Raja Ramanna Centre For Advanced Technology Tender
Know all about the latest MP tenders along with the tender details and downloadable document on BidAssist. Here, on this page, we shall help you search for every MPtender posted on the official website of mptenders.gov.in according to authority, district, etc. Be it an irrigation tender or MP PWD tender, and we will tell you how to bid for these and more.
Raja Ramanna Centre For Advanced Technology - RRCAT Tender
Electrical and Electronics
Eprocure
Opening Date28 Mar 2022
Closing Date21 Apr 2022
Tender Amount₹ 1,32,75,000
Costs
EMD
₹ 2,65,500Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_RRCAT_680913_1Bid Award Id
ViewTender No
RRCAT/E/2022/03 dated 17.03.2022Tender Authority
Raja Ramanna Centre For Advanced Technology ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Guaranteed Technical Particulars
BOQ Items
Incomer: 400 A, TP MCCB (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 400 A
Outgoings:
(1) 160 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 Nos
(2) 125 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 11 Nos.
1
-
-
Incomer: 800 A, TP MCCB (Ics ≥ 50 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 800 A
Outgoings:
(1) 400 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 4 Nos.
(2) 250 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 2 Nos.
(3) 125 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 6 Nos.
1
-
-
Incomer: 400 A, TP MCCB (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 400 A
Outgoings:
(1) 250 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 2 Nos
(2) 125 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 10 Nos.
1
-
-
Incomer: 400 A, TP MCCB (Ics ≥ 36 kA) with Microp. trip for O/L, S/C & E/F.- 1 No.
TPN copper bus bar - 400 A
Outgoings:
(1) 250 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L & S/C E/F protection - 2 Nos.
(2) 125 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L & S/C E/F protection - 8 Nos.
2
-
-
Incomer: 800 A, TP MCCB (Ics ≥ 50 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 800 A
Outgoings:
(1) 630 A TP MCCBs (Ics ≥ 50 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
(2) 400 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 2 Nos.
(3) 250 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 7 Nos.
(4) 100 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 3 Nos.
1
-
-
Incomer: 630 A TP MCCB (Ics ≥ 50 kA) with Microprocessor based trip release for O/L, S/C & E/F protection :- 1 No.
TPN copper bus bar - 630 A
Outgoings:
(1) 400 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection :- 2 Nos.
(2) 250 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection :- 4 Nos.
(3) 125 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection :- 10 Nos.
1
-
-
Incomer: 400 A, TP MCCB (Ics ≥ 36 kA) with Microp. trip for O/L, S/C & E/F.- 1 No.
TPN copper bus bar - 400 A
Outgoings:
(1) 250 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection :- 2 Nos.
(2) 125 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection :- 4 Nos.
(3) C-Curve 63 A FP MCB (Ics ≥ 10 kA) - 2 Nos.
1
-
-
Design, Fabrication, Supply, Installation, Testing & Commissioning of outdoor/indoor type Motor Control Centre (MCC) as per our specification, attached GA drawing /single line diagram having following configurations: Enclosure - Powder coated CRCA sheet 2 mm. Bus bar - EC grade tinned Copper.
MCCB - Having microprocessor based trip release O/L (40%-100%), S/C (Short time delay & instantaneous both) and E/F (min. 20% range with neutral current monitoring) fault protections with independent adjustable current & time settings &separate LED indications / LCD display for independent fault indications.
Metering - Digital multifunction meter for incomer of each MCC and digital ammeter for each soft starter outgoing feeder. Indication - LED type indication for RYB, ON, OFF & TRIP.
Push Button for each motor starter feeder - ON & OFF
Wiring - Flexible FRLS copper wire/cable.
Potential free contact for remote tripping and indication/metering.
The MCC shall have following configurations:
-
-
-
Incomer: 250 A, TP MCCB (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 250 A
Outgoings:
(1) 40 HP soft starter along with arrangement to operate as external D.O.L. starter mode in line with SLD :- 3 No.
(2) 7.5 HP D.O.L. starter motor feeder :-1 No.
(3) 100 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 Nos.
(4) C-Curve 63 A FP MCB (Ics ≥ 10 kA) - 2 Nos.
(5) C-Curve 63 A DP MCB (Ics ≥ 10 kA) - 4 Nos.
1
-
-
Incomer: 400 A, TP MCCB (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 400 A
Outgoings:
(1) 30 HP soft starter along with arrangement to operate as external D.O.L. starter mode in line with SLD :- 1 No.
(2) 20 HP soft starter along with arrangement to operate as external D.O.L. starter mode in line with SLD :- 4 No.
(3) 7.5 HP D.O.L. starter motor feeder :- 1 No.
(4) 100 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 2 Nos.
(5) C-Curve 63 A FP MCB (Ics ≥ 10 kA) - 2 Nos.
(6) C-Curve 63 A DP MCB (Ics ≥ 10 kA) - 4 Nos.
1
-
-
Incomer: 250 A, TP MCCB (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 250 A
Outgoings:
(1) 20 HP soft starter along with arrangement to operate as external D.O.L. starter mode in line with SLD :- 3 No.
(2) 7.5 HP D.O.L. starter motor feeder :-1 No.
(3) 100 A TP MCCBs (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 Nos.
(4) C-Curve 63 A FP MCB (Ics ≥ 10 kA) - 2 Nos.
(5) C-Curve 63 A DP MCB (Ics ≥ 10 kA) - 4 Nos.
1
-
-
Incomer: 125 A, TP MCCB (Ics ≥ 36 kA) with Microprocessor based trip release for O/L, S/C & E/F protection - 1 No.
TPN copper bus bar - 125 A
Outgoings:
(1) 3 HP D.O.L. starter motor feeder :- 5 No.
(2) C-Curve 63 A FP MCB (Ics ≥ 10 kA) - 2 Nos.
(3) C-Curve 63 A DP MCB (Ics ≥ 10 kA) - 4 Nos.
1
-
-
Supply, Installation, Testing & Commissioning of concealed in wall/surface mounted MS prefabricated and powder coated VTPN power distribution board with all switchgears, accessories & required hardware having IP42 protection class. The switchgear (MCB/MCCB) and distribution board enclosure shall be selected with identical make in line with list of prefferred make of material.
Incomer: 250 A TP MCCB (Ics ≥ 36 kA) with Microp. trip release for over load & short circuit protection Outgoing: 63 A TP MCB (10 kA) -12 Nos.
12 way/phase VTPN DB
3
-
-
End termination of 1100 volt voltage grade Aluminium Armoured XLPE/PVC power cable by using double compression Nickel Plated Brass Gland, Aluminium Small/Medium/Long barrel Lug and earth clamps duly connected to the equipment ground through GI/Copper Conductor. This includes Supply of end jointing materials with all accessories.
-
-
-
3.5 C X 400 sq. mm.
6
-
-
3.5 C X 240/150 sq. mm.
35
-
-
3.5 C X 120/95/70/50 sq. mm
70
-
-
3.5 C X 35/25 or 4 C X 25/16/10/6/4 sq. mm.
70
-
-
Stuctural Steel work including supply, cutting, fabricating, welding, necessory scaffolding erecting & fixing in position, including painting with a primer coat of approved steel primer.
1200
-
-
Supply and Installation of ladder type GI cable tray of 100 mm side channel & 300 mm wide.
70
-
-
Only Installation, Testing and Commisioning of 1100 V voltage grade Aluminium XLPE insulated, Armoured, FRLS PVC sheathed power cable on wall/trench by supply and fixing of clamps and other required hardware.
-
-
-
3.5 C X 400/240/150/120 sq. mm. cable
700
-
-
3.5 C X 70/50 sq. mm. cable
700
-
-
3.5 C X 35/25 or 4 C X 25/16/10/6 sq. mm. cable
800
-
-
Dismantaling and stacking of ACB/SFU/MCCB based Power Control Centre (PCC)/Motor Control Centre (MCC) having following size including removal of switchgears, Cu/Al bus bar, end termination of power cables etc. and safe storig within the 2.5 km radius with suitable vehicle.
-
-
-
Size of panel (2.1 x 2.1 x 0.4) to (4.0 x 4.0 x 0.5) mtr.
16
-
-
Size of panel (0.5 x 0.5 x 0.3) to (1.0 x 1.0 x 0.3) mtr.
10
-
-
Removing & reinstallation of following size of electrical armoured power cables connected in L.T. panels, already installed in cable tray/hume pipe/MS support/Trench etc. including disconnection of end termination from old panel, re-installation of L.T. electrical power cables in the wall & trench for new panel by supply and fixing of clamps and other required hardware.
-
-
-
3.5 C X 400/240/150/120 sq. mm. power cables.
650
-
-
3.5 C X 70/50/35/25 or 4 C X 25/16/10/6 sq. mm. power cables.
1000
-
-
Supply, installation, testing and commissiong of straight through joint of following sizes of 1100 V voltage grade Aluminium PVC/XLPE insulated, Armoured, PVC sheathed power cable by using appropriate jointing kit.
-
-
-
3.5 C X 400/240 sq. mm.
4
-
-
3.5 C X 150/120/95/70/50 sq. mm.
10
-
-
Supply and installation of G. I. strip/wire of required size under ground at a depth of 600 mm from FGL including excavation, black bitumin painting, backfilling and consolidation of soil. Installtion along cable trays / walls using G. I. clamps/Saddle & spacer at interval of 500 mm / as per site requirements including required hardware.
500
-
-
Supply, installation, testing & Commissioning of sheet steel panel and M. S. boxes with complete chemical and mechanical process on M. S. sheet or angle etc. Powder coated, rubber, gasket, locking arrangement, earthing bolt etc. shall be provided on the fabricated item as per requirement and specifications.
500
-
-
Removing of following 1100 V voltage grade Aluminium PVC/XLPE insulated, Armoured, PVC sheathed electrical power cables already installed in L.T. panels including disconnection of end termination from old panel, from wall & trench & safe storing within the 2.5 km radius with suitable vehicle.
-
-
-
3.5 C X 400/240/150/120 sq. mm. cable
900
-
-
3.5 C X 70/50/35/25 or 4 C X 25/16/10/6 sq. mm. cable
1100
-
-