Public Works Department Tender

Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.

Public Works Department - PWD Tender

Works
Civil And Construction
Building Construction
Eprocure
Opening Date11 Dec 2024
Closing Date21 Dec 2024
Tender Amount₹ 4,23,08,668 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
OD142012/2024-2025:Conducting Plate load test

2

23230

46460

... More
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil

25.38

309

7866

... More
2.6.1:Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil

604.79

223

135115.24

... More
2.26.1:Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil

151.2

111

16788.91

... More
2.25:Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.

393.41

269

106172.68

... More
50.2.25.1:Filling with contractor's own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge

5.84

548

3205.4

... More
4.3.1:Centering and shuttering including strutting, propping etc. and removal of form work for:Foundations, footings, bases for columns

445.19

350

155816.5

... More
5.9.5:Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers

1496.98

678

1015357.3

... More
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete

66.43

350

23249.1

... More
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)

75.42

7113

536466.44

... More
4.1.6:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size)

19.6

7527

147560.29

... More
OD88496/2024-2025:Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 340 kg/ cum. Excess or less cement used as per design mix is not payable or not recoverable separately. All work upto plinth level

266.03

9911

2636815.34

... More
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more

33943.95

102

3482988.71

... More
OD88497/2024-2025:Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 340 kg/ cum. Excess or less cement used as per design mix is not payable or recoverable separately. All work above plinth level upto floor V level

379.54

11636

4416400.3

... More
5.9.6:Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts

802.55

901

723456.89

... More
5.9.3:Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform

1244.12

851

1059352.33

... More
5.9.7:Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases)

38.22

764

29224.16

... More
5.9.16.1:Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide

204

212

43423.44

... More
5.9.19:Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges

148.82

942

140197.12

... More
5.22A.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more

62800.59

102

6443968.54

... More
50.6.2.1:Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15 cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 15cm in: CM 1:6 ( 1 cement :6 coarse sand) etc complete

2.97

6373

18896.83

... More
OD88498/2024-2025:Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300mm thick AAC blocks in superstructure up to floor 2 level with approved block laying cement mortar 1:6 all complete as per direction of Engineer-in-Charge.

233.22

6874

1603338.65

... More
50.9.1.1:Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately), using good quality Anjili wood /jack wood

0.5

110915

55235.98

... More
50.9.3.1:Providing and fixing paneled or paneled and glazed shutters for doors, windows and clerestory windows, 30 mm thick shutters including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws, excluding paneling which will be paid for separately, all complete as per direction 0f Engineer in- charge. using Anjili/ Jack wood

14.4

3088

44477.86

... More
50.9.4.1:Providing and fixing paneling or paneling and glazing in paneled or paneled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured) paneling for paneled or paneled and glazed shutters 25 mm to 40 mm thick using good quality Anjili/ Jack wood

20.79

2789

57992.67

... More
21.1.1.2:Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)

1196.4

560

670713.8

... More
9.97.2:Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:250x10 mm

18

127

2290.5

... More
9.100.1:Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm

9

73

659.43

... More
9.76:Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.

9

875

7881.84

... More
13.16.1:6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)

1161.39

279

324387

... More
13.1.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)

2907.99

327

953443.01

... More
13.7.1:12 mm cement plaster finished with a floating coat of neat cement of mix:1:3 ( 1 cement : 3 fine sand)

148.82

418

62323.72

... More
11.41.2:Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.

704.18

1843

1298271.85

... More
11.46.2:Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm

25.62

1899

48667.66

... More
OD142871/2024-2025:Providing and laying Matt finished vitrified tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.

224.82

1640

368736.46

... More
11.36:Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.

145.08

1265

183652.42

... More
11.37:Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete.

123.82

1138

141008.99

... More
13.43.1:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer

4093.53

73

301897.91

... More
13.50.1:Applying priming coat:With ready mixed pink or Grey primer of approved brand and manufacture on wood work (hard and soft wood)

157.95

70

11073.87

... More
13.46.1:Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)

748.74

202

151522.92

... More
13.60.1:Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work

4093.53

158

647023.51

... More
13.61.1:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work

309.87

149

46266.39

... More
9.53:Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)

36

220

7926.84

... More
21.3.1:Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness

109.12

1228

134012.86

... More
9.17A.3:Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Casement window double panels with top fixed with S.S. friction hinges (350 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. ( Area of window upto 2.50 sqm).

15.84

8578

135882.96

... More
9.147A.3:Providing and fixing factory made uPVC white colour casement/casement cum fixed glazed windows comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Casement window double panels with top fixed with S.S. friction hinges (350 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. ( Area of window upto 2.50 sqm).

2.74

8578

23505.01

... More
9.147B.1:543 SUB HEAD : 9 - WOOD & PVC WORK 9.147B Providing and fixing factory made uPVC white colour fixed glazed windows/ ventilators comprising of uPVC multi-chambered frame and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), , uPVC extruded glazing beads of appropriate dimension, EPDM gasket, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately). Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Fixed window / ventilator made of (small series) frame 47 x 50 mm & mullion 47 x 68 mm both having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. (Area upto 0.75 sqm.)

9.18

7960

73074.64

... More
9.147F.1:Providing and fixing factory made uPVC white colour sliding glazed door comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension uPVC extruded glazing beads, uPVC extruded interlock and uPVC extruded Inline sash adaptor (if required), EPDM gasket, wool pile, zinc alloy (white powder coated) handle with key on one side of extreme panels along with zinc plated mild steel multi point locking having transmission gear with keeps, zinc alloy (white powder coated) cresent lock (if required), stainless steel (SS 304 grade) body with adjustable double nylon rollers (weight bearing capacity to be 120 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in- Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately). Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Two track two panels sliding door made of (big series) frame 67 x 50 mm & sash 46 x 82 mm both having wall thickness of 2.3 +/- 0.2 mm and single glazing bead / double glazing bead of appropriate dimension. (Area of door above 2.00 sqm upto 5.00 sqm)

2.25

7378

16600.66

... More
9.147D.5:Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 +/- 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately) Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Three track three panels sliding window made of (big series) frame 116 x 45 mm & sash 46 x 62 mm both having wall thickness of 2.3 +/- 0.2 mm and single glazing bead / double glazing bead of appropriate dimension. (Area of window above 1.75 sqm)

61.05

10046

613360.19

... More
9.48.2:Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc

1027.42

225

231620.66

... More
22.23.2:Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin- charge. The product performance shall carry guarantee for 10 years against any leakage.For horizontal surface one coat @1.10 kg per sqm.

22

458

10093.6

... More
22.5:Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.

61.91

572

35414.42

... More
12.50:Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.

85

771

65540.95

... More
OD150798/2024-2025:Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) of 1 mm thickness with epoxy primer on both side of the sheet and polyester top coat. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation. The sheet shall be fixed using self drilling/self tapping screws complete upto any pitch in horizontal/ vertical or curved surfaces and including cutting to size and shape wherever required.

15.3

1363

20865.68

... More
50.10.1:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete

644.19

198

127685.69

... More
50.6.2.2:Solid masonry using pre cast solid blocks (factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete

8.83

7153

63127.34

... More
OD143767/2024-2025:Filling 6mm broken stone in sunken slab including all cost, carriage of materials and labour charges for filling etc complete.

7.23

2766

20002.45

... More
22.14.1:Grading roof for water proofing treatment with:Cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)

3.62

8508

30765.25

... More
50.13.1:9 mm cement plastering of mix : 1:3 (1 cement : 3 fine sand ) including all cost of materials, labour charges etc complete

928.88

304

282434.64

... More
21.2.1:Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side

873.92

1225

1071303.57

... More
9.7.7.1:Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick: Float glass panes4 mm thick glass pane

115.5

2202

254382.97

... More
RAMP(Civil work)

-

-

-

... More
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil

6.89

309

2134.28

... More
2.25:Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.

6.02

269

1625.22

... More
4.3.1:Centering and shuttering including strutting, propping etc. and removal of form work for:Foundations, footings, bases for columns

25.76

350

9016

... More
4.1.5:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)

2.58

7690

19810.26

... More
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)

1.84

7113

13060.26

... More
OD142881/2024-2025:Providing and laying Matt finished vitrified tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.

15.46

1843

28495.76

... More
10.28:Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)

223.45

707

157986.67

... More
16.90:Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS: 15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.

9

2375

21383.37

... More
Sanitary fittings(Civil work)

-

-

-

... More
17.2.1:Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid

12

6463

77567.16

... More
17.4.1:Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I. clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required:One urinal basin with 5 litre white P.V.C. automatic flushing cistern

10

6121

61214.8

... More
17.7.2:Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630 x 450 mm with a single 15 mm C.P. brass pillar tap

9

3380

30423.51

... More
50.17.1.1:Supplying and fixing Stainless steel soap dish including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.

10

67

671.7

... More
50.17.1.4:Supplying and fixing CP Health faucet good quality including cost of materials and labour charges etc. complete as per the direction of site engineer-in-charge.

11

758

8340.86

... More
50.18.7.4.2:Providing and fixing PVC, pipes fittings including fixing the pipe with clamps at 1.00 m spacing. this includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 32 mm dia 6 Kgf/cm2 - internal work- Exposed on wall

145.5

310

45123.92

... More
50.18.8.3.1:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 25 mm pipe 12 kgf/cm2

169.8

455

77389.75

... More
50.18.9.8.1:Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 75 mm dia 6 Kgf/ cm2

162

369

59820.12

... More
50.18.9.9.1:Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2

170

537

91453.2

... More
50.18.9.21.7:Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Vent cowl

16

88

1416.48

... More
50.18.9.20.5:Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes including jointing with PVC solvent cement - 63x63x63 mm dia Tee

15

87

1317.9

... More
50.18.9.22.1:Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia Elbow

15

109

1642.35

... More
50.18.9.22.4:Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend

21

162

3421.32

... More
18.51.1:Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore

13

678

8822.06

... More
17.32.3:Providing and fixing mirror of superior glass ( of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :Oval shape 450x350 mm (outer dimensions)

4

1456

5826.8

... More
50.17.1.2:Supplying and fixing CP Towel rod 45cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.

8

87

703.04

... More
OD88500/2024-2025:Supplying and fixing 304- grade stainless steel wall mounted swing up bathroom safety Grab Bar of size 740 mm length, including fixing charges etc. complete.

1

11615

11615

... More
OD88501/2024-2025:Supplying and fixing 304- grade Stainless Steel 90 & deg; with Anti- Slip Nylon Grip wall Mounted Safety L shaped Grab Bar for toilets, including fixing charges etc. complete.

1

2903

2903.75

... More
18.35.1:Constructing masonry chamber 120x120x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix ( 1 cement : 2 coarse sand : 4 grades stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 ( 1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:With common burnt clay F.P.S. (non modular) bricks of class designation 7.5

5

27476

137384.6

... More
18.48:Providing and placing on terrace (at all floor levels) polyethylene water storage tank :ISI 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.

10000

10

108300

... More
OD143672/2024-2025:Supplying and fixing 6mm thick Stainless Steel water tank including stand ,all fittings etc.complete as per direction of Engineer in Charge

10000

36

364900

... More
OD146333/2024-2025:Providing and fixing 1.5 HP submersible motor etc as per specification.

1

13938

13938

... More
Septic Tank(Civil work)

-

-

-

... More
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil

42.58

309

13199.99

... More
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete

89.68

350

31388

... More
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)

4.72

7113

33603.84

... More
OD144499/2024-2025: Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is not payable or recoverable separately.All work upto plinth level

11.55

9825

113489.49

... More
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more

2137.33

102

219311.23

... More
5.9.2:Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.

96.32

748

72107.08

... More
13.16.1:6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)

40.3

279

11256.19

... More
Rain WaterHarvestingTank(Civil work)

-

-

-

... More
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil

10.44

309

3236.3

... More
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)

1.58

7113

11267.67

... More
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete

36.11

350

12638.5

... More
OD144510/2024-2025: Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is not payable or recoverable separately.All work upto plinth level

4.96

9825

48736.61

... More
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more

694.4

102

71252.38

... More
13.9.1:Cement plaster 1:3 ( 1 cement : 3 coarse sand) finished with a floating coat of neat cement.12 mm cement plaster

22.86

430

9834.14

... More
Generator Room(Civil work)

-

-

-

... More
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil

8.94

309

2770.07

... More
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)

3

7113

21340.29

... More
4.1.6:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size)

6.87

7527

51718.36

... More
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete

37.87

350

13254.5

... More
5.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size

3.48

9483

32972.84

... More
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more

434.63

102

44596.87

... More
2.25:Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.

9.86

269

2661.83

... More
50.6.2.2:Solid masonry using pre cast solid blocks (factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete

5.9

7153

42232.73

... More
5.3:Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 15<sup>0</sup> landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) : 3 graded stone aggregate 20 mm nominal size).

0.58

11996

6981.9

... More
5.9.5:Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers

5.82

678

3947.53

... More
5.22A.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more

69.84

102

7166.28

... More
13.4.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 coarse sand)

90.69

339

30769.3

... More
11.20.2:Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand).Medium shade pigment using 50% white cement 50 % Grey cement

32.15

1356

43618.55

... More
13.43.1:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer

57.23

73

4220.71

... More
13.60.1:Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work

57.23

158

9045.77

... More
13.46.1:Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)

33.46

202

6771.3

... More
10.14.1.1:Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm pressed, mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge: Profile BFixing with adjustable lugs with split end tail to each jamb

7

513

3591.63

... More
OD146004/2024-2025:Providing and fixing pressed steel door shutter conforming to IS:4351 made out of mullion and intermediate supports, 75x 30 mm using 20 gauge door shutter 25 mm thick side folded wall panels all made out of Tatas 18 G thick Galvano steel sheets, welded or bolted together and fitted with door fittings and powder coated with suitable colour for doors including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm pressed, mild steel welded or rigidly fixed together by mechanical means, including M.S pressed but hinges 2.5mm thick with mortar guards ,lock strike- plate and shock absorbs as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by the Engineer-in-charge .

2.52

6095

15361.32

... More
10.6.1:Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.25 mm M.S. laths with 1.25 mm thick top cover

7.84

3617

28359.71

... More
10.7:Providing and fixing ball bearing for rolling shutters.

2

515

1031.76

... More
9.48.2:Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc

287.71

225

64861.79

... More
13.61.1:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work

107.84

149

16102.19

... More
50.10.1:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete

298.9

198

59244.97

... More
12.50:Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.

48.14

771

37119.31

... More
12.51.1:Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+ 0.05%) total coated thickness, zinc coating 120 grams per sqm as per IS:mm(+0.05%) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/self tapping screws complete:Ridges plain (500-600 mm)

18.1

511

9258.51

... More
ELECTRIFICATION(Electrical work)

-

-

-

... More
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C

230

1228

282488.3

... More
1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).

35

497

17416.7

... More
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire

425

180

76776.25

... More
90.3.20.3:Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture

65

1257

81747.25

... More
90.3.24.3:Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod <br> Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture

53

1528

80996.72

... More
90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps

9

520

4688.46

... More
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)

7

7522

52655.33

... More
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)

2

4632

9264.58

... More
OD116769/2024-2025:Supply, conveyance, installation, testing and commissioning of Bulk head light fittings directly on wall including giving connections with required length of 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS making good the damages, colour washing etc as required.

24

639

15359.76

... More
OD116781/2024-2025:Supplying and fixing 200mm Plastic sill shade. as required.

7

59

413.56

... More
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.

7

111

783.16

... More
OD116768/2024-2025:Supplying and fixing 9W LED Bulb. as required.

31

159

4959.07

... More
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.

63

178

11248.65

... More
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)

300

46

13845

... More
OD163735/2024-2025:Supply of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.

63

3148

198337.23

... More
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.

63

424

26725.86

... More
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.

9

488

4396.95

... More
OD116809/2024-2025:Supply, conveyance, installation , testing and commissioning of 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.

9

2094

18848.25

... More
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell

5

193

966.65

... More
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)

38

331

12609.54

... More
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)

6

355

2134.08

... More
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)

50

475

23751

... More
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch

107

105

11330.23

... More
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch

31

163

5066.02

... More
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet

157

137

21622.04

... More
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet

31

216

6722.97

... More
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator

9

566

5100.03

... More
90.10.3.23:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )16A 3 pin plug top

6

123

741.78

... More
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket

6

317

1905.3

... More
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.

1

1052

1052.71

... More
2.17:Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32amps 415 volts "C" curve TP MCB complete with connections, testing and commissioning etc. as required.

2

1422

2845.18

... More
90.14.24.1:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.1 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.

1

276

276.98

... More
90.14.28.1:S & F Motor starters of the following ratingsSingle phase DOL starters for 0.25HP to 3HP motor

1

898

898.15

... More
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door

4

2183

8735.68

... More
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door

7

2547

17830.47

... More
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)

9

2860

25741.71

... More
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)

3

6567

19703.34

... More
90.11.1.18:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)

1

7669

7669.28

... More
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole

110

247

27223.9

... More
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole

20

1025

20501

... More
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.

30

10

306

... More
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

10

420

4201

... More
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

9

1032

9292.77

... More
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps

5

1040

5203.8

... More
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

4

2600

10400.4

... More
OD164060/2024-2025:RCCB Double pole 40A Type Hpi Enhanced immunity to unwanted tripping in environments with disturbances. eg. diesels, computers, printers, etc. • Detects faults with DC components eg. thyristors, trio etc

5

6997

34986.15

... More
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

8

3258

26066.64

... More
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps

4

3445

13782.92

... More
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm

1450

103

150263.5

... More
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm

345

112

38705.55

... More
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm

30

114

3430.8

... More
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm

400

67

26812

... More
1.17.4:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm

70

82

5789.7

... More
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm

300

108

32514

... More
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm

85

124

10545.95

... More
1.17.7:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.7 x 1.5 sq. mm

150

149

22461

... More
1.17.8:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.8 x 1.5 sq. mm

65

165

10752.95

... More
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm

50

201

10053.5

... More
1.17.10:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.10 x 1.5 sq. mm

50

216

10838.5

... More
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm

300

93

27954

... More
1.17.13:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm

125

117

14697.5

... More
1.17.14:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 2.5 sq. mm

200

151

30394

... More
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm

80

176

14108.8

... More
1.17.16:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.7 x 2.5 sq. mm

50

210

10537.5

... More
1.17.17:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.8 x 2.5 sq. mm

50

235

11758.5

... More
1.17.18:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 2.5 sq. mm

60

279

16771.2

... More
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm

250

145

36250

... More
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm

175

193

33831

... More
1.17.23:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 4 sq. mm

50

235

11784

... More
1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm

50

207

10363.5

... More
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm

50

273

13651.5

... More
90.12.7.3:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp

100

225

22536

... More
90.12.7.4:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 16 sq mm with factory made clamp

70

231

16213.4

... More
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp

285

247

70480.5

... More
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp

80

278

22277.6

... More
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp

45

330

14879.7

... More
90.12.5.31:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 95 sq mm

120

659

79082.4

... More
90.12.7.31:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm

10

686

6866.2

... More
90.12.5.3:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 10 sq mm

75

203

15288

... More
90.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm

65

210

13657.15

... More
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size

35

143

5032.3

... More
90.12.10.3:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation63/50 mm or nearest size

75

305

22884.75

... More
90.12.10.4:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation77/63 mm or nearest size

50

334

16705.5

... More
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)

4

245

982.28

... More
9.1.3:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 16 sq. mm (22mm)

2

263

527.32

... More
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)

32

271

8700.16

... More
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)

2

309

619.36

... More
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)

2

309

619.36

... More
9.2.21:Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 95 sq. mm

7

2101

14712.67

... More
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)

55

2551

140318.75

... More
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.

6

3448

20689.62

... More
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet

116

7

890.88

... More
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)

15

1045

15681.45

... More
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board

75

168

12666.75

... More
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.

4200

6

27804

... More
90.14.7:Supply and providing copper earth bus in the panel board

1385

6

8725.5

... More
90.14.10.12:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC

1

23154

23154.69

... More
90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC

1

17755

17755.18

... More
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL

12

7717

92614.44

... More
90.14.10.2:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL

3

4832

14498.67

... More
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A

17

1931

32832.27

... More
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.

9

1370

12332.25

... More
2.1.3:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N

2

7476

14952

... More
2.1.4:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N

1

8309

8309.89

... More
OD128793/2024-2025:Supply and providing L&amp;T make 125A Enclosed ATS, Frame 2(Model No:CK90163BSOO) with 4PMotorized change over(Model No:CO2-200-L&T /equivalent) with ATC controller unit(Model No-AUXC2000-L&T /equivalent ) and wire way kit or equivalent, including auto start operation for existing DG set.

1

91569

91569.32

... More
OD128792/2024-2025:Supply and fixing 32-63A,4pole ATS in the existing panel board and giving connection etc as required

4

21182

84730.76

... More
OD128791/2024-2025:Supplying and fixing ACCL 230V 30A Single Phase in the existing MCB DB complete with connections, testing and commissioning etc. as required. (EB 30A / DG : 30A, L&T Make, Cat No: AUCL01030030)

1

2939

2939.64

... More
OD189007/2024-2025:Supply and providing Panel include 3Ph pluggable type surge arrester in suitable enclosure Class B+C/ Type 1+2 as per IEC 61643 -11 for lightning current equipotential bonding to VDE 0185-305 (IEC 62305). Modular connectable arrestor with dynamic cut-off unit and visual status display for each cartridge. It should be included Locking mechanism with vibration protection and voltage keying for safe operation of the device. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse and cooling gel(L to N) & spark gap encapsulated / non exhausting (N to E) . Total Lightning Impulse Current - 37.5 kA (10/350µ sec) for Line to Neutral & 50 kA(10/350µ sec) for Neutral to Earth, Total Nominal discharge current- 90 kA (8/20µ sec) for Line to Neutral & 50 kA(8/20µ sec) for Neutral to Earth, Total Max discharge current - 200 kA (8/20µ sec). Voltage protection level 1400V (L to N) & 1500V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E) DIN rail mounting type etc complete with back up fuse as required and as directed, TOV tested. The product should be tested and approved by any one of the following external testing institute(UL, KEMA, OVE, VDE)

1

30979

30979.29

... More
OD128794/2024-2025:Supply and fixing 150/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT in the existing panel assembly as required.

7

809

5665.59

... More
OD128795/2024-2025:Supply and providing Multifunction1 meter to read: V, A, F, 3 phase accuracy class 1

1

5336

5336.93

... More
OD128796/2024-2025:Supply and fix LED indicators for all voltage ranges- Blue colour

5

233

1165.8

... More
OD128797/2024-2025:Supply and fix LED indicators for all voltage ranges- Red, Green, Black, Yellow, Orange colour

10

150

1507

... More
OD128815/2024-2025:Supply and wiring with PVC insulated stranded single core copper conductor cables for interconnecting the control devices/ equipment's including the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.5Sqmm single run

55

19

1054.9

... More
OD128816/2024-2025:Supply and wiring with PVC insulated stranded single core copper conductor cables for interconnecting the control devices/ equipment&#39;s including the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 6Sqmm single run

25

59

1479.25

... More
OD128817/2024-2025:Supply and wiring with PVC insulated stranded single core copper conductor cables for interconnecting the control devices/ equipment&#39;s including the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 10Sqmm single run

25

93

2342.75

... More
OD128820/2024-2025:Supply and fixing 125A Cutout Fuse with 100/80A HRC Link connection in existing meter board

3

677

2033.79

... More
OD128802/2024-2025:Supply and fixing 63A Cutout Fuse with 25/40/50A HRC Link connection in existing meter board

12

743

8919.36

... More
OD128818/2024-2025:Supply and fixing 32A Cutout Fuse with 16/20/25A HRC Link connection in existing meter board

4

305

1220.76

... More
OD128819/2024-2025:Supply and fixing 100A 2Way neutral link with connection in existing meter board

1

452

452.84

... More
OD128824/2024-2025:Supplying and fixing 63 A, 2 Way neutral links mounted on DMC/SMC base with connections in existing meter board

4

246

984.12

... More
OD128825/2024-2025:Supplying and fixing 32A, 2Way Neutral Links Mounted on DMC/SMC Base with connections in existing meter board

1

228

228.61

... More
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.

6

279

1679.76

... More
OD128814/2024-2025:Supply and fixing Emergency push button with enclosure of MS Construction in surface/recess with stainless steel chain &amp; hammer assembly Complete with glass and push button on wall and giving connection etc. as required

2

348

697.44

... More
4.1.4:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness

100

770

77079

... More
OD128838/2024-2025:Supply and providing 4Kg ABC Fire Extinguisher cap filled with mono ammonium phosphate powder 50% confirms to IS 1409, stored pressure type, with pressure gauge, the discharge time 24 sec, controllable discharge mechanism, jet range 5 meters, average discharge is 90%, appliccable on A,B & C and electrically started fire, A rating-3A, B rating 21B, construction: deep drawn & co2 mig welded, EPDM rubber hose with both end aluminium clamped, internal coating-epoxy powder coating, external coating-pure polyster powder coating(UV resistant),brass forged valves with safety pin is of ss material, sheet metal thickness ISI approved.

2

2966

5933.78

... More
OD128843/2024-2025:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint &#39;FIRE&#39; mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.

2

272

544.42

... More
OD128840/2024-2025:Supply and providing 2.5mm thick synthetic VC fire retardent insulating sheet to withstand 3.3 KV dielectric strength conforming to IS

5

1939

9696.95

... More
OD128841/2024-2025:Painting letters or figures with enamel paint as identification mark to SB, DB, panel board etc as required

300

11

3486

... More
OD128842/2024-2025:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.

2

236

473.9

... More
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

5

7713

38568.9

... More
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip

30

480

14419.5

... More
90.16.4.8:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 3 mm copper strip

20

555

11109.6

... More
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)

505

45

22881.55

... More
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)

400

64

25740

... More
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)

200

99

19868

... More
90.16.1.6:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG)

60

177

10664.4

... More
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)

38

25

982.68

... More
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)

20

27

554.8

... More
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)

8

28

227.44

... More
90.16.5.6:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG)

12

31

381.24

... More
OD128831/2024-2025:Supply and Providing 25x3mm brass bolt

40

22

910.8

... More
OD128832/2024-2025:Supply and Providing 25x6mm Brass Bolt

25

23

593.75

... More
OD129665/2024-2025:Supply, Installation, Testing and Commissioning of 1.5 KVA UPS, tubular battery and all accessories having 60 min. backup time with the following specifications. a) 1 ph to 1 ph b) Input pf : 0.99 @ full load c) Output pf : unity d) Input voltage range : 140V -280V with cut off e) THD : ≤ 10% f) Overall Efficiency : ≥87% g) Ambient Temperature : 0-40°C h) Generator Compatibility. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. l) EN/IEC 620401 for General Safety compatibility m) EN/IEC 620402 for Electromagnetic Compatibility. n) EN/IEC 620403 for Performance o) EN/IEC 620404 for Environmental Compatibility p) battery : exide / panasonic or equivalent

1

49451

49451.31

... More
OD132395/2024-2025:Supply, Installation, Testing and Commissioning of 2KVA UPS, tubular battery and all accessories having 60 min. backup time with the following specifications. a) 1 ph to 1 ph b) Input pf : 0.99 @ full load c) Output pf : unity d) Input voltage range : 140V -280V with cut off e) THD : ≤ 10% f) Overall Efficiency : ≥87% g) Ambient Temperature : 0-40°C h) Generator Compatibility. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. l) EN/IEC 620401 for General Safety compatibility m) EN/IEC 620402 for Electromagnetic Compatibility. n) EN/IEC 620403 for Performance o) EN/IEC 620404 for Environmental Compatibility p) battery : exide / panasonic or equivalent

1

57483

57483.49

... More
OD132416/2024-2025:Supply, Installation, Testing and Commissioning of 2.5KVA UPS, tubular battery and all accessories having 60 min. backup time with the following specifications. a) 1 ph to 1 ph b) Input pf : 0.99 @ full load c) Output pf : unity d) Input voltage range : 140V -280V with cut off e) THD : ≤ 10% f) Overall Efficiency : ≥87% g) Ambient Temperature : 0-40°C h) Generator Compatibility. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. l) EN/IEC 620401 for General Safety compatibility m) EN/IEC 620402 for Electromagnetic Compatibility. n) EN/IEC 620403 for Performance o) EN/IEC 620404 for Environmental Compatibility p) battery : exide / panasonic or equivalent

4

78752

315008.88

... More
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid

100

790

79097

... More
90.9.1.2:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree

4

162

651.28

... More
90.9.1.3:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 Degree /Tee

4

157

629.96

... More
90.9.1.4:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree

4

157

629.96

... More
90.9.1.5:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal coupler

2

115

231.48

... More
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid

160

1099

175990.4

... More
90.9.2.5:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree

4

252

1011.72

... More
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap

4

143

574.28

... More
Fire Fighting Work(Electrical work)

-

-

-

... More
OD186442/2024-2025:Supply ,installation ,testing and commissioning of electric driven terrace pump mounted on anti vibration pads consisting of following,complete in all respects as required. a) Horizontal type, centrifugal, End suction pump of CI body & bronze impeller with stainless steel shaft, mechanical seal at a flow of 450 lpm at 35 m Head conforming to IS 1520. b)Suitable HP Squirrel cage induction motor, TEFC type having synchronous speed of 1500 RPM & class- 'F' insulation suitable for operation on 415 V, 3 phase 50 Hz AC supply with IP55 protection for enclosureconforming to IS-325 c)MS fabricated common base plate ,coupling,coupling guard ,foundation bolts etc as required d)Suitable cement concrete foundation duly plastered .

1

72819

72819

... More
90.17.12.5:Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :100mm dia

2

13051

26102.58

... More
90.17.14.5:Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :100mm dia

3

9904

29713.5

... More
90.17.9.1:Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :Single headed Gunmetal

2

6857

13714.98

... More
90.17.16.2:Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304)

4

3913

15654.64

... More
OD117674/2024-2025:Supply &amp; Fixing of Hose cabinet made of M.S Sheet with full front glass door and locking arrangements suitable to accommodate 2 Nos 15 M long Hose pipes and 1 No Branch pipe. The cabinet shall be painted to scarlet red colour out side &amp; Offwhite inside.

2

3878

7757.34

... More
90.17.22:Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required

1

1393

1393.6

... More
90.17.17.1:Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. a. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 b. 20 mm nominal internal dia gun metal globe valve & nozzle. c. Drum and brackets for fixing the equipmets on wall. d. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m

2

7870

15741.14

... More
90.17.18.2:Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Stainless Steel (Grade 304)

2

1471

2942.06

... More
90.17.7.7:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :100 mm dia

25

1485

37133.5

... More
OD165792/2024-2025:SITC OF ball valve C.I slim seal type with required flanges , nuts and bolts gasket etc complete 25mm dia

4

1445

5782

... More
OD165793/2024-2025:Supply and providing fire brigade inlet 63mm dia 4 way as required

1

13546

13546.87

... More
OD117760/2024-2025:Supply and providing 4Kg ABC Fire Extinguisher cap filled with mono ammonium phosphate powder 50% confirms to IS 1409, stored pressure type, with pressure gauge, the discharge time 24 sec, controllable discharge mechanism, jet range 5 meters, average discharge is 90%, appliccable on A,B & C and electrically started fire, A rating-3A, B rating 21B, construction: deep drawn & co2 mig welded, EPDM rubber hose with both end aluminium clamped, internal coating-epoxy powder coating, external coating-pure polyster powder coating(UV resistant),brass forged valves with safety pin is of ss material, sheet metal thickness ISI approved.

4

2966

11867.56

... More
OD117706/2024-2025:Supply and providing 4.5Kg CO2 fire extinguisher, filled with CO2 gas as per IS 15222, control discharge mechanism fitted with minimum 1.5 meter wire braided hose & flat horn with diffuser nozzle for dispersed discharge of CO2, discharge time 37 sec, average discharge is 95%, applicable on class B, C and electrcally started fire, external coating is of enamel spray painting, valve confirm to IS 3224 ISI marked, CO2 cylinder construction: hot spinning by seamless pipes & bearing ISI mark, body confirms to IS 7285 extinguishers to ISI marked. fire rating:89B

6

7549

45294.06

... More
OD117950/2024-2025:Suply and providing emergency fire escape lighting system consisting 2 nos lamp ,7 AH MF battery charging unit ,exit sign display etc in MS enclosure

4

4165

16660.12

... More
17.1.4:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.

4

490

1963.12

... More
17.1.7:FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in A.B.S. box with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.

4

593

2374.12

... More
17.1.9.2:Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required.6 Zone

1

14617

14617.84

... More
OD189018/2024-2025:Supply and laying Fire Survival cable having copper conductor with dual insulation of mica and XLPE with LSZH inner and outer sheathed with GI wire armouring as per IS 3975 suitable for circuit integrity of 950 deg centigrade 3 hours and made according to IS 17505-1 and working voltage upto and including 1100V.

120

287

34542

... More
17.5.4:Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.

120

61

7424.4

... More
OD117833/2024-2025:Supply & erection of Glow Sign Boardmade of 3mm thick PVC foam board for each floor 12" x 4" (appropriate places)

30

205

6174

... More
OD117834/2024-2025:Supply & erection of Glow Sign Board made of 3mm thick PVC foam board for Assembly Point sign board 16" x 16"

4

368

1473.64

... More
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)

1

2551

2551.25

... More
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet

2

46

93.86

... More
OD119589/2024-2025:Supply and fix LED indicators for all voltage ranges- Blue colour

1

233

233.16

... More
OD119590/2024-2025:Supply and fix LED indicators for all voltage ranges- Red, Green, Black, Yellow, Orange colour

2

150

301.4

... More
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps

1

1040

1040.76

... More
90.14.28.2:S & F Motor starters of the following ratingsThree phase DOL starters for 0.25HP to 7.5 HP motor

1

1630

1630.19

... More
OD119592/2024-2025:Supply and fixing Auto/Manual Selector Switch in existing Panel and giving connection etc. as required

1

581

581.61

... More
16.8:Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required

1

1548

1548.66

... More
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm

25

83

2096.75

... More
90.12.7.14:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 10 sq mm with factory made clamp

35

234

8216.6

... More
9.1.7:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 10 sq. mm (22mm)

2

262

524.02

... More
90.6.5.12:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 2.50 sq mm

15

110

1653.3

... More
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)

70

64

4504.5

... More
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)

4

27

110.96

... More
OD117831/2024-2025:Copying charges for additional copies per A2 sheet

15

17

261.3

... More
OD117832/2024-2025:Charges for preparation of Fire Drawing per A2 sheet first copy

5

776

3881.25

... More
OD188866/2024-2025:Supply and fixing (in appropriate location) of Fire emergency plan (colour) printed in photo paper of size A2 sand witched in clear acrylic sheet fixed using SS studs and other accessories complete as required as per the technical specification and conforming to IS 9457,IS 12349,IS 12407

2

1941

3883.58

... More
Diesel Generator(Electrical work)

-

-

-

... More
OD126039/2024-2025:Supply installation and commissioning of 82.5 kVA Diesel Generator set complete with integral acoustic enclosure as per existing CPCB 4+ norms and as per technical details given below 1Engine a) Make of Engine - as specified in accepted list of materials. b) Type of Engine - Diesel Engine c) No. of Cylinders- As per manufactures standards. d) Method of Cooling; Liquid cooled with radiator. e) Aspiration -Turbo charged, charge after cooled. f) Design - Suitable for generating set operating. g) Output- As per manufactures standards. 2. Standard accessories with Diesel Engine. a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Electronic Governor g) Fuel filter h) Exhaust silencer i) Exhaust Muffler j) Lubricating oil filter. k) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button. b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter. e) Battery charging Ammeter. 4. Safety Controls for Engine. a) Trip for low lubricating oil pressure. b) Trip for high water temperature. 5.Fuel pipe: Oil resistance flexible hoses of 20mm dia or nearest size MS pipe as per manufacturers standard, 6 Brush less Alternator a) Make - as specified in accepted list of materials b) Type - Self exited and self-regulated, brush less c) Capacity; 82.5kVA/ 66 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, 4 wire system. e) Speed - 1500 rpm f) Voltage regulation band - +/-2.5% of rated voltage g) Frequency - 50 Hz h) Insulation - Class -F/H .The Alternator should confirm to IS 4722. Operation and service manual shall be provided.7.Fuel Tank Suitable size built in type integrated with the acoustic enclosure. Fuel connection shall be done as per standards.7. Battery. Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 8.Supply of 75% HSD of fuel tank capacity for test and trail run,9. The DG shall be supplied along with specially designed company fabricated (to be fabricated in the same company from where the DG is delivered.)acoustic enclosure to meet the stingent MOEF/CPCB norms of 75 dB A @1m 75% load under free field condition 10. The standard Electric control panel integrated with acoustic enclosure comprising of the following. a) 125A,4Pole MCCB b) Digital Multi function meter with accuracy class 1 to read parameters such as KW, KVA, PF, voltage, Current Frequency etc: c) Digital type single function KWH meter with accuracy class 1, d) external source power (230V AC) battery charger e) Provision for connecting Auto start (AMF/ATS connection),10.Exhaust Piping, Exhaust Piping shall be vent to the top of the nearest tallest building if required . If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of Heat retardant aluminum paint shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacturer.) including arranging load test at site or company, assembly unit with presents of department staff and adding full tank diesel while hand over .The DG set should be provided with 5 year comprehensive maintenance (including oil change ) from the date of commissioning

1

1397307

1397307.63

... More
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.

1

409

409.08

... More
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.

1

9368

9368.05

... More
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board

25

168

4222.25

... More
90.17.7.5:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :65 mm dia

10

1037

10371.4

... More
90.17.7.6:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia

5

1140

5704.65

... More
90.6.5.18:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 1.50 sq mm

10

98

986.3

... More
90.6.5.12:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 2.50 sq mm

10

110

1102.2

... More
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip

20

480

9613

... More
90.16.4.8:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 3 mm copper strip

10

555

5554.8

... More
OD189008/2024-2025:Supplying and laying 25x3 mm copper strip at 0.60 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)

30

672

20179.8

... More
OD125814/2024-2025:Supply and Providing 25x3mm brass bolt

15

22

341.55

... More
OD125815/2024-2025:Supply and Providing 25x6mm Brass Bolt

10

23

237.5

... More
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm

20

103

2072.6

... More
OD188849/2024-2025:Copying charges of Electrical Drawing per A3 sheet additional copies

5

17

87.1

... More
OD188850/2024-2025:Charges for preparation of Electrical Drawing per A3 sheet first copy

25

776

19406.25

... More
Lift(Electrical work)

-

-

-

... More
OD186483/2024-2025:Supply, Installation,Testing and Commissioning of 20 Passenger gearless machine room less lift with the following specification including all required standard features.1 .Type of Lift:20 Passenger capacity , Gearless 2. Load / Persons :1360 Kg. / 20persons 3 .Rated speed :1 M/Sec. 4. Travel : 7.2 Mtr ( Approx) 5. No. of floor and entrance served: 3 stops and 3 openings 6. No. of floor served :Three floors 7. Method of control : Micro processor based V3F with ARD system. 8. Size of lift well :2500 mm X 3000 mm 9. Car entrance: As per IS. 10.Leveling accuracy : As per IS 11. Car door opening : As per IS 12. Drive : Variable voltage variable frequency(V3F) 13 .Operation : Simplex full selective collective control with ON/OFF switch 14. Construction of design and furnishing of car body work: Vandal proof Stainless steel(SS304,make:Tata/Jindal) finish cabinet with Scratch proof Stainless steel door(sheet minimum1mm thickness), Stainless steel mirror finish ceiling, Aluminium 3mm minimum thickness anti skid flooring, fan with timer cut-off, push to talk, LED display, LED light, hand rails and floor announcement system. All buttons in car and all landings should have Braille sign. 15. Landing entrance : Automatic centre/Telescopic opening Vandal proof stainless steel sliding door as per ISS with provision for mechanical opening key for emergency with full length infra red light curtains and half framed glass door . 16. Call and position indicators : Up/down direction & position Dot Matrix LED indication shall be provided at all landings 17. Electric supply : 1) Light 230/50C/s single phase 2 wire system. 2) 415V 50C/s 3 phase 4 wire system. 18. Infra red door opening system: To be provide for entire length of the door 19. Automatic Rescue Device :Provide automatic rescue device with an electronic controller powered by maintenance free batteries with capacity for minimum four rescue operation at full load . The rescue operation should act within 10 seconds of power failure 20. Regulation :350V- 450V (SMPS based) 21. Indication in the car : a) Car position b) Call indicator c) Door close/open push button d) Emergency stop button e) push button switch for fan and light f) Non stop button g) Battery operated emergency lamp with rechargeable batteries. h) Battery operated alarm bell i) Intercom wiring with one master unit with two slaves j) Fireman's switch at main lobby i) Auto attendant control (inside the car) 22. Winding handle: Manual winding handle for use in emergency. 23. Safeties a) Over speed governor, operated safety gear b) Buffers c) Motor over load and under voltage protection d) Phase reversal protection e) Other safeties as per ISS f) Single phase preventer g) Final limit switch 24. Leveling Automatic leveling at all landing as per IS. 25. Control panel :Control panel will be dust and vermin proof of sheet metal enclosure 26. Announcement System: To provide lift announcement system 27. Tests :At site test as per IS to be carried out and approval from Electrical Inspectorate before Handing over. 28. Scope of work:- a) Supply of lift materials b)Minor civil works such as removal of temporary brick work in the lift entrance without affecting the building structure, finishing/ altering civil works in lift entrance/ pit by providing brick work & plastering if necessary including minor civil works such as construction of buffer block in the pit machine foundation in the machine room, necessary core cutting , cutting pockets and grounding brackets for the guide rails, grouting boxes for control units, correction of wall opening in the front side in plastering c) Scaffolding d) Door frames e) Supporting steel f) Temporary electric supply for installation of lift. Electric supply for testing and commissioning of lift is to be arranged by the firm on their own account. g) Intercom facilities with one master and two slaves h) Battery operated alarm i) Obtaining Scheme approval as well as energization Certificate from the electrical Inspectorate including preparation of necessary drawing for the same. inclusive of necessary fee to the Inspectorate and first year insurance as per new lift rule by the firm for which no refund will be made from the department including taking insurance for one year as per new lift rule. j) Supply of book let with complete details of maintenance schedule and control diagram. k) Giving training to department staff for attending trouble shooting 28. Guarantee: Company shall carry out free maintenance and service during warranty period which also includes a) Cleaning lift equipment b) Lubrication of all moving parts c) Replacing of lubricating oil when required d) Checking and adjusting contacts e) Replacing fusible item alarm etc. f) Recharging batteries in case of drain/ renewing batteries g ) Replacing /rewinding of all defective parts of the lift including motors and V3F unit.

1

2689162

2689162.88



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.