Military Engineer Services Tender

... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for 81797 Addn / Altn To Oh Power Supply, Transmission Line With Ug Power Cables And Allied Items At Followers Qtrs, Stn Hq And Other Small Pockets At Nda Under Ge (nda) Khadakwasla in Pune, Maharashtra, with an estimated contract value of Rs. 1,43,94,000. The bid opening date for this tender is 16-05-2025 and the last date for bid submission is 13-06-2025. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender

Works
Electrical Cables And Wires
Electrical and Electronics
Electrical Works
Eprocure
Opening Date16 May 2025
Closing Date13 Jun 2025
Tender Amount₹ 1,43,94,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Dismantling stay assembly complete of existing LT Pole including earthwork etc complete all as specified and as directed.

5

-

-

... More
Dismantling Old unserviceable steel struts, any size including earthwork etc complete all as specified and as directed.

3

-

-

... More
Dismantling/Taking out old UG power cable of following sizes :- (Note : Excavation and Earth work shall be measured and paid separately)

-

-

-

... More
(a) 150 Sqmm 3.5 Core

100

-

-

... More
(b) 16 Sqmm 4 Core.

1320

-

-

... More
Relaying of old serviceable LT UG power cable retrieved from item No. 6.00 above of following sizes :- (Note :- Excavation & Earth Work shall be measured and paid separately under respective item of BOQ)

-

-

-

... More
(a) 150 Sqmm 3.5 Core

50

-

-

... More
(b) 16 Sqmm 4 Core.

200

-

-

... More
Dismantling Old unserviceable GI Protection Pipe of any type of 50mm dia complete all as specified and as directed.

130

-

-

... More
Supply & Laying including testing LT UG Power Cable XLPE Insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) suitable for 1100 Volts grade with multi-stranded aluminium conductor of following sizes :-

-

-

-

... More
(a) 3.5 Core 240 Sqmm

690

-

-

... More
(b) 3.5 Core 185 Sqmm

610

-

-

... More
(c) 3.5 Core 150 Sqmm

1020

-

-

... More
(d) 3.5 Core 120 Sqmm

880

-

-

... More
(e) 3.5 Core 95 Sqmm

190

-

-

... More
(f) 3.5 Core 70 Sqmm

210

-

-

... More
(g) 3.5 Core 50 Sqmm

40

-

-

... More
(h) 3.5 Core 35 Sqmm

250

-

-

... More
(j) 3.5 Core 25 Sqmm

3630

-

-

... More
(k) 4 Core 16 Sqmm

7582

-

-

... More
Excavation in trenches, not exc 1.5m wide and not exc 1.5 m depth and getting out in for foundation of pole, stay, laying of cable and pipe etc for the following :

-

-

-

... More
(a) Hard/Dense soil

2678.83

-

-

... More
(b) Soft/disintegrated rocks

297.65

-

-

... More
Returning and filling in, including spreading and well ramming in layers n exc 25 cm all as specified and directed by Engr-in-Charge.

2544.25

-

-

... More
Removing excavated material a distance n. exc 50 m & depositing where directed at a level n. exc 1.5 m above the starting point complete all as specified and as directed.

432.23

-

-

... More
Supply and laying 50 x 38 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e. coupler, Tee, elbow clamp for cable protection of size 16 to 25 sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. (Note : Sample / Make of DWC pipe shall be got appoved by the contractor from GE prior procurement and execution of work.)

9728

-

-

... More
Supply and laying 63 x 50 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e. coupler,Tee, elbow clamp for cable protection of size 35 to 50 Sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. (Note : Sample / Make of DWC pipe shall be got appoved by the contractor from GE prior procurement and execution of work.)

261

-

-

... More
Supply and laying 77 x 63 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e. coupler, Tee, elbow clamp for cable protection of size 70 Sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. . (Note : Sample / Make of DWC pipe shall be got appoved by the contractor from GE prior procurement and execution of work.)

189

-

-

... More
Supply and laying 90 x 75 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e.coupler,Tee, elbow clamp for cable protection of size 95 Sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. (Note : Sample / Make of DWC pipe shall be got appoved by the contractor from GE prior procurement and execution of work.)

171

-

-

... More
Supply and laying 110 x 95 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e.coupler,Tee, elbow clamp for cable protection of size 120 to 150 Sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. (Note : Sample / Make of DWC pipe shall be got appoved by the contractor from GE prior procurement and execution of work.)

1710

-

-

... More
Supply and laying 120mm x 103 mm outer & inner dia, double walled corrugated (DWC) HDPE duct pipe confirming to IS-16205 Pt-24 with antirodent and non flame propogating properties of approved colour complete with fittings i.e.coupler,Tee, elbow clamp for cable protection of size 185 to 240 Sqmm 3.5 core complete all as specified and directed by Engr-In-Charge. (Note : Sample / Make of DWC pipe shall be got appoved by the contractor from GE prior procurement and execution of work.)

1170

-

-

... More
M&L for PCC demolition of Strut Pole and Pole Cooping of any description and in any position complete all as specified and as directed.

9.3

-

-

... More
M & L for earthing complete with galvanized steel earth plate electrode 600 X 600 X 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m deep below normal ground level in any type of soil strata, connected to galvanized iron strip 25 x 4mm by means of bolts, nuts and washers of galvanised iron or steel all as shown in earth plate No 3 of MES schedule 2009 Part – I connected to LT Panel, Feeder Pillars, Sub Feeder Pillars etc. as required including necessary excavation and earth work, concrete pit & chamber in PCC 1:2:4 type B1 & pit cover with lifting handle and 20mm Dia GI watering pipe medium grade, Funnel, wiremesh, etc. and testing on completion including filling up the earth pit with black cotton soil for best result and removal of extra excavated material from the site complete all as specified and directed by Engr-in-Charge. (Note :- Cost of GI strip and protection pipe upto 7.5 Mtr length shall deemed to be included in quoted rate)

80

-

-

... More
M & L for spreading & levelling a layer of required thickness with 40 mm graded coarse aggregate in the Existing Sub Stn Yard including cleaning the Sub Stn Yard by cutting of Bushes/Grass over the existing area complete all as specified and directed by Engr-in-Charge.

8

-

-

... More
M & L for removing old/scraped paints from existing chain link fencing (approx size 15 x 20 mtr and height 2.5 Mtr), MS Angle, MS gate etc and preparation of surfaces for re-paint and re-paints with one coat Synthetic Enamel Paints of approved colour complete in all respect all as directed by Engr-in-Charge.

1

-

-

... More
S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size 200 mm x 150 mm for LT Supply complete all as specified and directed.

80

-

-

... More
Supply & Installation in replacement including testing and commissioning Main LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (TO BE APPROVED BY GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 1200 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be showing the arrangements of circuit shall be pasted inside the panel door and covered with transparent laminated plastic sheet. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 6 Nos 70x70x5mm thick angle iron supports of not less than each 1.5 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1800mmX850mmX1500mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cables and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
Incomer (a) Supply and fixing including testing of ACB 4 Pole, 415 Volts, 800 Amp, 50 KA, Manual Draw Out (MDO) type with microprocessor based LSIG & temprature rise protection consisting of digital LCD display with battery backup, Current Metering and RS 485 port complete all as specified and directed.- 01 No Outgoing (a) MCCB 4 Pole, 415 Volts, 250 Amp, with Electronic Protection Unit, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 02 Nos. (b) MCCB 4 Pole, 415 Volts, 100 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 02 No. (c) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 02 No.

-

-

-

... More
Supply & Installation in replacement including testing and commissioning Main LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (to be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 400 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.

1

-

-

... More
All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be showing the arrangements of circuit shall be pasted inside the panel door and covered with transparent laminated plastic sheet . The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x5mm thick angle iron supports of not less than each 1.5 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 250 Amp, with Electronic Protection Unit, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 01 Nos. Outgoing (a) MCCB 4 Pole, 415 Volts, 160 Amp with Electronic Protection Unit, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 01 No. (b) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, confirms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 02 Nos (c) Isolator 4 pole 40 Amps with adjustable setting - 01 No. (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 250 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts,160 Amp with Electronic Protection Unit, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 63Amp with thermal magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overload Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc.– 02 Nos (Outgoing) (c) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 01 No. (d) Isolator 4 pole 40 Amps with adjustable setting - 01 No. (Outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.

1

-

-

... More
All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts,63 Amp with Electronic Protection Unit, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 03 Nos. (c) Isolator 4 pole 40 Amps with adjustable setting -01 Nos (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

4

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts,100 Amp with Electronic Protection Unit, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts,63 Amp with Electronic Protection Unit, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. – 01 No. (c) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 02 Nos. (d) Isolator 4 pole 40 Amps with adjustable setting -01 Nos (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.

7

-

-

... More
All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1000mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 63 Amp with Electronic Protection Unit, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 02 Nos. (c) Isolator 4 pole 40 Amps with adjustable setting - 01 No (Outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 400 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.

3

-

-

... More
All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 250 Amp, with Electronic Protection Unit, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 01 No. (b) MCCB 4 Pole, 415 Volts, 200 Amp with Electronic Protection Unit, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 01 No. (c) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, confirms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 02 Nos. (d) Isolator 4 pole 40 Amps with adjustable setting -01 Nos (outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 300 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.

3

-

-

... More
The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 200 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 160 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In with both side of spreader links and phase separater etc. – 01 Nos (Outgoing). (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 02 Nos (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting -01 No (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 250 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.

1

-

-

... More
The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 160 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In with both side of spreader links and phase separater etc. – 01 No (Outgoing). (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 02 Nos (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting -01 No. (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 600 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.

1

-

-

... More
The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 400Amp with Thermal Magnetic release, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 250 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In with both side of spreader links and phase separater etc. – 01 Nos (Outgoing). (c) MCCB 4 Pole, 415 Volts, 200 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In with both side of spreader links and phase separater etc. – 01 Nos (Outgoing). (d) MCCB 4 Pole, 415 Volts,100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 02 No (Outgoing). (e) Isolator 4 pole 40 Amps with adjustable setting -01 Nos (outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 300 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured.

1

-

-

... More
The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 200 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 63 Amp with Thermal Magnetic release, 16 KA, Confirms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In with both side of spreader links and phase separater etc. – 01 No (Outgoing). (c) MCCB 4 Pole, 415 Volts, 40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 02 Nos (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting - 01 No (outgoing) (e) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA confim to IS/IEC 60947-2, Ics = 100%, Icu suitable for isolation, Adjustable overload setting 0.8 - 1.0 x In Magnetic Adjustable 5-10 x In with both side of Spreader links and phase seperator etc - 01 No. (Outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.

1

-

-

... More
The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : 1. Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 04 Nos (Outgoing). (c) Isolator 4 pole 40 Amps with adjustable setting -01 No (Outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 300 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 200 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 125 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Outgoing). (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 03 Nos (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting -01 Nos (Outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 200 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.

1

-

-

... More
The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 125 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 100Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Outgoing). (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 02 Nos (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting -01 Nos (outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment. The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers.

1

-

-

... More
The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 03 Nos (Outgoing). (c) Isolator 4 pole 40 Amps with adjustable setting -01 No (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

2

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts,100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 01 No (Outgoing). (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 01 No (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting -01 Nos (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1000mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts,63 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 01 No (Outgoing). (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 01 No (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting - 01 No (Outgoing )

-

-

-

... More
Supply & Installation in replacement including testing and commissioning Main LT Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 1000 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be showing the arrangements of circuit shall be pasted inside the panel door and covered with transparent laminated plastic sheet. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 6 Nos 70x70x5mm thick angle iron supports of not less than each 1.5 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1800mmX450mmX1500mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cables and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 630 Amp, with Electronic Protection Unit, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 01 No. Outgoing (b) MCCB 4 Pole, 415 Volts, 250 Amp, with Electronic Protection Unit, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 01 No. (c) MCCB 4 Pole, 415 Volts, 200 Amp, with Electronic Protection Unit, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable overload setting : 0.4 - 1.0 x In, Adjustable short circuit setting 1.5 - 10 x Ir, Manual type, inbuilt display for current metering with accuracy Class 1, Internal battery measure function, comm port, inbuilt USB Port for software diagnosis with both side of spreader links and phase separater etc. - 01 No. (d) MCCB 4 Pole, 415 Volts, 100 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 02 Nos. (e) MCCB 4 Pole, 415 Volts, 40 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 01 No.

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 250 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

2

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 160 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 100 Amp with thermal magnetic release, 16 KA, conforms to IS/IEC 60947-2, Ics = 100% Icu, suitable for Isolation, Adjustable Overlaod Setting : 0.8 - 1.0 x In with both side of spreader links and phase separater etc. - 01 No. (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 02 Nos (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting - 01 No (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 400 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1000mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 250 Amp with Thermal Magnetic release, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 200 Amp with Thermal Magnetic release, 36 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (c) MCCB 4 Pole, 415 Volts,63 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 01 No (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting -02 Nos (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 250 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement. All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mm X 450mm X 1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 160 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 02 Nos (c) MCCB 4 Pole, 415 Volts, 40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 02 No (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting - 02 Nos (Outgoing)

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 160 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

2

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1200mmX450mmX1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing.)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 03 Nos (Outgoing). (c) Isolator 4 pole 40 Amps with adjustable setting -02 Nos (outgoing )

-

-

-

... More
Supply & Installation including testing and commissioning of Feeder Pillar Panel weather proof outdoor type double door, fabricated out of 3.15mm thick CRCA sheet with epoxy powder coating of RAL-7032 (Siemens Gray) shade with matt finish with seven tank pre treatment process. The panel shall be fabricated by CPRI approved manufacturer (To be approved by GE). The panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-55, double door type with locking arrangement for front and back side, comprising of gaskets between all adjacent units and beneath all covers shall be fully gasketed with neoprene rubber and ventilation arrangement for heat dissipation from both side of panel. The panel shall be provided with Aluminium bus bars of high conductivity aluminium alloy, suitable for 3 phase 4 wire system (R,Y,B,N) rating not less than 250 Amp. The busbars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & Black colour coding. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in dedicated compartment.

1

-

-

... More
The panel shall be prewired with FRLS PVC insulated copper conductor cables of suitable size properly tagged and secured. All joints and connection shall be done with galvanized or cadmium plated high tensile nuts, bolts and washers. The panel shall be provided with digital multifunction meter with accuracy Class 1 with RS 485 Parameters with cast Resign CTs etc and RYB, ON, OFF & Trip LED indicating lamps at incoming. The panel shall be provided with manufacturer's name plate, skull & bones danger notice board, Name plate for Feeder Panel & all incoming and outgoing MCCBs etc. The panel shall be provided 4 Nos 50x50x6 mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 at suitable depth as per site requirement . All MCCBs shall be provided with spreader links with phase separators on both side and suitable extended rotary handles for all Incoming & Outgoing MCCBs complete all as specified and as directed. The overall size of the panel shall not less than 1500mm X 450mm X 1000mm (LxDxH). The panel shall be provided with 2 Nos of Earthing Terminals one on each side of the Panel with earth strip, suitable size of SS Cable glands for all incoming & outgoing XLPE Cable and including following accessories:- (Note : Drawing and design of panel must be approved by Engr-in-charge before manufacturing)

-

-

-

... More
(a) MCCB 4 Pole, 415 Volts, 160 Amp with Thermal Magnetic release, 25 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No (Incomer). (b) MCCB 4 Pole, 415 Volts, 100 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation, Adjustable Overload setting : 0.8-1.0 x In, Magnetic Adjustable 5 - 10 x In with both side of spreader links and phase separater etc. – 01 No. (c) MCCB 4 Pole, 415 Volts,40 Amp with Thermal Magnetic release, 16 KA, Conforms to IS/IEC 60947-2, Ics = 100% Icu suitable for Isolation with Adjustable Overload setting : 0.8-1.0 & both side of spreader links and phase separater etc. - 03 Nos (Outgoing). (d) Isolator 4 pole 40 Amps with adjustable setting -02 Nos (Outgoing)

-

-

-

... More
Supply, Fixing and commissioning automatic timer switch distribution board, factory assembled in powder coated sheet steel enclosure, comprising of 40 Amps 3 Pole power contactor and 230V digital time switch and 4 Pole 40 Amps, 10 KA MCB for controlling LED/SV etc street lights, including earth work for fixing Timer switch distribution Board and shall be provided on 4 Nos 35x35x4mm thick angle iron supports of not less than each 1.2 mtr height duly painted with anti corrosive black paint and grouted in PCC 1:3:6 type C-1 at suitable depth as per site requirement.

2

-

-

... More
Supply & Fix on pole, SMC Junction box inner dimensions (270 x 225 x 135)mm (LxBxD), 3 phase 4 wire system, including cable connecting base, 6 Amp DP MCB with mounting SS railing, Cable lugs suitable to 16 Sqmm 4 core cable, connection for incoming and outgoing cables including Fixing arrangement on pole etc complete all as specified and directed by Engr-in-Charge.

90

-

-

... More
S & F Cable Route Marker made up of Cast Iron of dia 100 mm and thickness 4.65 mm with supporting angle iron of size 20 x 20 x 3 mm and height 0.6 mtr for stand including priming, painting and wirting of "LT CABLE" in suitable size of letter including necessary earthwork and grouted at suitable depth in PCC 1:3:6 Type C2 (using 40 mm graded stone aggregate) in mass concrete complete all as specified and directed at site by Engr-in-Charge.

150

-

-

... More
M & L for PCC 1:3:6 type C2 (using 40 mm graded stone aggregate) for base and foundation, filing & mass concrete for Pole Cooping etc complete all as specified and directed at site by Engr-in-Charge.

9.3

-

-

... More
S & F of 2.5 Sqmm 3 core Weather proof aluminium multistranded cable PVC insulated not less than 7 mtr on existing street lights and properly drawn through existing street light bracket, Pole and hole of street light pole including making of two 20mm hole on existing street light pole and taking down existing 2.5 Sqmm aluminium twin core cable complete all as specified and directed at site. (Note : The contractor shall be responsible for any damage occured to the existing street light during execution of work and the damaged parts of street light if any shall be replaced by the contractor without any extra cost to the Deptt.)

90

-

-

... More
M & L for road cutting of size (45cm x 45 cm) as required for laying pipe/cable etc and making good to match with existing one including earthwork and necessary excavation, complete material required to match with the existing one or with PCC 1:2:4 type B1 complete all as specified and as directed by Engineer-in-charge.

150

-

-

... More
M & L for Straight Through Jointing Kit Heat Shrink type suitable for 1.1 KV LT XLPE armoured aluminium stranded conductor Cable Outdoor type complete with jointing material and accessories of size 3.5 Core 240 Sqmm complete all as specified and directed.

2

-

-

... More
All as per Ser. item No 53.00 above but 3.5 Core 185 Sqmm complete all as specified and as directed.

2

-

-

... More
All as per Ser. item No. 53.00 above but 3.5 Core 150 Sqmm complete all as specified and as directed.

2

-

-

... More
All as per Ser. item No. 53.00 above but 3.5 Core 120 Sqmm complete all as specified and as directed.

2

-

-

... More
All as per Ser. item No. 53.00 above but 3.5 Core 95 Sqmm complete all as specified and as directed.

2

-

-

... More
All as per Ser. item No. 53.00 above but 3.5 Core 70 Sqmm complete all as specified and as directed.

2

-

-

... More
All as per Ser. item No. 53.00 above but 3.5 Core 50 Sqmm complete all as specified and as directed.

2

-

-

... More
All as per Ser. item No. 53.00 above but 3.5 Core 35 Sqmm complete all as specified and as directed.

2

-

-

... More
All as per Ser. item No. 53.00 above but 3.5 Core 25 Sqmm complete all as specified and as directed.

4

-

-

... More
All as per Ser. item No. 53.00 above but 4 Core 16 Sqmm complete all as specified and as directed.

4

-

-

... More
S & F of LT Busbar panel weather proof outdoor type double door, fabricated out of 3.15 mm thick CRCA sheet with epoxy powder coating of RAL-7035 ( Siemens Gray) shade with matt finish with seven tank pre treatment process. The Panel shall be compartmentized design totally enclosed, dust and vermin proof, conforming to degree of protection IP-43, Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof. The Panel shall be fabricated by CPRI approved manufacturer (to be approved by GE). All doors and covers shall be provided with cylindrical panel locks and shall be fully gasketed with neoprene rubber and shall be lockable. The panel shall be provided with aluminium bus bars electrolytic grade of 300 amps current rating. The bus bars and Interconnecting links shall be insulated with heat shrinkable PVC sleeve with RYB & black colour coding and fix horizontally. The bus bars shall be supported on unbreakable, non-hygroscopic SMC insulated supports at sufficiently close intervals to prevent busbars sag and shall be housed in a dedicated compartment. All joints and connection shall be done with galvanised or cadmium plated high tensile nuts, bolts, washers and AL Lugs etc.

7

-

-

... More
SER. ITEM No. 63.00 ABOVE Contd.... The panel shall be provided with 04 Nos 35mmx35mmx4mm thick angle iron supports of not less than each 1.0 mtr height duly painted with anti corrosive black paint including earth work and grouted in PCC 1:3:6 at suitable depth as per site requirement including taking down existing one. The overall size of the Busbar panel shall not be less than 500mmx300mmx550mm (LxDxH) including 4 Nos cable entry holes suitable for cable entry up 3.5C 185 Sqmm at bottom complete all as specified and directed Engr in Chrage.

-

-

-

... More
M & L for tubes, light Grade, galvanised with all fittings, laid in trenches or with pole/wall for protection of Cable etc with fixing accessories such as Shaddle, nut-bolts etc of 50 mm dia size complete all as specified and directed by Engr-in-Charge.

110

-

-

... More
M&L for PCC / Interlocking tiles path way cutting of size (45 cm x45 cm) as required for laying pipe/cable etc and making good to match with the existing surface finishes / specification complete all as specified and as directed

100

-

-

... More
M&L for preparation of existing surface of steel tubular pole by scrapping down peeled off old paint, cleaning etc of length 8.5/9/11 mtrs and cross arms etc and applying one coat of aluminium coat paint including rewriting pole Nos as directed with black paint complete all as specified and directed by Engineer in Charge.

90

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.