Inter University Centre For Astronomy And Astrophysics Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Inter University Centre For Astronomy And Astrophysics - IUCAA Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date31 Jul 2024
Closing Date22 Aug 2024
Tender AmountRefer Documents
Costs
EMD
₹ 8,00,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_IUCAA_819123_1Bid Award Id
ViewTender No
M24-0202Tender Authority
Inter University Centre For Astronomy And Astrophysics ViewPurchaser Address
-Website
http://https://www.iucaa.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supplying, erecting, testing and commissioning of 18 HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100%capacity at 47° C, non stop cooling even at 55° C and coefficient of performance (COP) 4.00 to 4.80 at AHRI condition, modular type vertical hot air discharge suitable for longer piping range upto 1000m operation in cooling mode with inverter VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor having in built logic to automode to transfer on the remaining outdoor unitsof that system, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete. The rates are inclusive of first fill refrigerant gas and oil required, galvanised stand for outdoor units with SS fasteners and serrated rubber pads. The panel must be 100% compatible with BMS. The units must also be provided with self addressable control system for control of indoor and outdoor machines. The capacity and power consumption curves, deration/correction factor curves / charts for indoor temperature and piping derations must be submitted with offer, along with duly filled-up datasheet in the attached format. Deration Chart table highlighted at 47 Degree Celsius must be provided with the Technical Data Sheet/Technical Bid Form.
2
-
-
Supplying, erecting, testing and commissioning of 20 HP VRF/VRV air conditioning system outdoor unit (ODU) complies type-IV OEM standards working on HFC refrigerant R410A or other required/suitable green equivalent refrigerant, for minimum cooling capacity as delivering 100%capacity at 47° C, non stop cooling even at 55° C and coefficient of performance (COP) 4.00 to 4.80 at AHRI condition, modular type vertical hot air discharge suitable for longer piping range upto 1000m operation in cooling mode with inverter VRF/VRV technology microprocessor based control compressor starter/control panel with scroll compressor having in built logic to automode to transfer on the remaining outdoor unitsof that system, air cooled copper condenser coil of suitable shape for increasing maximum heat transfer area, rain protection cover, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V±10%, 50 Hz, 3 phase power supply (all suitable for high ambient conditions), internal copper refrigerant piping, internal wiring and refrigerant, etc. all housed in powder coated weather proof cabinet complete. The rates are inclusive of first fill refrigerant gas and oil required, galvanised stand for outdoor units with SS fasteners and serrated rubber pads. The panel must be 100% compatible with BMS. The units must also be provided with self addressable control system for control of indoor and outdoor machines. The capacity and power consumption curves, deration/correction factor curves / charts for indoor temperature and piping derations must be submitted with offer, along with duly filled-up datasheet in the attached format. Deration Chart table highlighted at 47 Degree Celsius must be provided with the Technical Data Sheet/Technical Bid Form.
7
-
-
Supply, installation, testing and commissioning of VRF/VRV based Hi-wall type room/indoor unit (IDU) of nominal cooling capacity 1.0TR to 1.25TR having EER as per BEE standards and specifications with multiple speed evaporator fan with motor, copper tube aluminium fin evaporator coil, washable air filter, insulated drain tray, in built drain pump, expansion device, cordless remote control with necessary controls and electrical terminal to receive power supply, etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be of decorative slim dimension suitable indoor wall mounting. The indoor unit shall also have an electronic control console. The unit shall be suitable for wall mounting and provided with suitable mounting brackets with any additional refrigerant and oil charge as per requirement during installation complete.
2
-
-
Supply, installation, testing and commissioning of VRF/VRV based Hi-wall type room/indoor unit (IDU) of nominal cooling capacity 2TR to 2.2TR having EER as per BEE standards and specifications with multiple speed evaporator fan with motor, copper tube aluminium fin evaporator coil, washable air filter, insulated drain tray, in built drain pump, expansion device, cordless remote control with necessary controls and electrical terminal to receive power supply, etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be of decorative slim dimension suitable indoor wall mounting. The indoor unit shall also have an electronic control console. The unit shall be suitable for wall mounting and provided with suitable mounting brackets with any additional refrigerant and oil charge as per requirement during installation complete.
3
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indoor unit (IDU) compact/ standard size of nominal cooling capacity 1.0TR to 1.3TR having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
31
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indoor unit (IDU) compact/ standard size of nominal cooling capacity 1.5TR to 1.8TR having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
36
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indoor unit (IDU) compact/ standard size of nominal cooling capacity 2.0TR to 2.3TR having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
11
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indoor unit (IDU) compact/ standard size of nominal cooling capacity 2.6TR to 2.8TR having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
10
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indoor unit (IDU) compact/ standard size of nominal cooling capacity 3.0TR to 3.2TR having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
9
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indoor unit (IDU) compact/ standard size of nominal cooling capacity 3.3TR to 4.0TR having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation.
7
-
-
Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 1 way cassette room/indoor unit (IDU-compact / standard size) of nominal cooling capacity 1.4TR to 2.0TR having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. IDU with drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anti corrosive coating suitable for coastal area in all respects suitable to operate on 1-phase, 230V, 50Hz, AC supply complete. The unit consisting with any additional refrigerant and oil charge as per requirement during installation complete.
39
-
-
Supplying, erecting, testing and commissioning of 2 core shielded cable complete as per specification no. FF-PA/MCC
1900
-
-
Supplying and erecting HMS uPVC FRLS grade conduit 20 mm dia. with uPVC FRLS accessories on wall / ceiling as per specification No:WG-MA/CON.
1520
-
-
Supplying and installation of high pressure grade required size copper connection Y or T- Joints/ refnet complete for indoor & outdoor units erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV/VRF air conditioning system.(consider two nos. of refnets in each set)
160
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 41.3mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
381
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 34.9mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
98
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 28.6mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
284
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 22.2mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
99
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 19.1mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
448
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 15.9mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
277
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 12.7mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
560
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 9.5mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
250
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 6.4mm dia (OD) for liquid line/suction line supply and return piping of suitable gauge (hard copper pipe for liquid main line and soft copper pipe for refrigerant) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19mm thick elastomeric nitrile rubber along with application of multicoating of VRV/VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations with OEM standards of VRV/VRF air conditioning system complete.
350
-
-
Supplying and erecting 20/25 mm (ID/OD) Unplasticized polyvinyl chloride pipe (UPVC), thickness 2.6 mm conforming to IS 15778 (CTS Series) with necessary UPVC fittings and solvent cement for Solar Water Heater System as per specification No. ESD-HWP/UPVC
50
-
-
Supplying and erecting 25/32 mm (ID/OD) Unplasticized polyvinyl chloride pipe (UPVC), thickness 3.2 mm conforming to IS 15778 (CTS Series) with necessary UPVC fittings and solvent cement for AC unit drain piping
355
-
-
Supplying and erecting 32/40 mm (ID/OD) Unplasticized polyvinyl chloride pipe (UPVC), thickness 3.8 mm conforming to IS 15778 (CTS Series) with necessary UPVC fittings and solvent cement for AC unit drain piping
100
-
-
Supplying and erecting 40/50 mm (ID/OD) Unplasticized polyvinyl chloride pipe (UPVC), thickness 3.8 mm conforming to IS 15778 (CTS Series) with necessary UPVC fittings and solvent cement for AC unit drain piping
265
-
-
Providing & erecting hot dipped galvanised perforated type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware.
1135
-
-
Providing & erecting hot dipped galvanised cover suitable for perforated type Cable tray manufactured from 18 SWG (1.2 mm thick) GI sheet of 300 mm width & 20 mm height complete with necessary hardware.
280
-
-
SITC of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required - 22 G
375
-
-
SITC of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required - 20 G
565
-
-
Supplying & applying of adhesive thermal insulation for supply / return air duct with 19 mm nitrile rubber insulation having R-value as per the prevailing provisions in ECBC-2007.
5
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 1850 CFM @ 15 mm SP FA FAN With EU5 Filter -Basement+ Ground flr
2
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 440 CFM @ 15 mm SP FA FAN with EU5 Filter -Basement Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCK series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 3500 CFM @ 25 mm ESP FA FAN With EU5 Filter - Basement
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 900 CFM @ 20 mm ESP FA FAN With EU5 Filter - Second Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 600 CFM @ 25 mm ESP FA FAN With EU5 Filter - First Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 200 CFM @ 25 mm ESP FA FAN With EU5 Filter - Ground Floor
2
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CSD/CSK series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 2540 CFM @ 25 mm ESP FA FAN With EU5 Filter - First Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 1220 CFM @ 25 mm ESP FA FAN With EU5 Filter - Second Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 1850 CFM @ 25 mm ESP EA FAN - Basement
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 1750 CFM @ 25 mm ESP EA FAN - Basement
2
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CSD/CCK series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 3030 CFM @ 25 mm ESP FA FAN Ground flr
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CSD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 150 CFM @ 25 mm ESP EA FAN - Ground Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CSD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 3240 CFM @ 25 mm ESP EA FAN - Terrace Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 200 CFM @ 15 mm ESP EA PROPELLER FAN - Second Floor
1
-
-
SITC of Inline cabinet type fan with galvanised steel cabinet, forward curved centrifugal fan. The fan shall be with hanger and cabinet support. Fan shall be suitable for Specified mm ESP. Single/Three Phase, Suitable KW motor, Kruger make CCD series or equivalent. The fan shall have its own starter panel with fan speed control regulator etc. The starter panel shall have BMS compatibility for ON & OFF. The panel shall also have the terminal junction / Marshalling box for terminating all control / Sensor cables Capacity 300 CFM @ 15 mm ESP EA SITC of Inline FAN -Ground+First Floor
2
-
-
SITC of G I Fresh Air Louvers & Exhaust Air Louvers with birdmesh in SS construction
8
-
-
Supplying and erecting galvanised/MS iron work, sheet metal work consisting of CRCA/GI sheets, various sections of galvanised/MS iron, plates, rods, L angles, C Channels etc. for panel board/OD Foundation or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears/OD units or as per directions by the authority.
1350
-
-
Supplying and erecting circular flexible/rigid PVC pipe duct of size 100mm dia, 4mm thickness with required couplers, reducers, T-joints, Y-joints elbows and necessary supports etc. with sealing with provided control/air flow regulating valves / dampers, filters at position complete.
170
-
-
Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 8 ways / phase (24 poles), with door, 1.2mm thickness surface/ flush mounted, IP 54 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB
9
-
-
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 54 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
1
-
-
Supplying, erecting and marking four pole isolators only switch version of miniature circuit breakers of 80/100A in provided distribution board.
8
-
-
Supplying, fixing and commissioning 4 pole RCBO 32/40A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO
5
-
-
Supplying, fixing and commissioning 4 pole RCBO 63A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO
13
-
-
SITC of CAV Boxes for Fresh Air Control to Cassette Unit 30 - 90 CFM self-powered volume flow controllers for the control of supply air or extract air in constant air volume systems.
148
-
-
SITC of Aluminium ABS Plastic Disc Valve 100 mm Dia
50
-
-
SITC Of Aluminium Powder Coated Fresh Air Diffuser with Damper size - 300 mm X 300 mm
14
-
-
Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100V, 4 core 10 sq. mm. copper conductor complete erected with double compressed glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification.
150
-
-
Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 25 sq. mm. copper conductor complete erected with double compressed glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU.
300
-
-
Supplying, erecting & terminating FRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 35 sq. mm. copper conductor complete erected with double compressed glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU.
400
-
-
Supplying and erecting aluminium powder coated door transfer linear grill of 700x 150mm suitable door thickness size for width length without collar dampers having matching colour with the existing false ceiling and suitable for deflection of 15/30/45°.
9
-
-