Police Department Tender
Know all about the latest MP tenders along with the tender details and downloadable document on BidAssist. Here, on this page, we shall help you search for every MPtender posted on the official website of mptenders.gov.in according to authority, district, etc. Be it an irrigation tender or MP PWD tender, and we will tell you how to bid for these and more.
Police Department Tender
Eprocure
Opening Date3 Jan 2019
Closing Date24 Jan 2019
Tender Amount₹ 4,41,44,000
Costs
EMD
₹ 4,41,440Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2018_MPPHC_657_1Bid Award Id
ViewTender No
08/2018-19 (III)Tender Authority
Police Department ViewPurchaser Address
-Website
http://http://www.mppolice.gov.in/en
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
H Beam 13 Mtr Long 152x152 or 150x150 mm 37.1 Kg/Mtr. Weight
40
-
-
H Beam 11 Mtr Long 152x152 or 150x150 mm 37.1 Kg/Mtr. Weight
18
-
-
R.S. Joist 9.3 Metre 175X85MM 19.6 KG/Mtr
7
-
-
STAY SET Supplying and erection of GI/MS stay set complete with stay rod, anchor plate of size 300x300x5mm, thimble, stay clamp, turn buckle, bow tightener etc. with stay wire, strain insulator, nut bolts as per specifications including excavation in all type of soil/ rocks and foundation in cement concrete 1:3:6 of required size and other necessary materials complete as required as per specifications
-
-
-
GI Stay Rod 20mm dia (Painted) 1.8 m long with 7/4.00 mm (7/8 SWG) stay wire for HT line
23
-
-
GI Stay Rod 16mm dia (Painted) 1.8 m long with 7/3.15mm stay wire for LT line.
16
-
-
33KV/11 KV DISC POLYMER L.ROAD TYPE T& C INSULATOR Supplying and fixing polymer type 11KV/33KV HT Disc (strain) insulator of approved make on existing pole or bracket with GI hardware and other necessary materials complete as required.
-
-
-
33 KV (45KN) Disc Polymer L.Rod type T&C Insulator with 33 KV Composite Polymer Strain set with hard ware suitable for panther conductor w L.ROD type T&C Insulator complete.
130
-
-
11 KV (45KN) Disc Polymer L.Rod type T&C Insulator with 11 KV Composite Polymer Strain set with hard ware suitable for panther conductor w L.ROD type T&C Insulator complete
30
-
-
POLYMER PIN INSULATOR Supplying and fixing polymer type 11KV / 33KV pin insulator with GI pin, of approved make on existing pole or bracket with other necessary materials complete as required.
(i) 11 KV 5 KN PIN Composite Polymer Insulator.
-
-
-
11 KV 5 KN PIN Composite Polymer Insulator.
30
-
-
33 KV 10 KN PIN Composite Polymer Insulator
24
-
-
33 KV 10 KN Polymer Pin Insulator
120
-
-
AAAC DOG Conductor 0.10 sq. inch (100sq. mm. Al.Eq) Supplying and drawing AAAC conductor of approved make with stringing making off complete with binding at existing insulator, jointing, jumpering, teeing off connecting etc. as required and clearing of obstacles (if any).
6690
-
-
AAA conductor Rabbit for jumpering
Supplying and drawing AAA conductor Rabbit for jumpering /guard wire/earth wire/bearer wire 18.62 mm sq (4.87mm dia/6 swg)conductor of approved make with stringing making of complete with binding at existing insulator, jointing, jumpering, teeing off connecting etc. as required and clearing of obstacles.
30
-
-
ACSR Panther Conductor 0.20 sq.inch (200 sq.mm. Al.Eq.) (30/3.00+7/3.00) Supplying and drawing ACSR/AAAC conductor of approved make with stringing making off complete with binding at existing insulator, jointing, jumpering, teeing off connecting etc. as required and clearing of obstacles (if any).
1600
-
-
DTR 11/0.4 KV CONVENTIONAL 3 STAR RATING TYPE 100 KVA,LUMINUM WOUND Supplying installing, connecting, testing and commissioning of 3 Phase, 50 Hz, 11/0.433 KV , Delta/Star connected, Aluminium/Copper wound, oil filled, Indoor/outdoor type, Distribution/Station transformer of accepted standard specifications, 3 star catagory class, with accessories such as drain & filter valve, earthing terminals, lifting arrangements of suitable size, dehydrating breather with silica gel of suitable size, Conservator tank, air release devise, Rating & diagram plate including CI rollers, Radiators with shut off valve, Cable end boxes on HT & LT side bushings, Explosion vent with diaphragm, Off load tap changing switch, Buchholz relay, thermometer pocket with 6” dial type thermometer & OTI, wherever required complete with first filling of oil with installation on existing DP structure or foundation etc. complete as per specifications. The no load and full load losses should not be more than as mentioned below.
1
-
-
LT DISTRIBUTION BOX WITH HRC FUSE FOR 100 KVA DTR Providing and fixing outdoor type pole mounting weather, dust and vermin proof LT distribution box made of 14 gauge MS sheet with clamping arrangements, lockable hinged door duly painted on all sides with red oxide after antirust and corrosion treatment, two coats of synthetic enamel paints of approved make and shade, consisting of following fittings
For 100 KVA Transformer
a) 160 Amps 25 KA breaking capacity TP MCCB with neutral link for incoming - 1No. b) 4 strip aluminium bus bar 160 Amps supported on epoxy insulators - 1 Set
c) 100/125 Amps, 415Volts DMC cutout with base for outgoing feeder with 160/200 amp HRC - 9 Nos.
d) GI earth terminals- 2 Nos
e) 6 Lever Godrej Padlock with 3 keys - 1 No.
f) Light point with switch and lamp holder with lamp - 1 No.
Distribution box complete as above (a to f) as per specifications complete.
1
-
-
EARTHING COIL OF 115 TURNS OF 50 MM DIA.2.5 MTR.LEAD OF 4.0 MM G.I.WIRE Providing and fixing earthing arrangement for HT/LT poles with 8SWG GI lead of 115 turns of 50 mm dia. connection with pole / cross arm / control junction box on pole with 4 mm dia. GI lead through 20 mm dia A class GI protection pipe of 2.5 m length duly bend, packing of charcoal powder and salt as per specifications including excavation of pit in all type of soil / rock, refilling of pit by black cotton soil etc. complete.
91
-
-
PVC Alluminium Armoured & XLPE Alluminium Un Armoured CABLES Supplying, laying, testing and commissioning of XLPE insulated and PVC sheathed heavy duty power cable confirming to IS 7098/Part-I/88 with latest amendments, 1100 volts grade armoured cable of approved make with aluminium solid / stranded conductor. The cable shall be laid in air/in existing pipe/in existing cable trench/on existing cable tray with clamp as required as per specifications including providing of metal/PVC cable identification tags at both ends and every 10 Mtr. length of cable with inscriptions there on.
-
-
-
XLPE HT 3 Core 11 KV Alluminium Armoured cable 300 sq.mm
2120
-
-
PVC Cable 2 Core Alluminium Armoured 2.5 SQ.MM
100
-
-
PVC Cable 4 Core Alluminium Armoured 16 SQ.MM
100
-
-
XLPE LT Single-Core Alluminium Un armoured cable 70 Sq.mm
80
-
-
XLPE LT single -Core Alluminium Un armoured cable 150 Sq.mm
40
-
-
ANTI CLIMBING DEVICE BARBED WIRE
Supplying and fixing 2 ply 12 gauge barbed wire around the existing HT/LT electric pole for safety measures as per IE rules including all stapples and all other necessary materials complete as required as per specifications.
31
-
-
DANGER BOARD ENAMELED Providing and fixing enamelled danger caution plate/board on existing electric poles or wherever required of size 250x200 mm, made of 1.6mm thick mild steel sheet and vitreous enamelled white, with latest, figures and the conventional skull and cross-bones in signal red colour (as per IS-5-1978 with latest amendment) on the front side. The rear side of the plate shall also be enamelled. The corner of the plate shall be rounded off with required material such as screws, wires clamps, nut bolts etc. complete.
-
-
-
11 KV
1
-
-
33 KV
48
-
-
Supplying Installatin Testing and Commissioning of D.P. structurre over existing support with painting in an approved manner consisting of following:
(a) D.C. cross arm with clamp and nuts bolts (100x50x6mm channel) – 1Set
(b) 11KV D.O. fuse unit, lighting arrester and A.B. switch mounting channels with nuts and bolts (75x40x6mm channel) as required –1 set.
(c) Transformer mounting cross arms with clamps nuts and bolts (100x50x6mm. Channels) – 1 set.
(d) Transformer clamping set with nuts and bolts etc. complete. (50x50x6mm1 set.
(e) Transformer belting set with nuts and bolts etc. complete. – 50x50x6mm angle 1 set.
(f) Distribution pannel mounting channel and clamp with nuts and bolts etc. (75x40x6mm channel).-1 set
(g) G.I. Pipe/bend as required for cable laying. -1 Job
(h) S/f DTR metering -LT 3 phase 4 wire 3x240 volts IB=5 amps lmax x 10 amp, trivector meter class of accuracy 0.5s, DLMS Compliant category A Meters along with GSM (GPRS compatible) modem with box as per specifications complete.
(i) G.I. pipe earthing complete with G.I. strip 25x3 mm as required complete.7 Nos.-1 Set
(j) A.B. Switch single phasing 400 AMP as per specifications. 1 Set
(k) L.A. polymer type as per specifications complete. (l) 11 KV 200 Amps DO Fuse (3.nos) 1 Set (m) 11 KV gap less polymer type LA (3.nos) 1 set
(n) D.P. structure Complete as above (a to m)
1
-
-
GUARD WIRE Supplying and drawing G.I. guard wire / bearer wire / earth wire including stringing, binding at existing insulators or brackets, jointing, jumpering, connecting etc. as required and clearing of obstacles (if any).
6 SWG (4.87 mm dia)
1200
-
-
CARPET GUARDING Supplying and erection of G.I. guarding of required size on existing HT/LT lines as required as per specifications. (A) Carpet/Cradle type
6 SWG (4.87mm. dia.)
60
-
-
Jointing sleeves suitable for conductors supply & fixing jointing sleeves suitable (ALUMINIUM) for DOG Conductor
14
-
-
Aluminium Binding Wire and Tapes
upply & fixing of Aluminium Binding Wire and Tape complet as per specifications.
14
-
-
Outdoor Heat Shrinkable Cable Jointing Kit Supply installation testing and commission of Outdoor Heat Shrinkable Cable Jointing Kit with Lugs for 11 KV Grade XLPE Cable For 3 Core 300 SQ. MM
10
-
-
SITC Earthing set of LA & Link Box 3 Meter long 100 MM Dia thickness 13.1 MM Cast Iron (CI) pipe along with GI Flat 50X6 MM
9
-
-
SITC Straight Through Heat Shrinkable Cable Jointing Kit with Lugs for 11 KV Grade XLPE Cable for 3 Core 300 SQ.MM
2
-
-
SITC END TERMINATION SUITABLE FOR 11 KV 3 CORE 150 SQ.MM UNDERGROUND XLPE CABLE
80
-
-
Supplying and fixing of angle / channel / flat iron / RS Joist fittings for over head lines as cross arms / brackets / clamps etc. including nut bolts, required holes, welding, cutting, fabricating with necessary materials including two coats of red oxide and two coats of aluminium or synthetic enamel paint etc. as required.
19576.26
-
-
Supplying installing, testing and commissioning of 11 KV Ring Main Unit (RMU) SF-6 type (1 circuit breaker 3 isolator) Complete as per specifications.
2
-
-
PACKAGE TRANSFORMER 630 KVA,11/433 V DYn11,dry type ,copper wound transformerHT & LT with Off load tap link ,rating +5 to -5% @2.5% with complete Ht RMU ,LT pannelOutdoor type enclosure internal interconnection & earthing.
Compact secondary sub-station (CSS):-Supplying installing, testing and commissioning of star rated (Ltest updated )out door type ready made compact secondary sub-station (CSS) complete with copper wound, dry transformer , corrugated tank, 11/0.433 KV sealed unit, top bushing for HT & LT with off load tap switch including making plate form of reinforced cement concrete of 1:3:6 ratio of suitable length and width and 1.0 meter depth (as desired) below ground level and 0.50 metre above ground level with excavation in all type of soil/rock up to 1.20 metre depth finishing,150 mm. dia. PVC pipe in concreting for entry and exit of cable complete with Ronis key inter locking system . The compact transformer sub-station consisting of following equopment/materials/accessories :--A) HT switch gear :- 3 way, 11 KV, 20 KA for 3 sec. SF6 insulated Ring Main Unit compact switch gear consisting of two nos. of fixed manual load break switch and 1 No. fixed manual circuit breaker in SF6 insulated enclosure with series trip, self powered microprocessor based numerical over current and earth fault protection relay complete . Inter connection between HT switch gear and transformer shall be of 1 core x 3 cable x 95 sqmm. Aluminium unarmoured HT XLPE cable. B) Transformer :- Star rated (latest updated) 630 KVA 11/0.433KV, 3 Phase DYn11, dry type, hermetically sealed transformer copper wound with corrugated wall design and top bushing for HT & LT with off load tap switch arrangement of rating +5 to -5 @2.5% including racing cost ring type LTCT of 1000/5 Amp. of 1.0 class accuracy and 5 VA burden. C) LT panel :- 433 V LT Indoor panel , Alluminium/copper bus bar, fabricating using 14 SWG CRCA M.S.sheet ingress protection IP4X, complete with internal wiring and consisting of 1 No.1000 A, 433V, 3 Pole, 50 Hz., 50KA fixed type vaccum circuit breaker with microprocessor based over current and earth fault protection relay as incomer and 06 Nos.320 Amp. 36 kA breaking capacity TP MCCBwith thermo magnetic base release as outgoing. D) Three phase LT DTR meter with meter box :- CT operated three phase , 4 wire , 0.5S accuracy class LTDTR enery meter with LPR feature including GSM,modem etc with 04 nos.resin moulded 300/5 ratio LTCT CALIBRATED FROM MPWKVV .CO.( calibration charges will be bourn by agency) , 3 phase meter box of suitable pattern as per MPWKVV .CO.requirement, fabricated with 14 SWG CRCA MS sheet , suitable space to accommodate LPR type LT DTR meter with CT's including mounting plate/strip for energy meter, glass window for meter reading, incoming/outgoing cable, connection with proper size of lugs, earthing terminals etc. complete . E) Out door enclosure :- outdoor type enclosure having GI sheet of 14 SWG with base frame sufficient to carry the load of HT switch gear, transformer and LT switch gear while lifting. The enclosure shall have IP54 degree of protection for HT & LT switch gear compartment and IP23 degree of protection for transformer compartment. The enclosure exterior shall be painted with paint suitable for outdoor application, each compartment will be provided with the door and pad locking arrangement and illumination lamp with door operated switch shall be provided for each compartment and interconnection between HT switch gear & Transformer shall be by using cable and Transformer & LT switch gear shall be by using busbar, internal earthing connection by GI strip and earth terminal as required as per specifications. (Make - ABB, SCHNEIDER,SIEMENS,)
8
-
-
SITC Shield Cable From Control Panel to RTU Panel complete as per specifications
1000
-
-
CAT 6 CABLE
Supplying installing, testing and commissioning of CAT 6 CABLE ISI mark Complete
87.96
-
-
Supplying of T&P required for 33/11 KV sub-station like 30 feet long double sliding aluminium ladder, DC and tubular spanner set, hand gloves, discharge rod, three ton capacity tirfur, insulated screw driver set, two ton capacity chain pully block, insulated cutting plier set, hammer (1 kg.), phawara, pickaxe, crobars, rechargeable torch, magger, electrical tool kit, earth tester, first aid box etc complete as per specifications.
1
-
-
EARTHING OF NEW 33/11 KV S/S Providing and fixing earthing arrangement with CI/Copper/ Galvanized iron plate electrode, including packing of char coal powder and salt providing GI watering pipe 20mm dia of 2.4 m length from brick chamber upto electrode having 6 mm dia holes all around as required including making connections refilling the pit by black cotton soil as required as per specifications including excavation of pit of required size and 3 m depth in all type of soils/rocks, providing brick masonry chamber of size 450x450x300mm, CI frame, cover with locking arrangement, wire mesh funnel etc. complete as per specifications.
-
-
-
600 x 600 x 6 mm GI plate electrode
55
-
-
600 x 600 x 3 mm Copper Plate electrode.
10
-
-
EARTH STRIP :- Supplying, laying and connecting of GI/copper earth strip duly installed on wall/cable tray/beam/column with suitable size of clamps or in trench including excavation in all type of soil/rock upto 500mm depth and refilling the same, joints/connections of the strips shall be made by using nut, bolts, washers/by riveting/by soldering as required. Dissimilar metal joints shall have suitable bimetallic connectors etc. complete with fixing accessories and Corrosion protection of buried conductor with bituminous coating.
-
-
-
50X 6 G.I. STRIP
400
-
-
600 x 600 x 3 mm Copper Plate electrode.
150
-
-
FIRE EXTINGUISHER CARTRIDGE CO2 10 KGS
Supplying and fixing of following type of ISI mark fire extinguisher with required clamps and other material complete as required.10 kg. BC CO2 type.
1
-
-
Supplying and installation of fire G.I. Buckets 3 Nos. duly painted with red oxide and synthetic enamel paint and filled with sand and stand complete as required as per specifications..As per enclosed drawing No.2
3
-
-
33/11 KV POWER TRANSFORMER ,OFTC TYPR 5000 KVA LOSS (4KW+23KW)
Supplying installing, connecting, testing and commissioning of 3 Phase, 50 Hz, 33/11 KV, Delta/Star connected ONAN cooling, step down, Copper wound, oil filled, Indoor/outdoor type, power transformer of accepted standard specifications with accessories such as drain & filter valve, earthing terminals, lifting arrangements of suitable size, dehydrating breather with silica gel of suitable size, Conservator tank, air release devise, Rating & diagram plate, CI rollers, Radiators with shut off valve, Explosion vent with diaphragm, Off load tap changing switch, Buchholz relay, thermometer pocket with 6” dial type thermometer & OTI including Cable end boxes on HT & LT side bushings wherever required complete with first filling of oil with installation with foundation etc. complete as per specifications. The no load and full load losses should not be more than as mentioned below. Power Transformer OFTC Type 33/11 KV, 5 MVA (NLL-4.0 KW and FLL-23KW)
2
-
-
VACCUM CIRCUIT BREAKER Supplying, installation, testing and commissioning of triple pole outdoor type 11KV / 33KV vaccum circuit breaker with outdoor control box, indoor control relay pannel for VCB and transformer protection and mounting structure for VCB and CTs complete as required. The indoor control relay panel shall consisting of Ammeter, Voltmeter, Selector Switch, auxilliary relays for anti pumping device, trip and alarm of buchholz relay, oil and winding temperature circuit, electronic hooter, KWH meter, 230 V AC to 110 V DC power pack for closing, tripping and indication, triple pole IDMTL two O/C and one E/F delay with current setting range 50-200% and 10-50%, push button high speed trip rely etc. complete. The installation of VCB shall be carried out in accordance with IS:3072. The VCB shall be mounted on suitable size duly painted MS channel / angle iron structure with nut bolts and washer. The structure shall be fixed on existing cement concrete foundation. The complete work should be done as per IS specifications.
-
-
-
33 KV
4
-
-
11 KV
6
-
-
SITC 33 KV CT OUTDOOR TYPE 200-100/ 5AMP AS PER specifications.
6
-
-
SITC 33 KV CT.(out door type) 300-150/5 Amps AS PER specifications.
6
-
-
SITC 33 KV CONTROL & RELAY PANEL WITH SCADA COMPATIBLE FOR TRANSFORMER PROTECTION AS PER specifications.
2
-
-
SITC 33 KV CONTROL & RELAY PANEL WITH SCADA COMPATIBLE FOR FEEDER PROTECTION (FOR 1 FEEDER) AS PER specifications.
2
-
-
SITC 11 KV.C.Ts.(Outdoor type) 200-100/5 Amps as per specifications.
12
-
-
SITC 11 KV.C.Ts.(Outdoor type) 300-150/5 Amps as per specifications.
6
-
-
SITC 11 KV CONTROL & RELAY PANEL WITH SCADA COMPATIBLE FOR TRANSFORMER PROTECTION (1T) AS PER specifications.
2
-
-
SITC 11 KV CONTROL & RELAY PANEL WITH SCADA COMPATIBLE FOR FEEDER PROTECTION (2F) AS PER specifications.
2
-
-
SITC 11 KV CONTROL & RELAY PANEL WITH SCADA COMPATIBLE FOR FEEDER PROTECTION (1F) AS PER specifications.
2
-
-
SITC WINDING TEMP. INDICATOR (WTI) (SCADA/LDMS COMPATIBLE THROUGH RS-232 & 485 PORT) AS PER specifications.
2
-
-
SITC OIL TEMP. INDICATOR (OTI) (SCADA/LDMS COMPATIBLE THROUGH RS-232 & 485 PORT)
2
-
-
SITC REMOTE TERMINAL UNIT (RTU) INCLUDING SOFTWARE FOR 2 NO. POWER TRANSFORMER AS PER specifications.
1
-
-
SITC DC VOLTAGE TRANSDUCER AS PER specifications.
10
-
-
SITC RTU BASE AND FOUNDATION (BASE SHOULD BE CAPABLE OF WITH STANDING 200 KG. LOAD )
1
-
-
SITC ROUTER 230 V AC, 2 GE ports, 48xFE, WAN speed 200 Mbps AS PER specifications.
1
-
-
SITC 2 Mbps VPN LINK FOR CONNECTIVITY FOR S/S WITH SCADA CONTROL CENTER AS PER specifications.
1
-
-
SITC LDMS/DESKTOP WITH UPS AS PER specifications.
Intel Core i7, Hard drive 2 TB 5400 rpm SATA Ram, 32 GB, windows 10 Operating System with HD Graphics and UPS 3KVA/ 72 V.
1
-
-
SITC 2KVA UPS (FOR LDMS ) WITH 160 AH, 72 V Battery set as per specifications
1
-
-
Supplying installation testing and commissioning of LASER PRINTER complete set.
Laser printer with 1 Hi-speed USB fast ethernet will all in one (Print, Scan, copy) up to 20 ppm
1
-
-
SITC 48V DC POWER SUPPLY (DCPS) SYSTEM BASED ON SMPS FOR RTU & COMM. EQUIPMENT WITH 80AH BATTERY
1
-
-
Supplying installation testing and commissioning of LDMS SOFTWARE COMPLETE
1
-
-
Supplying installation testing and commissioning of LEAD ACID BATTERY SET 30 VOLTS 200 AH COMPLETE
2
-
-
SITC BATTERY CHARGER 230 V AC INPUT 20 AMP, 30 V DC OUTPUT SOLID STATE TYPE COMPLETE
2
-
-
33 KV POLYMER LIGHTNING ARRESTER Supplying, installation, testing and commissioning of station/ distribution class, thyrite magne valve,0.10 W/KV watt loss polymer lightning arrester with earthing neutral system. Arrester shall be rated at 30 to 37 KV for 33 KV supply ( Set of three numbers for 3 phases) 33 KV polymer Station Class LA
12
-
-
11 KV LA POLYMER TYPE GAPLESS /METAL OXIDE 9 KV , 10 KA SUBSTATION Supplying, installation, testing and commissioning of station/ distribution class, thyrite magne valve,0.10 W/KV watt loss polymer lightning arrester with earthing neutral system.Arrester shall be rated 9 to 15 KV for 11 KV supply ( Set of three numbers for 3 phases) 11 KV LA POLYMER TYPE GAPLESS /METAL OXIDE 9 KV , 10 KA SUBSTATION TYPE AS PER specifications.
18
-
-
CHEQURE PLATE :Supplying, fabricating and installation of 6 mm thick MS chequered plate of required size with hook and finishing the same as required.
800
-
-
33 KV OIL IMMERSED 3 PHASE 4 WIRE CTPT combined UNIT HAVING RATIO 400/200/5 WITH 0.5 accuracy
Supplying, installation, testing and commissioning of 33 KV OIL IMMERSED 0.5 accuracy class 50 Hz.CT PT combined unit complete with all material required in including testing calibration charges of electricity board as required.
2
-
-
Supplying, installation, testing and commissioning of 11 KV OIL IMMERSED COMBINED CT:PT UNIT (ME) OF ACCURACY CLASS OF 0.5S WITH CT RATIOO 200-100/5 AMP AS PER specifications.
4
-
-
PROVIDING AND FIXING 5 HP SUBMERSIBLE PUMP
Providing new submersible pump of three phase 5 HP (30 stages to 36 stages ) of standard ISI make.Providing Starter Panel of reputed make like L&T ,Havells or equivalent make having single phase protection ,over load protection ,pre- set timer of L&T make star delta starter ,Indications for load currents in all three phases ,indications for supply voltage in all three phases etc.starting panel must confirm to IP 52 proction for encloser.it should be mounted indoor inside the control room on 50x50x6 mm MS angle supports .Start panel must be earthed with 2Nos.8SWG wires,4 core 16 sq.mm aluminium armored cable must be used for energizing this start panel.Three phase ,4 wires,copper flexiable supply cables suitable for submersible pump opertaion of approved ISI make,1100 V grade should be connect to submersible pump through under ground trench up to the well as per CPWD specifications duly protected from brick and sand cushioning.A Heavy duty gunmetal wheel valve (tap) may be provided on the discharge line for drinking water requirements.provvision for lifting the pump in case of overhauling/breackdown maintenance may also be provided.ISI marked 2nd class G.I.pipes with heavy duty sockets and othe fittings,are to be used for suction as well as discharges water lines.An open drain must be provided in the vicinity of the tube well.detail arrengement shall be finalized in detailed engineering.The cable from tube well to control panel shall be encased with GI pipe of medium grade of 40 mm dia.including excavation of trenches,laying of GI pipe and refilling of trenches complete.The drilling of Tube well shall be done to a depth at which sufficient yeild of water is available as per resistivity survey report ,to meet out the water requirement for earthing,Toilet and drinking purposes.Pipe line Medium class GI pipe and heavy duty pipe fittings are to be used for water supply system .steel taps are to be provided in the toilet.for earth pit water supply heavy duty wheel valves shall be provided.pipe connection made out of 1" and 1/2 " dia.GI pipes of medium class ISI marked quality must be eextended up to the power transformer locality for watering requirments of earth pits.arrengements shall be finalized during details engineering.
1
-
-
11 KV/3/110/3 Volts PT SINGLE PHASE OUTDOOR TYPE
Supplying, installation, testing and commissioning of oil filled out door type single phase, 50 Hz 11 KV/110V, 100VA burden, class 1.0 voltage transformer complete.
6
-
-
SITC HT METER For substation metering- 3 phase 4 wire 3x63.5 volts lb=5 amps Imax = 10 amp, HT trivector meter class of accuracy 0.5s, DLMS Compliant category A Meters along with GSM (GPRS compatible ) modems, complete.
6
-
-
SITC SHEET METAL METER BOX SUITABLE FOR H.T. STATIC TRAVECTOR METERS WITH TTB AS required as per specifications.
6
-
-
LED LAMP 90 WATT WITH TUBLAR POLE 7 MTR. HEIGHT. Supplying and erection of steel tubular pole swaged type as per IS:2713 1980 Complete with baseplate and top Canopy (with G.I. pipe bracket as required), supports complete with digging and keeping it in truly vertical position i/c digging pit of required size filling with 1:3:6 cement concrete of 0.60 meter dia. of required length around the pole i/c muffing of 0.45meter from ground level as per specifications with 20cm.thick base foundation providing and busying 15mm.dia.G.I.pipe from bottom to 1.5meter above ground level on pole, refilling the pit i/c. painting of pole with bitumen paint in bottom and one coat of red oxide and two coat of aluminum paints etc. complete as per specifications. The depth of foundation shall be1/6th of the length of pole with 90 watt LED lamp complete.
10
-
-
Supplying, installation, testing and commissioning OF T CLAMP ALUMINUM FOR BUS BAR PANTHER RUN PANTHER TAP.
120
-
-
SITC BIMETALLIC CLAMPS FOR POWER TRANSFORMER OF BRASS FLAT 50x50x10MM
120
-
-
SITC Three phase 20-80 Amps.with L.S. & TOD Facility with box as per specifications.
1
-
-
SITC COPPER CONTROL CABLE 12 CORE, 2.5 SQMM PVC UNARMORED
1500
-
-
SITC COPPER CONTROL CABLE 8 CORE, 2.5 SQMM PVC UNARMOURED
1500
-
-
SITC COPPER CONTROL CABLE 4 CORE, 2.5 SQMM PVC UNARMOURED
1500
-
-
SITC COPPER CONTROL CABLE 2 CORE, 2.5 SQMM PVC UNARMOURED
1000
-
-
11 KV 1500 KVAR capacitor bank including associatd equipments such as 11 KV VCB,CONTROL PANEL,11 KV CT ,WITH ADEQUATE METERING..MATCHING RVT ,SUITABLE GAPLESS LA NECESSARY CABLES FOR SUCCESSFUL COMMISSIONING COMPLETE.
SITC 11 KV 1500 KVAR AUTO SWITCH CAPACITOR BANK INCLUDING ASSOCIATED EQUIPMENTS SUCH AS 11 KV VACUUM CIRCUIT BREAKER, CONTROL PANEL, 11 KV OUTDOOR CURRENT TRANSFORMER WITH ADEQUATE METERING & PROTECTION CLASS OF SERVICE, BUS & EQUIPMENT ISOLATORS WITH EARTH SWITCH, MATCHING RVT, SUITABLE GAPLESS LIGHTENING ARRESTORS, NECESSARY CABLES FOR SUCCESSFUL COMMISSIONING COMPLETE AS PER SPECIFICATIONS
2
-
-
Supplying, installation, testing and commissioning of Electro-mechnical isolation contacts complete.
20
-
-
33 KV Isolator 600 Amp .(TURN & TWIST TYPE ISOLATOR) Supplying installation testing and commissioning of 600 Amp.(TURN & TWIST TYPE ISOLATOR) triple pole outdoor type two stack and three Insulator padestals per phase, manual operated rotating type Isolator complete with fixed and moving contact of hard drawn electrolytic copper flat, 8 mm dia GI rod for fixed and moving arching horn, 32 mm dia GI pipe for operating handle, 19mm dia GI pipe for phase coupler,brass bush and trust bearing, isolator base channel, post insulator, padlock with key, earth/without earth switch and other required accessories etc. complete as required. 33 KV Isolator 600 Amp with earth switch (set of 3 Nos. for 3 phases)
7
-
-
11 KV Isolator 800 Amp (TURN & TWIST TYPE ISOLATOR) Supplying installation testing and commissioning of 800 Amp.(TURN & TWIST TYPE ISOLATOR) triple pole outdoor type two stack and three Insulator padestals per phase, manual operated rotating type Isolator complete with fixed and moving contact of hard drawn electrolytic copper flat, 8 mm dia GI rod for fixed and moving arching horn, 32 mm dia GI pipe for operating handle, 19mm dia GI pipe for phase coupler, brass bush and trust bearing, isolator base channel, post insulator, padlock with key, earth/without earth switch and other required accessories etc. complete as required. 11 KV Isolator 800 Amp with earth switch (set of 3 Nos. for 3 phases)
12
-
-
Direct Curent Distribution Board (DCDB) 24 Volts Indoor floor / wall mounted comprising of 1 No. 2P/100A DC MCCB 5A Switch Fuse Unit as incommer and 8 No. 2P/40A MCCB 5A switch fuse units
Supplying, fixing, testing and commissioning of wall/floor mounted LT metering and distribution cubical panel, weather,dust and vermin proof, seven tank treatment process, 100 micron powder coating, suitable for 415 volt 3 phase 4 wire 50 Hz. system, fabricated out of CRCA 1.6mm thick sheet (1.2mm for doors and partition) with base frame of angle /channel iron, necessary support of slot angle/plates/MS plates, conduits as required duly compartmentalized for incomer, bus section, outgoings, cable alleys, energy meter etc. suitable cutout for ammeter, voltmeter, selector switch, frequency meter, phase indicating lamp, energy meter, push button etc. complete as required. The rate include for supply and fixing DMC/SMC supports, earthing terminals, detachable gland plate with knock out, door knob/industrial door lock, internal control and power wiring with required size of copper cable, lugs, complete with nut, bolt, washer, providing name plates of all chambers etc. as per approved design, pattern and specifications comprising of Direct Curent Distribution Board (DCDB) 24 Volts Indoor floor / wall mounted comprising of 1 No. 2P/100A DC MCCB 5A Switch Fuse Unit as incommer and 8 No. 2P/40A MCCB 5A switch fuse units for each individual outgoing circuit of indoor control panels, indoor/outdoor VCB panels, 1 No. 2P/40A MCCB 5A switch for control room emergency DC lighting including 20% as spare. Each incoming & outgoing shall have indicating lamp complete.
1
-
-
ACDB 415 V, along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 1No. 200 Amps TPN switch fuse unit as incomer
Supplying, fixing, testing and commissioning of wall/floor mounted LT metering and distribution cubical panel, weather, dust and vermin proof, seven tank treatment process, 100 micron powder coating, suitable for 415 volt 3 phase 4 wire 50 Hz. system, fabricated out of CRCA 1.6mm thick sheet (1.2mm for doors and partition) with base frame of angle /channel iron, necessary support of slot angle/plates/MS plates, conduits as required duly compartmentalized for incomer, bus section,outgoings, cable alleys, energy meter etc. suitable cutout for ammeter, voltmeter, selector switch, frequency meter, phase indicating lamp, energy meter, push button etc. complete as required. The rate include for supply and fixing DMC/SMC supports, earthing terminals, detachable gland plate with knock out, door knob/industrial door lock, internal control and power wiring with required size of copper cable, lugs, complete with nut, bolt, washer, providing name plates of all chambers etc. as per approved design, pattern and specifications comprising of ACDB 415 V, along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 1No. 200 Amps TPN switch fuse unit as incomer, 1No. 63 Amp. TPN MCCB switches as outgoing feeders & 2No. 32 Amp. MCCB as outgoing for yard and control room lightining and 6 No. 16 No. MCCB for control panels, Each incoming & outgoing shall have indicating lamp. including 20% spare complete
1
-
-
Supplying and Laying in position of ISI marked rubber mat rated for 1100 volts grade and 12.5 mm thick. Size 1000 mm x 2000 mm.
5
-
-
YARD FENCING WITH CHAIN LINK FENCING Fencing of substation land to be provided using chain link mesh (75x75x8 G) wire mesh fencing ,confirming to IS :2721/199 (top and bottom wires should be 4mm dia,sizeof chain link mesh 75x75 mm,gauge of chain link mesh wire 8 SWG),with post made of 65x65x6mm Mild steel angle of over all length (2400+450+175+1000)=4025mm for fixing fencing post angle 65 x 65 x 6 mm, column footing foundation shall be provided at centre to centre distance of 2400 mm in M-20 grade concrete after excavation depth of 2.50 m or up to suitable strata of required safe bearing capacity, footing shall be rest on layer of CC M7.5 of 100 mm thickness, the column size shall be 200 x 200 mm with 4 nos. steel bars of 12 mm dia up to ground level, after that at ground level plinth beam of size 200 x 350 mm shall be provided to prevent lateral movement of columns for overall length of chain link fencing, supporting horizontal angle at top & bottom of size45x45x5mm MS angle fixed with MS nut bolts and washer (30x100x3mm )fixes with mild steel Nut bolts(12mm diameter).three rows of barbed wire (9.35 kg/100RM) will be tied at the top 450mm bent portion of supporting angle 65x65x6mm .Individual barbed wire shall be lightened with the help of tension bow 10mm diameter at each section point.all angles should be painted with two coats of aluminium paint over a coat of red oxide zinc chromate primer.As per enclosed drawing No.3
145
-
-
FENCING OF S/S LAND WITH BARBED WIRE (As per Drawing No. 1)
145
-
-
YARD LEVELING BY KOPRA FILLING AND LAYING OF YARD 100 MM THICK METALLING WITH 40 MM SIZE B.T. IN BRICK INCASED AREA PLACED VERTICAL 100 MM ABOVE THE GROUND AND REMAINING PART OF THE BRICK KEPT INSIDE THE GROUND. As per the topography of the land it will be required to be leveled to arrive at the final leveled surface required for morrum spreading and metalling .The yard shall be leveled up to 150mm above average 'pacca'road level.The quanitity of leveling shall vary from place to place .For Leveling the contractor will be required to execute cutting and filling of earth up to the final level.The Leveling shall include excavation of soil within yard area and filling of selected earth from with watering and compaction in layers.No payment will be made separately for transportion of suitable earth filling.
YARD METALLING & MOORUM SPREADING: A sketch depicting these details is enclosed herewith .Yard metalling shall be executed using curb-stone of size 450x600x75 mm size.Switchyard area (covering buses ,power transformer ,station transformer,breakers,Isolator,capacitor bank,Lightning arresters ,gantry structure at 33 KV as well at 11 KV side etc.) is to be cleaned ,leveled and filled with 120mm thick layer of moorum followed by 80 mm bed of hard metal stone 40 mm size.The stone should not have stone dust /particles of less than defined size.The metal should be of best quality .Before filling surface should be cleaned and leveled.Gravel filling shall be up to one meter beyond the structure gantry area.Before providing gravel on the leveled surface ,employer's clearance must be obtained by the contractor .suitable measure may be taken to stop possibillity of spreading of stone beyond defined area may be by means of providing curb stone (450x600x75 mm) As per enclosed drawing No.4
410
-
-
150 MM DIA TUBEWELL After resistivity survey, The final location of the tube well will be finalized by The Engineer-in-charge, tube well shall be drilled with a minimum 150 mm dia, with M.S. Pipe casing up to collapsible strata of tube well, having minimum dischage of 4500 liter/ hour potability water testing shall be got done at Govt. lab at the cost of contractor.
1
-
-
SITC 1000 LITER P/F SINTEX OVERHEAD TANK & GI PIPE (WITH LENGTH OF 125 MTRS) FITTING FOR WATER SUPPLY INCLUDING PROVIDING WATER TAP(17 NO.) NEAR TRANSFORMER NEUTRAL EARTHING AS specifications
1
-
-
SUBSTATION CABLE TRENCH :-Preparation of permanent cable trench of required size including excavation in all type of soil/rock providing base concrete of 1:4:8 ratio of 20 cm thick size providing 50 mm dia PVC sleeve pipe in base concreting at 10 meter intervals intervals for clearing of water, 20 cm thick brick masonary wall on both side of trench of required height, plastering etc. complete with providing and fixing angle iron of 50x50x5mm size duly painted with two coats of red oxide, duly embedded in brick masonry at a distance of every 1 meter lengthwise in trench, above 20cm. from finished base of trench including providing and fixing of required size of flat clamps and removing of waste soil up to a lead of 50 meters.
-
-
-
300 X 400 mm ( Clear inside )
50
-
-
300 X 600 mm ( Clear inside )
150
-
-
450 X 750 mm ( Clear inside )
150
-
-
Earth work in excavation by mechanical means (Hydraulic Excavator) / manual means in all kind of soil, moorum, copra etc and for all types and sizes of foundations, drains, and trenches for pipes and cables with a free lead upto 50m and 1.5m lift, including disposed excavated stuff to be leveled and neatly dressed.
20
-
-
Providing and laying in foundation/plinth, mechanically mixed
1:2:4 (1 cement, 2 sand, 4 metal) cement concrete with 20 mm BT nominal size graded stone aggregates including ramming in layers, curing complete including cost of form work and cost of cement
20
-
-
Supply and fabrication of Iron work for reinforcement mild steel / tar steel, tested fixed in position complete i/c cutting, bending, all handling and binding with binding wire placing in position etc. complete
600
-
-
providing & fixing 11 KV underground cable Trench 750 x900 mm with Excavation ,Base Concreting ,Cable Support Angle ,Cover Chamber as Required as per specifications
170
-
-
SITC Stone Block/Pre cast block for base pedding 450x450x75mm complete for covering.
64
-
-
PROVIDING & FIXING PERFORATED G.I. CABLE TRAY 300X50 MM WIDE & 2 MM THICK FIXED ON 45X45X5 MM M.S. ANGLE STAND GROUTED IN C.C 1:24.As per enclosed drawing No.5
150
-
-
Furniture for control room Table 600mmx 900mm (Model T-32) - 1 No., Chair (Model CH-7B) - 3 Nos., Computer table (Model C-11) 1 No. (Godrej Make)
1
-
-
FLAG STONE Supplying and fixing of flag stone of following size as required.
-
-
-
900 X 450 X 50 mm
50
-
-
900 X 600 X 50 mm
150
-
-
600 X 600 X 50 mm
150
-
-
MS MAIN GATE AND WICKET GATE ON RCC COLUMN MS gate is to be provided at each substation as per drawing .The gate is to be fixed on 2 Nos.cement concrete RCC pillars 400x400mm size provided with 6 Nos.12 mm dia.tor steel reinforcement and 8 mm dia tor steel rings at 150 mmc/c.The height of piller will be 2400mm above ground level. Depth of the foundation for footing will be rest 2.50M.or up to suitable strata as per requiredsafe bearing capacity will be 2 meters.The centrally open able gate will be of length 4000mm.The gate will be made of 50x50 mm MS hollow pipe frame of heavy sectin ,10 mm square bars 100 mm c/c,2 mm thick CRCA sheet welded with 50x50mm MS hollow pipe .The name "Madhya Pradesh Paschim kshetra vidyut vitaran company limited"will be depicted on the sheet in hindi.Entire gate structure shall be de-rusted and painted using wire brush and emery paper etc.The surface shall be cleaned and painted with two or more coats of red oxide zinc chromate primer paint using painted brush,on smooth surface finish ,two or more coats of aluminium paint using painting brush shall be applied till final smooth surface finish and even shade on surface appears.The name MPPKVV CO. Ltd. shall be written using post office red paint of approved brand and shade having 250 mm height of letters.The wicket gate shall be size 1.0 mx2.0m.supported on RCC piller of size 400x400mm with vertical reinforcement as 6 No.,10mm dia tor steel bars and 8mm dia for steel rings at 200 mmc/c.Depth of the piller foundation will be 2 meters.The wicketgate will be made of 50 x50 mm MS hollowpipe frame of heavy section with 10mm square bars 100mm c/c,2mm thick CRCA sheet welded with 50 x50 mm MS hollow pipe,Entire gate structure shall be de-rusted and painted using wire brush and emery paper etc.The surface shall be cleaned and painted with two or more coats of red oxide zink chromate primer paint using painted brush .On smooth surface finish,two or more coats of aluminum paints using painting brush shall be applied til final smooth surface finish and even shade on surface appears.Thesuitable locking arrangements shall be provided for Main Gate and wicket gate.As per enclosed drawing No.6
1
-
-
CABLE ROUTE MARKER Supplying and fixing of cable route marker with 10x10cms. GI plate 5mm. thick with inscription thereon, bolted / welded to 35x35x6mm. angle iron 60cm. long and fixed the same in ground with cement concrete of 1:2:4 ratio as required.
5
-
-
MS SIGN BOARD,BAY INDICATION BOARD & RYB PHASE INDICATION BOARD A sign board in hindi laungauge ,depicting monogram of company and "madhya pradesh paschim kshetra vidyut vitran company ltd.Indore" Name of Substation /division /circle/location and maximum value of voltage in KVA rating of available equipment (like 33 kv ,2x5 MVA grid substation) in the substation should be provided in all substation.The sign board should be made of 2mm hick mild steel sheet ,65x65x8 mm MS equals angles for main supports having 3500 mm over all laying on length (1000 mm below ground level and 2500 above ground level),MS 35x35x5 mm equal angle for frame and MS 20x5 mm flat for support of CRCA sheet of mm thick over which name of substation and other detail will be depicted .The main support shall be grouted in400 x400 size piller and base plinth of 500x500x75 mm.Overall size of sign board will be 900x600 mm.The CRCA shall be painted with two coats of zinc oxide all around and thereafter two or more coates of base paints of approved shade and brand to be finalized in detailed engineering.As per enclosed drawing No.7
1
-
-
Concreting (1:3:6) of FOUNDATION OF VCB @ 3.5 CMT and Isolator Support Structure @ 0.1 CMT Per Structure floor finish with painting complete
103
-
-
APPROACH ROAD ,MADE BY 60 MM THICK FACTORY MADE CEMENT CONCRETE PAVER BLOCK OF M-30 GRADE ,ALONG THE CABLE TRENCHES UPTO VARIOUS EQUIPMENT IN THE YARD 1.00 metre wide M-30 grade made from vibratory compaction machine 60 mm thick concrete pavor block over 200 mm thick GSB , approach path way to be provided in periphery of transformer & other instruments.As per enclosed drawing No.8
60
-
-
APPROACH ROAD FROM MAIN GATE T POWER TRANSFORMER FOUNDATION ,SIZE (20X3) MTR FOR ALL TYPE OF SOIL
C.C. Road: 3.00 Metre wide C.C. raod of M-40 grade concrete shall be provided over 100 mm thick dry lean concrete for which sectional plan is enclosed .A 300 mm dia RCC NP2 class pipes crossing arrangement shall be provided for external cables.As per enclosed drawing No.9
60
-
-
CONTROL ROOM & INTERNAL ELECTRIFICATION WORK FOR CONTROL ROOM i) Foundation : R.C.C.column –footings foundation will be provided in M-20 grade concrete after excavation depth of 2.5 M or up to suitable strata.footings shall be rest on layer of cement concrete M-7.5 of 100 mm thickness.Plinth height of building shall be 450 mm or as per the direction of Engineer in charge,from existing concrete road level. R.C.C. plinth beams shall be provided in M-20 grade filling shall be done with available soil received from excavated stuff and remaining pit or under floor shall be done with hard moorum or sand or stone crusher dust well rammed and waterd in layers. R.C.C. floor slab is to be provided 100 mm thickness with reinforcement as per drawing & design.ii) Superstructure: Outer wall shall be 20 cm as per drawings with fly ash brick having crushing strength of more than 75 kg/cm2 in cement mortar (1:6) & Partition wall shall be 10 cm as per drawings with fly ash brisk having crushing strength of more than 75 kg/cm2 in cement mortar (1:4),reinforcement at every third course properly anchored as per specifications. The height of the building shall be 4.50 Metre from plinth level.iii) Flooring: 25 mm Thick Kota stone slab size 450 x 600 mm of stone flooring over 20mm (Average) thick base of C.M.1:4,ceramic glazed floor tile 300x300 mm or more(having thickness 9 to 10mm) of first quality conforming to IS :15622 and ceramic glazed wall tile 300x450 mm or more(having thickness 6 to 7mm) conforming to IS :15622 will be applicable as per approved make iv) R.C.C. Roof Slab: The Roof slab will be in C.C. M-20 grade having thickness 125 mm with 20mm and down graded hard crusher broken metal as per the approved design for Water Proofing Treatment over building 50 mm thick cement concrete grading with 1:2:4 the top of roof slab.v). Doors shutters : providing & fixing factory made 100% solid wood plastic composite (wpc) door frame for toilet door with 100% 24 thick plain solid pvc flush door shutter and remaining doors of control room MS profile sheet having 1.60 mm thick double rebate 115 x 50 mm frame, shall be 35 mm thick flush door shutter confirming to IS2202 part 2 Non decorative type of approved brand. vi). Windows and ventilators fully glazed ventilation of steel with 10 mm Sq. bar grill window of frame 35x35x5mm and shutter of steel M.S.angle 25 x 25 x3 mm & M.S. flat bracing 25 x3 mm with 5.50 mm thick plain glass and MS stoper,handels etc. vii). Plaster: The thickness of plaster shall be 12mm in 1:6 on smooth sides , 15 mm thick cement plaster on rough side of the brick masonry and 18mm thick cement Plaster in two coats outer side face of building. viii) Painting : The door and windows will be painted with two or more coats of superior quality enamel paint of including one coat of primer of approved make. Finishing Work: Applying Birla/J.K putty for masking the surface smooth, Ceiling and Walls shall be finished with two or more coats of oil-bound washable distemper. Outer walls be finished with Acrylic Smooth exterior paint of approved make. ix) Sanitary and water supply: Orissa pattern W.C. seat with low level flushing cistern .The disposal pipes and their fitting shall be ISI marked PVC.the sewer lines will be unplasticised pvc,pipe with stand working pressure of 4kg/cm2 and laying P.C.C.(1:5:10) all round the P.V.C. pipe line CPVC pipe shall be used for external and internal water supply x) Internal Electrification: Public Domestic House with provision of fan points light points and plug points Exhaust fan CFL,Tubelight etc. PVC conduit (Concealed wiring) and earthling of the installation will be provided .internal electrification includes metering panel and service cable up to nearest L.T.poles fo approved make.As per enclosed drawing No.10.
1
-
-
Evaluation Notes How It Works ?