The Pharmaceutical Corporation IM Kerala Limited Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 17,500Document Cost
₹ 1,652Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_PCIMK_630228_1Bid Award Id
ViewTender No
RE-E2-124/23-24Tender Authority
The Pharmaceutical Corporation IM Kerala Limited ViewPurchaser Address
-Website
http://etenders.kerala.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
TECHNICAL SPECIFICATION AND SPECIAL CONDITIONS
BOQ Items
Load Break Switch (LBS) (1 Set) each comprising of the following:
-
-
-
11 KV, 630A, 21KA for 3sec Motorized Load break switch; with built in line side manual earth switch. Earthing should be completed within 2 operations only (i.e 1. Main switch - OFF, 2. Earth switch - ON). LBS shall have 3 positions, open or disconnected, closed and earthed, and will be constructed in such a way that interlocking prevents unauthorized operations. For earth switch, manual opening and closing will be driven by a fast-acting /snap action mechanism, independent of operator action. LBS and earth switch shall have a min of 1000 (M1) mechanical operations , and 5 nos closing operations at rated SC current. LBS should have 100 electrical operations at rated current
-
-
-
Position indicator through clear front mimic in line with IEC 62271-103
-
-
-
Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases. VPI should be of same make as that of RMU
-
-
-
Cable box with termination bushing suitable for upto 2 RUN 3Cx300 Sq mm, XLPE cable
-
-
-
Fault passage indicator (FPI) with in-built Overcurrent, Short Circuit and earth fault indication . The FPI should be self-powered and should have internal lithium battery for external indication and setting of FPI in the absence of current. FPI should have 4 digit LCD display, ammeter feature and preferably of same make as that of RMU
-
-
-
Cable Boots suitable for actual cable size
-
-
-
Auxilary switch : LBS - 2 NO +2 NC, Earth switch - 1 NO + 1 NC
-
-
-
Mechanical operation counter
-
-
-
Vacuum circuit breaker (VCB) (2 sets) each comprising of the following:
-
-
-
11 KV, 630A, 21KA for 3sec Motorized VCB with spring assisted mechanism and series trip coil; with built in manual line side three position disconnector cum earth switch. Earthing should be completed within 2 operations only (i.e 1. Main switch - OFF, 2. Earth switch - ON). Vaccuum interrupter should be of same make as that of RMU. The circuit breakers shall have 2 positions: open or disconnected and closed. A separate and independent 3 position earthing switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorized operations. An independent mechanism shall be fitted for the 3 positions earthing switch and disconnector. Circit breaker shall have a min of 2000 mechanical and 2000 electrical operations at rated current and 50 nos of operations at rated short circuit current. Disconnector and earthswitch shall have a min of 1000 (M1) mechanical operations. The earthing switch shall be fitted with its own operating mechanism and manual closing shall be driven by a fast-acting mechanism, independent of operator action.
-
-
-
Position indicator through clear front mimic in line with IEC 62271-103
-
-
-
Suitable ratio CT 30-75-150/1 A, Class 10P5-5P10-5P10, 2.5VA for protection
-
-
-
Live cable indicator with indications (Voltage Presence Indicator) at the front and three inlets provision to check the synchronization of phases.VPI should be of same make as that of RMU
-
-
-
Cable box with termination bushing suitable for upto 1 RUN 3Cx300 Sq mm, XLPE cable
-
-
-
Cable Boots suitable for actual cable size
-
-
-
Mechanical operation counter
-
-
-
Emergency trip push button
-
-
-
Accessories
-
-
-
Antireflex operating handle (1 no)
-
-
-
Battery 24V DC , 12Ah, (1 no)
-
-
-
Battery charger (I/P-230V AC, O/P - 24V DC) (1 no)
-
-
-