50 mm
100
-
-
50 mm x 50 mm
50
-
-
50 mm x 16 mm
150
-
-
38 mm x 25 mm
50
-
-
Supply and Application of fire retardant coating for Smoke extraction ducts connected as per the specifications. Ducts shall be treated externally with CISBOND FR 802 having fire rating for 2 Hours Conforms BS 476 Part 6 & Part 7, Class 0 and fire propagation Class 1 surface spread of flame & materials, surface burning characteristics as per ASTM E-84 NABL certified & UL 723, pull of adhesion as per ASTM D 4541, Impact resistance as per ASTM 2794, Toxic Content as per ASTM D5184-01. VOC content must be as per IS 101(P-2/Sec-3) 2015. MAKE - CISCHEM, CISBOND, 3M, HILTI/ Pidilite
850
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements