Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Repair/ Replacement Of Lt Ug Cable, Junction Box And Connected Works At Af Stn Thoise Under Ge (af) Thoise in Leh, Ladakh, with an estimated contract value of Rs. 35,00,000. The bid opening date for this tender is 02-04-2025 and the last date for bid submission is 30-04-2025. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Costs
EMD
₹ 70,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_703286_1Bid Award Id
ViewTender No
GEAF/T-16/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://https://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
REPAIR/ REPLACEMENT OF LT UG CABLE, JUNCTION BOX AND CONNECTED WORKS AT AF STN THOISE UNDER GE (AF) THOISE
REPAIR/ REPLACEMENT OF LT UG CABLE, JUNCTION BOX AND CONNECTED WORKS AT AF STN THOISE UNDER GE (AF) THOISE
BOQ Items
... More
M&L for PCC cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm laid Flat in trenches over the cable with length 250mm perpendicular to the direction of cable, adjacent/ abutting each other complete all as specified and directed.
Note:-Excavation and earth work to be measured and paid for separately
15300
130
1989000
... More
Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cm thick, complete all as specified and directed by Engineer-In-Charge.
Note: Punned thickness shall be measured.
185.89
131
24351.589999999997
... More
M&L for in repair / replacment XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross-sectional area 16.0 Sqmm, 2-core, laid in trenches or passing through pipes, including suitable lugs and accessories for making connections at both ends, complete all as specified and as directed.
250
132
33000
... More
All as per Srl Item No 6 above but of size cross-sectional area 16.0 Sqmm, 4-core.
275
134
36850
... More
All as per Srl Item No 6 above but of size cross-sectional area 25.0 Sqmm, 4-core.
275
135
37125
... More
All as per Srl Item No 6 above but of size cross-sectional area 35.0 Sqmm, 4-core.
325
139
45175
... More
All as per Srl Item No 6 above but of size cross-sectional area 50.0 Sqmm, 3.5-core.
375
140
52500
... More
All as per Srl Item No 6 above but of size cross-sectional area 70.0 Sqmm, 3.5-core.
375
141
52875
... More
All as per Srl Item No 6 above but of size cross-sectional area 95.0 Sqmm, 3.5-core.
375
142
53250
... More
All as per Srl Item No 6 above but of size cross-sectional area 120.0 Sqmm, 3.5-core.
300
143
42900
... More
S & F in replacement Cable jointing kit for 1.1 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 120 sqmm, complete all as specified and directed. Make : Denson/ M Seal/ Raychem
13
143
1859
... More
Replacement of old unserviceable/ damaged MCCB with new MCCB, four pole, 415 Volts, adjustable thermal and fixed magnetic setting,63 Amps with breaking capacity 16 KA, having indicating lamp, Ics=100% Icu and as per IEC 60947-2, complete all as specified and as directed by Engineer-In-Charge.
Make: Schneider cat part No- LV426167 or equivalent in in L&T/ Legrand/ ABB/ Merlin Gerin/ Siemen/ havells
3
134
402
... More
Replacement of old unserviceable/ damaged MCCB with new MCCB, four pole, 415 Volts, adjustable thermal and fixed magnetic setting 125 Amps with breaking capacity 16 KA, having indicating lamp, Ics=100% Icu and as per IEC 60947-2, complete all as specified and as directed by Engineer-In-Charge.
Make: Schneider cat part No- LV426167 or equivalent in in L&T/ Legrand/ ABB/ Merlin Gerin/ Siemen/ havells
4
135
540
... More
Supply, installation, testing and commissioning of electric LT Feeder Pillar Box, outdoor, cubical type, Pedestal mounted, factory made, CPRI approved,, Al Bus Bar 400 Amps fabricated out of 3.4mm thick mild steel sheet mounted on frame of mild steel angle iron 40x40x6mm also comprising of following Inccoming:- (a) Change Over Switch 200 Amps -01 Nos (b) MCCB, four pole, 200 Amps, 415 Volts, adjustable type, with breaking capacity 35 KA- 02 No ( incl 02Nos Amp meter).
(c) MFn Meter V, A, F, kW, KVA, kVAr, kWh, , PF etc Make L&T , Equivelent in Seimns and Schinider -01 Nos (e) Suitable Contacter, relay,& circuit protection device Outgoing (i) MCB 4 pole 415 Volts TPN of capacity 63 amps thermal magnetic release adjustable type of breaking capacity 10 KA-06 No (incoming) With addition to Amp meter-06
(ii) MCCB 4 pole 415 Volts of capacity 40 amps thermal magnetic release adjustable type of breaking capacity 16 KA-02 Nos (outgoing) With addition to Amp meter-02
1
136
136
... More
Supply, installing, testing and commissioning, factory made & tested, CPRI approved, LT Feeder pillar box outdoor type of size 2.0 m x 1.5m x 0.9 m suitable for 415Volts 3phase 4wire 50Hz AC supply having bus bar chamber with insulated copper bus bar 900amp rating installed on pocelain insulators, The panel shall be dust and vermin proof, IP65 protection & made out of MS CRCA quality sheet 3.15mm thick, and 50mm x 50mm x 6mm angle iron base frame with 04 Nos legs 75cm long made out of MS angle iron of size 50mm x 50mm x 6mm, legs embedded in PCC (1:2:4) having bottom of the panel at height of 45cm above ground level, duly powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer inside (after anticorrosive treatment (7tank) front opening type with aprons for cable entry with double door shutter and locking arragements, internal wiring with PVC insulated solid copper conductor FRLS cable, IS-694 marked of adequate size, the scope of work comprising the following including taking down old unserviceable feeder pillar box:-
(a) ON LOAD Change over switch front operated of capacity 630 Amps TPN :- 02 Nos.
(b) Copper Bas bar mounted on synthetic bas bar insulation of 900 Amps Capacity.
(c) MCCB 4 pole,630 Amps, 415 Volt, 50 KA AC with thermal setting 70% to 100% and rupturing capacity not less than 35 KA = 02 Nos (I/C).
(d) MCCB 4 pole,400 Amps, 415 Volt, 50 KA AC with thermal setting 70% to 100% and rupturing capacity not less than 35 KA = 01 Nos (O/G) (e) MCCB 4 pole,200 Amps, 415 Volt, 50 KA AC with thermal setting 70% to 100% and rupturing capacity not less than 35 KA = 02 Nos (O/G) (f) MCCB 4 pole,100 Amps, 415 Volt, 50 KA AC with thermal setting 70% to 100% and rupturing capacity not less than 35 KA = 02 Nos (O/G) (g) MCCB 4 pole,63 Amps, 415 Volt, 50 KA AC with thermal setting 70% to 100% and rupturing capacity not less than 35 KA = 02 Nos (O/G) (e) Digital Ammeter 0 to 800 Amp with selector switch & suitable range of CTs = 02 No. (f) Digital Voltmeter 0 to 500 Volts with selector switch = 02 No. (g) LED Phase indicating lamp = 03 Nos (R, Y, B).
1
138
138
... More
Attanding day to day complaints for maintenance and repair of LT Network of any type and any specifications or any accessories related to Electric Supply of any descriptions, fitted/ fixed on poles, buildings or watching towers of any heights and any location, and re-fixing the same after necessary repairs/ replacement of defective parts including rectifying the same as per directions by concerned JE E/M and Engineer-In-Charge, at various locations, complete all as specified and directed by Engineer-In-Charge.Note: (i) Cost of T&P, ladder or mechanical lift shall be deemed included in quoted rate.
(ii) Supply of spare parts of light fittings shall be measured and paid separately.
32
139
4448
... More
Note: The work under subject BoQ (item No. 1 to 19 ) is meant for maint of External Electric Supply in AF Stn Thoise under GE(AF ) Thoise. The work shall be executed on ground on required basis. Contractor shall deploy sufficient resources to keep smooth working of External Electric Supply in the AF station. Contractor or his representative will daily attend the complaints at E/M complaint cell and in addition any breakdown shall be communicated to contractor or his representative by concerned Engineer-in-charge/JE E/M through phone call, text message, complaint slip and or in writing through site order book or through other means. Non complying of attending breakdown by contractor within 24 hours after notify the complaint, recovery @ Rs 1500/- per day shall be recovered from contractor's payment for each complaint so notified.
-
-
-