Sree Sankaracharya University Of Sanskrit Tender

Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.

Sree Sankaracharya University Of Sanskrit - SSUS Tender

Works
Eprocure
Opening Date20 Jan 2020
Closing Date4 Feb 2020
Tender Amount₹ 33,84,932 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
1.10.3 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C

220

-

-

... More
1.11 : Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.

10

-

-

... More
1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire

3500

-

-

... More
1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire

1500

-

-

... More
1.14.9 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 6 sq. mm + 2 X 6 sq. mm earth wire

280

-

-

... More
1.18.2 : Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair

200

-

-

... More
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm

3000

-

-

... More
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm

798

-

-

... More
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch

219

-

-

... More
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch

32

-

-

... More
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet

255

-

-

... More
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet

32

-

-

... More
1.24.6 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet

3

-

-

... More
1.24.8 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell push

1

-

-

... More
1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.

120

-

-

... More
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)

3

-

-

... More
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)

38

-

-

... More
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)

53

-

-

... More
1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden blockincluding connection etc as required.

460

-

-

... More
1.34 : Supplying and fixing brass batten/ angle holder including connection etc. as required.

70

-

-

... More
90.3.19.3 : Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required

300

-

-

... More
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.

30

-

-

... More
1.48 : Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)

100

-

-

... More
90.4.5.2 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.

120

-

-

... More
90.4.8 : Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.

39

-

-

... More
90.4.9 : Charges for cutting holes suitable for accommodating exhaust fans above 305mm sweep and up to 450mm sweep including plastering colour washing etc. as required.

4

-

-

... More
od8560/2019_2020 : supply of 380 mm sweep, 1400 rpm Heavy Duty Exhaust fan in metal frame working on 230 V A/C

4

-

-

... More
od8561/2019_2020 : supply of 305 mm sweep, 1400 rpm Heavy Duty Exhaust fan in metal frame working on 230 V A/C

39

-

-

... More
1.50.1 : Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep

43

-

-

... More
od8563/2019_2020 : Supply and fixing of 9W LED bulb

115

-

-

... More
1.38 : Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.

2

-

-

... More
90.5.1.8 : Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.

4

-

-

... More
90.3.18.2 : Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.

18

-

-

... More
od8565/2019_2020 : Supply and fixing of 25 W LED street light fitting with all accessories. Extruded aluminium housing, designed to act as heat sink for efficient dissipation of heat- imported for LED luminaries. Luminaire provided with heat resistant toughened glass. Extracted aluminium control gear compartment. LEDs are provided with secondary lens optics to get optimum optical performance. The driver is used is specially designed to have surge voltage, open /short circuit protections. Degree of protection - IP66. (Including giving connections)

12

-

-

... More
90.11.1.10 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required

9

-

-

... More
90.11.1.14 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required

4

-

-

... More
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole

111

-

-

... More
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole

13

-

-

... More
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.

25

-

-

... More
2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

9

-

-

... More
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps

4

-

-

... More
2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

10

-

-

... More
2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps

4

-

-

... More
2.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps

1

-

-

... More
90.12.10.3 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation

40

-

-

... More
90.12.10.10 : Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation

320

-

-

... More
90.12.5.27 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.

40

-

-

... More
90.12.7.27 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.

160

-

-

... More
90.12.5.48 : Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.

350

-

-

... More
9.1.20 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm)

10

-

-

... More
9.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)

2

-

-

... More
7.10 : Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate withinscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixingthe same in ground as required.

12

-

-

... More
5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, andproviding masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

4

-

-

... More
5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.

70

-

-

... More
5.19 : Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.

200

-

-

... More
6.2 : Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube,having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc.complete as required.

2

-

-

... More
6.4 : Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.

40

-

-

... More
6.7 : Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightningconductor complete as required.(For horizontal run)

100

-

-

... More
6.8 : Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightningconductor complete as required.(For vertical run)

35

-

-

... More
6.12 : Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.

4

-

-

... More
90.14.1.1 : Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.br Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.

12

-

-

... More
90.14.2.2 : Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.

0.8

-

-

... More
90.14.3.2 : Supply and providing heavy duty 'A' section neoprene gasket in the panel board

50

-

-

... More
90.14.4 : Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)

6

-

-

... More
90.14.6 : Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.

3600

-

-

... More
90.14.7 : Supply and providing copper earth bus in the panel board

1200

-

-

... More
90.14.10.4 : Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.

9

-

-

... More
2.2.16 : Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.250 Amp, 36 KA

1

-

-

... More
90.14.11.3 : MCCB Accessories

1

-

-

... More
90.14.11.12 : MCCB Accessories

1

-

-

... More
90.14.11.13 : MCCB Accessories

10

-

-

... More
od8616/2019_2020 : Supplying, threading, laying, jointing & clamping of the following sizes of PVC pipe (6 Kgf/ cm2) with all required accessories and clamp including cutting and making good the walls, colour washing etc. on surface of wall / parapet etc. as required.

40

-

-

... More
od8617/2019_2020 : Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength.

2

-

-

... More
od8618/2019_2020 : Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.

6

-

-

... More
od8619/2019_2020 : Supply and fixing of 100/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT

3

-

-

... More
od8620/2019_2020 : Supply, Conveyance, installation, testing and commissioning of Three phase multifunction meters to read V, A F, accuracy class 0.5(Digital type)

1

-

-

... More
od8621/2019_2020 : Supply and fixing of LED indicators for all voltage ranges - Red, Yellow and blue

6

-

-

... More
2.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.

2

-

-

... More
od8622/2019_2020 : Preparing necessary drawings, connected paper works etc. for obtaining approval from Kerala State Electrical Inspectorate. (The statutory fees remit at KSEI will be reimbursed to the contractor only on production of receipts )

1

-

-

... More
od8972/2019_2020 : Lettering with black Japan paint of approved brand and manufacture as identification mark to SB, DB, panel board etc as required

200

-

-

... More
od8968/2019_2020 : Supply ITC of following type of 120W LED flood light fitting with all accessories. Extruded aluminium housing, designed to act as heat sink for efficient dissipation of heat- imported for LED luminaries. Luminaire provided with heat resistant toughened glass. Extracted aluminium control gear compartment. LEDs are provided with secondary lens optics to get optimum optical performance. The driver is used is specially designed to have surge voltage, open /short circuit protections. Degree of protection - IP66.

2

-

-

... More
od8969/2019_2020 : Supply, Conveyance, installation, testing and commissioning of bulhhead light fittings ,with glass as shade material and all accessories including 9W LED bulb, directly on wall including giving connections with required length of 1.5 sq mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required

5

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.