Ladakh Autonomous Hill Development Council Tender
Bidassist is designed as a single destination for all government tenders from across the world in one place. If you require any information or detail about any e-tender the Ladakh government has posted, Bidassist helps a registered bidder to get the same.As BidAssist is a very user-friendly website it will help you find the specific Ladakh etender you're looking for. Read further to learn how to search and bid for etender Ladakh.
Costs
EMD
₹ 2,12,360Document Cost
₹ 3,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_LAHDC_9954_1Bid Award Id
ViewTender No
E-TENDER -16 OF TDA KARGIL 2023-24 DATED 10-06-202Tender Authority
Ladakh Autonomous Hill Development Council ViewPurchaser Address
-Website
http://tenders.ladakh.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Hot water Circulation Pumps Hot Water Circulation Mono-block Pump (secondary) complete with electric motor mounted common base frame duly grouted in cement concrete foundation along with control valves (Sluice valve NRVs of minimum PN 10 rating) of desired size and capacities,
-
-
-
Discharge: 8-12 LPS at 25 m Head
2
360000
180000
Gear Oil Transfer Pumps
Gear Oil Transfer Pump with electric motor single phase rating along-with common base frame duly grouted in cement concrete foundation including control valves
-
-
-
Discharge = 1 LPS(min) @ 12 mtr Head
2
140000
70000
Soft water / Glycol Pumps
Soft Water Pump complete with electric motor of 1-ɸ, 230 V, 50 Hz, 1 HP rating along with common base frame duly grouted in cement concrete foundation.
-
-
-
Capacity 1 LPS (min) at 20 m Head
1
25000
25000
Bulk HSD Tank (10kL)
Bulk oil tank of 6/8 mm MS plate with require red stiffener, manhole dully covered along-with unit to be laid underground with allied Civil Works, as per IOC specifications, Complete with required piping connections and valves.
-
-
-
10000 litres, size 2.0 M DIA X 3.50 M long.
1
450000
450000
Day Oil Tank
Day oil tank 1000 ltr capacity HDPE triple layer insulated with 25mm thick nitrile foam with 26 Gauge aluminum cladding and mounted on a suitable support structure.
1
80000
80000
Expansion Tank
SITC of Expansion tank 1000 ltr capacity HDPE triple layer insulated with 25mm thick nitrile foam with 26 Gauge aluminium cladding and mounted on a suitable iron stand.
1
60000
60000
Makeup tank
Soft water tank of HDPE (tripple layer) with necessary connections Capacity 500 Ltrs.
1
25000
25000
Mixing Tank
Hot water mixing tank made of 6/8 MM M.S. Plate with dished ends, manhole. Suitable to withstand 6kg/cm2 operating pressure as per IOC specifications, dully covered and necessary connections covered insulated with 25mm thick nitrile foam with 26 Gauge aluminium cladding and complete with structural support to raise the tank at least 300 mm above finish FL.
2500 litres, size 1.2 M DIA X 2.20 M long.
1
320000
320000
Hot Water Radiators Steel panel heating radiators conforming to EN442 with working pressure ranging from 10-13 bar having working temperature at 110°C , complete with Top grilles and side covers as standard along-with inlet valve, outlet valve, air purge valve and threaded plug as per OEM.
Inlet Water Temp: 75oC
Outlet Water Temp: 65oC
Room Temp: 22oC 3500 Kcal/Hr (Type 33)
35
1225000
35000
Fan Coil Unit
Wall mounted fan coil unit, with adequate airflow rate for efficient air circulation. Compact size suitable for wall mounting, acceptable noise levels, with control options such as remote control, , fan speed and 4 way direction adjustment, and air direction control suitable for input supply 220-240 / 50 hz. Job include all electrity supply point with required cable.
-
-
-
Cap 2.0 TR
30
840000
28000
Cap: 1.5TR
18
414000
23000
PIPING AND CONTROL VALVES
MS ERW pipe ( with resin bonded fiber glass insulation)
MS C-class pipe as per IS-1239 & IS 3589 pipe of following nominal size with necessary clamps, vibration isolators and fitting but excluding valves, stationers, gauges etc. duly insulated with 80kg/cum desig resin bonded fibre glass or 144 kg/cum mineral wool (non combustible) pipe section insulation covered with alyer of 120gm/sqm polythene sheet (vapor barrier) and finally applying 0.63 aluminum sheet cladding complete with type3, grade 1 roofing felt strip at joints and repair to the damage to building etc as per specifications as required.
-
-
-
150 mm DIA (50mm insulation)
80
360000
4500
100 mm DIA (50mm insulation)
40
120000
3000
50 mm DIA (50mm insulation)
220
550000
2500
40 mm DIA 50mm insulation)
160
320000
2000
32 mm DIA 50mm insulation)
80
120000
1500
Heavy Duty PP-R pipe,
3-Layer, PP-R pipe for hot and cold water supply, conforming to IS 15801, DIN 8077 of PN16/SDR7.4, Complete with joints and fittings, exposed or concealed fitting including wall clamps and making good the wall as per site condition and direction of site engineer
-
-
-
40mm Dia
150
96000
640
32 mm Dia
400
200000
500
20/15 mm Diia
1500
675000
450
Insulated Valve
-
-
-
Valves and Strainers with Min PN 16 ratting duly insulated the same specifications as the connected pipe and adequately supported
Butter fly valves/balancing valves with built in measuring facality sizes as per Qty: as per site condition.
1
220000
220000
Industrial type Pressure Gauges Glycerine fillied as per specifications (0-20 Kg/sqcm.)
4
4000
1000
Industrial type Digital Thermometer as per specifications
(100 mm Dial)
4
4000
1000
Air release valves with isolation ball valves (15mm)
145
217500
1500
Electrical Control Panel & electrical Cabling
-
-
-
Main Control Panel having separate cubical for each equipment viz. isolation for Hot Water Generator 3 No's , DOL Starter for Hot Water Circulation Pumps 2No's , Soft Water Pumps 2 No's (1 hp each), DOL starter Softener pump 1 No and for HSD Transfer Pump 2 No's, and On-Load Change Over Switch, MCCB The control panel shall be provided with the copper bus bars dully insulated of required ratings and 3 in 1 digital Voltmeter / Ammeter / Frequency meter, indicators etc. including multi-core armored copper conductor cables of required current rating from main panel board to various equipments to be laid over cable trays with appropriate clamps and fixing arrangements as per site conditions. The current rating/sizes of electrical components of panel shall be in accordance with respective electrical loads of boilers/pumps/AHUs etc.
1
350000
350000
Service Cable for Armored, 3.5 Core, 120 Sq.mm Al. Cable
80
128000
1600
Servo Voltage Stabilizer
-
-
-
3-phase, Oil cooled Servo Stabilizer micro processor controlled with high and low voltage cut off, single phase preventer, short circuit and over load protection having digital display 220 – 460 volts Phase to phase with panel as per specifications duly filled with recommended transformer oil upto full capacity
-
-
-
Capacity: 83 kVA with input of 220-460 Volts Phase to phase and output of 415 volts ±1% phase to phase
1
450000
450000
Earthing
-
-
-
Earthing Pit
Earthing for various equipments inside boiler house using copper plate electrode of size 500 x 500x 3 mm placed in 1000 x 1000x 1800 mm pit filled with charcoal & salt by copper strip of size 20 x 3 mm alongwith perforated G.I pipe.
Earthing Strip
Copper strip of size 15x3 mm from ear-thing electrode to the Electric Panel, Stabilizer, boiler and pumps using proper fasteners concealed under floor.
2
70000
35000
Coolant
-
-
-
Providing and filling of Nontoxic antifreeze coolant (the right antifreeze product intended for use in heating boiler) of ethylene glycol solution.
2500
975000
390
Charge on account of fixing of existing radiator panel / FCUs in the ground and first floor as per direction of site engineer
1
120000
120000
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements