Military Engineer Services Tender

Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.

Military Engineer Services - MES Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date13 Dec 2024
Closing Date20 Jan 2025
Tender Amount₹ 46,00,000 
Notes
Download

Costs

Summary

Improvement And Augmentation Of Lt Distribution System And Dg Set Canopy At Cgra Rameswaram And Dhq-4 Kochi And Provision Of Trolley Mounted Transformer Of Capacity 500 Kva For Aor Of Ge(i) (cg) Kochi.

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply,spreading and levelling clean dry sand in trenches all as specified for cable protection complete all as specified and as directed. Note: Punnned thickness shall be measured and paid.

83

-

-

... More
Supply and lay unreinforced precast cable cover size 250X150X40 mm LV1 complete all as specified and as directed.

6900

-

-

... More
Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor 1100 Volts grade of size 120 Sqmm 3.5 core including connecting/testing after taking out from trenches/ pole unserviceable LT UG cable complete all as specified and directed. NOTE: Excavation, earth work shall be measured and paid for separately.

230

-

-

... More
Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor 1100 Volts grade of size 95 Sqmm 3.5 core including connecting/testing after taking out from trenches/ pole unserviceable LT UG cable complete all as specified and directed. NOTE: Excavation, earth work shall be measured and paid for separately.

150

-

-

... More
Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor 1100 Volts grade of size 70 Sqmm 3.5 core including connecting/testing after taking out from trenches/ pole unserviceable LT UG cable complete all as specified and directed. NOTE: Excavation, earth work shall be measured and paid for separately.

200

-

-

... More
Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor 1100 Volts grade of size 50 Sqmm 3.5 core including connecting/testing after taking out from trenches/ pole unserviceable LT UG cable complete all as specified and directed. NOTE: Excavation, earth work shall be measured and paid for separately.

140

-

-

... More
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric cable, heavy duty, 1100 volt grade with stranded aluminium conductor cables of 4 core 25 Sqmm sizes fixed in wall/ roof or laying in trenches etc., after taking out from trenches/ pole unserviceable LT UG cable complete all as specified and as directed. NOTE: Excavation, earth work shall be measured and paid for separately.

760

-

-

... More
Supply, install, test and commissioning of LT Panel, outdoor type, powder coated, 3.15 mm thick CRCA Sheet, CPRI approved having, IP 55, MS angle iron section of 50X50X6 mm frame, suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with Horizontal aluminium bus bar 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators, factory fabricated, roof canopy, with front and back openable double door system lockable/openable by keys from both sides, louvers & air vent gasket for natuaral flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The inner shell be made out of 3.15 mm thick CRCA Sheat duly compartmentalised for each control gear with louvers and air vent gasket for natuaral flow of air and suiatable provision to accomodate incomer/outgoing MCCB's/MCBs and metering devices and suitable busbar chamber for passing and connecting UG cables. Providing bus bar for phases and neutral and shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made on non hygroscopic, non combustile, track resistant, high strength FRP/SMC/DMC material at an interval of not more than 300 mm through out the length of the TPN bus bar after taking out unserviceable Panel complete all as specified and directed by the Engr-in-Charge with and including the following:- (a)Horizontal Aluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 600 Amps for phases and 400 Amps for Neutral. METERING UNIT:- b) RY B Indications (LED Type) - 1 sets. c) Digital Multifunction meter 01 No d) CT's - 600/5A, CL-1, 15VA-1set

1

-

-

... More
INCOMING :- e) MCCB 4 Pole, 415 V, Thermal magnetic release type, 350 Amps, Ics =100% Icu with breaking capacity 50 KA - 01 Nos Out going: f) MCCB 4 Pole, 415 V, Thermal magnetic release, 160 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos g) MCCB 4 Pole, 415 V, Thermal magnetic release, 125 Amps, Ics =100% Icu with breaking capacity 36 KA - 02 Nos h) MCCB 4 Pole, 415 V, Thermal magnetic release, 63 Amps, Ics =100% Icu with breaking capacity 16 KA - 02 Nos j) Street light timer for automatic operation of street light Note: (a) The quoted rate includes the cost of sutable foundation PCC 1:2:4 type B1 (using 20mm graded stone aggregate) pedestals recommended by the manufacturer of panel board and Angle iron base frame as required size as per above panel ,total leg height 600mm and grouting in side PCC 150mm legs and made out of ISA 50x50x6mm thick angle iron duly painted. (b)The quoted rate includes connecting the cables from the existing panel board after taking out the cable glands and connecting the same in the new panel board all as directed by Engineer-in-charge (c) The quoted rate includes the cost of suitable cable glands for the cable connections all as directed bv Enar-in-charae. (d) The quoted rate includesAluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 600 Amps for phases and 400 Amps for Neutral.

-

-

-

... More
Supply, install, test and commissioning of LT Panel, outdoor type, powder coated, 3.15 mm thick CRCA Sheet, CPRI approved having, IP 55, MS angle iron section of 50X50X6 mm frame, suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with Horizontal aluminium bus bar 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators, factory fabricated, roof canopy, with front and back openable double door system lockable/openable by keys from both sides, louvers & air vent gasket for natuaral flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The inner shell be made out of 3.15 mm thick CRCA Sheat duly compartmentalised for each control gear with louvers and air vent gasket for natuaral flow of air and suiatable provision to accomodate incomer/outgoing MCCB's/MCBs and metering devices and suitable busbar chamber for passing and connecting UG cables. Providing bus bar for phases and neutral and shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made on non hygroscopic, non combustile, track resistant, high strength FRP/SMC/DMC material at an interval of not more than 300 mm through out the length of the TPN bus bar after taking out unserviceable Panel complete all as specified and directed by the Engr-in-Charge with and including the following:- (a)Horizontal Aluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 400 Amps for phases and 250 Amps for Neutral. METERING UNIT:- b) RY B Indications (LED Type) - 1 sets. c) Digital Multifunction meter 01 No d) CT's - 400/5A, CL-1, 15VA-1set

1

-

-

... More
INCOMING :- e) MCCB 4 Pole, 415 V, Thermal magnetic release type, 160 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos Out going: f) MCCB 4 Pole, 415 V, Thermal magnetic release, 125 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos g) MCCB 4 Pole, 415 V, Thermal magnetic release, 100 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos h) MCCB 4 Pole, 415 V, Thermal magnetic release, 63 Amps, Ics =100% Icu with breaking capacity 16 KA - 02 Nos j) MCB, TPN, 415V, 40Amps, with breaking capacity 10 KA - 02 Nos Note: (a) The quoted rate includes the cost of sutable foundation PCC 1:2:4 type B1 (using 20mm graded stone aggregate) pedestals recommended by the manufacturer of panel board and Angle iron base frame as required size as per above panel ,total leg height 600mm and grouting in side PCC 150mm legs and made out of ISA 50x50x6mm thick angle iron duly painted. (b)The quoted rate includes connecting the cables from the existing panel board after taking out the cable glands and connecting the same in the new panel board all as directed by Engineer-in-charge (c) The quoted rate includes the cost of suitable cable glands for the cable connections all as directed bv Enar-in-charae. (d) The quoted rate includesAluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 400 Amps for phases and 250 Amps for Neutral.

-

-

-

... More
Supply, install, test and commissioning of LT Panel, outdoor type, powder coated, 3.15 mm thick CRCA Sheet, CPRI approved having, IP 55, MS angle iron section of 50X50X6 mm frame, suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with Horizontal aluminium bus bar 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators, factory fabricated, roof canopy, with front and back openable double door system lockable/openable by keys from both sides, louvers & air vent gasket for natuaral flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The inner shell be made out of 3.15 mm thick CRCA Sheat duly compartmentalised for each control gear with louvers and air vent gasket for natuaral flow of air and suiatable provision to accomodate incomer/outgoing MCCB's/MCBs and metering devices and suitable busbar chamber for passing and connecting UG cables. Providing bus bar for phases and neutral and shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made on non hygroscopic, non combustile, track resistant, high strength FRP/SMC/DMC material at an interval of not more than 300 mm through out the length of the TPN bus bar after taking out unserviceable Panel complete all as specified and directed by the Engr-in-Charge with and including the following:- (a)Horizontal Aluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 400 Amps for phases and 250 Amps for Neutral. METERING UNIT:- b) RY B Indications (LED Type) - 1 sets. c) Digital Multifunction meter 01 No d) CT's - 400/5A, CL-1, 15VA-1set

1

-

-

... More
INCOMING :- e) MCCB 4 Pole, 415 V, Thermal magnetic release type, 160 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos Out going: f) MCCB 4 Pole, 415 V, Thermal magnetic release, 100 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos g) MCCB 4 Pole, 415 V, Thermal magnetic release, 63 Amps, Ics =100% Icu with breaking capacity 16 KA - 02 Nos h) MCB, TPN, 415V, 40Amps, with breaking capacity 10 KA - 02 Nos Note: (a) The quoted rate includes the cost of sutable foundation PCC 1:2:4 type B1 (using 20mm graded stone aggregate) pedestals recommended by the manufacturer of panel board and Angle iron base frame as required size as per above panel ,total leg height 600mm and grouting in side PCC 150mm legs and made out of ISA 50x50x6mm thick angle iron duly painted. (b)The quoted rate includes connecting the cables from the existing panel board after taking out the cable glands and connecting the same in the new panel board all as directed by Engineer-in-charge (c) The quoted rate includes the cost of suitable cable glands for the cable connections all as directed bv Enar-in-charae. (d) The quoted rate includesAluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 400 Amps for phases and 250 Amps for Neutral.

-

-

-

... More
Supply, install, test and commissioning of LT Panel, outdoor type, powder coated, 3.15 mm thick CRCA Sheet, CPRI approved having, IP 55, MS angle iron section of 50X50X6 mm frame, suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with Horizontal aluminium bus bar 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators, factory fabricated, roof canopy, with front and back openable double door system lockable/openable by keys from both sides, louvers & air vent gasket for natuaral flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The inner shell be made out of 3.15 mm thick CRCA Sheat duly compartmentalised for each control gear with louvers and air vent gasket for natuaral flow of air and suiatable provision to accomodate incomer/outgoing MCCB's/MCBs and metering devices and suitable busbar chamber for passing and connecting UG cables. Providing bus bar for phases and neutral and shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made on non hygroscopic, non combustile, track resistant, high strength FRP/SMC/DMC material at an interval of not more than 300 mm through out the length of the TPN bus bar after taking out unserviceable Panel complete all as specified and directed by the Engr-in-Charge with and including the following:- (a)Horizontal Aluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 400 Amps for phases and 250 Amps for Neutral. METERING UNIT:- b) RY B Indications (LED Type) - 1 sets. c) Digital Multifunction meter 01 No d) CT's - 400/5A, CL-1, 15VA-1set

1

-

-

... More
INCOMING :- e) MCCB 4 Pole, 415 V, Thermal magnetic release type, 160 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos Out going: f) MCCB 4 Pole, 415 V, Thermal magnetic release, 100 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos g) MCCB 4 Pole, 415 V, Thermal magnetic release, 63 Amps, Ics =100% Icu with breaking capacity 16 KA - 02 Nos h) MCB, TPN, 415V, 40Amps, with breaking capacity 10 KA - 02 Nos j) Street light timer for automatic operation of street light Note: (a) The quoted rate includes the cost of sutable foundation PCC 1:2:4 type B1 (using 20mm graded stone aggregate) pedestals recommended by the manufacturer of panel board and Angle iron base frame as required size as per above panel ,total leg height 600mm and grouting in side PCC 150mm legs and made out of ISA 50x50x6mm thick angle iron duly painted. (b)The quoted rate includes connecting the cables from the existing panel board after taking out the cable glands and connecting the same in the new panel board all as directed by Engineer-in-charge (c) The quoted rate includes the cost of suitable cable glands for the cable connections all as directed bv Enar-in-charae. (d) The quoted rate includesAluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 400 Amps for phases and 250 Amps for Neutral.

-

-

-

... More
Removing the old canopy of DG Set of capacity 160 KVA and Supply and installation of DG set Acoustic Enclosure or soundproofing canopy of capacity 160 KVA installed at CGRA Rameswaram of approved make. The framework/Acoustic Enclosure shall be made out of suitable sheet steel with anti-corrosive paint. Specially designed acoustic doors shall be provided with glass window for visibility of the DG sets from outside. These doors shall have a proper sealing arrangement to ensure that there is no sound leakage. The enclosure shall be provided with suitable ventilating/exhaust fans for fresh air & hot air exhaust with all accessories required. The ventilation system shall be designed so that the temperature rise in acoustic enclosure shall be less than 15 Deg C above ambient. The enclosure shall be supplied with necessary anti vibration pads between DG & Enclosure and also between enclosure & foundation. Noise level - 75dB right around measured at a distance of 1 meter from the enclosure complete all as specified and directed.

2

-

-

... More
Earthing complete with Galvanized steel earth plate electrode of size 600mmX600mm, 6.00 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below the normal ground level with top edge of the plate not less than 1.5m below normal GL and connected to galvanized iron strip of size 32 x 6 mm size by means of bolts, nuts, check nuts and washers of galvanized iron steel all as shown in Electrical Plate No.5 connecting to earthing test point, including necessary earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1 (using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form work complete including necessry test on completion all as specified and as directed. ( LT panels-2 nos x 2=4 nos, Note : The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 , RCC cover slab, GI funnel with 15 mm dia watering pipe, wire mesh, 40mm dia light grade GI protection pipe for earth lead etc., complete.

16

-

-

... More
Supply, install, testing and commisioning of Dstribution transformer stepdown Level 2 (Prevously EE Level 3 before Amendment No 4 to IS 1180), 11KV/0.433KV, Three Phase complying with IS: 1180/IEC-76(Part-1) 2014 with latest ammanmendts, indoor type double copper wound suitable for 50 Hz system of capacity 500 KVA, oil immersed naturally cooled delta connected on HT side and Star connected on LT side, Vector Group Dyn11, provided with OFF load tap changer to vary secondary voltage from -7.5% to + 7.5% in step of 2.5%. Losses should be confined to the limits specified as follows:

1

-

-

... More
maximum allowable losses at full load (100%) & Half Load (50% )shall not be exceeded 5838 watts & 2147 Watts Respectivly as per GRIHA RATING, Percentage Impedance: 4.5%. Losses and Impedance are subjected to tolerance as specified in IS 1180. The transformers should be supplied with first filling of oil confirming to IS 335. The transformer should have both side cable end box with neutral brought out complete all as directed by Engineer - in -Charge, and installation of transformer shall be carried out as per IS-10028 and comprising with the following standerd fittings/ Technical specifications: (a) Lifting lug for transformer and tank. (b) Earthing terminal rating and diagram plate. (c) Air release device. (d) Oil filling inlet pipe with plug.

-

-

-

... More
(e) Drain outlet pipe with brass gate valve. (f) Conservator tank with oil level indicator (g) Silica jel breather (j) First fill of oil upto level including conservator tank with fresh new oil conforming to IS335. (k) Type of connection Delta/Star (1) Type of cooling: Oil and Natural Air. (m) Vector group: DYN 11. (n) Temperature rise over an ambient of 50 °C maximum. (o) Cable end box on both side for HT/LT cables of suitable size. (p) Provision of thermometer with pocket. (q) Provision of oil and winding temperature gauge.

-

-

-

... More
Material and labour for fabrication of towing type transformer trolley for 500 KVA Transformer step down outdoor type 11KV/433 V capacity complete made up of MS "I" beam of 250x125x6.9mm(37.3 Kg/mtr) and MS sheet for platform 6mm thick(47.10 Kg/sq mtr) mounted on 4 wheels with rims mounted on 02 Nos front and rear axle wheel with leaf spring clamps cushioned arrangement between platform and front and rear axle complete with towing arangement with hook to take full load of trolley and transformer, jali(XPM) around platform on angle iron frame of size 40x40x5 mm opening arrangement from both side with locking arrangement for loading and unloading of transformer including welding, bending and drilliing holes. Spray painting with two coat of synthetic enamel paint over a coat of primer on overall surface complete all as specified and directed by Engineer-in-charge. Note- (A) LT Panel with all accessories, HT cable and LT cable will be measured and paid separately (B) Trolley suitable for 500 KVA transformer with following fittings/accessories:

1

-

-

... More
(i) Size of the trolley platform shall be 4 Mtr x 2.5 Mtr and sufficient space all around the transformer for ventilation/maint purpose as recommended by OEM and accommodate HT/LT connecting cables loop on the platform. (ii) The trolley shall be provided with steel square net of suitable gauge fixed on iron in all round the trolley body with opening arrangement as protection. (iii) Necessary provision for PVC insulated heavy duty copper cable multistranded single core 95 Sq mm with cable lugs to connect the earthing as cut to required length - 50 mtr (iv) The complete unit of transformer should be mounted on a mobile trolley suitable for a maximum speed of 30 km/hr. (v) Trolley should be mounted on four solid rubber tyres (with one spare wheel) and turning radius of trolley shall be suitable for roads. (vi) Tow bar shall be prrovided at front and hook on rear side shall be provided. (vii) The trolley shall be minimum ground clearance of 250mm. (viii) All vibrating components should be mounted on anti vibrating pads/mounts

-

-

-

... More
(ix) Mud guards at rear, front and side reflectors are also required in the trolley. (x) Cable, LT Panel with accessories and connector- Trolley should be provided with separate cable drums suitable for 50 meter HT power cable and 2 runs of 35 M LT power cable made with 2.5 mm thick MS sheet and 50mm dia soft with 2 nos beering mounted at suitable place on the trolley with 50x50x6mm angle iron braket. Trolley shall be mounted with LT Panel, outdoor type, powder coated, 3.15 mm thick CRCA Sheet, CPRI approved having, IP 55, MS angle iron section of 50X50X6 mm frame, suitable for 3 Phase 415 volts 50 Hz, AC supply with MCCB, 4 Pole, 630 Amps as incomer and other required accessories. (xi) Walk around space is required around transfer with guards on trolley. (C) Other Accessories:- (i) Tool Box -Tool box shall be made with 1 mm thick mild steel sheet with suitable locking arrangement and fixed on trolley. The tool box shall have adequate size to accommodate following ISI marked tools which are to be very high quality.

-

-

-

... More
Supply, install, test and commissioning of LT Panel, outdoor type, powder coated, 3.15 mm thick CRCA Sheet, CPRI approved having, IP 55, MS angle iron section of 50X50X6 mm frame, suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with Horizontal aluminium bus bar 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators, factory fabricated, roof canopy, with front and back openable double door system lockable/openable by keys from both sides, louvers & air vent gasket for natuaral flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The inner shell be made out of 3.15 mm thick CRCA Sheat duly compartmentalised for each control gear with louvers and air vent gasket for natuaral flow of air and suiatable provision to accomodate incomer/outgoing MCCB's/MCBs and metering devices and suitable busbar chamber for passing and connecting UG cables. Providing bus bar for phases and neutral and shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made on non hygroscopic, non combustile, track resistant, high strength FRP/SMC/DMC material at an interval of not more than 300 mm through out the length of the TPN bus bar after taking out unserviceable Panel complete all as specified and directed by the Engr-in-Charge with and including the following:- (a)Horizontal Aluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 1000 Amps for phases and 750 Amps for Neutral. METERING UNIT:- b) RY B Indications (LED Type) - 1 sets. c) Digital Multifunction meter 01 No d) CT's - 630/5A, CL-1, 15VA-1set

1

-

-

... More
INCOMING :- e) MCCB 4 Pole, 415 V, Thermal magnetic release type, 630 Amps, Ics =100% Icu with breaking capacity 50 KA - 01 Nos Out going: f) MCCB 4 Pole, 415 V, Thermal magnetic release, 250 Amps, Ics =100% Icu with breaking capacity 36 KA - 01 Nos g) MCCB 4 Pole, 415 V, Thermal magnetic release, 125 Amps, Ics =100% Icu with breaking capacity 16 KA - 01 Nos h) MCCB 4 Pole, 415 V, Thermal magnetic release, 63 Amps, Ics =100% Icu with breaking capacity 16 KA - 01 Nos Note: (a) The quoted rate includes the cost of sutable foundation PCC 1:2:4 type B1 (using 20mm graded stone aggregate) pedestals recommended by the manufacturer of panel board and Angle iron base frame as required size as per above panel ,total leg height 600mm and grouting in side PCC 150mm legs and made out of ISA 50x50x6mm thick angle iron duly painted. (b)The quoted rate includes connecting the cables from the existing panel board after taking out the cable glands and connecting the same in the new panel board all as directed by Engineer-in-charge (c) The quoted rate includes the cost of suitable cable glands for the cable connections all as directed bv Enar-in-charae. (d) The quoted rate includesAluminium busbar for 3 phase, 440 volts, 50Hz, 4 wire system of rating 600 Amps for phases and 400 Amps for Neutral.

-

-

-

... More
Supply and fix XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor, 1100 volts Earthed grade, 3 core cross sectional area 185 sq. mm including taking out complete all as specified and directed.

40

-

-

... More
Supply and fix XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor, 1100 volts Earthed grade, 3.5 core cross sectional area 300 sq. mm including taking out complete all as specified and directed.

60

-

-

... More
Schedule of Credit (Minus) Rs.14500.00 NOTE: Bidder shall insert credit amount of Rs. 14500.00 as rate in Green field under Col-13.

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.