Tata Memorial Centre Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Tata Memorial Centre Tender
Healthcare and Medicine
Electrical and Electronics
Electrical Works
Eprocure
Opening Date5 Sep 2024
Closing Date10 Oct 2024
Tender Amount₹ 3,89,32,600
Costs
EMD
₹ 7,78,652Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_TMC_824675_1Bid Award Id
ViewTender No
ET-62/SITC of HVAC system for CGMP Centre/2024Tender Authority
Tata Memorial Centre ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supplying,Installation, testing and commissioning of Energy Efficient Air cooled Heat Pump System. Hot Water System comprises of high performance semi hermetic scroll/compressor, air cooled condenser. Machine is equipped with microprocessor based control, safety device, digital display unit, electrical panel, inbuilt primary Pump & Clean in place system. Heat Pump shall include all necessary hardware, flexible connection, strainer,accessories along with pressure guages,temperature guages etc. Unit shall be supply with control panel and internal wiring. Note:- foundation require as per manufacturer recommandation is in the scope of contractor.Cost of Witness Test to be borne by Supplier. Test procedure to be followed is as AHRI/ASHRAE/BIS.
5
-
-
... More
Heating Capacity : min 44 KW at ambient 38 Deg C (4W+1S)
-
-
-
... More
No. of Compressors circuit :One
-
-
-
... More
Hot Water Inlet/Outlet Temperature : 50/54 Deg C
-
-
-
... More
Chiller Water Circulating Centrifugal Pumps:- Primary Circulating Supply, installation, testing and commissioning of Vertical in line axial Split Coupled PN 16 centrifugal pumps with CI casing and Bronze/steel Impeller complete with CED coating, externally flushed outside type balanced Mechanical Seal and non overloading motor, as per specifications. Suitable HP, TEFC permanent magnet motor with min. Efficiency IE4, class ‘F’ insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply for each pump. Pump should be provided with motor mounted/Panel mounted IP55 integrated VFD for sensor less/wireless control (2 no's of wireless DPTs should be considered for wireless control across the load). To maintain the redundancy of VSPS(Variable Speed Pumping System), separate Controller must be provided with IP54 protection. Controller should be capable of controlling the two way modulating valve at by-pass line to ensure the minimum flow to the chillers in case of load variation is below the minimum flow required by the Chillers. Controller must have BMS compatibility via Modbus/BACNET connectivity. The controller should stage/destage the variable pumps basis the best efficiency points (BEP) for the optimum efficiency of variable speed pumping system (VSPS). Pump/Panel mounted VFD must display dynamic frequency, amps, volts, flow and head of operating pump. Suction Guide and Triple Duty Valves to be provided by the pump manufacturer for the unit responsibility. Efficiency should more than 70%.Each pump shall comprise of following as required as per specifications.
-
-
-
... More
Electrical by pass starter for pump set.
-
-
-
... More
25 mm thick polyvinyl nitrile rubber insulation duly cladded between aluminium sheets of 0.5mm thickness and properly clamped to pump.
-
-
-
... More
2 Nos. - 150 mm dia type pressure gauges , Suitable size of ball valve for drain and reducer to be consider, fexible connection of 2 nos of sutable size and Connecting chilled water pipe with same insulation for completion of piping network.
-
-
-
... More
Mounting frame with antivibration pads (In case pumps are inline, anti vibration system shall be as per Manufacturers recommendation)
-
-
-
... More
RCC/Cement concrete foundation for the pump unit. (In case pumps are inline, foundation shall be as per Manufacturers recommendation). Also SKID option can be provided based on site condition.
-
-
-
... More
Pump capacity are as under:
-
-
-
... More
For Capacity pump set not less than 240 USGPM of water at 35 mtr head each including the triple duct valve and End Suction guide.
-
-
-
... More
For Capacity pump set not less than 180 USGPM of water at 35 mtr head each including the triple duct valve and End Suction guide.
-
-
-
... More
All Variable Pumps must be provided with BMS enabled Active Performance Management. It must proactively tracks and manages pump performance and provides early diagnostic messaging, web accessible trends and analysis along with automated reports helping end customer to make performance-based decisions and take immediate action to deliver the best possible HVAC pump performance.The cloud based subscription should deliver real-time alerts, such as:
1) Alarms & warnings on excessive vibration
2) Pump in hand
3) Dead head
4) VFD & Motor Overheating.
The connectivity kit supplied by pump supplied should have ability to connect and provide real time data for 5 pumps in a single plant room.
-
-
-
... More
Flow: 240 USGPM, Head: 35 meter. (2W+ 1S)- chilled water
3
-
-
... More
Variable Flow Control Panel with accessories integrartion with Installed for Main Plant
1
-
-
... More
Flow: 180 USGPM, Head: 35 meter. (1W+ 1S)-Hot water
2
-
-
... More
Air Separator
-
-
-
... More
Supply ,Installation , Testing and commissioning of 125 mm dia. with 50 mm thick polystyrene Insulation with 26 gauge Aluminium cladding for chilled water with all assesories and Valves etc as per require.
1
-
-
... More
Supply ,Installation , Testing and commissioning of 100mm dia. with 50 mm thick polystyrene Insulation with 26 gauge Aluminium cladding for Hot water with all assesories and Valves etc as per require.
1
-
-
... More
EXPANSION TANK and Pressurisation Unit:
-
-
-
... More
Supply, Installation, Testing and commissioning of INSULATED PRESSURISED CLOSED WATER EXPANSION TANK suitable for total volume of Water Solution, circuit along with necessary accessories such as along with necessary accessories such as 2 Nos pumps (1working +1standby) with Pressure Transmitter and interconnecting Pipe & Isolating Valve complete with piping connections, safety relief valve, drain valve, pressure gauge, automatic air purging arrangement, etc. With Pressure Transmitter and interconnecting Pipe & Isolating Valve complete with piping connections, safety relief valve, drain valve, pressure gauge, automatic air purging arrangement, etc. The tank shall be pre-charged. Expansion tank Shall be with replaceable heavy duty butyl rubber bladder. The tank connection's should be as per OEM recommendations and 20 mm drain and charging valve connection to facilitate the on site charging of nitrogen in the tank. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The tank must be constructed in accordance with IS-STANDARD 2825-1969 (with lates Revision) and Rated at PN 16. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures required for proper functioning of the complete hydronic system. The tank shall be duly painted in approved colour shall be complete with pressure switches and power distribution and control panel IP55 Control Panel, Pressure Transmitter, interconnecting piping & wiring. (Tank capacity 1000 Litres). Hot Glycol - Water closed vessel pressurized expansion tank as described above shall be duly Insulated with 50 mm thick PUF/Nitrile Rubber insulating material or Equivalent U value Insulating Material and cladded with aluminium Sheet (20G). Note:- Pipe line require for make up to be consider with nearest tank as per directed and as instructed by OIC-ES.
-
-
-
... More
Expansion Tank of 1000 Lts
2
-
-
... More
PRESSURIZATION UNIT: Pump Set with Control Panel and accessories.
2
-
-
... More
Insulated Pipe
-
-
-
... More
Supplying, fixing, testing and commissioning of Chilled water/Hot Water pipes (Pre-Insulated) of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends, tees, MS support etc. But excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. The pipes should be insulated with closed cell puff of density 36±2 Kg/Cum of below mentioned thickness. The Pipe should be workable in the temp. range of -50 Degree Celsius to 120 Degree Celsius. Note:-The Pipes size 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes up to 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
-
-
-
... More
Inside Building/Exposed
-
-
-
... More
125 mm with 50 mm PUF thickness and 26 Gauge AI Cladding
150
-
-
... More
100 mm with 50 mm PUF thickness and 26 Gauge AI Cladding
250
-
-
... More
80 mm with 50 mm PUF thickness and 26 Gauge AI Cladding
180
-
-
... More
65 mm with 36 mm PUF thickness and 26 Gauge AI Cladding
50
-
-
... More
50 mm with 36 mm PUF thickness and 26 Gauge AI Cladding
150
-
-
... More
40 mm with 36 mm PUF thickness and 26 Gauge AI Cladding
90
-
-
... More
32 mm with 36 mm PUF thickness and 26 Gauge AI Cladding
24
-
-
... More
25 mm with 36 mm PUF thickness and 26 Gauge AI Cladding
100
-
-
... More
20 mm with 36 mm PUF thickness and 26 Gauge AI Cladding
50
-
-
... More
Supplying, fixing, testing and commissioning of following diameter valves(PN-16 Rating) (Complete with Flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), strainers (Complete with flanges integral or welded, fittings, Nuts, Bolts & Gaskets (PN-16 Rating), gauges etc for condenser water circulation as per specifications. Insulation thickness of valves should be equal to the Insulation of PUF and AL Cladding of Pipe Section as specified.
-
-
-
... More
Butterfly Valve ( Insulated Valves) with CI body SS disc nitrile sheet & O ring, Complete with fittings, Nuts, Bolts & Gaskets.
-
-
-
... More
100 mm
10
-
-
... More
80 mm
25
-
-
... More
40 mm
2
-
-
... More
32 mm
25
-
-
... More
25 mm
6
-
-
... More
Y - STRAINER ( Insulated) of Ductile CI Body flanged ends with stainless steel strainer for hot water circulation including Insulation thickness of valves should be equal to the Insulation of PUF and AL Cladding of Pipe Section as specified.
-
-
-
... More
80 mm
5
-
-
... More
32 mm
5
-
-
... More
Supply, Installation, Testing and Commissioning of following sizes self-balancing with built in measuring facility with CI Body flange construction with EDPM coated disc with long pitch with protected pipe insulation and PN 16 pressure rating for chilled water/hot water circulation as specified.
-
-
-
... More
80 mm
5
-
-
... More
32 mm
5
-
-
... More
Automatic Air Purge Valves with ball valve for hot water/cold water circulation header as specified and required by Engineer In Charge.
10
-
-
... More
AIR HANDLING UNIT with AHU control Panel
-
-
-
... More
RECIRCULATION TYPE AHU FOR 'CLASSIFIED' SYSTEMS (ISO-7).
-
-
-
... More
SITC of Floor mounted horizontal type EU certified Plug type motor Air Handling unit. Sheet metal sectionalised cabinet type AHU in double skin construction fabricated from Thermal break Aluminium extruded section frame structure. The inner skin 0.8 mm GI & outer skin 0.8mm Precoated GI construction with 43mm thick PUF insulation panel with internal coving and in thermal break construction, etc. complete with necessary frame work for supporting channels, foundation bolts and complete with following section Mixing Section with Extruded Aluminium low leakage type manual supply & return air damper ,Fresh air module with Extruded Aluminium low leakage type manual volume control damper with filter. There will be opening for cable entries for humidity & temp. sensors in mixing chamber section.Pre Filter, Microvee and HEPA Section filter with Flange type filter section with combination of EU-4, EU-5 filters, H-13 ( 0.3µ with 99.997% efficiency) filters at discharge end with Aluminium frame with section. 2 bend GSS/PVC eliminators, Chilled Water Cooling Coil Section With 6 row deep Chilled water coil (20 gauge Cu tubes & 0.2mm thick Al fins with hydrophobic coating) Extruded Aluminium low leakage manual by-pass damper Sandwich type insulated drain pan ,drain pan will be 18G SS 304 construction. 2 Row deep Hot water coil section (20 gauge Cu tubes & 0.2mm thick Al fins with hydrophobic coating) ,DIDW Blower section with Kruger/Greenheck AMCA certified blower with antivibration spring isolators, TEFC fan motor of efficiency class IE-3 or more suitable for 415 volts, 50 Hz, 3 phase IP 55 AC supply suitable for VFD application, & mounted on common base frame ( N+N set working & stand by).PVC Canvas connection at the outlet of the fan. Bleed air module with, Extruded Aluminium low leakage type manual volume control damper. AHU shall be supplied with limit switch, view port, marine lamp and necessory internal control wiring.There will be opening for cable entries for motor in section , unit with Magnehelic Gauges & Necessary Tubing across the filter.There will be access door across every section of AHU.
-
-
-
... More
Starter cum control panel having VFD and by pass starter. VFD should be Auto control on temeprature/RH intregation and required controller with field sensors should be included. Panel shall have Volt meter, Amp meter, VFD by pass selector switch, Motor selector switch, Auto manual change over with on/off/trip indication lamp. manual start stop button.It should have saperate PID controler for 2 way/3 way valve actuator for chw & hot water(for humidity). Combo duct mounted sensors (Temp&RH) with wiring & other aceesories as required for functioning of the same shall be included. cable require from AHU to control panel with cable tray shall be included.
-
-
-
... More
AHU 02 - 13260 CMH (7800 CFM) with 11TR cooling & 26.0 KW Heating capacity @ 160 mm Static Pressure (ISO 7) ( N+N blower-motor set)(Product storage)
1
-
-
... More
AHU 03 -16830 cmh (9900 cfm) with 11TR cooling & 20.0KW Heating capacity @ 160 SP (ISO 7) with 2 motor ( N+N blower-motor set) (Lab 1,2,3)
1
-
-
... More
AHU 04 -10200 cmh (6000 cfm) with 9TR cooling & 12.0KW Heating capacity@ 160 SP (ISO 7) with 2 motor ( N+N blower-motor set) (Lab 4,5)
1
-
-
... More
RECIRCULATION TYPE AHU FOR 'CLASSIFIED' SYSTEMS
-
-
-
... More
SITC of Floor mounted horizontal type EU certified Plug type motor Air Handling unit. Sheet metal sectionalised cabinet type AHU in double skin construction fabricated from Thermal break Aluminium extruded section frame structure. The inner skin 0.8 mm GI & outer skin 0.8mm Precoated GI construction with 43mm thick PUF insulation panel with internal coving and in thermal break construction, etc. complete with necessary frame work for supporting channels, foundation bolts and complete with following section Mixing Section with Extruded Aluminium low leakage type manual supply & return air damper ,Fresh air module with Extruded Aluminium low leakage type manual volume control damper with filter. There will be opening for cable entries for humidity & temp. sensors in mixing chamber section.Pre Filter, Microvee and HEPA Section filter with Flange type filter section with combination of EU-4, EU-5 filters at discharge end with Aluminium frame with section. 2 bend GSS/PVC eliminators, Chilled Water Cooling Coil Section With 6 row deep Chilled water coil (20 gauge Cu tubes & 0.2mm thick Al fins with hydrophobic coating) Extruded Aluminium low leakage manual by-pass damper Sandwich type insulated drain pan ,drain pan will be 18G SS 304 construction. 2 Row deep Hot water coil section (20 gauge Cu tubes & 0.2mm thick Al fins with hydrophobic coating) ,DIDW Blower section with Kruger/Greenheck AMCA certified blower with antivibration spring isolators, TEFC fan motor of efficiency class IE-3 or more suitable for 415 volts, 50 Hz, 3 phase IP 55 AC supply suitable for VFD application, & mounted on common base frame ( N+N set working & stand by).PVC Canvas connection at the outlet of the fan. Bleed air module with, Extruded Aluminium low leakage type manual volume control damper. AHU shall be supplied with limit switch, view port, marine lamp and necessory internal control wiring.There will be opening for cable entries for motor in section , unit with Magnehelic Gauges & Necessary Tubing across the filter.There will be access door across every section of AHU.
-
-
-
... More
Starter cum control panel having VFD and by pass starter. VFD should be Auto control on temeprature/RH intregation and required controller with field sensors should be included. Panel shall have Volt meter, Amp meter, VFD by pass selector switch, Motor selector switch, Auto manual change over with on/off/trip indication lamp. manual start stop button.It should have saperate PID controler for 2 way/3 way valve actuator for chw & hot water(for humidity). Combo duct mounted sensors (Temp&RH) with wiring & other aceesories as required for functioning of the same shall be included.cable require from AHU to control panel with cable tray shall be included.
-
-
-
... More
AHU 01 - 6120 cmh (3600 cfm) with 5.0TR cooling & 7.0KW heating capacity@ 120 SP (ISO 8) with ( N+N blower-motor set)( Scrub area)
1
-
-
... More
AHU 06 - 1700 cmh (1000 cfm)with 2.0TR cooling & 3.0KW heating capacity @ 120 SP (ISO 8) with ( N+N blower-motor set) ( Cryo AHU)
1
-
-
... More
AHU 07 - 11900 cmh (7000 cfm)with 9.0TR cooling & 12.0 KW heating capacity @ 100 SP with ( N+N blower-motor set)-(QA QC area)
1
-
-
... More
Once through type AHU
-
-
-
... More
SITC of Floor mounted horizontal type EU certified Plug type motor Air Handling unit. Sheet metal sectionalised cabinet type AHU in double skin construction fabricated from Thermal break Aluminium extruded section frame structure. The inner skin 0.8 mm GI & outer skin 0.8mm Precoated GI construction with 43mm thick PUF insulation panel with internal coving and in thermal break construction, etc. complete with necessary frame work for supporting channels, foundation bolts and complete with following section Mixing Section with Extruded Aluminium low leakage type manual supply & return air damper ,Fresh air module with Extruded Aluminium low leakage type manual volume control damper with filter. There will be opening for cable entries for humidity & temp. sensors in mixing chamber section.Pre Filter, Microvee and HEPA Section filter with Flange type filter section with combination of EU-4, EU-5 filters, H-13 ( 0.3µ with 99.997% efficiency) filters at discharge end with Aluminium frame with section. 2 bend GSS/PVC eliminators, Chilled Water Cooling Coil Section With 6 row deep Chilled water coil (20 gauge Cu tubes & 0.2mm thick Al fins with hydrophobic coating) Extruded Aluminium low leakage manual by-pass damper Sandwich type insulated drain pan ,drain pan will be 18G SS 304 construction. 2 Row deep Hot water coil section (20 gauge Cu tubes & 0.2mm thick Al fins with hydrophobic coating) ,DIDW Blower section with Kruger/Greenheck AMCA certified blower with antivibration spring isolators, TEFC fan motor of efficiency class IE-3 or more suitable for 415 volts, 50 Hz, 3 phase IP 55 AC supply suitable for VFD application, & mounted on common base frame ( N+N set working & stand by).PVC Canvas connection at the outlet of the fan. Bleed air module with, Extruded Aluminium low leakage type manual volume control damper. AHU shall be supplied with limit switch, view port, marine lamp and necessory internal control wiring.There will be opening for cable entries for motor in section , unit with Magnehelic Gauges & Necessary Tubing across the filter.There will be access door across every section of AHU.
-
-
-
... More
Starter cum control panel having VFD and by pass starter. VFD should be Auto control on temeprature/RH intregation and required controller with field sensors should be included. Panel shall have Volt meter, Amp meter, VFD by pass selector switch, Motor selector switch, Auto manual change over with on/off/trip indication lamp. manual start stop button.It should have saperate PID controler for 2 way/3 way valve actuator for chw & hot water(for humidity). Combo duct mounted sensors (Temp&RH) with wiring & other aceesories as required for functioning of the same shall be included. cable require from AHU to control panel with cable tray shall be included.
-
-
-
... More
AHU 05 -13090 cmh (7700 cfm) with 45TR cooling & 41.0KW Heating capacity@ 160 SP (ISO 7) with ( N+N blower-motor set)(Vector area)
1
-
-
... More
EXHAUST UNIT
-
-
-
... More
Floor mounted horizontal type Exhaust unit. Sheet metal sectionalised cabinet type AHU in double skin construction fabricated from Thermal break Aluminium extruded section frame structure. The inner skin 0.63 mm GI & outer skin 0.63mm Precoated GI construction with 25mm thick PUF insulation panel, suitable 20 micron filter, Blower and motor, exhaust damper, vibration mounts etc with all necessary hardware.
-
-
-
... More
Starter cum control panel having VFD and by pass starter.Panel shall have Volt meter, Amp meter, VFD by pass selector switch, Motor selector switch, Auto manual change over with on/off/trip indication lamp. manual start stop button with wiring & other aceesories as required for functioning of the same shall be included. cable require from AHU to control panel with cable tray shall be included.
-
-
-
... More
VEU 05 - 13430 cmh (7900 cfm) @ 75 SP Motor: (1 W+1S) belt driven type
1
-
-
... More
Chilled water Fan Coil Units
-
-
-
... More
Supply, Installation, Testing and Commissioning of chilled water Ceiling Suspended Fan Coil Unit(Cassette Type/ Hi Wall/ Fan Coil Unit- Ceiling) complete with G.I. casing, with Side/bottom return Air Plenum (5mm PE insulation) or as per site requirement For Hi Wall Units the Casing has to be as per OEM(ABS casing) , Filter box with 8mm Nylon Filter, 3 Row Deep cooling coil with coper tube diameter is 9.52 mm and thickness 0.33 mm with hydrophilic Aluminium fins. Complete coil must be designed for standard working pressure is 1.6 MPa(16bar) and the test pressure is 3.3MPa(33bar). Unit to be provided with SS drain pan with 7mm PE insulation and +200 mm extended. Direct driven fan (three speed) motor, operated on 230 volts, single phase, 50Hz, AC supply. Unit to be provided with Wireless remote. It shall also have RS485 Modbus communication function for BMS control. ESP for the Fan Coil Unit be 80 Pa Minimum( In case of 3 Tr, 4 Tr and 5 Tr) or Else Specified. Units need to BIS/Euro vent Certified. The Cut outs to be made in ceiling as per the Machine for the Servicing purpose/Trap Door should be included in the price.The unit with Infrared Remote Control,micro-controller, drain pump & necessary supporting arrangement with ready made Valve Station complete with butterfly Valves / Gate valves , 2 way Valves with Actuators–Strainer,Pressure cum balancing valves. The entire skid shall be coated with Zinc-chromate primer coating and then painted with enamel paint.Electrical cable connection from MCB/Isolator to Cassette unit shall be done by HVAC contractor. Pipe line require from the main header also to be considered. Minimum Capacity should be as follows:
-
-
-
... More
Each Unit to be provided with Cordless Remote with Temperature display. It has to based on microprocessor operations which can realize intelligent control of room temperature. It shall also have RS485 Modbus communication function or BACnet for BMS control.
-
-
-
... More
1.0TR (cabin and passage area) (Cassette type)
4
-
-
... More
3.0TR (Office area) (Cassette type)
1
-
-
... More
2.0TR (For UPS and Battery room, storage room) (1W+1S) (Hi wall type)
7
-
-
... More
SITC Fabricated chilled water manifold for AHU's as below having CHW/HW requirement for CHW pipe size as below comprising of
1) 8 Rmt of MS ERW 'C' class pipe as per IS 1239 with all necessary fittings i.e. bends, reducers, flanges etc.
2) 5 Nos. Ball valve / Butterfly valve
3) 1 No. 2-modulating control valve
3) 1 No. Balancing Valve
4) 1 No. Y strainer screwed/flanged end.
5) 2 Nos. Pressure Gauges (1 in supply line & 1 in return line)
6) 2 Nos. Temperature Gauges with thermowell (1 in supply line & 1 in return line)
7) 1 No. Auto Air Vent Valve of size 15mm
8) 1 No. Drain Valve of Size 25mm
9) insulation as mentioned above for the Manifold pipe & valve. Insulation to be provided complete for fittings (Valves, bends, Tees, reducers, flanges etc.) with GC Check Cladding above insulation all as per specifications.
10) Structural steel for supporting Manifold.
11) Reducer + Flanges and along with all Acessories to installed control valve. Note:- Pipe line require form the header to be included.
-
-
-
... More
100 mm Ø
1
-
-
... More
50 mm Ø
5
-
-
... More
40 mm Ø
2
-
-
... More
32 mm Ø
3
-
-
... More
25mm Ø
3
-
-
... More
supply and installation of Condensate drain piping with 19 mm nitrile rubber insulation rigid GI pipes with U-trap and fittings.
-
-
-
... More
80 mm Ø
120
-
-
... More
40 mm Ø
100
-
-
... More
25 mm Ø
90
-
-
... More
Supply of HEPA filter modules with SS 304 supply perforated grill in CRCA powder coated finish side inlet type, with provision for DOP, pressure drop measurement along with volume control Damper and provision for a Flange type HEPA filters ( HEPA filter H14 type )including flexible connection. Price also include the HEPA filter.
-
-
-
... More
Size: 610 x 610 x150 mm
45
-
-
... More
Size: 450 x 450x150 mm
23
-
-
... More
Size: 305 x 305x150 mm
6
-
-
... More
Supply, installation, testing & commissioning of 25mm thick thermal insulated Aluminium flexible duct of 250mm dia duly supported at regular interval as per site requirement etc. complete as required as per specifications.
74
-
-
... More
AIR DISTRIBUTION AND CONTROL SYSTEM
-
-
-
... More
DUCTING
-
-
-
... More
Supply, fabrication, installation and testing of following sizes of Aluminium metal ducting Aluminium supports, angle iron flanges for all sizes of ducts, neoprene gaskets for all transverse joints, splitter dampers, tees, reducers, elbows etc. The frame shall slide over the duct ends to form flange connection. The flange connection shall be supplied with airtight seals. Ducts shall be suitably reinforced using diagonal bends, distance pieces, etc. A permanent non-etching, silicone free elastic sealing material shall be used. ducting as per SMACNA standard. Exposed duct should have provide 26G Al. cladding.Duct leak test to carry out after installation.
-
-
-
... More
22 G Sheet
1800
-
-
... More
20 G Sheet
700
-
-
... More
18 G Sheet
185
-
-
... More
INSULATION
-
-
-
... More
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. exposed duct should be provide with 26 G AL cladding.
-
-
-
... More
32 mm thick on Supply air Duct
1400
-
-
... More
19 mm thick on Return air Duct
1600
-
-
... More
Dampers
-
-
-
... More
Supply installation of Aluminium extruded powder coated volume control damper constructed in 18G GI frame and 18G blades complete with handle for main and branch ducts.
18
-
-
... More
Diffuser
-
-
-
... More
AL. sq. four way type Air Diffuser (Supply & Return) with 18G, G.I. Powder coated Box with Aluminum Collar Damper:
15
-
-
... More
Fire Damper: Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
-
-
-
... More
Fire Damper
8
-
-
... More
Actuator
14
-
-
... More
SUPPLY GRILLS
-
-
-
... More
Supplying & Installtion of perorated type SS grill for return air riser with 1.2mm thick GIPC capsulation perforations and retun air pre filter with all necessary fixing arrangement.
16
-
-
... More
GI powder coated Fresh air Louvre with filter and Brid screen
6
-
-
... More
Room Magnehelic Gauge ( -50 to 50 pa )
-
-
-
... More
Magnehelic gauges with MS powder coated box and SS top cover complete with necessary tubing with Probe to measure the differential pressure acroos the rooms
27
-
-
... More
Dismatling & re-installtion
-
-
-
... More
Dismatling and re-installtion of fire fighting line as per the requirement for the area. Design in the scope of the vendor and any additional material require the same to be considered.
1
-
-
... More
dismatling of Split along with copper pipe, cable , drain and all other asscessories of AC of 1.0T, 1.5T and 2.0T of appx 15 nos as per instructed and as directed by OIC-ES
1
-
-
... More
Design, fabrication, assembling, supply, testing & commissioning of PCC Panel of suitable for 415V, 3-phase, 50Hz 4 wire power supply system.Panel shall be fabricated out of 2mm thick CRCA Sheet steel in cubical formation, compartmentalized, Floor mounted, Panel shall be Outdoor type with IP-67 degree of protection, Free standing and shall be dust and vermin proof with 3 mm thick cable gland plate. Bus Bar: TPN+E Copper bus bars with color coded heat shrinkable insulating sleeves.
A. Incoming Air circuit Breaker, EDO Type
(i) 800 Amps 4 Pole electrically operated fully drawout type air
circuit breaker with required protection 1 no.
(ii)Phase indicating lamp R Y B
(iii)Breaker ON/OFF/TRIP Indicating lights
(iv)Emergency Stop push button. guidelines.
B. Outgoing MCCBs
5*125 Amps, 4 Pole, 45Kw Breaking capacity TM MCCB with
ON, OFF, TRIP Indications,LS Protection,Earth leakage protection 2Nos
C. Outgoing MCCBs
5*32 Amps, 4 Pole, 12Kw Breaking capacity TM MCCB with
ON,OFF,TRIP Indications,LS Protection,Earth leakage protection 2Nos
D. Outgoing MCCBs
3*25 Amps, 4 Pole, 11Kw Breaking capacity TM MCCB with
ON,OFF,TRIP Indications,LS Protection,Earth leakage protection 2Nos
D. Outgoing MCCBs
2*20 Amps, 4 Pole, 7.5Kw Breaking capacity TM MCCB with
ON,OFF,TRIP Indications,LS Protection,Earth leakage protection 2Nos
E. Outgoing MCCBs
2*20 Amps, 4 Pole, 1.5Kw Breaking capacity TM MCCB with
ON,OFF,TRIP Indications,LS Protection,Earth leakage protection 2Nos
1
-
-
... More
Supply, laying, testing & commissioning of 3.5 x 35 sq. mm Al conductor 1.1 KV AC grade PVC insulated ISI mark armored, bright annealed Aluminium conductor cable in ground at 900 mm through suitable size of DWC HDPE pipes, along with cable pulling chamber with heavy duty openable cover at the both end & if required in between as directed by in-charge, back filling & re-instatement, consolidation & removal of excess earth with in a radius of 500 mtr. as per instruction of E-I-C.
500
-
-
... More
Supply, laying, testing & commissioning of 4 x 6 sq. mm Al conductor 1.1 KV AC grade PVC insulated ISI mark armored, bright annealed Aluminium conductor cable in ground at 900 mm through suitable size of DWC HDPE pipes, along with cable pulling chamber with heavy duty openable cover at the both end & if required in between as directed by in-charge, back filling & re-instatement, consolidation & removal of excess earth with in a radius of 500 mtr. as per instruction of E-I-C.
900
-
-
... More
Supply, laying, testing & commissioning of 4 x 4 sq. mm Al conductor 1.1 KV AC grade PVC insulated ISI mark armored, bright annealed Aluminium conductor cable in ground at 900 mm through suitable size of DWC HDPE pipes, along with cable pulling chamber with heavy duty openable cover at the both end & if required in between as directed by in-charge, back filling & re-instatement, consolidation & removal of excess earth with in a radius of 500 mtr. as per instruction of E-I-C.
400
-
-
... More
Supply, laying, testing & commissioning of 4 x 2.5 sq. mm Al conductor 1.1 KV AC grade PVC insulated ISI mark armored, bright annealed Aluminium conductor cable in ground at 900 mm through suitable size of DWC HDPE pipes, along with cable pulling chamber with heavy duty openable cover at the both end & if required in between as directed by in-charge, back filling & re-instatement, consolidation & removal of excess earth with in a radius of 500 mtr. as per instruction of E-I-C.
300
-
-
... More
Supply ,Installation,Testing & Commisioning of Hot deeped Galvanised Perforated type Cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 750 mm width & 75 mm height complete with necessary coupler plates, MS channel support from ceiling, hardware , making cut-outs in wall & finishing of the same in approved manner.Painting of MS support and cable dressing complete in all respect.
300
-
-
... More
HVAC consultancy charges alongwith provsion of co-ordinated drawings with civil and MEP for complete design for HVAC system and vetting of BOQ and monitoring the work and issuance of final completion of project as per the requirement of CGMP.
1
-
-
... More
On-site validation and Testing of the complete Clean room System:
-
-
-
... More
After completion of E&C of all equipment and accessories, validation test shall be conducted as described below: Testing & Validation as per ISO 14644:2001 standards (Velocity, Particulate count, Temp, Humidity, filter, integrity tests to be carried out at the site) by 3rd party. A comprehensive on-site validation and certification service for clean room installation is in the scope. These includes leak detection, clean room level measurement and certification, air flow pattern analysis, dead zone identification and elimination and comprehensive documentation with regard to maintenance & validation procedure.
-
-
-
... More
following validation & testing of the installed clean -room during final commissioning of the above clean room project:
Cleanliness levels as per ISO 14644 Air Quality Monitoring
Particle size Efficiencies and quantity count Airborne Particulate contamination Monitoring
Air Velocity Measurement & Air-flow Quantity Measurement Temperature control range tests
Humidity control range tests
Filter pressure drop measurements Air flow pattern and strength
Light level checks at 1m working height in clean room
Room pressurization
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements