Regional Cancer Center Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Regional Cancer Center - RCC Tender
Eprocure
Opening Date14 Nov 2019
Closing Date22 Nov 2019
Tender Amount₹ 63,97,900
Costs
EMD
₹ 50,000Document Cost
₹ 5,900Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2019_RCC_313023_2Bid Award Id
ViewTender No
RCC/ENG-M/2018-19/E-R10Tender Authority
Regional Cancer Center ViewPurchaser Address
-
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
20 TR 8000 CFM- II STAGE
1
-
-
Supply, installation, testing and commissioning of cooling thermostat shall be electronic room temperature controller with digital display temp & fan speed control, capable of providing individual space temperature control for cooling application. The controller shall produce a dual output to cooling coils in response to load change in rooms. Thermostat for AHUs
2
-
-
Supply, Installation, testing and commissioning of electronic, Self-balancing, PRESSURE INDEPENDENT TYPE DYNAMIC BALANCING VALVE with integrated 2 way modulating Control valves in a single body. The actuator shall be capable of accepting 2-10VDC, 4- 20 mA electric signal and shall provide similar transduced feedback output signal to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above.Valves should have pressure rating of 25 Bar minimum.
-
-
-
65 mm dia pipes for AHUs
1
-
-
50 mm dia pipes for AHUs
2
-
-
40 mm dia pipes for AHUs
1
-
-
PIPING - INSULATED CHILLED WATER PIPING
-
-
-
Site fabricated pipe with PUF insulation & GI cladding for pipe AHU room area & valve insulation with openable boxing for inspection.
Note : The Pipes of sizes 150mm & below shall be M.S. ‘C’class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
-
-
-
65mm dia. (50mm thick insulation)
150
-
-
50mm dia. (50mm thick insulation)
130
-
-
40mm dia. (50mm thick insulation)
1
-
-
25mm dia. (50mm thick insulation)
1
-
-
DRAIN PIPING
-
-
-
Providing and fixing in position the following PVC -shd 40 blue threaded pipes for drain cut to required lengths and installed complete with all necessary fittings like elbows tees & reducers.
-
-
-
25 mm dia
1
-
-
32 mm dia
1
-
-
40 mm dia
18
-
-
BUTTERFLY VALVE (MANUAL)
-
-
-
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water circulation as specified
-
-
-
65 mm dia pipes
1
-
-
50 mm dia pipes
4
-
-
40 mm dia pipes
1
-
-
32 mm dia pipes
1
-
-
BALANCING VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water circulation as specified
-
-
-
65 mm dia pipes
1
-
-
GLOBE VALVE (MANUAL)
-
-
-
GLOBE VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water circulation as specified
-
-
-
40 mm dia pipes
1
-
-
32 mm dia pipes
1
-
-
25 mm dia pipes
2
-
-
Y - STRAINER
-
-
-
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.
-
-
-
65 mm dia pipes
1
-
-
50 mm dia pipes
2
-
-
40 mm dia pipes
1
-
-
32 mm dia pipes
1
-
-
25 mm dia pipes
1
-
-
Providing and fixing in position the industrial type PREESURE GAUGE with gun metal / brass valves complete as required
4
-
-
Providing & fixing in position the mercury in glass industrial type THERMOMETER complete as required
4
-
-
Supplying, installation, testing and commissioning of AUTO AIR VENTS.
2
-
-
Supplying, installation, testing and commissioning of DSR self sealing TEST POINTS in chilled water lines complete in all respect.
4
-
-
Supply, installation, testing and commissioning of drain cocks in chilled water line etc. complete in all respects confirming to technical specifications.
2
-
-
DUCTING,GRILLS,DIFFUSER AND INSULATION
-
-
-
Supply, installation balancing and commisnioning of factory fabricated Aluminium sheet metal rectangular / round ducting complete with neoprene rubber gaskets,elbows,splitter,dampers,vanes,hangers,supports etc as per approved drawings & specification of following sheet thickness
-
-
-
Thickness 0.63 mm sheet
300
-
-
Thickness 0.80 mm sheet
250
-
-
Supply, installation balancing and commisnioning of site fabricated Aluminium sheet metal ducts rectangular/round ducting complete with neoprene rubber gaskets,elbows,splitter,dampers,vanes,hangers,supports etc as per approved drawings & specification of following sheet thickness
-
-
-
Thickness 0.63 mm sheet
50
-
-
Thickness 0.80 mm sheet
5
-
-
Supply, Installation, Testing and Commissioning of Al VOLUME CONTROL DAMPERS complete with neoprene rubber gaskets,nuts,bolts,screw linkages,flanges etc. as per specifications.
8
-
-
Supply,fixing, testing & commissioning SUPPLY AIR DIFFUSER of poweder coated aluminium with aluminium volume control dampers with anti smudge ring & removal core.
1
-
-
Supply,fixing, testing & commissioning RETURN AIR DIFFUSER of poweder coated aluminium with volume control dampers with anti smudge ring & removal core.
10
-
-
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
-
-
-
Damper
2.1
-
-
Actuator
2
-
-
Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction. inlet air louvers with bird screen, volume damper & filter for fresh air as per specifications and approved shop drawings.
Note:All exposed surfaces & duct shall be painted in black mat finish by the HVAC contractor.
2
-
-
THERMAL INSULATION
-
-
-
Supply & fixing of following thickness duly laminated aluminum foil of mat & finish closed cell Nitrile rubber ( Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The Joints Shall Sealed with 50 mm wide & 3 mm thick self adhesive nitrile rubber tape insulation complete as per specification & as required.
-
-
-
19 mm
550
-
-
25 mm
1
-
-
Supply, installation, testing and commissioning of Acoustic duct lining using 10mm nitrile rubber insulation open cell type inside the ducts, antimicrobial protection at the outlets of all indoor units upto 4m distance from fan outlet as per spec provided.
60
-
-
Dismantling & Removing existing AHUs, Ducting and other accessories, to a suitable place inside the building as per the instruction from engineer in charge.
2
-
-
SITC of Exhaust fan 100 cfm with suitable static and with removable type hepa filter, louver and bird screen for Isolation room exhaust.
5
-
-
HEPA FILTERS
-
-
-
PLENUM : Supply, installation, testing and commissioning of Aluminium plenum of size 8ft L x 6ft W for attaching multiple banks of HEPA filters as per the drawing and shall have perforated 1mm thick aluminium sheet with powder coated at the outlet to ensure laminar flow. Front face shall have removable perforated grille for filter access and bottom loading. Plenum shall be single skin with outer insulation of 19mm thick nitrile rubber. The station shall have central hollow for OT light fitting and shall have suitable collars as per the drawing.
4
-
-
Supply and fixing of Terminal HEPA Filters having filtering efficiency of 99.97% down to 0.3 microns with aluminium frame works along with supply air plenum boxes
32
-
-
Supply installation testing and balancing of continous Perforated Stainless Steel Grilles for supply and return air grilles in accordance with the approved shop drawings size 610 x 610 mm & 450 x 450 mm
3
-
-
Supply and installation of acoustic lining on walls of AHU room with 50 mm thick fibre glass rigid board and 48 Kg/Cum density with GI frame grid and covered with 22G perforated GI sheet as per the approved shop drawings & specifications.
140
-
-
Supply, Installation, Testing and Balancing of Powder coated extruded aluminium construction LINEAR GRILLES with removable core as per approved drawings and specifications. Quoted price shall be inclusive of volume control damper behind supply air collar.
3
-
-
UNDERDECK INSULATION
-
-
-
Supply and fixing of underdeck insulation with 30mm thick fire retardent glass nitrile rubber stuck with synthetic adhesive and held in position with GI screw and washer at 600mm centers and cross braced with GI 20swg wire netting.
11
-
-
Removing & clearing from RCC site including transpotation of existing AHUs, Chilled water line, ducts, Valves etc. as per the instructions of HOD, Engineering Division, to be done with upmost precautions, and making good of surfaces.
2
-
-
Rubber beeding for doors
1
-
-
Plain glass film
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements