Kerala State IT Infrastructure Limited Tender

Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.

Kerala State IT Infrastructure Limited - KSITIL Tender

Works
Coronavirus COVID 19
Eprocure
Opening Date17 Jun 2019
Closing Date23 Jul 2019
Tender Amount₹ 26,30,50,641 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Summary

Building 2 At Technology Innovation Zone, Kalamassery

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Earth work in excavation by mechanical means (Hydraulic excavator ) / manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed-All kinds of soil

2239.2

-

-

... More
Extra for every additional lift of 1.50 m or part thereof in ( for taking out excavated earth/Rock beyond the depth of 1.50 m from Ground level)

-

-

-

... More
All kinds of soil 1.50 - 3.0 m depth

2239.2

-

-

... More
All kinds of soil 3.0 - 4.50 m depth

10

-

-

... More
Ordinary / Hard rock 1.50 - 3.0 m depth

10

-

-

... More
Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.

-

-

-

... More
a) Ordinary rock

20

-

-

... More
b) Hard rock (blasting prohibited)

20

-

-

... More
Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. Note: PCC area as per GFC x depth of excavation will be considered for calculating volume of excavation. Working space and extra space for side slope soil stablisation will not be measured and paid for, it is deemed to be included in the rate. All kinds of soil.

1796

-

-

... More
Excavation work by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50m.

-

-

-

... More
a) Ordinary rock

10

-

-

... More
b) Hard rock ( blasting prohibited).

10

-

-

... More
Filling available earth (including available ordinary rock) in trenches, plinth, foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

6667.84

-

-

... More
Carriage of material by mechanical transport including loading, unloading and stacking / spreading / leveling lead upto 1 km. Rate includes consolidating each deposited layer by ramming and watering.

-

-

-

... More
a) Earth

7553.73

-

-

... More
b) Excavated Rock

10

-

-

... More
ANTI - TERMITE TREATMENT-Supplying, diluting and injecting Chloropyriphos Emulsifiable concentrate 20% with 1% concentration conforming to IS:8944 for pre-constructional anti-termite treatment, using chemical emulsion under and all around the column pits, wall trenches, basement, plinth surface, junctions of wall and floor, all along the external perimeter of building, expansion joints, surrounding of pipes, conduits, etc. The application should ensure continuous chemical barrier for the building as per IS:6313 specifications. In case the surface doesn't allow the emulsion to seep through,  then holes upto 50 to 75mm deep at distance of 150mm centres on bothways may be made with 12mm diameter mild steel rod on the surface to facilitate saturation of the soil with chemical emulsion  etc In soils which do not allow percolation of chemicalsto the desired depth, the uniform dispersal of the chemical to adepth of 300 mm shall b e ob tained b y suitab ly modifying themode of treatment depending on the site condition. T he dosageof 2.25 litre per linear metre shall however remain the same.. as per IS:6313 specifications. Guarantee for ATT should be for a period of 10 years from the date of practical completion of the project.  Guarantee bond shall be submitted by the Main Contractor undertaking responsibility for free performance during the guarantee period. Work shall be carried out as per the instructions of Engineer in charge. The work should be carried out by an approved and registered specialist pest control agency only. Contractor to furnish the details of the proposed specialist firm. The rate shall include cost of materials, labour, loading and unloading, transportation, scaffolding and all other incidental charges etc., with all leads and lifts, complete and as directed by the Engineer-in-charge at all levels. (Plinth area of the building at ground floor only shall be measured for payment).Location: Foundation and Basement, Top surface of plinth filling, Junction of wall and floor, External perimeter of building, soil surrounding pipes, Expansion joints, Treatment under Apron and Treatment over DPC.

917

-

-

... More
CEMENT CONCRETE & REINFORCED CEMENT CONCRETE WORKS- Note: 1. Cost of Scaffolding is included for all the concrete & reinforced cement concrete items 2. The rates are included for all the wastages. 3. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification. 4. Plinth level shall be considered as Ground floor raft slab level.

-

-

-

... More
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:- 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)

201

-

-

... More
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm bed by dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top to smooth.

135

-

-

... More
Providing and laying in position ready mixed concrete manufactured in fully automatic batching plant and transported to site of work in transit mixer having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge. Providing M-40 grade concrete BMC/RMC.(Note :Minimum Cement content considered in M- 40 is @ 360 kg/cum, ) quote shall contian additional cement used for arriving the required strength

-

-

-

... More
a).All work up to Plinth Level.

865

-

-

... More
b).All work above plinth level.

1528

-

-

... More
Providing and Fixing of Precast Concrete Slab 100mm thick with M40 grade of concrete Rates shall include formwork, Curing, Compaction all Lead and Lifts etc.,

25

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for -providing M 40 grade concrete: Note: 1. Cost of Scaffolding is included for all the Centering works at all levels 2. The rates are included for all the wastages. 3. The bottom of the slab surface should be thoroughly cleaned at all areas particularly at joint areas. 4. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification. 6. In slab/ beam that item rate shall include cost in curved slab ends as well as shown by tender drawings

-

-

-

... More
Foundations, footings, bases of columns etc. for mass concrete.

275

-

-

... More
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.

512

-

-

... More
Suspended floors, roofs, landings, balconies and access platform.

3275

-

-

... More
Lintels, beams, plinth beams, girders, bressumers and cantilevers.

3418

-

-

... More
Columns, Pillars, Piers, Abutments, Posts and Struts

2655

-

-

... More
Stairs, (excluding landings) except spiral-staircases.

297

-

-

... More
Vertical and horizontal fins individually or forming box louvers band, facias and eaves boards.

10

-

-

... More
Small lintels not exceeding 1.5m clear span, moulding as in cornices, window sills, string courses, bands,copings, bed plates, anchor blocks and the like.

10

-

-

... More
Weather shade, Chajjas, corbels etc., including edges

10

-

-

... More
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a height of 4.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured)- Suspended floors, roofs, landing, beams and balconies (Plan area to be measured).

10

-

-

... More
STEEL WORKS: Note: 1. Cost of Scaffolding is included for all the Steel works 2. The rates are included for all the wastages. 3. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
Supplying, straightening, cutting, bending, placing in postion reinforcement bars of all diameters to RCC work and binding with 18 SWG black annealed binding wire (double fold) etc., all complete as per drawings and specifications . The rate shall include cost of materials, cost of binding wire, pvc cover blocks as specified, labour, loading and unloading, transportation, scaffolding and all other incidental charges etc., with all leads and lifts, complete and as directed by the Engineer-in-charge at all levels. (Payments will be based on actual approved BBS qty. Only authorized laps, chairs and spacers will be measured and paid for).High yield strength ( TMT bars ) confirming to IS-1786 of Fe 500 grade.

-

-

-

... More
a).Upto Plinth level

98

-

-

... More
b).Above Plinth level

278

-

-

... More
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete

1

-

-

... More
MASONRY WORKS-Note: 1. Scaffolding is included for all the Masonry works 2. The rates are included for all the wastages. 3. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete 

22.3

-

-

... More
Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level, thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc. complete 

499.8

-

-

... More
Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level, thickness 20cm and above in : CM 1:6 ( 1 cement : 6 coarse sand sand) etc. complete 

363.9

-

-

... More
Solid block masonry using pre cast solid blocks ( Factory made) of size 40x20x10cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth for 10 cm thick wall in CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding etc complete 

20

-

-

... More
PLASTERING WORKS-Note: 1. Cost of Scaffolding is included for all the Plastering works 2. The rates are included for all the wastages. 3. Refer Technical specification for curing works 4. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification. 5.Cost including Providing and fixing of 150 mm wide GI plaster mesh of Arpitha or equivalent approved make with nominal thickness of individual thread 0.35mm with a Zinc coating of 120 gms per Sqm at the junctions of masonry & RCC work, plastering the mesh in CM 1:2 including tying in position with suitable nails/screws etc

-

-

-

... More
Plastering with cement mortar 1:3 of 12 mm thick for RCC surfaces upto Five floor level

948.05

-

-

... More
Plastering with cement mortar 1:4 of 15 mm thick for inside walls upto Five floor level for wall surfaces

6817

-

-

... More
External plastering - 18 mm cement plaster in two coats, under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge. Height upto 10 m from GL

1388

-

-

... More
Extra for plastering exterior walls of height more than 10m from ground level for every additional height of 3m or part thereof a). 10m -13m height

458

-

-

... More
b).13m to 16m height

458

-

-

... More
c).16m to 19m

458

-

-

... More
d).19m to 22m

960

-

-

... More
Providing water proof Plaster with CM 1:3, 15mm thick finished smooth with a floating coat of cement mixed thoroughly with approved brand and quality water proofing compound of Fosroc/BASF at 2% by weight of cement at all levels and heights including scaffolding etc complete.

533

-

-

... More
Extra for providing and mixing water proofing material of approved make in cement plaster work in proportion recommended by the manufacturers (min 2% by weight of cement to be considered).

526

-

-

... More
JOINERIES-Note: 1. Cost of Scaffolding is included for all the Joineries works 2. The rates are included for all the wastages. 3. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position Second class teak wood (Burma Teak). ( Frame size to be vary from 2" to 4".)

0.53

-

-

... More
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand :6 graded stone aggregate 20mm nominal size)

72

-

-

... More
Door D - 1200 x 2100 mm with the following hardwares with Approved make,Dorma BB 4330, 5 Knuckle, 2 Ball bearing butt hinges size 4" x 3" x 3mm, in SS 304 and in SSS finish. Suitable for door weights upto 120kgs. Template drilled.DORMA 288a with 55mm backset, 20mm square forend prepared for euro profile cylinder including strike plate. and EPC 60mm Length both side key operation & Escutcheons in SSS Finish.DORMA pull Handle TGDI-D 300 back to back with adjustable fixing for glass, wood and metal doors in satin stainless steel. The pull handles should have supporting washer with raised bevelling on the outer surface. Length =300mm, 22mm dia, -SS304.DORMA TS 92 B contur, cam action door closer with G-N slide channel arm for pull side fixing. Spring size EN 2-4 as per EN 1154 and CE marked. Silver finish.DORMA floor stop half dome with 45mm dia with fixing accessories, in satin Chrome.

2

-

-

... More
Door D3 - 1000 x 2400 mm with the following hardwares with Approved make.Dorma BB 4330, 5 Knuckle, 2 Ball bearing butt hinges size 4" x 3" x 3mm, in SS 304 and in SSS finish. Suitable for door weights upto 120kgs. Template drilled.Pure 8998 Type 1 Package with Pair of Pure 8998 Design Lever Handle on Roses & escutcheons. Including 271a Sash lock with 72mm CTC, 55mm Backset 20mm Square forend. EPC 60mm length one side key & one side Thumb turn operation.Dorma floor stop half dome with 45mm dia with fixing accessories, in satin Chrome.DORMA TS 92 B contur, cam action door closer with G-N slide channel arm for pull side fixing. Spring size EN 2-4 as per EN 1154 and CE marked. Silver finish.

10

-

-

... More
Supplying and fixing fire rated door with hardwares-Providing and fixing of Hollow metal fire rated doors as per IS 3614 part-1 & part-2 for stability and integrity. Pressed Galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall have doors tested at CBRI or ARAI for maximum rating of 2hrs with vision panel. Test certificates should be available for vision lites /panels as part of the fire door assembly. Independent glass test certificates will not be accepted. Manufacturer test certificate shall cover doors both single and double leaf and all doors supplied should be within the tested specimen, deviation in specification and sheet thickness other than what is mentioned in the test certificates are not allowed. Proper label confirming the type of door and the hourly rating is mandatory. Door frame shall be double rebate frame profile of size 125 x 60mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be Mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system and shall be site fitted with EPDM gasket as standard.All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed should be filled with PUF or with cement & sand slurry as recomended by the manufacturer of the engineer.Door leaf shall be 46mm thick fully flush double skin door with or without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. 200x300mm Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement.The glass should be 6mm clear borosilicate fire rated glass of relavant rating of the door. All doors and frames shall be finished with polyurethane aliphatic grade powder coating minimum 50 microns of approved colour. The door leaf and frame shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule.

-

-

-

... More
2Hrs Fire Rated Door FD1 Unequal Double leaf 1500x2400mm with vision panel with hardware .Hinges 3090 F, 5 Knl, 2 Ball bearing butt hinges size 4" x 3" x 3mm SS 304.Fire rated Mortice sash lock 281, 55mm BS/20mm sq. fornd, SSS.EP Cyl. 3525, 5pin one side key & one side thumb turn Length=65mm, SNP.Lever Handle Plus 8100/6501 -S114, with roses & esc. SSS.Door closer TS 72 EN 2-4 with Std. arm.Lever action flush bolt 3101-2, L=600mm, SC.Lever action flush bolt 3101-1, L=300mm, SC. Fire Rated Seal for Grooved Frame Profile C421 - EPDM Black

15

-

-

... More
2Hrs Fire Rated Door FD2 Single leaf 1200x2400mm with vision panel :1200x2400mm with hardware Hinges 3090 F, 5 Knl, 2 Ball bearing butt hinges size 4" x 3" x 3mm SS 304 One point panic device PHA 2001 - PHA2102, PHA 2105 L=1300mmExternal trim PHT 3905 prepared for euro profile cylinder.EP Half Cyl. 3010, 5pin one side key Length=42mm, SNPDoor closer TS 72 EN 2-4 with Std. armFire Rated Seal for Grooved Frame Profile C421 - EPDM Black

12

-

-

... More
2Hrs Fire Rated Door FD2a Single leaf 1200x2100mm with vision panel with hardware Hinges 3090 F, 5 Knl, 2 Ball bearing butt hinges size 4" x 3" x 3mm SS 304,One point panic device PHA 2001 - PHA2102, PHA 2105 L=1300mm,External trim PHT 3905 prepared for euro profile cylinder.EP Half Cyl. 3010, 5pin one side key Length=42mm, SNPDoor closer TS 72 EN 2-4 with Std. arm,Fire Rated Seal for Grooved Frame Profile C421 - EPDM Black

2

-

-

... More
Providing and fixing of Hollow metal door at all levels from ISO 9001-2000 certified Manufacturer. The metal doors should be made from high grade galvanised steel stretched level sheet flush, with vision panel, louvers etc. Single /Double leaf to required sizes and approved make shakti met-dor or equivalent which consists of frame, shutter, infill and finish as detailed below and conforming to IS 277. Door frame shall be single rebate profile of size 100 x 57 mm made out of 1.20mm minimum thick galvanized steel sheet (18 gauge ). Frames should be mitered and field assembled with self tabs. Door frames should be prepared for suitable hardware as scheduled and should have necessary reinforcement to withstand regular wear and tear. All provision should be mortised, drilled and tapped for receiving the hardware. Rubber door silencers should be provided on the striking jamb. All door frames should be provided with backplate and anchor fasteners for installation on a finished plastered masonry wall opening. Once the frame is installed it should be grouted with cement & sand slurry.Door leaf should be 46mm thick flush double skin door with vision panel of suitable size. Door leaf shall be manufactured from 0.8mm (22 guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid with steel stiffeners/ pads and reinforcement. The infill material shall be resin bonded honeycomb core. All doors should be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, shaft locks, flush pull and tower bolt etc. The edges should be interlocked with lock seam. For pair of doors astragals will be provided as required. 450x750mm Vision lite wherever applicable should be of size fixed with rubber beeding. The glass should be 4mm clear toughned glass. All doors and frames shall be finished with polyurethane aliphatic grade powder coating minimum of 50 microns of approved colour. The door leaf and frame shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule.

-

-

-

... More
a). Steel Door TD1 Single leaf 600x1500mm without vision panel with frame on Four sides & hardware set ,Hinges 3090 F, 5 Knl, 2 Ball bearing butt hinges size 4" x 3" x 3mm SS 304, Mortice Shaft Dead lock with Allen key 8681, SSS, Flush Pull Handle 1208, OVAL, SSS

34

-

-

... More
b0.Steel Door TD2 Single leaf 900x1500mm with 450x750mm vision panel with frame on Four sides & hardware set Hinges 3090 F, 5 Knl, 2 Ball bearing butt hinges size 4" x 3" x 3mm SS 304, Mortice Shaft Dead lock with Allen key 8681, SSS, Flush Pull Handle 1208, OVAL, SSS

4

-

-

... More
FLOORING WORKS: Note: 1. The rates are included for all the wastages. 2. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) - 25 mm thick in single slab of stone not less than 1.5m length shall be used. Rate shall include for preparation of base surface & finished the surface, protection with gypsum/POP layer over plastic sheet and removing the same before handing over,work at all levels, as directed.

10

-

-

... More
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.

394

-

-

... More
Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab.

210

-

-

... More
Extra for Kota stone/ sand stone in treads of steps and risers using single length up to 1.05 metre.

100

-

-

... More
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 of approved make in all colours, shades except burgundy, bottle green, black of any size ( not less than 300 x 450mm ) as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. (Basic cost of tile minimum Rs. 300 /sqm)

863.58

-

-

... More
Providing and laying vitrified floor tiles in different sizes with water absorption's less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600mm x 600 mm (Basic cost of tile Rs. 858 /sqm)

2497

-

-

... More
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete. Size of Tile shall be 600 x 600 mm with basic cost of tile Rs. 858.00 / Sqm)

510

-

-

... More
Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edge to give high gloss finish etc. complete at all levels. Rate shall include necessary cut open for fixing sink, sanitary / plumbing fittings.

-

-

-

... More
a). Granite of any colour and shade - Area of slab above 0.50 sqm (Basic rate Rs. 2574 / sqm)

100

-

-

... More
b). Granite skirting 100 mm thick

10

-

-

... More
Extra for providing edge moulding to 18mm thick Granite stone counters, Vanities etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.

50

-

-

... More
Providing and laying in panels not more than 20 sqm. in plan granolithic flooring with cement concrete M30 by using coarse graded aggregate of 6 to 12 mm size laid monolithic with floor concrete and finished smooth with power trowel including preparation of concrete surface and form work. The screed strips shall be fixed on the base concrete with 6 mm thick Glass strips or other metals strips for effective separation of panels not exceeding 20 sqm. in plan etc. complete as per Specifications and as directed. Unevenness in floor finish shall not exceed +2mm in one square metre area.Rate to include lead , lift at all levels, pumping, placing, necessary formwork, curing etc. providing and fixing required size angles for edge nosing of platform portions including grouting of lugs etc. complete. but excluding cost of angles which shall be paid seperately under relevant items

-

-

-

... More
a) 50 mm thick

50

-

-

... More
b)75mm thick

296

-

-

... More
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : a. Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent. .(Basic rate of granite Rs. 2431 /sqm)

355

-

-

... More
Preparing the surface with 25-40 mm thick concrete screed( 1:2:4) by using coarse graded aggregate of 6 to 12 mm size laid over floor concrete and finished smooth and even surface to receive the Tile adhesive/Cement mortor as instructed by Client.

-

-

-

... More
a) Thickness upto 25 mm

10

-

-

... More
b) Thickness upto 40 mm

2497

-

-

... More
c) Thickness upto 75 mm

10

-

-

... More
Providing & installing of Point elastic multipurpose PVC Sports flooring as per manufacture specification over finished flooring surface. ( finished floor surface shall be treated self leveling epoxy coating to achieve the even surface to facilitate the fixing of  vinyl floor with out undulation and the cost of the the same will be include in the quoted rates of flooring cost ) . vinyl shade may be in 2 or 3 different colour as per the provided pattern and joints of two diffferent colur will treated properly , Cost to include covering the laid floor with necessary protection, cleaning for any stains before handover. etc. complete as per the drawing and to complete satisfaction of the Engineer. The adhesive used for laying the floor shall be as per written recommendation made by the manufacturer & and the joints to be welded using suitable welding rods and cost to include welding rods as approved by the Architect. 6.0 mm thick Vinyl Sports floor (roll form of 2000mm width)Sports floor covering to conform to the following standards: Sports floor covering to conform to the following standards :Resistance to Wear layer Thickness  -  0.098g Total Weight /sqmt.  -  4.71Kg/M2, Friction - 88%Shock Absorption - 26-28%, Residual Indentation  -  approx. 0.21mmVertical deformation - 1.1mm, Vertical Ball Behaviour - above 100%Dimensional Stability - 0.10%6.0 mm thick Vinyl Sports floor (roll form of 2000mm width)Sports floor covering to conform to the following standards:Sports floor covering to conform to the following standards :Resistance to Wear layer Thickness  -  0.098g , Total Weight /sqmt.  -  4.71Kg/M2, Friction - 88% Shock Absorption - 26-28%, Residual Indentation  -  approx. 0.21mm, Vertical deformation - 1.1mmVertical Ball Behaviour - above 100%, Dimensional Stability - 0.10%

300

-

-

... More
PAINTING WORKS- Note: 1. Cost of Scaffolding is included for all the Painting works 2. The rates are included for all the wastages. 3. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.

6817

-

-

... More
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre.

50

-

-

... More
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water thinnable priming coat with cement primer.

948.05

-

-

... More
Finishing walls with water proofing cement paint of required shade: New work (Two or more coats applied @ 3.84 kg/ 10 sqm) including primer.

50

-

-

... More
Wall painting with acrylic emulsion paint of approved brand and manufacture. to give an even shade : Two or more coats on new work

7117

-

-

... More
Providing and applying exterior grade water based Hi-Built acrylic resin texture body coat incorporating natural sand stone ceramic chips with Specific gravity of 1.6 (+or-0.2), minimum film thickness having 90 to 100 microns and subject to approved texture and colour and the material contents shall be solids of 82% with viscosity of 1500-3000 ps/30 Deg.c. in such a way to create tile like effect. Product of approved make with approved shade and pattern of approved colour shall be applied with undercoat or primer (1 or 2 coats) using roller/brush/spray, Elegance tile texture spray (1 or 2 coats) with 2 coats of finish paint of Ceramic Top A / PU Clear matt complete and application sequence shall be as per manufacturer specification and direction. Applicator shall ensure that the surface to be painted free from any loose paint, dust or grease, any previous growth of fungus, algae or moss needs to be removed completely by vigorous wire brushing and cleaning with water. Surface imperfections such as holes, dents and crakes are to be filled by using mixture of white cement and fine sand in the ratio of 1:3. Freshly plastered wall shall be allowed to cure completely to receive the primer. Application of paint shall include preparation of surface, washing and cleaning using necessary tools and plants, providing the samples at site to the size of minimum 1200x900 mm with 3 or 4 alternatives etc. Providing two coats of first quality water proof cement paint of approved make and colour over one coat of priming coat white colour water proof cement paint or any primer specified by the manufacture including preparation of surface, scaffolding, curing etc., complete at all levels, elevations and heights. The surface should be thoroughly cleaned and wetted before painting. The painting and curing must be done as per manufacturer’s specification. (Basic rate of texture Rs. 1600 / sqm)

1861

-

-

... More
Supply and apply water based, modified acrylic, anti algal, non flammable high performance weather proof emulsion exterior wall finish – 2 coats by brush/roller or spray over the acrylic based texture surface shall have Dry film thickness (DFT) of 0.5 to 1.0 mm with a coat of Exterior wall primer by brush or Spray. Applicator shall ensure that the surface to be painted free from any loose paint, dust or grease, any previous growth of fungus, algae or moss needs to be removed completely by vigorous wire brushing and cleaning with water. Surface imperfections such as holes, dents and crakes are to be filled by using mixture of white cement and fine sand in the ratio of 1:3. Freshly plastered wall shall be allowed to cure completely to receive the primer. The primer / paint shall not be applied when ambient temperature is less than 100C or if the temperature might drop to the level of 100C with in specified period of application and maintain the surface dry time and sheen level as per Manufacturer specification. (Basic Rate of Texture Rs. 500 /sqm)

1861

-

-

... More
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. On steel works.

50

-

-

... More
WATERPROOF WORKS-Note: 1. Cost of Scaffolding is included for all the Waterproof works 2. The rates are included for all the wastages. 3. Leak proof test should be carried out by contractor as directed by Engineer in- charge. Water and other facilities should be included the rates of each items. 4. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
I. WATER PROOFING FOR BELOW RAFT-Providing and laying integral cement based treatment for water proofing on top of PCC laid for Grade slab,Raft & beam,etc in the following order and consisting of following operations. :

-

-

-

... More
1) Providing and laying water proofing treatment in PCC below RAFT etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : (a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours (b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry

48

-

-

... More
2) Providing and fixing 20 mm thick Cement Mortor 1:3 over PCC with for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification (TOP LAYER)

48

-

-

... More
Providing and applying injection grouting on Raft slab using cement admixed with water proofing compound as per following operations and as directed by Engineer–in–Charge : i) Providing and Fixing 18 mm dia GI nozzles (the nozzle shall be embedded about half the depth of the member to be grouted) in grid pattern at a spacing not more than 1.0 metre c/c while casting the raft slab and along construction joints at a spacing not more than 1.0 metre c/c along the construction joints. Nozzles can also be post fixed by drilling holes using drill machine and to be fixed with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight .The Caps shall be fixed in the mouth of the nozzles to avoid chocking of cement slurry etc, while concreting or Post fixing the Nozzle. (Nothing extra shall be paid for post fixing) ii) Applying injection grouting through the nozzles by hand operated grouting pumps with a minimum pressure of 2 kg/sqcm with cement slurry admixed with Approved Non shrink Polymeric Water Proof Grouting Compound at the rate of 2% by weight of cement .Grouting operations to be taken up after the concrete reached the full strength, i.e 28 days after casting of concrete. iii) Sealing off the nozzles after grouting operation is over with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight. iv) Cut the projected nozzles if required over the concrete surface and fill with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight. Note- The length and width of the RCC area to be treated shall be measured correct to a cm and its area for payment shall be calculated in square metres correct to two places of decimal.

48

-

-

... More
Providing and applying injection grouting on Basement Retaining walls internal surface using cement admixed with water proofing compound in the following order and as directed by Engineer–in–Charge : i) Making ' V ' grooves at the construction joints of size 20 x 20 mm and clean the surface with wire brush . ii) Fill the honeycombs, if any and the prepared ' V ' grooves in the concrete surface by using cement putty admixed with quick setting integral Waterproofing compound approved make in the ratio 1:1 by weight. iii) Providing and Fixing 18 mm dia GI nozzles (the nozzle shall be embedded about half the depth of the member to be grouted) in grid pattern at a spacing not more than 1m c/c while casting the retaing wall and along construction joints at a spacing not more than 1m c/c . Nozzles (can also) shall be post fixed by drilling holes using drill machine and to be fixed with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight .The Caps shall be fixed in the mouth of the nozzles to avoid chocking of cement slurry etc, while concreting or Post fixing the Nozzle. (Nothing extra shall be paid if nozzels are post fixed) iv) Applying injection grouting through the nozzles by hand operated grouting pumps with a minimum pressure of 2 kg/sqcm with cement slurry admixed with Approved Non shrink Polymeric Water Proof Grouting Compound at the rate of 2% by weight of cement .Grouting operations to be taken up after the concrete reached the full strength, i.e 28 days after casting of concrete. v) Sealing off the nozzles after grouting operation is over with cement putty admixed with quick setting integral Waterproofing compound of Approved make in the ratio 1:1by weight.vi) Cut the projected nozzles if required over the concrete surface and fill with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight. Note- The length and width of the RCC area to be treated shall be measured correct to a cm and its area for payment shall be calculated in square metres correct to two places of decimal

27

-

-

... More
II. RETAINING WALL ( EXTERNAL ): Providing and applying integral cement based treatment for water proofing on Basement Retaining walls external surface,beam sides,pile cap sides etc using cement admixed with water proofing compound in the following order and and as directed by Engineer–in–Charge :

-

-

-

... More
1) Making ' V ' grooves at the construction joints of size 20 x 20 mm and clean the surface with wire brush . ii) Fill the honeycombs if any and the prepared ' V ' grooves in the concrete surface by using cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1 by weight. iii) Providing and laying water proofing treatment in PCC below RAFT etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : (a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours (b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry

27

-

-

... More
2) Lay protective plaster layer with 12mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound of approved make conforming to IS 2645 at the rate of 2% by weight of cement over the third coat of brush topping. Plaster shall be cured by spraying of water for the next 7days. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonary with polymer mixed slurry. Note- The length and width of the RCC area to be treated shall be measured correct to a cm and its area for payment shall be calculated in square metres correct to two places of decimal

27

-

-

... More
III. TOILET SUNKEN AREA -Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc. by applying cement slurry mixed with Approved Acrylic Polymer in the following order and consisting of applying:

-

-

-

... More
1) plaster layer of 12mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound of approved meke conforming to IS 2645 at the rate of 2% by weight of cement over the prepared surface. Plaster shall be cured by spraying of water for the next 48 hours.ii) First layer of slurry of cement @ 0.488 kg/sqm. mixed with Approved Acrylic Polymer 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. iii) Third layer of 1.5mm thickness consisting of slurry of cement @ 1.289 kg./sqm. mixed with Approved Acrylic Polymer @ 0.670 kg/sqm. and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 6 hours. iv) Lay protective plaster layer with 12mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound of approved make conforming to IS 2645 at the rate of 2% by weight of cement over the third coat of brush topping. Plaster shall be cured by spraying of water for the next 7days. v)The whole surface so finished shall be flooded with water for a minimum period of two weeks for curing and testing of treatment. In case of any leakage, required rectifications shall be carried out as per directions of Engineer-in-Charge and the surface retested. Note- The length and width of the area to be treated shall be measured correct to a cm and its area for payment shall be calculated in square metres correct to two places of decimal The rate includes preparation of surcace, treatment and sealing of all joints, corners, junctions of pipes and masonary with polymer mixed slurry all complete as per direction of Engineer in charge. Toilet sunken bottom area

300

-

-

... More
2) Sealing the pipe sleeves with Approved waterproofing Grout - GP

10

-

-

... More
3) Supplying and filling the sunken slab area by BRICK-BATCOBA by adding integral Waterproofing compound approved make admixture at the rate specified in the manufacturer's specification after entire completion of laying pipes, sanitary fittings etc. Rate shall include for preparation of surface, protecting the laid pipes and sanitary fittings, finishing the surface smooth to receive the top coat of water proofing application etc. complete and all as directed.

90

-

-

... More
4) Toilet Floor Treatment after filling-Providing and laying water proofing treatment in WCs, bathroom etc. over vermiculate concrete by applying cement slurry mixed with Acrylic Polymer of Approved manufacturer in the following order and consisting of applying: First layer of slurry of cement @ 0.488 kg/sqm. mixed with Acrylic Polymer @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours.ii) third layer of 1.5mm thickness consisting of slurry of cement @ 1.289 kg./sqm. mixed with Acrylic Polymer @ 0.670 kg/sqm. and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 6 hours.iii) Lay protective plaster layer with 12mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound of approved make conforming to IS 2645 at the rate of 2% by weight of cement over the third coat of brush topping. Plaster shall be cured by spraying of water for the next 7days. Note- The length and width of the PCC area to be treated shall be measured correct to a cm and its area for payment shall be calculated in square metres correct to two places of decimal The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonary with polymer mixed slurry all complete as per direction of Engineer in charge.

300

-

-

... More
IV. FLOOR LANDSCAPE: The concrete slab and wall surface shall be thoroughly cleaned to remove debris and dust, and applying one coat of Approved Acrylic Polymer Modified Cementitious Slurry Coat over well prepared surface as a Primer and applying Approved Polyurethane Based Elastomeric Coating to the thickness of 1.5 mm over Acrylic Polymer slurry coat applied surface.ii)Providing protective layer of CC 1:2:4 with 40 mm screed with Acrylic Polymer Modified Cementitious coat @ 2 % by weight of cement over treated area iii) Spreading the CM 1 : 3 - 20 mm thick, provide and lay well burnt brick bats (COBA) to a average minimum thickness of 55 mm (ie. minimum 40 mm thickness at lower end and 70 mm thickness at higher end). An additional layer of brick bat (COBA) shall be laid over the existing brick bat COBA surface if required to get the required gradient for adequate drainage giving a slope of approximately 1 in 100, which will be measured separately under relevant item. iv)The gap between brick bat shall be filled with cement mortar 1:4 admixed with waterproofing compound of approved make afterwards curing shall be carried out for two days a final layer of cement mortar of 1:3 admixed with water proofing compound of approved equivalent make shall be laid to a thickness of 20 mm and draw a falseline of 300 mm x 300 mm.Rate shall include for preparation of surface by mechanical upgrading to remove all loose mortar and laitance, oil, grease etc. and washing the surface with water to get neat surface,dewatering, finishing, curing, scaffolding, supply and adding water proofing chemicals at the specified proportion as per manufacturer's specifications, all materials, wastages, conveyance, tools and plants, mixing device and gauge, shuttering and also include for conducting leakage test at terrace by storing water on the terrace for about 25 mm depth continuously for a period of 7 days etc.complete, as directed.

90

-

-

... More
V. ELEVATED TANK

-

-

-

... More
a) FLOOR :i) Providing and Fixing 18 mm dia GI nozzles (the nozzle shall be embedded about half the depth of the member to be grouted) in grid pattern at a spacing not more than 1.0 metre c/c while casting the raft slab and along construction joints at a spacing not more than 1.0 metre c/c along the construction joints. Nozzles can also be post fixed by drilling holes using drill machine and to be fixed with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight .The Caps shall be fixed in the mouth of the nozzles to avoid chocking of cement slurry etc, while concreting or Post fixing the Nozzle. (Nothing extra shall be paid for post fixing) ii) Applying injection grouting through the nozzles grouting pumps with a minimum pressure of 2 kg/sqcm with cement slurry admixed with Non shrink Polymeric Water Proof Grouting Compound of approved make at the rate of 2% by weight of cement .Grouting operations to be taken up after the raft / slab concrete reached the full strength, i.e 28 days after casting of concrete. iii) Sealing off the nozzles after grouting operation is over with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight. iv) Cut the projected nozzles if required over the concrete surface and fill with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight. vi)The concrete slab shall be thoroughly cleaned to remove debris and dust, and application of two coats of Approved Acrylic Polymer Modified Cementitious Slurry Coat over well prepared surface vii) Laying of cement concrete screed of Mix 1:2:4 (1 cement:2 coarse sand: 4 stone grit 6 mm and down size by volume) to an average thickness of 25 mm and the concrete shall be admixed with Normal setting integral Waterproofing compound of approved make conforming to IS 2645 at the rate of 2% by weight of cement over treated surface

33

-

-

... More
b) WALL: Making ' V ' grooves at the construction joints of size 20 x 20 mm and clean the surface with wire brush .ii) Providing and Fixing 18 mm dia GI nozzles (the nozzle shall be embedded about half the depth of the member to be grouted) in grid pattern at a spacing not more than 1m c/c while casting the retaing wall and along construction joints at a spacing not more than 1m c/c . Nozzles (can also) shall be post fixed by drilling holes using drill machine and to be fixed with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight .The Caps shall be fixed in the mouth of the nozzles to avoid chocking of cement slurry etc, while concreting or Post fixing the Nozzle. (Nothing extra shall be paid if nozzels are post fixed)iii) Filling the "V" Groove with Approved Quick Setting Waterproofing Compound admixed with cementiv) Applying injection grouting through the nozzles by hand operated grouting pumps with a minimum pressure of 2 kg/sqcm with cement slurry admixed with Non shrink Polymeric Water Proof Grouting Compound of approved make at the rate of 2% by weight of cement .Grouting operations to be taken up after the concrete reached the full strength, i.e 28 days after casting of concrete.v) Sealing off the nozzles after grouting operation is over with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight.vi) Cut the projected nozzles if required over the concrete surface and fill with cement putty admixed with quick setting integral Waterproofing compound of approved make in the ratio 1:1by weight.vii)The wall surface shall be thoroughly cleaned to remove debris and dust, and application of two coats of Approved make Acrylic Polymer Modified Cementitious Slurry Coat over well prepared surface viii) Lay protective plaster layer with 12mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound of approved make conforming to IS 2645 at the rate of 2% by weight of cement over the third coat of brush topping. Plaster shall be cured by spraying of water for the next 7days.

95

-

-

... More
VI. Terrace Water proofing

-

-

-

... More
Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with Acrylic Polymer of Approved make in the following order and consisting of :i) after surface preparation, applying first layer of slurry of cement @ 0.488 kg/sqm. mixed with Approved make Acrylic Polymer @ 0.253 kg./sqm.This layer will be allowed to air cure for 4 hours.ii) laying second layer of Fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm.iii) Applying layer of slurry of cement @ 0.242 kg/sqm. mixed with Approved make Acrylic Polymer @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours.iv) Applying third layer of 1.5mm thickness consisting of slurry of cement @ 1.289 kg./sqm. mixed with Approved make Acrylic Polymer @ 0.670 kg/sqm. and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 6 hours.v) Laying protective plaster layer with 20mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound of approved make conforming to IS 2645 at the rate of 2% by weight of cement over the third coat of brush topping. Plaster shall be cured by spraying of water for the next 48 hours.Providing and laying IRC mesh over treated area.Laying concrete scrred with 1:2:4, to form the slope to drain the rain water and the top surface finished with power trowl and draw 300 mm x 300 mm falseover frinished surface.ix) making machine cut grooves of size of 4 x 4mm on a grid of 5 x 5 M (Plan area not exceeding 25 Sqm) and fill the grooves with Polysulphide sealent of approved make. x) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. Rectification of leakage if any and conducting the test again to ensure there is no leakage after rectification. (Note- The length and width of the RCC slab area to be treated from wall to wall shall be measured correct to a cm and its area for payment shall be calculated in square metres correct to two places of decimal. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonary with polymer mixed slurry all complete as per direction of Engineer in charge.)

855

-

-

... More
Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) 78, solar reflection 0.70 and initial emittance 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner.

50

-

-

... More
MISCELLENEOUS- Note: 1. Cost of Scaffolding is included for all the Miscelleneous works 2. The rates are included for all the wastages. 3. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
Providing and fixing hand rail of approved size by welding etc. to, balcony railing and staircase railing including applying a priming coat of approved steel primer by using G I Pipes of required sizes as shown in the drawings.

6400

-

-

... More
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).

2200

-

-

... More
SS HANDRAILS-Providing and fixing Handrail with stainless steel pipe for Staircase / Atrium Balcony / Terrace at all levels fabricated with 32mm dia SS pipe as verticals bent to the shape. Top horizontal hand railing with S.S pipe of 50 mm dia and as per drawing with 12.52 mm thick laminated glass having 6 mm thick as outer panel and 5 mm thick as inner panel with interlayer of 1.52 mm thick Sentry Glass. Both Outer pane and Inner pane shall be uncoated clear glass and shall be heat treated and heat soaked as shown in the drawing etc complete, as directed. The work include necessary tools & Plants, supplying and fixing of glass, Welding with consumables & buffing charges etc. complete as directed. Ht of Railing shall be 1050 mm from FFL.& height of glass shall be 900mm at suitable level and to be held in position using 2 point Articulated bolts / clamp. SS 316 Grade of approved make.All exposed laminated glass edges shall be protected with UV protected Hi-Density Nylon clear strip to suit the thickness of laminated glass. "U" shaped nylon strip shall be provided on the edges of laminated panel to cover a minimum depth of 20 mm on both faces of the laminated Glass and as snap-fit. These strips are locally available with any EPDM / Nylon Extruder or supplier.In addition to the Glass railing, SS pipe - 50 mm dia - 2.8 mm thick shall be provided as protective railing and supported between walls using SS base Plate - 5 mm thick round shape with necessary anchors as shown in the drawing. This pipe shall be provided for the specified areas only and the base plate shall be covered with SS cover cup with Clip on type with tools & Plants, Support Channel, glass as specified, ABS/PE wedges, Silicon gaskets, SS 316 anchor fastener & screws, Welding with consumables & buffing charges etc at all levels as directed

10

-

-

... More
Supplying and fixing poly-propelene rungs of 20 mm square bar of size 263 x 165 mm for access way including anchorage in walls to a minimum depth of 100 mm with C.C 1:2:4 etc. complete and as directed.

10

-

-

... More
Construction of catch basin of 600mm x 600mm size and depth upto 1200mm for external storm water drainage with 230mm thick walls in well burnt table moulded bricks in CM 1:4 over a bed of 100 mm thick PCC 1:4:8 internal walls plastered smooth in CM 1:3 and external walls plastered in1:6 with sponge finish. Fixing precast RCC grating of size 600 x 600mm on top surface flushed to the finished floor level with necessary excavation, back filling the selected excavated earth with all leads and lifts etc., complete. The quoted rate shall include 110dia PVC pipe sleeves from road GSM to the chamber as shown in the drawings.

-

-

-

... More
a) 1000 x 1000 x 900 mm

10

-

-

... More
b) 900 x 900 x 750 mm

10

-

-

... More
c) 750x 750 x 600 mm

10

-

-

... More
d) 600x600x600 mm

10

-

-

... More
Providing and fixing PVC (6 Kg/sqcm class) pipe of specified dia below and approved make as water down take pipe with all specials, accessories and joints with solvent cement solution according to manufacturer’s specification to all levels. 160mm dia pipe

440

-

-

... More
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 dia pipe

10

-

-

... More
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.

-

-

-

... More
a) 110mm coupler

20

-

-

... More
b) 110X110x110 mm single TEE with door

20

-

-

... More
c) Bend 87.5

20

-

-

... More
d) Shoe (plain)

20

-

-

... More
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete.

100

-

-

... More
Providing and fixing CI manhole covers of size 750*750mm of including providing locking arrangement and of approved manufacture as per the specifications. The rate shall be inclusive of fixing edge angle of size 40*40*5mm with protective coat of paint to all-round the opening. Including finishing to the edge angle and C I cover.

-

-

-

... More
a) Light Duty (min. 50 kg weight)

5

-

-

... More
b) Medium Duty (min. 60 kg weight)

5

-

-

... More
c) Heavy Duty(min. 75 kg weight)

5

-

-

... More
Providing and filling Cinder of approved quality for toilets and other sunken portions in 1:10 ratio ( 1 cement :10 cinder) with proper compaction incl placing, finishing, with M10 cement concrete topping of 50 mm mixed with approved waterproof compound, even surface finished and to slope as required to receive tiles etc. cost of materials, labours, tools & plants, loading and unloading charges, transportation, with leads and lifts at all levels, all other incidental charges, etc. complete and as directed by the Engineer- in-charge.

10

-

-

... More
Supplying and fixing anchor fasteners of HILTI including necessary drilling as per the locations shown in the drawing etc. complete as per approved manufacturer.

-

-

-

... More
a) 12mm dia

10

-

-

... More
b) 16mm dia

10

-

-

... More
c) 20mm dia

10

-

-

... More
Making Core Cutting in slabs / beams / retaining walls and any other R.C members to any dia & depth by using 'HILTI' make diamond drilling machine with tolerance for any type of inserts, anchor fasteners etc. Rate shall include for sealing the gaps between RC surface and inserts with fire retardent grouting material as per manufactures specification ,all charge, preparation of surface, cutting of reinforcement, cleaning the surface, staging, scaffolding with necessary tools and equipments water and power, removal of debris from the site, staging scaffolding etc complete, as directed.

-

-

-

... More
75 to 110 mm dia pipe to the following depth:

-

-

-

... More
a) 150 mm Depth

10

-

-

... More
b) 200 mm Depth

10

-

-

... More
c) 250 mm Depth

10

-

-

... More
d) 300 mm Depth

10

-

-

... More
110 to 160 mm dia pipe to the following depth:

-

-

-

... More
a) 150 mm Depth

10

-

-

... More
b) 200 mm Depth

10

-

-

... More
c) 250 mm Depth

10

-

-

... More
d) 300 mm Depth

10

-

-

... More
160 to 250 mm dia pipe to the following depth:

-

-

-

... More
a) 150 mm Depth

10

-

-

... More
b) 200 mm Depth

10

-

-

... More
c) 250 mm Depth

10

-

-

... More
d) 300 mm Depth

10

-

-

... More
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)

5

-

-

... More
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge.

5

-

-

... More
Demolishing brick work in cement mortor manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.

5

-

-

... More
Providing and fixing Modular Toilet Cubicals with the following speicifications Height = 2100 mm Thickness of Compact Laminate : 12 mm Color of HPL Boards: As per Approved Cubicle Shade CardSize of Cubicle : As per the drawingOverall Height Of Cubicle : 2100 mm (Including bottom Gap of 130mm) Stainless Steel - 304 Grade accessoriesa) SS “U” Channelb) SS “F” channel c) SS Top Rail d) SS Coat Hook e) SS Privacy Thumb turn c/w Occupancy Indicator f) SS Door Knob g) SS Hinges with Coverh) SS Adjustable Foot - 316 Gradei) Rubber Lining for Groovej) S.S.Screws 304 G & P.V.C Wall Plugs

29

-

-

... More
Providing and fixing of corner bead to protect columns made out of EPDM rubber of size 50mmX50mm and to a length 1.00 mts and thinkness of 6mm along with a reinforced base of galvanized iron of nominal thickness 1.00 mm with a Zinc coating of 120gms per Sqm at the corners including tying in position with suitable nails / screws etc., complete and as per manufacturer specification. The work shall include for preparation of surface, cleaning, curing etc; complete, all as directed

50

-

-

... More
Providing and applying 2.5 mm thick road marking strips (retro- reflective) of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on road surface including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete as per direction of Engineer-in-charge and accordance with applicable specifications.

100

-

-

... More
Providing and fixing of speed Humps, smooth finish solid rubber of one piece construction and shall be supplied with countersunk 8mm diameter holes in two rows for fixing with not less than 4 holes for each 500mm length. Two night vision reflectors - one on each side of the hump - shall be provided for every 500mm length. All guards shall be of self colour in black and in yellow and shall not be painted. The hump shall be of width 425mm with a height of 50mm and shall be supplied in lengths of not less than 500 mm. The humps are to be fixed to the reinforced concrete slab/ roads with M12 expansion fasteners as directed by the PMC/Client/Architect

100

-

-

... More
Providing and fixing 20mm thick polyethylene board to the concrete surfaces for expansion joints as per the locations shown in the Good For Construction drawings with necessary fixing arrangement etc. complete as per the manufacturer's specifications. The manufacturer's for the same shall be considered as approved make.

10

-

-

... More
SITE DEVELOPMENT

-

-

-

... More
Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.-All kinds of soil

5066

-

-

... More
Extra for every additional lift of 1.50 m or part thereof in ( for taking out excavated earth/Rock beyond the depth of 1.50 m from Ground level)

-

-

-

... More
a) All kinds of soil 1.50 - 3.0 m depth

10

-

-

... More
b) All kinds of soil 3.0 - 4.50 m depth

10

-

-

... More
c) Ordinary / Hard rock 1.50 - 3.0 m depth

10

-

-

... More
Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.

-

-

-

... More
a) Ordinary rock

10

-

-

... More
b) Hard rock (blasting prohibited)

10

-

-

... More
Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sum on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.-All kinds of soil.

10

-

-

... More
Excavation work by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains not exceeding 1.5 m in width or 10 sqm on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50m.

-

-

-

... More
a) Ordinary rock

10

-

-

... More
b) Hard rock ( blasting prohibited).

10

-

-

... More
Filling available excavated earth (including available ordinary rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

5000

-

-

... More
Carriage of material by mechanical transport including loading, unloading and stacking / spreading / leveling lead upto 1 km.

-

-

-

... More
a) Earth

451

-

-

... More
b) Excavated Rock

10

-

-

... More
Formation of Landscape area with making slope and consolidate with water as per drawings and instructions

1000

-

-

... More
CEMENT CONCRETE & REINFORCED CEMENT CONCRETE WORKS

-

-

-

... More
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:-1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)

151.08

-

-

... More
Providing and laying in position ready mixed concrete manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead upto 10kms having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge. M-30 grade Reinforced cement concrete by using minimum 335 kg of cement per cum of concrete as per IS standard plus fly ash 20 % or more confirming to Grade I of IS 3812 (Part-I) with uniform blending with cement in accordance with clauses 5.2 and 5.2.1 of IS 456:2000 .(quote shall contian additional cement used for arriving the required strength). Note : Contractor shall submit the necessary design mix reports from the approved Lab for the above grade of concrete with 28 days test results to the Engineer in charge for the approval of design mix prior to start of any type of concreting works at site. The contractor should quote his rate considering minimum 335 kg plus required fly ash as per IS code. In case additional qty of cement is required to achieve the desired target strength as per design mix ,the same shall be used but shall not be paid separately. All work up to Plinth Level.

791.9

-

-

... More
Providing and fixing at or near ground level precast cement concrete in kerbs, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand) including the cost of required centering, shuttering and finishing smooth with 6mm thick cement plaster 1:3 (1 cement : 3 fine sand) on exposed surfaces complete.-1:1½:3 (1 Cement: 1½ coarse sand(zone-III) : 3 graded stone aggregate 20 mm

28

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for removal of form for:

-

-

-

... More
a) Foundations, footings, bases of columns etc. for mass concrete.

415.2

-

-

... More
b) Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.

3068

-

-

... More
c) Suspended floors, roofs, landings, balconies and access platform.

92

-

-

... More
STEEL WORKS

-

-

-

... More
Supplying, straightening, cutting, bending, placing in postion reinforcement bars of all diameters to RCC work and binding with 18 SWG black annealed binding wire (double fold) etc., all complete as per drawings and specifications . The rate shall include cost of materials, cost of binding wire, pvc cover blocks as specified, labour, loading and unloading, transportation, scaffolding and all other incidental charges etc., with all leads and lifts, complete and as directed by the Engineer-in-charge at all levels. (Payments will be based on actual approved BBS qty. Only authorized laps, chairs and spacers will be measured and paid for). High yield strength ( TMT bars ) confirming to IS-1786 of Fe 500 grade.. Upto Plinth level

146

-

-

... More
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete

10

-

-

... More
MASONRY WORKS- Note: 1. Scaffolding is included for all the Masonry works 2. The rates are included for all the wastages. 3. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification.

-

-

-

... More
Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete 

120

-

-

... More
Solid block masonry using pre cast solid blocks ( Factory made) of size 40x20x10cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth for 10 cm thick wall in CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding etc complete 

2

-

-

... More
PLASTERING WORKS- Note: 1. Cost of Scaffolding is included for all the Plastering works 2. The rates are included for all the wastages. 3. Refer Technical specification for curing works 4. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification. 5.Cost including Providingng and fixing of 150 mm wide GI plaster mesh of Arpitha or equivalent approved make with nominal thickness of individual thread 0.35mm with a Zinc coating of 120 gms per Sqm at the junctions of masonry & RCC work, plastering the mesh in CM 1:2 including tying in position with suitable nails/screws etc

-

-

-

... More
Plastering with cement mortar 1:3 of 12 mm thick for RCC surfaces upto Five floor level

814

-

-

... More
FLOORING WORKS

-

-

-

... More
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) - 25 mm thick in single slab of stone not less than 1.5m length shall be used. Rate shall include for preparation of base surface & finished the surface, protection with gypsum/POP layer over plastic sheet and removing the same before handing over,work at all levels, as directed.

10

-

-

... More
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.

10

-

-

... More
Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab.

10

-

-

... More
Extra for Kota stone/ sand stone in treads of steps and risers using single length up to 1.05 metre.

10

-

-

... More
Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : a. Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.

310

-

-

... More
Preparing the surface with 25-40 mm thick concrete screed( 1:2:4) by using coarse graded aggregate of 6 to 12 mm size laid over floor concrete and finished smooth and even surface to receive the Tile adhesive/Cement mortor as instructed by Client.

-

-

-

... More
a) Thickness upto 25mm

10

-

-

... More
b) Thickness upto 40 mm

10

-

-

... More
Providing and laying factory made chamfered edge Cement Concrete paver blocks of required strength, thickness & size/shape, made by table vibratory method , to attain superior smooth finish using PU or equivalent moulds, laid in required Grey colour & pattern over 50mm thick compacted bed of coarse sand, compacting and proper embedding / laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with jamuna sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand in footpath, parks, awns, drive ways or light traffic parking etc. all complete as per manufacturer’s specifications & direction of Engineer -in-Charge: a) 80 mm thick c.c. paver block of M-30 grade with approved colour design and pattern.

1480

-

-

... More
Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. With material conforming to Grade-I (size range 75 mm to 0.075 mm ) having CBR Value-30

504

-

-

... More
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by tipper to site, for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge.

370

-

-

... More
Providing and laying Multi groove Paver tile of size 500 x 250mm x 40mm thick of Besant beton / approved make in all colours, finish, laid on 20mm thick bed of Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with cement etc., complete. Work include for preparation of base surface & finished the surface as directed.

800

-

-

... More
PAINTING WORKS

-

-

-

... More
Finishing walls with water proofing cement paint of required shade: New work (Two or more coats applied @ 3.84 kg/ 10 sqm) including primer.

120

-

-

... More
Enamal Paint for structural steel works

300

-

-

... More
MISCELLENEOUS

-

-

-

... More
Construction of catch basin of 600mm x 600mm size and depth upto 1200mm for external storm water drainage with 230mm thick walls in well burnt table moulded bricks in CM 1:4 over a bed of 100 mm thick PCC 1:4:8 internal walls plastered smooth in CM 1:3 and external walls plastered in1:6 with sponge finish. Fixing precast RCC grating of size 600 x 600mm on top surface flushed to the finished floor level with necessary excavation, back filling the selected excavated earth with all leads and lifts etc., complete. The quoted rate shall include 110dia PVC pipe sleeves from road GSM to the chamber as shown in the drawings.

-

-

-

... More
a) 1000 x 1000 x 900 mm

2

-

-

... More
b) 900 x 900 x 750 mm

2

-

-

... More
c) 750x 750 x 600 mm

2

-

-

... More
d) 600x600x600 mm

10

-

-

... More
Providing and fixing PVC (6 Kg/sqcm class) pipe of specified dia below and approved make as water down take pipe with all specials, accessories and joints with solvent cement solution according to manufacturer’s specification.

-

-

-

... More
a) 160mm dia pipe

50

-

-

... More
b) 110 mm dia

50

-

-

... More
Providing and fixing CI manhole covers of size 750*750mm of including providing locking arrangement and of approved manufacture as per the specifications. The rate shall be inclusive of fixing edge angle of size 40*40*5mm with protective coat of paint to all-round the opening. Including finishing to the edge angle and C I cover

-

-

-

... More
a) Light Duty (min. 50 kg weight)

2

-

-

... More
b) Medium Duty (min. 60 kg weight)

2

-

-

... More
c) Heavy Duty(min. 75 kg weight)

2

-

-

... More
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete:

-

-

-

... More
a) 150 mm dia R.C.C. pipe

10

-

-

... More
b) 250 mm dia R.C.C. pipe

10

-

-

... More
c) 300 mm dia R.C.C. pipe

50

-

-

... More
d) 450 mm dia R.C.C. pipe

50

-

-

... More
e) 700 mm dia R.C.C. pipe

50

-

-

... More
SEWAGE TREATMENT PLANT

-

-

-

... More
Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30cm in depth. 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.-All kinds of soil

200

-

-

... More
Extra for every additional lift of 1.50 m or part thereof in ( for taking out excavated earth/Rock beyond the depth of 1.50 m from Ground level)

-

-

-

... More
a) All kinds of soil 1.50 - 3.0 m depth

360

-

-

... More
b) All kinds of soil 3.0 - 4.50 m depth

10

-

-

... More
c) Ordinary / Hard rock 1.50 - 3.0 m depth

10

-

-

... More
Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sum on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.-All kinds of soil.

10

-

-

... More
Excavation work by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains not exceeding 1.5 m in width or 10 sum on plan including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50m.

-

-

-

... More
a) Ordinary rock

10

-

-

... More
b) Hard rock ( blasting prohibited).

10

-

-

... More
Filling available excavated earth (including available ordinary rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

168

-

-

... More
Carriage of material by mechanical transport including loading, unloading and stacking / spreading / leveling lead upto 1 km.

-

-

-

... More
a) Earth

392

-

-

... More
b) Excavated Rock

10

-

-

... More
CEMENT CONCRETE & REINFORCED CEMENT CONCRETE WORKS

-

-

-

... More
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:- 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)

30

-

-

... More
Providing and laying in position ready mixed concrete manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead upto 10kms having continuous agitated mixer, manufactured as per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying , excluding the cost of centering, shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge. M-30 grade Reinforced cement concrete by using minimum 335 kg of cement per cum of concrete as per IS standard plus fly ash 20 % or more confirming to Grade I of IS 3812 (Part-I) with uniform blending with cement in accordance with clauses 5.2 and 5.2.1 of IS 456:2000 .(quote shall contian additional cement used for arriving the required strength). Note : Contractor shall submit the necessary design mix reports from the approved Lab for the above grade of concrete with 28 days test results to the Engineer in charge for the approval of design mix prior to start of any type of concreting works at site. The contractor should quote his rate considering minimum 335 kg of cement plus required fly ash as per IS code.

-

-

-

... More
a) All work up to Plinth Level.

220.105

-

-

... More
b) All work above Plinth level

8.37

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for removal of form for:

-

-

-

... More
a) Foundations, footings, bases of columns etc. for mass concrete.

24.4

-

-

... More
b) Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.

588

-

-

... More
c) Beam

153.4

-

-

... More
d) Staircase

16.8

-

-

... More
e) Suspended floors, roofs, landings, balconies and access platform.

125

-

-

... More
f) Column

26.1

-

-

... More
STEEL WORKS

-

-

-

... More
Supplying, straightening, cutting, bending, placing in postion reinforcement bars of all diameters to RCC work and binding with 18 SWG black annealed binding wire (double fold) etc., all complete as per drawings and specifications . The rate shall include cost of materials, cost of binding wire, pvc cover blocks as specified, labour, loading and unloading, transportation, scaffolding and all other incidental charges etc., with all leads and lifts, complete and as directed by the Engineer-in-charge at all levels. (Payments will be based on actual approved BBS qty. Only authorized laps, chairs and spacers will be measured and paid for).-High yield strength ( TMT bars ) confirming to IS-1786 of Fe 500 grade.

-

-

-

... More
a) Upto Plinth level

34

-

-

... More
b) Above Plinth level

1.1

-

-

... More
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete

0.5

-

-

... More
MASONRY WORKS- Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete 

14

-

-

... More
PLASTERING WORKS- Note: 1. Cost of Scaffolding is included for all the Plastering works 2. The rates are included for all the wastages. 3. Refer Technical specification for curing works 4. Technical specification should follow for the all the works and any clarification / variation between BOQ and Technical specification, contractor should follow BOQ specification. 5.Cost including Providingng and fixing of 150 mm wide GI plaster mesh of Arpitha or equivalent approved make with nominal thickness of individual thread 0.35mm with a Zinc coating of 120 gms per Sqm at the junctions of masonry & RCC work, plastering the mesh in CM 1:2 including tying in position with suitable nails/screws etc

-

-

-

... More
Plastering with cement mortar 1:3 of 12 mm thick for RCC surfaces upto Five floor level

41.8

-

-

... More
Plastering with cement mortar 1:4 of 15 mm thick for inside walls upto Five floor level for wall surfaces

70

-

-

... More
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge

70

-

-

... More
Extra for providing and mixing water proofing material of approved make in cement plaster work in proportion recommended by the manufacturers.min 2% by weight of cement to be considered .

10

-

-

... More
Providing water proof Plaster with CM 1:3, 15mm thick finished smooth with a floating coat of cement mixed thoroughly with approved brand and quality water proofing compound of Fosroc/BASF at 2% by weight of cement at all levels and heights including scaffolding etc complete.

50

-

-

... More
JOINERIES

-

-

-

... More
2hrs. Fire rated hollow metal doors - PaintedProviding and fixing of Hollow metal fire rated doors as per IS 3614 part-1 & part-2 for stability and integrity. Pressed Galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall have doors tested at CBRI or ARAI for maximum rating of 2hrs with vision panel. Test certificates should be available for vision lites /panels as part of the fire door assembly. Independent glass test certificates will not be accepted. Manufacturer test certificate shall cover doors both single and double leaf and all doors supplied should be within the tested specimen, deviation in specification and sheet thickness other than what is mentioned in the test certificates are not allowed. Proper label confirming the type of door and the hourly rating is mandatory Door frame shall be double rebate frame profile of size 125 x 60mm made out of 1.60mm (16gauge) minimum thick galvanized steel sheet. Frames shall be Mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system and shall be site fitted with EPDM gasket as standard.All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed should be filled with PUF or with cement & sand slurry as recomended by the manufcaturer of the engineer.Door leaf shall be 46mm thick fully flush double skin door with or without vision lite. Door leaf shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. 200x300mm Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement.The glass should be 6mm clear borosilicate fire rated glass of relavant rating of the door. All doors and frames shall be finished with polyurethane aliphatic grade powder coating minimum 50 microns of approved colour. The door leaf and frame shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule.

-

-

-

... More
2Hrs Fire Rated Door FD2 Single leaf 1200x2400mm with vision panel :1200x2400mm with hardware Hinges 3090 F, 5 Knl, 2 Ball bearing butt hinges size 4" x 3" x 3mm SS 304One point panic device PHA 2001 - PHA2102, PHA 2105 L=1300mmExternal trim PHT 3905 prepared for euro profile cylinder.EP Half Cyl. 3010, 5pin one side key Length=42mm, SNPDoor closer TS 72 EN 2-4 with Std. armFire Rated Seal for Grooved Frame Profile C421 - EPDM Black

1

-

-

... More
Louvered ventilators

5.4

-

-

... More
FLOORING WORKS

-

-

-

... More
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) - 25 mm thick in single slab of stone not less than 1.5m length shall be used. Rate shall include for preparation of base surface & finished the surface, protection with gypsum/POP layer over plastic sheet and removing the same before handing over,work at all levels, as directed.

10

-

-

... More
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.

22.8

-

-

... More
Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab.

10

-

-

... More
Extra for Kota stone/ sand stone in treads of steps and risers using single length up to 1.05 metre.

10

-

-

... More
Providing and laying in panels not more than 20 sqm. in plan granolithic flooring with cement concrete M30 by using coarse graded aggregate of 6 to 12 mm size laid monolithic with floor concrete and finished smooth with power trowel including preparation of concrete surface and form work. The screed strips shall be fixed on the base concrete with 6 mm thick Glass strips or other metals strips for effective separation of panels not exceeding 20 sqm. in plan etc. complete as per Specifications and as directed. Unevenness in floor finish shall not exceed +2mm in one square metre area.Rate to include lead , lift at all levels, pumping, placing, necessary formwork, curing etc. providing and fixing required size angles for edge nosing of platform portions including grouting of lugs etc. complete. but excluding cost of angles which shall be paid seperately under relevant items

51.7

-

-

... More
PAINTING WORKS

-

-

-

... More
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.

10

-

-

... More
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre.

10

-

-

... More
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade. New work (two or more coats) over and including water tinnable priming coat with cement primer.

10

-

-

... More
Finishing walls with water proofing cement paint of required shade: New work (Two or more coats applied @ 3.84 kg/ 10 sqm) including primer.

10

-

-

... More
Wall painting with acrylic emulsion paint of approved brand and manufacture. to give an even shade : Two or more coats on new work

145

-

-

... More
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two or more coats on new work including primer.

10

-

-

... More
MISCELLENEOUS

-

-

-

... More
Providing and fixing hand rail of approved size by welding etc. to, balcony railing and staircase railing including applying a priming coat of approved steel primer by using G I Pipes of required sizes as shown in the drawings.

400

-

-

... More
Supplying and fixing poly-propelene rungs of 20 mm square bar of size 263 x 165 mm for access way including anchorage in walls to a minimum depth of 100 mm with C.C 1:2:4 etc. complete and as directed.

100

-

-

... More
Construction of catch basin of 600mm x 600mm size and depth upto 1200mm for external storm water drainage with 230mm thick walls in well burnt table moulded bricks in CM 1:4 over a bed of 100 mm thick PCC 1:4:8 internal walls plastered smooth in CM 1:3 and external walls plastered in1:6 with sponge finish. Fixing precast RCC grating of size 600 x 600mm on top surface flushed to the finished floor level with necessary excavation, back filling the selected excavated earth with all leads and lifts etc., complete. The quoted rate shall include 110dia PVC pipe sleeves from road GSM to the chamber as shown in the drawings.

-

-

-

... More
a) 1000 x 1000 x 900 mm

2

-

-

... More
b) 900 x 900 x 750 mm

2

-

-

... More
c) 750x 750 x 600 mm

2

-

-

... More
d) 600x600x600 mm

2

-

-

... More
Providing and fixing PVC (6 Kg/sqcm class) pipe of specified dia below and approved make as water down take pipe with all specials, accessories and joints with solvent cement solution according to manufacturer’s specification.

-

-

-

... More
a) 160mm dia pipe

10

-

-

... More
b) 110 mm dia

10

-

-

... More
Providing and fixing CI manhole covers of size 750*750mm of including providing locking arrangement and of approved manufacture as per the specifications. The rate shall be inclusive of fixing edge angle of size 40*40*5mm with protective coat of paint to all-round the opening. Including finishing to the edge angle and C I cover

-

-

-

... More
a) Light Duty (min. 50 kg weight)

2

-

-

... More
b) Medium Duty (min. 60 kg weight)

2

-

-

... More
c) Heavy Duty(min. 75 kg weight)

2

-

-

... More
Providing, Fabricating and fixing puddle flanges made of GI 'c' class pipe with 6mm thick MS plate around 50 mm fixed to sump and water tank etc. all complete as directed by the Engineer-in-Charge.

-

-

-

... More
a) 200 NB

2

-

-

... More
b) 150NB

2

-

-

... More
WATERPROOFING WORKS - STP

-

-

-

... More
Providing and laying integral cement based treatment for water proofing on top of PCC laid for Grade slab,Raft & beam,etc in the following order and consisting of following operations. : i) Laying of cement concrete of Mix 1:2:4 (1 cement:2 coarse sand: 4 stone grit 6 mm and down size by volume) to an average thickness of 20mm and the concrete shall be admixed with Normal setting integral Waterproofing compound CICO NO.1 or approved equivalent conforming to IS 2645 at the rate of 2% by weight of cement over PCC surface. Concrete shall be cured by light spraying of water for the next 48 hours. ii) Providing and applying one coat of TAPECRETE Acrylic Polymer Modified Cementitious Slurry Coat over well prepared surface as a Primer and applying CICO CORCHEM 206 - I Polyurethane Based Elastomeric Coating to the thickness of 1.5 mm over TAPECRETE slurry coat applied surface. iii) Laying of cement concrete of Mix 1:2:4 (1 cement:2 coarse sand: 4 stone grit 6 mm and down size by volume) to an average thickness of 20mm and the concrete shall be admixed with Normal setting integral Waterproofing compound CICO NO.1 or approved equivalent conforming to IS 2645 at the rate of 2% by weight of cement over TAPECRETE applied surface. Conrete shall be cured by light spraying of water for the next 48 hours.

200

-

-

... More
RAFT (INTERNAL)-i) Providing and Fixing 18 mm dia GI nozzles (the hole shall be about half the depth of the member to be grouted and nozzle should be 75mm length) in grid pattern at a spacing not more than 1.0 metre c/c while casting the raft slab and along construction joints at a spacing not more than 1.0 metre c/c along the construction joints. Nozzles can also be post fixed by drilling holes using drill machine and to be fixed with cement putty admixed with quick setting integral Waterproofing compound CICO NO.3 or approved equivalent in the ratio 1:1by weight .The Caps shall be fixed in the mouth of the nozzles to avoid chocking of cement slurry etc, while concreting or Post fixing the Nozzle. (Nothing extra shall be paid for post fixing). ii) Applying injection grouting through the nozzles grouting pumps with a minimum pressure of 2 kg/sqcm with cement slurry admixed with CICO Non shrink Polymeric Water Proof Grouting Compound or approved equivalent at the rate of 2% by weight of cement .Grouting operations to be taken up after the raft / slab concrete reached the full strength, i.e 28 days after casting of concrete. iii) Sealing off the nozzles after grouting operation is over with cement putty admixed with quick setting integral Waterproofing compound CICO NO.3 or approved equivalent in the ratio 1:1by weight. iv) Cut the projected nozzles if required over the concrete surface and fill with cement putty admixed with quick setting integral Waterproofing compound CICO NO.3 or approved equivalent in the ratio 1:1by weight. v) Application 2 coats of TAPECRETE Acrylic Polymer Modified Cementitious Coating over RAFT TOP. vi) Laying of cement concrete of Mix 1:2:4 (1 cement:2 coarse sand: 4 stone grit 6 mm and down size by volume) to an average thickness of 20mm and the concrete shall be admixed with Normal setting integral Waterproofing compound CICO NO.1 or approved equivalent conforming to IS 2645 at the rate of 2% by weight of cement over TAPECRETE applied surface. Conrete shall be cured by light spraying of water for the next 48 hours.

200

-

-

... More
RETAINING WALL (INTERNAL)Providing and applying injection grouting on Basement Retaining walls internal surface using cement admixed with water proofing compound in the following order and as directed by Engineer–in–Charge : i) Making ' V ' grooves at the construction joints of size 20 x 20 mm and clean the surface with wire brush .ii) Providing and Fixing 18 mm dia GI nozzles (the hole shall be about half the depth of the member to be grouted and nozzle should be 50mm) the retaining wall and along construction joints at a spacing not more than 1m c/c . Nozzles (can also) shall be post fixed by drilling holes using drill machine and to be fixed with cement putty admixed with quick setting integral Waterproofing compound CICO NO.3 or approved equivalent in the ratio 1:1by weight .iii) Filling the "V" Groove with CICO No. 3 Quick Setting Waterproofing Compound admixed with cementiv) Applying injection grouting through the nozzles by hand operated grouting pumps with a minimum pressure of 2 kg/sqcm with cement slurry admixed with CICO Non shrink Polymeric Water Proof Grouting Compound or approved equivalent at the rate of 2% by weight of cement .Grouting operations to be taken up after the concrete reached the full strength, i.e 28 days after casting of concrete.v) Sealing off the nozzles after grouting operation is over with cement putty admixed with quick setting integral Waterproofing compound CICO NO.3 or approved equivalent in the ratio 1:1by weight.vi) Cut the projected nozzles if required over the concrete surface and fill with cement putty admixed with quick setting integral Waterproofing compound CICO NO.3 or approved equivalent in the ratio 1:1by weight.vii) Application 2 coats of TAPECRETE Acrylic Polymer Modified Cementitious Coating over well prepared wall surface.viii) Lay protective plaster layer with 12mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound CICO NO.1 or approved equivalent conforming to IS 2645 at the rate of 2% by weight of cement over the third coat of brush topping. Plaster shall be cured by spraying of water for the next 7days.

546

-

-

... More
RETAINING WALL ( EXTERNAL )Providing and applying integral cement based treatment for water proofing on Basement Retaining walls external surface,beam sides,pile cap sides etc using cement admixed with water proofing compound in the following order and and as directed by Engineer–in–Charge : i) Making ' V ' grooves at the construction joints of size 20 x 20 mm and clean the surface with wire brush, and filling the "V" Groove with CICO No. 3 Quick Setting Waterproofing Compound admixed with cementii) Providing and applying one coat of TAPECRETE Acrylic Polymer Modified Cementitious Slurry Coat over well prepared surface as a Primer and applying CICO CORCHEM 206 - I Polyurethane Based Elastomeric Coating to the thickness of 1.5 mm over TAPECRETE slurry coat applied surface.iii) Lay protective plaster layer with 12mm thick Cement Mortar 1:4 (1 cement: 4 coarse sand) admixed with Normal setting integral Waterproofing compound CICO NO.1 or approved equivalent conforming to IS 2645 at the rate of 2% by weight of cement over the third coat of brush topping. Plaster shall be cured by spraying of water for the next 7days.

168

-

-

... More
FLOOR SLAB WATER PROOF-i)The concrete slab and wall surface shall be thoroughly cleaned to remove debris and dust, and applying one coat of TAPECRETE Acrylic Polymer Modified Cementitious Slurry Coat over well prepared surface as a Primer and applying CICO CORCHEM 206 - I Polyurethane Based Elastomeric Coating to the thickness of 1.5 mm over TAPECRETE slurry coat applied surface.ii)Providing protective layer of CC 1:2:4 - 40 mm thick Screed admixed with CICO No. 1 @ 2 % by weight of cement over treated area

200

-

-

... More
Terrace Water proofing1-(a) -By mechanical upgrading / hydro blasting to remove all loose mortar and laitance, oil, grease etc. and washing the surface with water to get neat surface and to ensure a good bond between the topping and the substrate. grouting the periphery of rain water down take pipes with water insensitive epoxy, pressure grouting of construction joints and honey comb areas with cement grout.1-(b)- Repairing the construction joints by cutting & making V groove in 25 x 25mm, with polimer modified mortor filling the grroves with CM 1:3 - mixed with polimer 5% by weight of cement. (2)- Providing and applying water repellant nano technology coating system over well prepared dry surface covering the surface area of 30 sqm per liter by mixing ratio of the component with water in 1:10 by volume i.e. (one liter of Water proofing compound and 10 liters of water)(3) -Providing and applying 2 coats of cement based flexible water proofing slurry modified from acrylic based polymer to a minimum dry film thickness of 2mm and cured for 7 days or and as per manufacturer's specification. (4) -Providing and applying a protective layer of 20 mm thick cement mortar 1:4 admixed with normal setting integral water proofing compound and to be spread over the cement based slurry coating. Normal setting integral water proofing (5) -Providing and laying brickbat coba in C.M.1:4 or Screed Concrete 1:2:4 mixed Polypropelene Fibres @ 50sqm / bag. to maintain the slope as shown in the drawing with an average thickness of 75 to 100 mm maintaining 40mm thick at drain point and slurry admixed with Normal setting integral water proofing compound @ 2% by the weight of cement and level the surface to receive the final coat of screed plaster. (6) -Providing and applying a final protective layer of 20 mm thick cement screed mortar 1:4 admixed with chips, normal setting integral water proofing compound and polypropelene fibres at the rate of 225 grams per bag of cement and to be spread over the top surface of the Brickbat coba/screed and the top surface shall be finished neatly including drawing a false line of 300mm x 300 mm over the finished surface.

100

-

-

-

-

-

... More
Providing and fixing White Color European Water Closet - Wall mounted type with integral low level flushing cistern(Dual flushing type-3 liter/ 6 liter (adjustable to 4 liter/ 2.5 liters)- 'P' trap including following accessories: solid seat and cover with rubber buffers and flap, brackets, brass screws with washer, 15mm CP Angle valve with connection tube,CP wall flange, pan connector, CI chair bracket,all hardware items like wallbrackets bolts washers & screws & brackets to be painted with two coats of enamel paint of approved shade over a coat of primer and necessary screws,etc.complete. Works including cutting and making good the walls /floor wherever required, etc., complete.

27

-

-

... More
Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 710 x 450 x 330mm including sensor flush valve having pre & post flushing with water ( 250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.Works including cutting and making good the walls /floor wherever required, etc., complete.

16

-

-

... More
Providing and fixing Granite stone slab of approved shade with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-Charge and finished smooth.Works including cutting and making good the walls /floor wherever required, etc., complete.

16

-

-

... More
Supplying,installing, testing and commissioning of White color Oval Wash basin size 550x410mm(below counter ) type with CP Pillar tap, 32mm dia CP waste coupling, 32mm dia CP bottle trap with extension pipe, pair of stainless steel bolts,with bracket (MS /CI ) to support to the basin, 15mm CP angle valve with CP inlet connection tube , CP wall flange, including necessary brakets etc complete. Works including cutting and making good the walls /floor wherever required, etc., complete.

37

-

-

... More
Providing and fixing 600x450mm bevelled edge Mirror of superior glass (of approved quality) complete with 6mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. Works including cutting and making good the walls /floor wherever required, etc., complete.

37

-

-

... More
Supplying and fixing CP Double Coat hook fixing with necessary screws etc., complete.

30

-

-

... More
Supplying , fixing in position and testing C.P. health faucet wall hook 1.2 metre long flexible tube, angle cock with wall flange all complete, Works including cutting and making good the walls /floor wherever required, etc., complete.15mm CP Angle valve with connection tube model no: CON-053-KN

30

-

-

... More
Providing and fixing 15mm nominal bore C.P. brass long body bibcock of approved quality conforming to IS standard and weighing not less than 690 gms.Works including cutting and making good the walls /floor wherever required, etc., complete.

5

-

-

... More
Providing and fixing liquid soap container of approved make near wash basins with necessary fixing screws and clamps etc., complete.

18

-

-

... More
Providng and fixing 600mm long CP towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arangement of approved quality colour and make .Works including cutting and making good the walls /floor wherever required, etc., complete.

22

-

-

... More
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, bottle trap including painting of fittings and brackets, cutting and making good the walls wherever required:Works including cutting and making good the walls /floor wherever required, etc., complete.

5

-

-

... More
Supplying,installing, testing and commissioning of CP sink cock with swivel spout wallmounted etc, including cutting and making good the walls wherever required etc., all complete as directed by Engineer.Works including cutting and making good the walls /floor wherever required, etc., complete.

5

-

-

... More
Supplying, Installing, testing and commissioning of White color Floor Mounted European water closet with inbuilt low level PVC flushing cistern and Wash Basin for Physically Challenged Persons with necessary Grab Rails, hinged rails for support , pan connecter bend,checknut, stopcock etc., colour solid seat and cover with polythene buffer and flap, CP flanges, CP bolts and nuts, bracket with nuts and bolts wall flanges etc.,complete, Wash Basin shall include 15mm dia CP liver operated pillar Cock with waste coupling, 32mm dia CP bottle trap with extension pipe,supporting bracket with necessary steel to support basin 1 No.15mm CP angle valve with 450mm long CP connection pipe and CP wall flanges all of approved make etc., complete. Works including cutting and making good the walls /floor wherever required, etc., complete.

3

-

-

... More
Supplying,installing, testing and commissioning of Electric hand drier twin blower integrated with timer (0-3min) and infrared arrangement. The timer shall be fully automatic,Works including cutting and making good the walls /floor wherever required, etc., complete.

18

-

-

... More
Supplying installing testing and commissioning of hot and cold cp single lever mixture unit with provision for over head shower, 15mm dia. CP elbow coupling pipe, spout and over head shower comprising of CP shower arm, pressure adjustable shower rose with cp wall flange etc., complete.Works including cutting and making good the walls /floor wherever required, etc., complete.

2

-

-

... More
Providing and fixing toilet paper holder :C.P. brass

30

-

-

... More
INTERNAL WATER SUPPLY

-

-

-

... More
Providing and fixing chlorinated Polyvinyl chloride (CPVC) pipes, fittings up to 50 mm dia SDR 11 ASTM CTS and above 50mm dia CPVC schedule 80 , having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fitting including fixing the pipe with clamps at 1.00m spacing. this includes jointing of pipes &fittings with one step CPVC solvent cement and cost of cutting chases and making good the same include testing of joints complete as per direction of Engineer in charge. Internal work –Exposed on wall

-

-

-

... More
a) 25 mm nominal outer dia .pipes

15

-

-

... More
b) 32 mm nominal outer dia .pipes

20

-

-

... More
c) 40 mm nominal outer dia .pipes

25

-

-

... More
d) 50 mm nominal outer dia .pipes

30

-

-

... More
e) 62.5 mm nominal outer dia pipes

20

-

-

... More
f) 80 mm nominal outer dia pipes

60

-

-

... More
g) 100 mm nominal outer dia pipes

50

-

-

... More
Providing and fixing chlorinated Polyvinyl chloride (CPVC) pipes, fittings up to 50 mm dia SDR 11 ASTM CTS and above 50mm dia CPVC schedule 80, pipes having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fitting i/c fixing the pipe with clamps at 1.00m spacing. This includes jointing of pipes &fittings with one step CPVC solvent cement and cost of cutting chases and making good the same include testing of joints complete as per direction of Engineer in charge.Concealed work including cutting chases and making good the wall etc.

-

-

-

... More
a) 15 mm nominal outer dia .pipes

125

-

-

... More
b) 20 mm nominal outer dia .pipes

80

-

-

... More
c) 25 mm nominal outer dia .pipes

100

-

-

... More
d) 32 mm nominal outer dia .pipes

35

-

-

... More
Providing and fixing ball valve (brass) of approved quality etc. Complete

-

-

-

... More
a) 25 mm nominal bore

10

-

-

... More
b) 32 mm nominal bore

8

-

-

... More
c) 40 mm nominal bore

16

-

-

... More
d) 50 mm nominal bore

8

-

-

... More
Supplying and fixing of 25mm dia Air release valve etc. complete

2

-

-

... More
INTERNAL DRAINAGE

-

-

-

... More
Providing, fixing and testing UPVC Class-3 pressure rating 6 kg /sqcm pipe of approved Make for underground drainage and sewerage systems - Confirming to IS 4985:2000 and speciels such as such as coupler, elbow, bends and Tee,etc This includes jointing of pipes &fittings with solvent cement and cost of cutting chases and making good the same include testing of joints for suspended lines and work in below ground. Woks includes necessary scaffolding,cutting and making good the walls wherever required ,complete as per direction of Engineer in charge.

-

-

-

... More
a) 40mm dia

20

-

-

... More
b) 50mm dia

100

-

-

... More
Providing, fixing and testing UPVC SWR- B Class pipe confirming to IS 13592-1992. and fittings confirming to IS 14735-1999, such as such as coupler, elbow, bends, Tee, Y, vent cowl etc for Soil, Waste and rain water pipe works in shaft and suspended in ceiling., laid in ground( from shaft to Inspection chamber and Gully chamber), etc., using rubber ring joints(rubber ring confirming to IS 15382) for shafts lines and solvent cement joints for suspended lines and work in below ground. Woks includes necessary scaffolding,cutting and making good the walls wherever required all complete as directed by the Engineer-in-Charge.

-

-

-

... More
a) 75mm dia

150

-

-

... More
b) 110mm dia

110

-

-

... More
Supplying,fixing and testing of UPVC floor trap with cockroach trap and CP grating 150 mm nominal size square 100mm diameter of the inner hinged round grating various inlet from 40mm dia to 110mm dia and various outlet from 75mm dia to 100 mm dia with the extension pipe, boss tee connections, fixed in sunken floors /Suspended support with ceiling level etc., complete.

60

-

-

... More
Supplying,fixing and testing of UPVC floor clean out used in sunken floors,75 or 110mm dia with extension pipes,specils such as 45 degree bend , tee ,CP tile grating and end cap (clean out plug ).the cap arrangements with female thread fix with the upvc clean out plug in male thread with gascet and s.s screws etc. complete. Works including cutting and making good the walls /floor wherever required, etc., complete.

20

-

-

... More
Supplying, fixing and testing of UPVC urinal trap with CP anti foul drainer square cockroach trap, 150 mm nominal size square 100mm diameter of the inner hinged round grating various inlet from 40 dia to 110 dia and various outlet from 75 dia to 100 dia with the extension pipe, boss tee connections, fixed in sunken floors /Suspended support with ceiling level etc., complete. Works including cutting and making good the walls /floor wherever required, etc., complete.

8

-

-

... More
EXTERNAL WATER SUPPLY

-

-

-

... More
Excavating trenches of required width for pipes, cables, etc, including excavation for sockets and dressing of sides ramming of bottoms, depth upto 1.5 m including getting out the excavated soil and then, returning the soil as required in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming watering etc.and disposing of surplus excaveted soil as directed, with in a lead of 50m.-Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia

150

-

-

... More
Providing and fixing chlorinated Polyvinyl chloride (CPVC) pipes, fittings up to 50 mm dia SDR 11 ASTM CTS and above 50mm dia CPVC schedule 80, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings this includes jointing of pipes & fittings with one step CPVC solvent cement,trenching, refilling &testing of joints complete as per direction of Engineer in Charge.-External work-100 mm nominal outer dia pipes

150

-

-

... More
Providing and fixing gun metal non return valve with C.I. wheel of approved quality(screwed end )-80mm nominal bore-Horizontal

2

-

-

... More
Supplying, installing, testing & commissioning approved make Butterfly valve with standard lever conforming to IS 13039 with necessary flange,nuts and boltsetc.,complete.

-

-

-

... More
a) 65mm nominal bore

2

-

-

... More
b) 80mm nominal bore

2

-

-

... More
c) 100mm nominal bore

2

-

-

... More
Constructing masonry Chamber 120x120x100 cm, inside with 75 class designation brick work in cement mortar 1:4 ( 1 cement :4 coarse sand ) for sluice valve, with C.I. surface box 100 mm. top diameter, 160 mm bottom diameter and 180 mm deep ( inside) with chained lid and RCC top slab 1:2:4 mix ( 1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) necessary excavation foundation concrete 1:5:10 ( 1 cement :5 fine sand:10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 ( 1 cement :3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design.-With F.P.S. bricks class

2

-

-

... More
Providing and fixing enclosed type water meter (bulk type) conforming to IS: 2373 and tested by municipal board complete with bolts, nuts, and rubber insertions etc. (the tail pieces if required will be paid separately):-80 mm dia nominal bore

2

-

-

... More
Providing and fixing C.I dirt box strainer for bulk type water meter with nuts, bolts, rubber insertions etc complete conforming to IS: 2373-80 mm dia

2

-

-

... More
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete: 25 mm nominal bore

2

-

-

... More
EXTERNAL DRAINAGE

-

-

-

... More
Excavating trenches of required width for pipes, cables, etc, including excavation for sockets and dressing of sides ramming of bottoms, depth upto 1.5 m including getting out the excavated soil and then, returning the soil as required in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming watering etc.and disposing of surplus excaveted soil as directed, with in a lead of 50mt.-Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia

150

-

-

... More
Providing, fixing and testing UPVC Class-3 pressure rating 6 kg /sqcm pipe of approved Make for underground drainage and sewerage systems - Confirming to IS 4985:2000 - pipe in trenches to required gradients and provide sand cushion for pipes to the full width of trench above and below the pipe to required minimum thickness etc., complete. rates including for laying pipes,forming bottom surface to required level, etc., complete

-

-

-

... More
a) 160mm diameter

30

-

-

... More
b) 200mm diameter

120

-

-

... More
Constructing brick masonry manhole in cement mortar 1:4 (1cement:4 graded stone aggregated 20mm nominal size), foundation concrete 1:4:8 mix (1cement:4coarse sand: 8graded stone aggregated 40mmsize nominal size) in side plastering 12mmthick with cement mortar 1:3(1cement:3coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1cement :2coarse sand :4graded stone aggregate 20mm nominal size) finished with floating coat of neat cement complete as per standard design:

-

-

-

... More
a) Inside size 90x80 cm and 45cm deep including C.I cover with frame (light duty ) 455x610mm internal dimensions total weight of cover and frame to be not less than 38kg(weight of cover 23kg and weight of frame 15 kg):-With Sewer bricks conforming to IS:4885

5

-

-

... More
b) Inside size 120x90 cm and 90cm deep including C.I cover with frame (heavy duty ) 560 mm internal diameter total weight of cover and frame to be not less than 208 kg(weight of cover 108kg and weight of frame 100 kg):-With Sewer bricks conforming to IS:4885

5

-

-

... More
Extra depth for manholeS

-

-

-

... More
a) Size 90x80cm-With Sewer bricks conforming to IS:4885

5

-

-

... More
b) Size 120x90cm-With Sewer bricks conforming to IS:4885

5

-

-

... More
Providing orange colour safety foot rest of minimum 6mm thick plastic encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS : 1786 having minimum cross section as 23 mmx25mm and over all minimum length 263mm and width as 165mm with minimum 112mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture's permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1 cement :3 coarse sand :6 graded stone aggregate 20 mm nominal size ) complete as per design.

80

-

-

... More
Making connection of drain or sewer line with existing manhole including breaking in to and making good the walls, floors with cement concrete 1:2:4 mix (1 cement: 2coarse sand: 4 graded stone aggregate 20 mm nominal size) cement plaster on both side with cement plaster 1:3 (1cement:3 coarse sand) finished with a floating coat of neat cement and making necessary channels for drain etc.complete-For pipes 100 to 250 mm diameter

1

-

-

... More
Providing and fixing square-mouth S.W.gully trap grade ‘A’’ complete with C.I grating brick masonry chamber with water tight C.I cover with frame of 300x300mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70kg as per standard design :100x100 mm size P type-With Sewer bricks conforming to IS:4885

4

-

-

... More
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenchs or drains (not exceeding 1.5 m in width or 10sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5m, including getting out the excaveted soil and disposal of surplus excaveted soil as directed, within a lead of 50m-All kinds of soil (for manhole)

60

-

-

... More
FAÇADE AND FAÇADE ACCESS SYTEM WORKS

-

-

-

... More
SEMI UNITIZED STURCTURAL GLAZING SYSTEM

-

-

-

... More
Semi unitized Glazing / Window system with Vision, Vision on Spandrel panel & Spandrel panel (System with Segmented Glass without Fin) - All Elevation: Designing, providing and fixing Semi Unitized structural glazing vision panel & vision on spandrel panel structurally held in position by Structural sealant and factory fabricated with Aluminium adaptor of suitable size in order to satisfy the structural design criteria specified in the Technical specification. In general, the system comprising Aluminium anodized extruded frames confirming to IS 8147 and anodizing AC 25 grade confirming to IS 1868 & Adapters supported on the brackets (spanning 3.0 to 3.2 M), Toggle cleats, Concealed HDG brackets & SS anchors and bolts, aluminium subframe around the window, flashing etc with Insulated glass of 24 mm thick having 6 mm thick Reflective coated low E glass on # 2 surface with SKN 754 of Saint Gobain make or Solarban 70 XL(2) Solar blue of PPG make or Excel 40 Blue Pearl of Asahi make as outer pane and 12 mm airgap and 6 mm thick glass uncoated clear as inner pane of same make. Both panes are shall be heat strengthened.-Rate shall exclude the cost of supply & fixing of top hung window hardwares with shutter frame, insulation tray, which will be measured and paid separately under the respective item below. Rate shall include the cost of supplying & fixing of glass, Offsite proto type test, visual mock up and field water test etc. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified and other load parameters specified in Technical specification. Refer Particular Specification item - 22.01 & 22.02, which shall form part of BOQ.

315

-

-

... More
Semi unitized Glazing / Window system with Vision, Vision on Spandrel panel & Spandrel panel (System with Segmented Glass & to support the Metal Fin) - Elevation - A & C: Designing, providing and fixing Semi Unitized structural glazing vision panel & vision on spandrel panel structurally held in position by Structural sealant and factory fabricated with Aluminium adaptor of suitable size in order to satisfy the structural design criteria specified in the Technical specification. In general, the system comprising Aluminium anodized extruded frames confirming to IS 8147 and anodizing AC 25 grade confirming to IS 1868 & Adapters supported on the brackets (spanning 3.0 to 3.2 M), Toggle cleats, HDG inserts (If required)Concealed HDG brackets & SS anchors and bolts, aluminium subframe around the window, flashing etc with Insulated glass of 24 mm thick having 6 mm thick Reflective coated low E glass on # 2 surface with SKN 754 of Saint Gobain make or Solarban 70 XL(2) Solar blue of PPG make or Excel 40 Blue Pearl of Asahi make as outer pane and 12 mm airgap and 6 mm thick glass uncoated clear as inner pane of same make. Both panes are shall be heat strengthened.-Rate shall exclude the cost of supply & fixing of top hung window hardwares with shutter frame, insulation tray & Metal fin which will be measured and paid separately under the respective item below. Rate shall include the cost of supplying & fixing of glass, Offsite proto type test, visual mock up and field water test etc. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified and other load parameters specified in Technical specification. Refer Particular Specification item - 22.01 & 22.02, which shall form part of BOQ.

300

-

-

... More
Metal Fin: Designing, providing & fixing the Aluminium PVDF finished of approved colour and perforated (as per the drawing) metal Fin of 75 to 100 mm wide with thickness not less than 5mm thick. Thickness of coating shall be not less than 30 microns. Aluminium fin to be fixed in to the glazing mullion by using continuous aluminium extruded PVDF finished bracket (Thickness not less than 5.0mm) with SS 316 fasteners, bolts & nuts & sealant and as per drawing. Rate shall include the cost of all materials, accessories etc complete. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified in Technical specification. Refer Particular Specification Item. No. 22.01.

250

-

-

... More
System for Frameless glazing: Designing, providing and fixing Point fixed glazing system using 2 way spider / GT Spiders as mentioned in Particular Specification including supplying and fixing of 19.52 mm thick laminated glass having 10 mm thick as outer panel and 8 mm thick as inner panel with interlayer of 1.52 mm thick Sentry Glas (R) of DuPont make. Outer pane glass shall be reflective coated glass - ST 167 of Saint Gobain make or Spring (SC60/52) clear of Asahi make. Inner pane shall be heat soak tested un coated clear glass and both panes shall be heat treated. Rate shall include cost of spiders, Articulated bolts, PVC clear edge strip for all exposed laminated edges and supply and fixing the Glass fin with required size to satisfy the structural criteria, but excluding the cost of door, which will be measured separately under the respective item. The thickness of glass fin shall be 21.52mm thick (Min) laminated toughened and heat soak tested as per specification. Rate shall include the cost for ceramic fritt (standard pattern) glass panel on the column and spandrel area. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified and other load parameters specified in Technical specification. Refer Particular Specification item - 22.03 & 22.05, which shall form part of BOQ.

25

-

-

... More
DOORS AND WINDOWS

-

-

-

... More
Designing, providing and fixing colour anodized aluminium Swing Door as part of Glazing system and fabricated as per drawing and fixed at all levels, elevations and heights by using aluminium box frame of size 100 x 40 mm and thickness not less than 2.0mm as outer frame and suitable aluminium frames with rebated profile shall be used for Doors with thickness not less than 2.0mm. Aluminium box frame shall be fixed into wall/RC by using SS anchor fasteners of Hilti make or approved equivalent. All glass panels shall be fixed by using snap fit aluminium colour anodized beading with special water proof cascades, Neoprene, hardwares etc. complete, as directed. All aluminium sections shall be 63400 (H9) grade conforming to IS 8147. All aluminium sections shall be finished with exterior grade powder coat of thickness not less than 70 microns and weight ratio joints mitered adjoined with heavy duty aluminium pressure die cast cleats with fins to match the sections of frames.Door shall be provided with necessary hardwares such as Door closer - ITS 96 EN 2 - 4 or TS 91 EN 3 (Opening restrict to 85 deg), Mortise dead lock - Model No. 278 (both side key operation) SS forend and SS strike plate (Suitable for both single / double leaf shutter) of Satin finish - Grade SS 316, SS satin finish handle - TG9377- 25 (Angled Spacer) - 600 mm long with back to back handle SS 316 grade, SS hinges (Minimum 4 Nos / Shutter) SS Door stoppers floor mounted, Door buffers etc. complete and as directed. All Hardwares shall be Dorma / Kinlong / Geze Make.Rate shall include the cost of supplying & fixing 12.52 mm thick laminated glass having 6 mm thick as outer panel and 5 mm thick as inner panel with interlayer of 1.52 mm thick sentry Glas (R) of Dupont make. Outer pane glass shall be reflective coated glass - Inner pane and Outer pane glass shall be uncoated clear glass of Saint Gobain make or Asahi make. Both panes shall be heat treated and heat soak tested. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified in Technical specification.

-

-

-

... More
a) Single Leaf door (1.20 x 2.40M)

6

-

-

... More
b) Double Leaf door (1.50 / 2.00 x 2.40/2.50M)

35

-

-

... More
Providing and fixing of aluminium extruded Sub frame of the section size of 14 mm x 62 mm having a weight not less than 0.855 Kg/m of Section No 1698 of Bhoruka Aluminium Ltd make or approved equivalent and finished with exterior grade powder coat of thickness not less than 70 microns. Refer Particular Specification item - 22.06. Refer item B - 3.00 to B - 5.00.

300

-

-

... More
Designing, providing and fixing Side Hung Window with Aluminium Extruded sections of approved Extruder and fabricate the windows as per drawing and fixed at all levels, elevations and heights. All aluminium sections shall be 63400 (H9) grade conforming to IS 8147 and thickness of aluminium sections shall not be less than 2.0mm. All aluminium sections shall be finished with exterior grade powder coat of thickness not less than 70 microns. Main / outer frames shall be fixed into masonry wall / RC concrete surface with necessary clamps, fasteners with Hilti make and other fastening materials shall be in stainless steel SS 316 grade, Window shall have Monolithic glass of 6 mm thick uncoated clear / Tinted heat Treated glass of Saint Gobain or Asahi make.Rate shall also include for providing and fixing aluminium extruded frames, with necessary accessories, flashing, L - angle etc as specified above and hardwares like concealed locks, SS friction hinges Stay arm (Minimum 2Nos per shutter) of Securistyle make / Flap Hinges (Minimum 4Nos per shutter) approved equivalent make and Heavy duty lock with multipoint lock cum Handle of Alualpha make or approved equivalent make etc, cost for scaffolding, non staining weather silicon sealant of Dowcorning or approved equivalent make shall be provided at the junctions between wall, main frames and wherever required, safety clips at each corner of glass and also to be provided with EPDM gasket as weather strip to ensure water and air tightness. System to be designed to with stand design wind pressure of 150 Kg/Sqm and other load as per IS code or relevant international code. Aluminium members given are subject to satifying the structural design criteria given in the tender. Refer Particular Specification item - 22.07, which shall form part of BOQ.

10

-

-

... More
Designing, providing and fixing Fixed Window with Louver with Aluminium Extruded sections of approved Extruder and fabricate the windows as per drawing and fixed at all levels, elevations and heights. All aluminium sections shall be 63400 (H9) grade conforming to IS 8147 and thickness of aluminium sections shall not be less than 2.0mm. All aluminium sections shall be finished with exterior grade powder coat of thickness not less than 70 microns. Main / outer frames shall be fixed into masonry wall / RC concrete surface with necessary clamps, fasteners with Hilti make and other fastening materials shall be in stainless steel SS 316 grade, window shall have Monolithic glass of 6 mm thick uncoated clear / Tinted heat Treated glass of Saint Gobain or Asahi make.Rate shall also include for providing and fixing aluminium extruded aluminium frame with suitable size, with necessary accessories like EPDM Gaskets, SS screws, cleats, cost for scaffolding, non staining weather silicon sealant of Dowcorning or approved equivalent make shall be provided at the junctions between wall, main frames and wherever required. rate shall also include the cost of safety clips at each corner of glass as an additional safety to avoid breakage of corner of the glass and also to be provided with EPDM gasket as weather strip to ensure water and air tightness. System to be designed to with stand design wind pressure of 150 Kg/Sqm and other load as per IS code or relevant international code. Aluminium members given are subject to satisfying the structural design criteria given in the tender. Refer Particular Specification item - 22.08, which shall form part of BOQ.

25

-

-

... More
Designing, providing and fixing Fixed Window with Louver with Aluminium Extruded sections of approved Extruder and fabricate the windows as per drawing and fixed at all levels, elevations and heights. All aluminium sections shall be 63400 (H9) grade conforming to IS 8147 and thickness of aluminium sections shall not be less than 2.0mm. All aluminium sections shall be finished with exterior grade powder coat of thickness not less than 70 microns. Main / outer frames shall be fixed into masonry wall / RC concrete surface with necessary clamps, fasteners with Hilti make and other fastening materials shall be in stainless steel SS 316 grade, window shall have Monolithic glass of 6 mm thick uncoated clear / Tinted heat Treated glass of Saint Gobain or Asahi make and louver shall be Storm proof Louver - Louver - 75 x 28 x 1.5 mm thick section no 2089 - weight not less than 0.464 Kg/Rmt "Z" type and to be fixed with pitch not less than 50 mm and overlapping shall be 25 mm as minimum as shown in the drawing with L - angle around the louver.Rate shall also include for providing and fixing aluminium extruded aluminium frame with suitable size, glass, Louver with necessary accessories like EPDM Gaskets, SS screws, cleats, cost for scaffolding, non staining weather silicon sealant of Dowcorning or approved equivalent make shall be provided at the junctions between wall, main frames and wherever required. rate shall also include the cost of safety clips at each corner of glass as an additional safety to avoid breakage of corner of the glass and also to be provided with EPDM gasket as weather strip to ensure water and air tightness. System to be designed to with stand design wind pressure of 150 Kg/Sqm and other load as per IS code or relevant international code. Refer Particular Specification item - 22.08, which shall form part of BOQ and as per Drawings.

40

-

-

... More
Designing, providing and fixing aluminium extruded louver "Z" type finished with exterior grade powder coat of thickness not less than 70 microns of approved colour and as described below and System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified in Technical specification. Aluminium members given are subject to satifying the structural design criteria given in the tender. Refer Particular Specification item - 22.09, which shall form part of BOQ.Support system to fix the Louver: Providing and fixing complete louver system having aluminium box frame, aluminium flat to receive the louvers and aluminium angles around the louvered window to protect the water ingress through the outer frame etc and to be designed to with stand design wind pressure specified. Main aluminium frames shall be fixed with suitable brackets, fasteners etc, complete. Note : Weight will be considered only for the assembled frame part and hence necessary wastage shall form part of the rate quoted.

65

-

-

... More
Fixed Louver: Providing and fixing Storm proof Louver - Louver - 75 x 28 x 1.5 mm thick section no 2089 - weight not less than 0.464 Kg/Rmt "Z" type made out of specially extruded aluminium with powder caoted finish and as specified in Particular specifications and to be fixed with pitch not less than 50 mm and overlapping shall be 25 mm as minimum as shown in the drawing. Rate shall include supply and fixing of Louver, but excluding cost frames, plates, L - angle, brackets, fasteners and other accessories, which shall part of Item above.

5

-

-

... More
Canopy works

-

-

-

... More
Canopy / Pergola cladding with ACP: Providing and fixing the system to clad the Laminated sandwiched composite panel of Alucobond or Knauf of Fameline make or Alpolic make with approved colour and shade (4 mm (0.5 + 3.0 + 0.5) ACP with 3with 5000 series with 70% Virgin Mineral white core & 30% Resin polymer as per the specification described in Technical specifications for Canopy / Pergola as per profile and shape shown in the Drawing with necessary Hot dip Galvanized Structural steel support to clad the ACP and all support to be designed to withstand the Design wind pressure and the specification specified in Particular specifications etc complete. Main structural steel support will be measured under respective item separately. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified in Technical specification..Rate shall include the cost of supplying and fixing of Laminated sandwiched composite panel, Non staining weather for Vertical & horizontal joints in general the frame work for ACP cladding consists of aluminium anodized box frame (50 x 50 x 2.0 mm thick Box Tube subject to satisfying the structural design criteria) with Toggle cleat spacing shall not exceed 450 mm on both horizontal and vertical sides of each panel. All ACP fold at corners shall be provided with continuous 'L' cleat of 1.5mm thick and HDG bracket etc, complete. All Bolts, nuts and screws shall be SS 316 grade of approved make. Necessary stiffeners behind ACP shall be provided at every 600 mm to avoid the permanent deformation over a period with thickness not less than 2 mm and stiffener to be fixed with suitable adhesive or VHB tape for bonding the stiffener into panel and profiling of ACP to form a cut out and finishing the Cut out Jamb as shown in the drawing. NOTE :- Main structural steel frame work for Canopy and Pergola to receive the aluminium frame work for cladding will be considered under the respective item given below. Refer Particular Specification Item. No. 22.10

105

-

-

... More
System for Point fixed glazed Canopy: Designing, providing and fixing Point fixed glazed Canopy over the M.S base frame with Spiders as per specification (Main frame) to the required size to satisfy the structural criteria as per IS code or relevant international code) to fix the Spider / Articulated bolts of Dorma/Kinlong make.Rate shall include for supplying and fixing of 17.52 mm thick laminated glass having 8 mm thick as outer panel and 8 mm thick as inner panel with interlayer of 1.52 mm thick Sentry Glas (R) plus of Dupont make. Outer pane glass shall be reflective coated glass - Spring (SC60/52) clear of Asahi make or ST 167 Clear of Saint Gobain make. Inner pane of un coated clear glass heat soak tested but both panes shall be heat treated. Rate shall include cost for spiders, Articulated bolts, Bush, PVC clear edge strip for all exposed laminated edges PVC clear edge strip for all exposed laminated edges and necessary scaffolding works to erect the canopy works at all level. But, rate shall exclude the cost of M.S supports to receive the spiders which will be measured under the respective item. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified in Technical specification. Refer Particular Specification item - 22.04 & 22.05, which shall form part of BOQ.

10

-

-

... More
Cladding Works

-

-

-

... More
Laminated Sand witched composite panel - Dry wall cladding: Providing and fixing the system to clad the Laminated sandwiched composite panel (ACP) of Alucobond or Knauf of Fameline make or Alpolic make with approved colour and shade (4 mm (0.5 + 3.0 + 0.5) ACP with 3with 5000 series with 70% Virgin Mineral white core & 30% Resin polymer as per the specification described in Technical specifications, on the external surface the external surface like column, wall, jambs, sills, projected area, decorative capping, ceiling or any surface to any profile and shape, horizontally, vertically, sloped, curved, circular etc complete to a projection up to 200mm from the base structure. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified and other load parameters specified in Technical specification. Rate shall include the cost of supplying and fixing of Laminated sandwiched composite panel, Non staining weather for Vertical & horizontal joints in general the frame work for ACP cladding consists of aluminium anodized box frame (50 x 50 x 2.0 mm thick Box Tube subject to satisfying the structural design criteria) with Toggle cleat spacing shall not exceed 450 mm on both horizontal and vertical sides of each panel. All ACP fold at corners shall be provided with continuous 'L' cleat of 1.5mm thick and HDG bracket etc, complete. All anchors, bolts and screws shall be SS 316 grade of Hilti / Fischer make. Necessary stiffeners behind ACP shall be provided at every 600 mm to avoid the permanent deformation over a period with thickness not less than 2 mm and stiffener to be fixed with suitable adhesive or VHB tape for bonding the stiffener into panel. Refer Particular Specification item - 22.10, which shall form part of BOQ. Provisional Qty.

25

-

-

... More
Dry wall granite cladding: Designing, providing and fixing Granite slab - Dry type fixing using Silver grey or approved shade granite slab cladding the external surface on any surface to any profile and shape, horizontally, vertically, sloped, curved, circular etc with approved shade of Granite thickness not less than 25 mm thick and as per the sizes shown in the Drawing etc complete and as directed.(On the Facade areas). Granite shall be fixed with a groove of 6mm and to be filled with weather sealant recessed by 2mm and the granite joints at corners shall be chamfered as per Architectural requirements and granite shall be fixed in the M.S / RCC wall with SS brackets and SS anchor bolts. Projection upto 200 mm from the Main base structure either RCC / Masonry / steel. Granite shall be fixed in the RCC / Masonry / steel with SS brackets and SS anchor bolts. Granite basic cost of Rs.160/- per Sq.ft shall be considered subject to compliance of the above specification. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified and other load parameters specified in Technical specification. Refer Particular Specification item - 22.12, which shall form part of BOQ.

25

-

-

... More
Dry wall cladding with High pressure laminated panel Cladding: Providing and fixing the 8 mm thick High pressure laminated panel with approved Unique color with composition of cellulose fibrous cured phenol-formaldehyde resins for the core layers and melamine-formaldehyde resin for the surface with urethane-acrylic coating Exterior panel with suitable panel size as per drawing. System to be designed to with stand design wind pressure of 150kg/Sqm and other load parameters specified in the Technical specification. The panel shall be held in position by using the aluminium bracket, T - angle, L - angle with colored rivet at spacing not to exceed 450 mm on both direction and fixing the profile with suitable aluminium die-cast brackets. Refer Particular Specification item - 22.15, which shall form part of BOQ.

25

-

-

... More
Dry wall cladding with Clay tile: Designing, supplying and fixing of Clay tile of Hunter Douglas or Wienerberger make with suitable size and thickness not less than 28 mm as per manufacturer with approved color and pattern with composition of finest powdered clay and colour mixtures.  The Clay tile shall be fixed on the suitable farming system by using continuous aluminium anodized profiled section as per manufacturer with suitable size and spacing  to withstand the Structural design criteria specified in the technical specification by using necessary HDG brackets, SS 316 grade anchor bolts etc as per manufacturer specification. Cladding joints shall be sealed with Gasket / open groove system. The size of clay tile shall be as per architectural requirement and the suitable fixing system shall be designed in accordance with the size of clay tile proposed in the drawing. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified and other load parameters specified in Technical specification.Cladding the external surface to any surface, any profile and shape, horizontally, vertically, sloped, curved, circular etc by using Clay tile as given above. Jambs for glazing / windows & ventilators / doors and parapet copings are shall be considered with 2 mm thick aluminium PVDF finished sheet fixed with SS 316 grade screws / rivet. The aluminium sheets shall have overlap of 100 to 125 mm in plan with sealant at joints to make sure that no water leakage through jambs / coping joints. Rate shall include the cost of all materials 2 mm thick aluminium PVDF finish SS screws / rivets, weather sealant and necessary accessories etc as per the manufacturer profile. Rate shall include the cost of all materials like Clay tile with necessary framing system by using profiled aluminium sections, HDG brackets, SS anchors, weather sealant, 1.2 mm thick aluminium anodized flashing sheet at terrace & and all required levels and necessary accessories etc.Supplying and fixing of Clay tile cladding other than Jambs of glazing / windows & ventilators / doors and parapet copings. - Curved shape with Segmented Tile. (Not Bent Tile)

350

-

-

... More
Supplying and fixing 2 mm thick aluminium PVDF finished sheet as per the manufacturer profile for Jambs of glazing / windows & ventilators / doors and parapet copings other than Clay tile cladding.

75

-

-

... More
Associated Works

-

-

-

... More
Hardware for top hung window: Quote extra rate over & above the Curtain wall glazing / window item for designing, supplying and fixing of hardwares for top hung openable outward shutter having Heavy duty Multi point lock with required points based on the window panel size and handle with or without key with detachable handle of Model no 610 K / 670 of Alualpha make or equivalent of Kinlong make, SS friction hinges of Model no SPT 26, Corner Transmission Model no 9312, corner locking point model no 9313 and restrictor stay arm assembly model no SR 8 with release key of model no R 7437 of Securestyle (UK) make or equivalent of Kinlong make and as per particular specification. Rate shall exclude cost for supplying and fixing of glass and main frame, but include the cost of supplying and fixing of hardwares and sub frame for shutter. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified in Technical specification. Refer Particular Specification item - 22.01, which shall form part of BOQ.

35

-

-

... More
Insulation for Spandrel: Providing and fixing of Mineral wool slab - 50 Kg/cum - confirming to EN 13501-1/UL 723) and having 'K' value of 0.034 w/Mok - 50 mm thick - Thermal Rock of Roxul Rockwool Insulation India Pvt. Ltd make confirming to ASTM, C518, C1104, / IS. 3346) and laminated between factory pressed Black glass tissue and using 1.2mm thick Aluminium anodized tray on both sides with fold alround to a height of 25mm minimum to fix the stiffener flat and as thermal insulation to be fixed behind Spandrel area / ACP Cladding area as mentioned. All the edges between aluminium anodized tray and frame to be sealed with Non-Staining weather silicon sealant of approved make. System to be designed to with stand design wind pressure of 150Kg/Sqm confirming to IS 875 part 3 and other load parameters specified in Technical specification. Refer Particular Specification item - 22.01, which shall form part of BOQ.

25

-

-

... More
Providing and applying Cold Bituminous coating on the External wall behind Cladding area by using two coats of Multi-purpose anti-corrosive black water based cold bituminous of `Shalikote - T 32' of STP Ltd or Bitufix of Dr.Fixit make at the rate of application as specified by the manufacturers. Refer Particular Specification item - 22.13, which shall form part of BOQ.

375

-

-

... More
Quote rate for providing and fixing in position Hot rolled structural steel Members / Sections consists of MS joists, channels, angles, purlins, pipes, hollow tubes, runners, insert plates, flats etc. at all levels. Surface preparation of all MS members by Sand blasting to SA 21/2 grade and painted with anti corrosive, low VOC PU paint (metallic finish) with compatible primer to a minimum film thickness of 75 microns and 2 coats of low VOC PU paint of Akzonoble make and total dry film thickness 225 microns. (Only related to Facade works and no base frame or support structure included). Refer Particular Specification item - 22.14, which shall form part of BOQ.

6

-

-

... More
Providing and fixing Handrail of specilized Manufacturer of Dorma or Kinlong or Kich with stainless steel member for Balcony / Terrace at levels fabricated with 40 x 40 mm - 3 mm thick Square hollow tube or SS Plate 8mm thick - Twin plates as verticals with suitable height to support the glass as specified and spacing not more than 1050 mm. Top horizontal hand railing with S.S pipe of 50 mm dia - 3 mm thick and the top hand rail shall be fixed over the vertical member by using 6 mm thick SS Plate to profile as a connector between Horizontal railing and verticals with suitable size as per drawing and the vertical tubes/plates shall be fixed on the top or face of parapet by using suitable size of SS base plate with thickness not less than 8 mm and SS anchors (Min 2 Nos) as shown in the drawing. Rate shall include the cost for providing 900 mm high - 12.52 mm thick laminated glass having 6 mm thick as outer panel and 5 mm thick as inner panel with inter layer of 1.52 mm thick Sentry Glas of Dupont make. Both Outer pane and Inner pane shall be uncoated clear glass of Saint Gobain / Asahi make and shall be heat treated and heat soaked as shown in the drawing etc complete. All the exposed edges of laminated glass shall be covered with Clear PVC edge strip as a edge protection. The laminated glass shall be fixed in to the vertical member by using 20 mm square/circular pipe to support SS two way arm and articulated bolts of Kinlong / Dorma make or approved equivalent make as directed. Rate shall include necessary tools & Plants, supplying and fixing of glass, railing, articulated bolts and arm, SS cover plate, screws, 225 x 75 - 10 mm thick SS base plate & SS 316 grade anchors (Minimum 2 nos of M10 - 90 mm long) to receive the vertical member, welding with consumables & buffing charges etc. complete as directed. All Railing, 2 way arm, stud & articulated bolts etc shall be SS 316 grade - Mirror finish.

130

-

-

... More
FAÇADE ACCESS SYSTEM

-

-

-

... More
Design, supply, install and commission of Facade Access system with the help of specified equipment's and facilitate to reach any shape and profile of the desired area of cleaning required. The system shall be designed to with stand a minimum design wind pressure of 150 Kg/sqm, Dead and Live loads conforming to IS 875-Part 3 and Lateral forces as per IS 1893 (Latest Revision) and the system support at parapet wall as specified. Bidder shall be responsible to determine the maximum design wind pressure and lateral forces, moments, stresses etc. applicable for the system. Negative / suction pressures if determined as per IS 875 - part - 3 and Lateral forces as per code IS 1893 shall make additional allowances as described in the code for corner effects on the system. Quoted rate shall include the following, but not limited to:a) Designing the system, preparation of shop drawing for approval, supply, fabricate, erect as per approved drawing at all levels, elevation & heights including conducting necessary test according to the codes etc complete.b) In general, the system comprising of Permanent Motorized Trolley, Portable Aluminium Davit system with Standard arm to the required out reach to suspend Gondola / Cradle having Imported motors, wire ropes and winches.c) Supply and install Soffit / Face / Floor mounted brackets at a minimum spacing specified and at straight / curved portion. Extra bracket if any required at corners / projected area shall be provided. All brackets shall be hot dip galvanized steel with base Plates and all anchor bolt assemblies (Either double sleeve or Single sleeve wedge anchors as per site condition requirements) shall be SS 316 grade of Hilti / Fischer or approved equivalent make etc complete.d) Anchor the brackets with suitable dia of anchor bolts / Fasteners (Either double sleeve or Single sleeve wedge anchors of Hilti make as per site condition requirements) permanently on the RC wall, Soffit as specified in the approved shop drawing. e) Install the support system including required scaffolding, hoists, minor civil works and any other works related to the complete installation of the system as per specification and approved shop Drawing.f) Manufacture / fabrication, transport and handling, installation / fixing, testing, commissioning and Insurance.g) Obtain & submit certification of design by independent professional engineer / consultant along with final design and shop drawings. j) Quoted rate shall include for maintenance of the all systems as specified in the conditions of contract during the defects liability period.k) Quoted rate shall deemed to have the above stipulated provision and rate shall include the cost for applying bituminous coating on the RC surface at the bracket locations.

-

-

-

... More
Operating System

-

-

-

... More
Providing and fixing for complete system with Motorized Traverse Trolley (Permanent System) fixed on the parapet mounted combination bracket (Upper and Lower Brackets) and Hot rolled steel sections running on the bracket to move the trolley to the desired location and in accordance with the technical specification and drawing and in general the system shall include the following. - For Block A

-

-

-

... More
Hot dip galvanized Parapet mounted combination bracket (Upper and Lower Brackets) of suitable size and Long and to be fixed at a required spacing as per design with suitable dia & type of SS 316 grade anchor fasteners at specified locations including grouting the surface with all other accessories etc complete. Rate shall include the cost of Moisture resistance coating behind the base plate and all other accessories etc complete.

45

-

-

... More
Hot dip galvanized Hot rolled sections"I"Beam of 200 x 100 mm or suitable size (Size given is indicative and the bidder shall confirm the size of member based on structural requirements) and to be fixed on the Upper and Lower brackets with suitable dia & type of SS 316 grade bolts at specified locations including grouting the surface with all other accessories etc complete. (Note: Each Track shall be measured separately)

100

-

-

... More
Aluminium Motorized Retractable / Swivel & Telescopic traverse trolley (Permanent) and to be fixed on the Upper and Lower Beams to operate the system at specified locations with all other accessories etc complete. Out reach of the system shall be 2.10M (Each Trolley containing 2 Arm)

2

-

-

... More
Providing and fixing Aluminium Retractable Davit (Portable System) suitable for Roof / Parapet mounting with the required length/outreach and complete system to be fixed on the parapet or slab with combined single bracket to sustain both tensile, torsional and any other loads at the desired location and in accordance with the technical specification and drawing and in general the system shall include the following. - For Block B.

-

-

-

... More
Hot dip galvanized Roof / Parapet mounted combined brackets for support system (Upper and Lower Brackets for Roof / Parapet mounting Davit bracket) of suitable size and Long and to be fixed at a required spacing as per design with suitable dia & type of SS anchor fasteners at specified locations including grouting the surface with all other accessories etc complete.

110

-

-

... More
Providing and fixing Aluminium Retractable Davit (Portable System) suitable for Roof / Parapet mounting with the required length/outreach and to a out reach of 1600 mm and as per drawing including all accessories.

2

-

-

... More
Providing and fixing Eye bolts made out of Forged High Tensile Steel and heat treated after manufacturing process and finished with zinc plate coating. Eye bolt shall be designed to sustain a load of 300 to 400 kg and in general, the dimensions of bolt shall be 36 mm OD & 18 mm ID, threaded shank of M12, unthreaded shank of 16 mm with shank length 75 mm and fixing depth shall be 120 mm in 20mm dia hole with chemical infill. Eye bolt shall be designed smooth in such a way to avoid wear and tear of suspension shackles. Socket sleeve shall be specially knurled for obtaining proper grip and strength after installation. Eye bolts shall be fixed at required intervals and bolts are to be fixed only into structural concrete surface as per suit site condition, by using chemical anchoring (adhesive mortar) as per the requirement and cured for at least 120 minutes (at ambient temperature). All the bolts shall be tested at site for pull out load of 1000 kg after installation etc., all complete as directed by the Engineer-in-charge.

300

-

-

... More
Accessible System

-

-

-

... More
Providing and fixing of Cradle platform (Gondola) with complete system , as given below and in general the cradle made out Aluminium tubes with Frame work and in accordance with the technical specification and drawing. Gondola/ Cradle having Imported motors, wire ropes and winches of approved make. Standard- 2 Meter Cradle platform with all other accessories etc complete.

1

-

-

... More
Supplying of Bosun's chair and to be fitted with a seat attached to a powered climber unit. Rate shall include the cost of suspended rope, full body harness, rope, lanyards and other connecting equipment, ascenders, descanters, belay devices, backup devices and fall arresters etc complete.

1

-

-

... More
ELECTRICAL

-

-

-

... More
SECTION- A: HT WORKS

-

-

-

... More
HT CABLE: Supply, laying, testing and commissioning of 3core 300 sqmm 11 kV, HT XLPE aluminium conductor individual core screened, flat steel strip armoured, PVC sheathed cable in existing hume pipes, trenches etc

150

-

-

... More
Supply, Erection, Testing and Commissioning of 11KV, 500MVA, not less than 36 kA, 630Amps extensible outdoor type RMU with 2 Incomer LBSs & 2 Outgoing VCBs along with with copper busbars, Metering & protection and necessary accessories as per KSEB/local electrical authorities requirements and as per technical specification enclosed etc,.(12 kV, SF6 Ring Main Unit with 2 Load break switch +2 VCB with fixed type FBX-E /12-20/ CT2CT2/Outdoor – Motorised + Battery Charger)

1

-

-

... More
HT TERMINATIONS:Supply, termination, testing and commissioning of INDOOR type termination kit and accessories suitable for 11KV, 3 core 300 Sqmm aluminium conductor, XLPE cable. ( 1set = RYB phase)

2

-

-

... More
SECTION – B : MAIN POWER CONTROL CENTRE , LT SWITCH BOARDS AND LT- RAISING MAIN

-

-

-

... More
For all Panel boards in section-B, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same. All the meter should have RS 485 modbus output for BMS integration i) Incomerand outgoing breaker shall be shall be O/L,SC,& EF realse and also refer detailed specification & drawing enclosed ii) All MCCB have microprocessor based. iii) All breakers should have minimum kA rating as mentioned in SLD. iv) All live parts should be shrouded by FRP transparent polycarbonate sheet of 2mm thick v)Current density of aluminium busbar - 0.8A /Sq. mm. (Main and branch), Copper bus bar - 1.2 A/ Sq.mm vi) All breaker should have LOTO arrangement

-

-

-

... More
Main Switch Board (MSB-3&4) LOC: GND Electrical roomSupply, erection, testing and commissioning of cubicle type floor Indoor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification and SLD enclosed. Incomer 1 No. 630 Amps 4 pole not less than 35KA µP based MCCB EO with over load, ,short circuit & Earth fault release , door interlock and and all other required necessary accessories. Instruments Panel (for Incomer)Incomers shall be having with Neccessary CTs, Digital Load Manager (LM) (consist of A,V, Kw, kWH, kVA, TOD, PF, Hz (F)), surge protection device/TVSS, RYB & ON, OFF, TRIP indication lamps and MCB etc. for the Incomers and as per schematic layout.BUS BAR630 Amps TPN,35KA Aluminium busbars OUTGOINGS :400A TP&N not less than 35 kA, micro processor based,EO MCCB – 2 Nos. 250A TP&N not less than 35 kA, micro processor based,EO MCCB – 1 Nos. 160A TP&N not less than 35 kA micro processor based,EO MCCB – 2 Nos. Note : All the Outgoing feeders shall be having with Neccessary CTs, control MCBs, Digital Multifuntion Meter (MFM with RS-485 port.) (Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.). ON, OFF, TRIP indication lamps etc. for the out goings as per schematic layout. The rate shall inclusive of necessary CTs, Fuse, Switch control, Front operating handles etc., All switch boards shall be fabricated as per the detailed specification enclosed. Suitable size outgoing cable chamber and extra busbars should be provided for connecting the number of outgoing cables as per the schematic drawing.The board shall be fabricated for future extension of the panel board

2

-

-

... More
Supply, Installation, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification and SLD enclosed SSB-1Incoming160A 25KA, 4P MCCB with all connected accessories – 2Nos. as incomers with Electrical interlocking arrangements.Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoing40 A TPN 16 KA MCCB- 1 Nos. 80 A TPN 25KA MCCB- 2Nos. 100A TPN 25 KA MCCB- 2 Nos. With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and On/Off / Trip indication lamp with all other necessary accessories etc.,for the outgoings as per schematic layout. 160 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Supply, Installation, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification and SLD enclosed UTILITY PANEL Incoming 200A 25KA, 4P MCCB with all connected accessories – 3Nos. as incomers with Electrical interlocking arrangements.Instruments compartmentMulti function meter with RS-485 port (Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoing 32 A TPN 25KA MCCB- 1No. 40 A TPN 25KA MCCB- 1No.80 A TPN 25KA MCCB- 1No. 125 A TPN 25KA MCCB- 2Nos. With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and On/Off / Trip indication lamp with all other necessary accessories etc.,for the outgoings as per schematic layout. 200Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Supply, Installation, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification and SLD enclosed.HVAC PANEL - INDOOR (not less than IP55)Incoming 400A 4P 35 KA ,M/P MCCB with all connected accessories – 2Nos. as incomer with Electrical interlocking arrangementsInstruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.),Metering CTs, R,Y,B and On/Off/Trip indication lamp with MCB etc., Outgoing 32A TPN 16KA MCCB - 8 Nos. 40A TPN 16KA MCCB - 6 Nos. 100A TPN 25KA MCCB - 2 Nos. With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and On/Off / Trip indication lamp with all other necessary accessories etc.,for the out goings as per schematic layout. 400Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Supply, Installation, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification and SLD enclosed COMMON LIGHTING PANEL Incoming 80A,4P,ATS 1No.80A TPN 25KA MCCB - 1No.Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoing16A TPN MCB – 7 No. as incomer.32A TPN MCB – 1 No. as incomer.With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and On/Off / Trip indication lamp with all other necessary accessories etc.for the out goings as per schematic layout. 80 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed. LIFT PANEL INCOMER1 No:125A 4P 25KA MCCB Each incomers shall have 1 set - Multi Function meter (Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.),1 set - LED type RYB,ON,OFF,TRIP indication lamps & CT OUTGOING 63A 16KA TPN MCCB - 4Nos,25A 16KA TPN MCCB - 1No.With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and On/Off / Trip indication lamp with all other necessary accessories etc..for the outgoings as per schematic layout. 125 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed.PSB - 1 (LOWER GND FLOOR)Incoming1 No: 125A 4P ATS 1No:125A TPN 25KA MCCB Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoings:3Nos - 20A 10KA TPN MCB3Nos - 32A 10KA TPN MCB1Nos - 40A 10KA TPN MCB1Nos - 63A 10KA TPN MCBWith necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and On/Off / Trip indication lamp mcb control with all other necessary accessories etc,.as per schematic layout. 125 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed.PSB - 2 (GND FLOOR) Incoming1 No: 125A 4P ATS 1No:125A TPN 25KA MCCB Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoings:2Nos - 20A 10KA TPN MCB7Nos - 32A 10KA TPN MCB3Nos - 40A 10KA TPN MCB With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and mcb control with all other necessary accessories etc,as per schematic layout. 125 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed.PSB -3 (FF FLOOR)Incoming1 No: 125A 4P ATS 1No:125A TPN 25KA MCCB Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoings:2Nos - 20A 10KA TPN MCB4Nos - 32A 10KA TPN MCB2Nos - 40A 10KA TPN MCBWith necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and mcb control with all other necessary accessories etc,as per schematic layout. 125 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed.PSB -4 (SF FLOOR) Incoming1 No: 125A 4P ATS 1No:125A TPN 25KA MCCB Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoings:2Nos - 16A 10KA TPN MCB2Nos - 20A 10KA TPN MCB4Nos - 32A 10KA TPN MCBWith necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and mcb control with all other necessary accessories etc,as per schematic layout. 125 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed.PSB -Third FLOOR Incoming1 No: 125A 4P ATS 1No:125A TPN 25KA MCCB Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoings:2Nos - 16A 10KA TPN MCB3Nos - 20A 10KA TPN MCB5Nos - 32A 10KA TPN MCBWith necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and mcb control with all other necessary accessories etc,as per schematic layout. 125 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed. LSB - 1,2,3 (LOWER GROUND/GROUND/FFLOOR's) Incoming1 No: 40A 4P ATS 1 No:40A TPN 16KA MCCB Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoings:7Nos - 25A 10KA TPN MCBWith necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and mcb control with all other necessary accessories etc,as per schematic layout. 40 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

3

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed. LSB - 4&5 (Second/Third Floors)Incoming1 No: 40A 4P ATS 1No:40A TPN 16KA MCCB Instruments compartmentMulti function meter(Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., Outgoings:5Nos - 16A 10KA TPN MCBWith necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and mcb control with all other necessary accessories etc,as per schematic layout. 40 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

2

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification & SLD enclosed. UPS SB-1 FIRST FLOORIncoming40 A TP+2N 16KA MCCB - 1No.Each incomers shall have 1 set - Multi Function meter (Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.),1 set - LED type RYB,ON,OFF,TRIP indication lamps. & CTOutgoings:25A, 10KA TP+2N MCB - 5 Nos With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock,ON,OFF,TRIP indication lamps and mcb control with all other necessary accessories etc, as per schematic layout. 40 Amps TP+2N Aluminium busbars:- All the neutral busbars shall have Double the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed. UPS SB -2 SECOND FLOORIncoming80A TP+2N 25KA MCCB -1 No.Each incomers shall have 1 set - Multi Function meter (Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.),1 set - LED type RYB,ON,OFF,TRIP indication lamps. & CTOutgoings:25A 10KA TP + 2N MCCB - 5 Nos With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock,ON,OFF,TRIP indication and mcb control with all other necessary accessories etc,as per schematic layout. 80 Amps TP+2N Aluminium busbars:- All the neutral busbars shall have Double the capacity of phase busbars.

1

-

-

... More
Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed. UPS SB -3 THIRD FLOORIncoming100A TP+2N 25KA MCCB - 1No.Each incomers shall have 1 set - Multi Function meter (Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.),1 set - LED type RYB,ON,OFF,TRIP indication lamps. & CTOutgoings:25A 10KA TP + 2N MCB - 6 Nos With necessary aluminium busbars, interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock,ON,OFF,TRIP indication and mcb control with all other necessary accessories etc, as per schematic layout. 100 Amps TP+2N Aluminium busbars:- All the neutral busbars shall have Double the capacity of phase busbars.

1

-

-

... More
Supply, Installation, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification and SLD enclosed SOLAR LT PANEL- LOC: TERRACE FLOORIncoming100A TPN 25KA MCCB - 1No.Instruments compartmentNET METERING UNIT( METER WILL BE TESTED BY KSEB), Metering.CTs, R,Y,B and On/Off / Trip indication lamp with MCB etc., With necessary interconnections, neutral link, suitable aluminium busbar for cable termination, door interlock and all other necessary accessories etc, All the RS-485 port of the meter connected together through single cable and terminated with terminal block in the common cable chamber for easy termination. The rate inclusive of MCCB Feeder of relevant rating for SPV System 1 No. to be provided by Electrical Vendor at Solar LT Panel with net metering ( Meter Tested by KSEB & supplied by Electrical vendor ) located at Terrace Floor. However, both the vendor should be co-ordinated ( Solar & Electrical ) for the Systems.100 Amps TPN Aluminium busbars:- All the neutral busbars shall have half the capacity of phase busbars.

1

-

-

... More
RAISING MAIN

-

-

-

... More
Sandwich type Rising Main (RM-1&2) 250A Aluminium conductor

-

-

-

... More
Supply, Installation, Testing and Commissioning of Indoor : Not less then 250A,25kA ,TPN, Aluminium condutor sandwich type Rising Mains with Plug-in Point ,Vertical Spring Hanger/Fix hanger,End Cover,External aluminium earthing, Plug in Point at every 500mm, Fire Barriers at every Floor Crossing Including flexible joints suitable for above said sandwich type TPN Aluminium rising main at end terminals including all accessories.(RYBN=1 set), Mounting Brackets (Recommended 1No. per 1.5 Mtrs) and tool kit. The product shall be based on Temp. rise & not on current density and as per techical specification and drawing.

42

-

-

... More
End Feed Unit with Not less then 250A,35kA,TPN MCCB with Multi Function meter (Having the parameters of Ammeter,Voltmeter and KWH meter,kW,KVA,Hz,PF.), & 1 set - LED type RYB,ON,OFF,TRIP indication lamps & CT with all necessary accessories. The inclusive Flexible , Mounting Brackets, etc

2

-

-

... More
40A Tap Off Box with 16kA, TPN MCCB

12

-

-

... More
125A Tap Off Box with 25 kA,TPN MCCB

12

-

-

... More
SECTION – C : DISTRIBUTION BOARDS (For all distribution boards in Section-B, the rate includes necessary connected civil works.)

-

-

-

... More
HVAC DB - ( customized Outdoor DB) Supply, fixing, testing and commissioning of Outdoor polycarbonate double door type IP65 comprising of the following : 100 A TPN MCCB 25 KA – 1No. as incomer.16 A 4P MCB – 7 Nos. as outgoings. 16 A DP MCB – 5 Nos. as outgoings. With necessary tinned copper busbars, interconnections, earth bus, neutral bus. The board shall be powder coated type fixed with concealed system in wall/ fixed in column. The rate shall include necessary connected civil works like chipping, rough plastering etc.

1

-

-

... More
12 WAY SPN DB :LDB-1 GND-1no, LDB-2GF -1no, LDB-1 FF-1 No Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :25A, 4P, 30mA RCBO – 1 No. as incomer (Type-Compact) .Outgoing consist of 8 nos. 6/10A SP MCB (C-Curve) with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

6

-

-

... More
4 WAY SEVEN SEG. DB :LDB ( LDB: LGF-1no, GF-1no,FF-1no)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :25A TPN MCB – 1 No. as incomer.25A DP RCBO C-Curve 30mA – 3 Nos. as outgoings.Each Phase 16A DP RCBO outgoing consist of 4 nos. 6/10A SP MCB (C-Curve) with necessary phase segregation as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

6

-

-

... More
12 WAY SPN DB :LDB SF-2nos,TF-3nos)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :16A, 4P,30mA RCBO – 1 No. as incomer (Type-Compact) .Outgoing consist of 8 nos. 6/10A SP MCB (C-Curve) with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

5

-

-

... More
12 WAY SPN DB :LDB SF-1no,TF-1no)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :16A, 4P,30mA RCBO – 1 No. as incomer (Type-Compact) .16A, DP MCB – 2 No. as outgoing.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

2

-

-

... More
4 WAY SEVEN SEG.DB :(Common DB -LG-1no.,GND-1no.,FF-1no.,SF-1no.,TF-1no.)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :16A TPN MCB – 1 No. as incomer.16A DP RCBO C-Curve 30mA – 3 Nos. as outgoings.Each Phase 16A DP RCBO outgoing consist of 4 nos. 6/10A SP MCB (C-Curve) in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

5

-

-

... More
12 WAY SPN HVACDB : (FF-1no.)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :10A,4P,30mA RCBO – 1 No. as incomer.Outgoing consist of 8 nos. 10A SP MCB (C-Curve) with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

1

-

-

... More
4 WAY SEVEN SEG. AC DB -1 NOS (LG-1No.,GND-1no,SF-1No,TF-1No)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :20 A TPN MCB – 1 No. as incomer.20 A DP RCBO C-Curve 30mA – 3 Nos. as outgoings.Each 20 A DP RCBO outgoing consist of 4nos. 10 A SP MCB in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

6

-

-

... More
12 WAY SPN DB :PDB -(LG-1No,GND-1 No,FF-2 Nos,SF-2 Nos.,TF-3Nos).Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :32A,4P, 30mA RCBO – 1 No. as incomer (Type-Compact).Outgoing consist of 8 nos. 16/20A SP MCB (C-Curve)with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

9

-

-

... More
4 WAY SEVEN SEG.PDB -( LG-1No,GND-1No.,FF-1No,SF-1No,TF-1No)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB as per SLD comprising of the following :32 A TPN MCB – 1 No. as incomer.32 A DP RCBO C-Curve 30mA – 3 Nos. as outgoings.Each 32 A DP RCBO outgoing consist of 4 nos. 16/20 A SP MCB (C-Curve) in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

7

-

-

... More
4 WAY SEVEN SEG.PDB -( Gnd-2No.)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB as per SLD comprising of the following :40 A TPN MCB – 1 No. as incomer.40 A DP RCBO C-Curve 100mA – 3 Nos. as outgoings.Each 40 A DP RCBO outgoing consist of 4 nos. 16/20 A SP MCB (C-Curve) in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

2

-

-

... More
4 WAY SEVEN SEG.PDB -( FF-1no.)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB as per SLD comprising of the following :40 A TPN MCB – 1 No. as incomer.40 A DP RCBO C-Curve 30mA – 3 Nos. as outgoings.Each 40 A DP RCBO outgoing consist of 4 nos. 16/20 A SP MCB (C-Curve) in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

1

-

-

... More
6 WAY SEVEN SEG. DB :PDB ( LG-1No.)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB as per SLD comprising of the following :63A TPN MCB – 1 No. as incomer.63A DP RCBO C-Curve 30mA – 3 Nos. as outgoings.Each R &Y Phase 63A DP RCBO outgoing consist of 6 nos. 16A /20A SP MCB (C-Curve) and B-Phase to Inverter Emergency Lighting in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

1

-

-

... More
4 WAY SEVEN SEG. UPS DB (FF-2Nos,SF-1Nos, TF-2Nos)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :25 A TP+2N MCB – 1 No. as incomer.25 A SP+2N RCBO 30mA (hi/hpi/si) – 3 Nos. as outgoings.Each 25 A SP+2N RCBO outgoing consist of 4nos. 10 A SP MCB (D-Curve) in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

5

-

-

... More
6 WAY SEVEN SEG. UPS DB (SF-1Nos.TF-1No)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :25 A TP+2N MCB – 1 No. as incomer.25 A SP+2N RCBO 30mA (hi/hpi/si) – 3 Nos. as outgoings.Each 25 A SP+2N RCBO outgoing consist of 6nos. 10 A SP MCB (D-Curve) in a separate compartment with necessary accessories as required.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

2

-

-

... More
4WAY (Vertical TPN) MCCB DB (External lighting GND )Supply, fixing, testing and commissioning of the double door type VTPN 4 way MCCB DB comprising of the following :32 A TPN MCCB 16 KA – 1No. Incomer10A TP MCB – 4 Nos. as outgoings.With necessary tinned copper busbars, interconnections, earth bus, neutral bus. The board shall be powder coated type fixed with concealed system in wall/ fixed in column. The rate shall include necessary connected civil works like chipping, rough plastering etc.

1

-

-

... More
12 WAY SPN DB :LDB SF-1no,TF-1no)Supply, fixing, testing and commissioning of the double door type compartmental MCB DB comprising of the following :16A, 4P,30mA RCBO – 1 No. as incomer (Type-Compact) .16A, DP MCB – 2 No. as outgoing.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases. The board shall be powder coated type fixed with concealed system in wall/fixed in column. The rate shall include necessary connected civil works like chipping and plastering etc.

2

-

-

... More
Supply,Erection, Testing and Commosioning of the following MCCBs / MCBs of type-II coordination etc.in manufacturer's sheet steel enclosures for MCBs, and suitable 16SWG enclosure for MCCBs with provision for cable entry boxes, IP 20/65 Protection, fixed on the wall including all interconnections and accessories etc,.

-

-

-

... More
16A 4P RCBO 30mA with poly carbanate Enclosure -OUTDOOR

9

-

-

... More
32A 4P RCBO 30mA with poly carbanate Enclosure -OUTDOOR

7

-

-

... More
40A 4P RCBO 30mA with poly carbanate Enclosure -OUTDOOR

6

-

-

... More
6 /10/16/20A DP MCB with Sheet Steel Enclosure

40

-

-

... More
63A 16KA FP RCBO with 100 mA Sheet Steel Enclosure

3

-

-

... More
40A 16KA 4P MCCB with Sheet Steel Enclosure

2

-

-

... More
40A 16KA TP+2N MCCB with Sheet Steel Enclosure

2

-

-

... More
80A 25KA TP+2N MCCB with Sheet Steel Enclosure

1

-

-

... More
80A 4P MCCB- 25KA with Sheet Steel Enclosure

1

-

-

... More
100A,4P MCCB- 25KA with Sheet Steel Enclosure

1

-

-

... More
100A 25KA TP+2N MCCB with Sheet Steel Enclosure

1

-

-

... More
TOD type Energy Meter with indicating lamps in Sheet Steel Enclosure

1

-

-

... More
Design, supply, erection testing and commissioning of following starters with Isolator sheet steel enclosure with necessary interconnections, Isolator, single phase preventor, overload relay, transformer coil, time delay relay, ON/OFF indication lamp etc., complete.

-

-

-

... More
DOL upto 1.5 HP for jet fans & toilet exhaust fans

1

-

-

... More
DOL upto 7.5 HP

1

-

-

... More
Star delta upto 10HP

1

-

-

... More
Design, supply, erection testing and commissioning of following ON/OFF Push buttons with sheet steel enclosure with necessary interconnections, ON/OFF indication lamp etc., complete.

-

-

-

... More
upto 5.5 KW for pressurisations fans

5

-

-

... More
SECTION – D : WIRING AND CONNECTED ACCESSORIES

-

-

-

... More
For all items in section-D, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same.

-

-

-

... More
Wiring to the circuit mains using 3 Runs of 2.5sqmm multi strand PVC insulated copper conductor (FRLS-ZH) in a suitable size PVC conduit etc.(Lighting and HVAC)

7500

-

-

... More
Wiring to the light points/ 6A plug point using 3R of 1.5 sq mm multi strand PVC insulated copper conductor (FRLS-ZH) in suitable size PVC pipe in open system in above false ceiling and concealed system in below false ceiling. The rate should inclusive of supply and fixing of 6A modular type switch in a suitable size modular box in concealed system including wiring upto the light fittings in GI flexible hose.Point wiring:

-

-

-

... More
1 Light controlled by 1 switch

110

-

-

... More
2 light controlled by 1 switch / (1 set = 2 lights)

50

-

-

... More
3 light controlled by 1 switch / (1 set = 3 lights)

5

-

-

... More
4 light controlled by 1 switch / (1 set = 4 lights)

5

-

-

... More
5 light controlled by 1 switch / (1 set = 5 lights)

5

-

-

... More
6 light controlled by 1 switch / (1 set = 6 lights)

10

-

-

... More
7 light controlled by 1 switch / (1 set = 7 lights)

5

-

-

... More
10 light controlled by 1 switch / (1 set = 10 lights)

4

-

-

... More
Staircase light points (Dual control)

18

-

-

... More
6A socket controlled by 1 switch

5

-

-

... More
Direct DB control: (Light control by direct ) Circuit main using 3R of 2.5 sq mm multi strand PVC insulated copper conductor (FRLS-ZH) in suitable size PVC pipe in open system in above false ceiling and concealed system in below false ceiling with all accessories like bends,elbows,junction boxes, clamps,GI flexible hose etc.,

350

-

-

... More
Wiring to the circuit mains using 3 Runs of 4sqmm multi strand PVC insulated copper conductor (FRLS-ZH) in a suitable size PVC conduit etc.(Power circuits)

4000

-

-

... More
Supply, fixing, testing and commissioning of 1No.6A modular universal socket and switch combination in a suitable size modular box in recessed system.(6A modular socket controlled by 1 no. 6A switch)

30

-

-

... More
Supply, fixing, testing and commissioning of 1 Nos. 16A universal socket for UPS/ Raw Power supply and switch combination in a suitable size modular box in recessed system. (1 Nos. 16A socket controlled by 1 no. 16A Switch)

10

-

-

... More
Supply, fixing, testing and commissioning of 1No. 6/16A modular universal socket for Raw Power/UPS supply and switch combination in a suitable size modular box in recessed system. (6/16A socket controlled by 1 no. 16A Switch)

32

-

-

... More
Supply, fixing, testing and commissioning of 1No. 6/16A modular socket for AC supply FOR CEILING/WALL SUSPENDED UNITS and switch combination in a suitable size modular box in recessed system. (6/16A socket controlled by 1 no. 16A Switch)

35

-

-

... More
Supply, fixing, testing and commissioning of 3 Nos. 6A universal socket for UPS Power supply and switch combination in a suitable size modular box in recessed system. (3 Nos. 6A socket controlled by 1 no. 16A Switch)

5

-

-

... More
Supply & Installation of non-metallic industrial receptacle mounted in Polycarbonate enclosure, 16A, 3 Pin socket and 16A DP MCB suitable for connecting 3C x 4 sq.mm, Cu. pvc insulated armoured cable with necessary earthing etc.,

5

-

-

... More
Supply & Installation of non-metallic industrial receptacle mounted in Polycarbonate enclosure, 32A, 3 Pin socket and 32 A DP MCB suitable for connecting 3C x 4 sq.mm, Cu. pvc insulated armoured cable with necessary earthing etc.,

8

-

-

... More
Supply & Installation of non-metallic industrial receptacle mounted in Polycarbonate enclosure, 40A, 3 Pin socket and 40 A DP MCB suitable for connecting 3C x 4 sq.mm, Cu. pvc insulated armoured cable with necessary earthing etc.,

6

-

-

... More
Supply and laying of following size PVC/MS conduits in floor / wall /ceiling etc. including necessary bends,elbow,etc, in concealed system below the false ceiling on wall/floor and open system on above false ceiling.(for Telephone/Data cabling etc.) The rate shall includes minor civil works such as chipping, plastering and to make good finished surface to match with the original surface.

-

-

-

... More
20mm dia MS conduit.

100

-

-

... More
25mm dia MS Conduit

200

-

-

... More
SECTION – E : CABLES AND TERMINATION, For all items in section-E, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same. Supply and Laying of following size PVC (FRLS) /XLPE insulated outer sheathed (1100 V grade) copper/aluminium armored & un armored conductor cable partly laid in existing cable tray and partly laid in wall/ ceiling with suitable individual clamps at every 1 mtr interval . Cable tray will be measured and paid separately. Cable Tags to be provided at every 50mtr interval and at either side of the bends.Only for Lighting cables cable tie will be permitted other cables clamps to be provided

-

-

-

... More
3.5C 400 Sq.mm XLPE aluminium armoured Cable

10

-

-

... More
3.5C 300 Sq.mm XLPE aluminium armoured Cable

1200

-

-

... More
3.5C 240 Sq.mm XLPE aluminium armoured Cable

15

-

-

... More
3.5C 185 Sq.mm XLPE aluminium armoured Cable

300

-

-

... More
3.5C 150 Sq.mm XLPE aluminium armoured Cable

9

-

-

... More
3.5C 120 Sq.mm XLPE aluminium armoured Cable

11

-

-

... More
3.5C 95 Sq.mm XLPE aluminium armoured Cable

50

-

-

... More
3.5C 70 Sq.mm XLPE aluminium armoured Cable

150

-

-

... More
3.5C 50 Sq.mm XLPE aluminium armoured Cable

100

-

-

... More
4 C 35 Sq.mm XLPE aluminium armoured Cable

300

-

-

... More
4 Core 25 Sq.mm XLPE aluminium armoured Cable

800

-

-

... More
4 Core 16 Sq.mm XLPE aluminium armoured Cable

1600

-

-

... More
4 Core 10 Sq.mm XLPE aluminium armoured Cable

3000

-

-

... More
4 Core 6 Sq.mm PVC multistrand Aluminium armoured Cable

750

-

-

... More
4 Core 6 Sq.mm PVC multistrand Copper armoured Cable

50

-

-

... More
4 Core 4 Sq.mm PVC multistrand Copper armoured Cable

15

-

-

... More
4 Core 1.5 Sq.mm PVC multistrand Copper armoured Cable

12

-

-

... More
3 Core 6 Sq.mm PVC multistrand Copper armoured Cable

18

-

-

... More
3 Core 4 Sq.mm PVC multistrand Copper armoured Cable

300

-

-

... More
3 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

25

-

-

... More
2 Core 1.5 Sq.mm PVC multistrand Copper armoured Cable

10

-

-

... More
12 Core 1.5 Sq.mm PVC multistrand Copper armoured Cable

9

-

-

... More
12 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

6

-

-

... More
16 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

11

-

-

... More
24 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

12

-

-

... More
1Core 185 Sq.mm PVC Copper unarmoured Cable

18

-

-

... More
1Core 25 Sq.mm PVC Copper unarmoured Cable

130

-

-

... More
1Core 50 Sq.mm PVC Copper unarmoured Cable

15

-

-

... More
1Core 6 Sq.mm PVC Copper unarmoured Cable

1700

-

-

... More
1 Core 16 Sq.mm PVC Copper Unarmoured Cable

450

-

-

... More
1 Core 10 Sq.mm PVCmultistrand Copper Unarmoured Cable

200

-

-

... More
Screened communciation cable

11

-

-

... More
4 Core 6Sq.mm XLPE aluminium armoured Cable

13

-

-

... More
Supply, Fixing of Termination kit(Glands & lugs) of the following size cables with suitable double compression glands with suitable crimping socket. The rate shall be inclusive of Gland Earthing Plate Prefabricated as per Gland Size with provision for connecting Cu.SWG and Cable Tags should be engraved type for all I/C,O.G& lighting Circuits (copper sockets for copper cables and Alu. Sockets for alum. Cable)

-

-

-

... More
3.5C 400 Sq.mm XLPE aluminium armoured Cable

6

-

-

... More
3.5C 300 Sq.mm XLPE aluminium armoured Cable

12

-

-

... More
3.5C 240 Sq.mm XLPE aluminium armoured Cable

6

-

-

... More
3.5C 185 Sq.mm XLPE aluminium armoured Cable

8

-

-

... More
3.5C 150 Sq.mm XLPE aluminium armoured Cable

6

-

-

... More
3.5C 120 Sq.mm XLPE aluminium armoured Cable

6

-

-

... More
3.5C 95 Sq.mm XLPE aluminium armoured Cable

2

-

-

... More
3.5C 70 Sq.mm XLPE aluminium armoured Cable

8

-

-

... More
3.5C 50 Sq.mm XLPE aluminium armoured Cable

2

-

-

... More
4 C 35 Sq.mm XLPE aluminium armoured Cable

24

-

-

... More
4 Core 25 Sq.mm XLPE aluminium armoured Cable

24

-

-

... More
4 Core 16 Sq.mm XLPE aluminium armoured Cable

94

-

-

... More
4 Core 10 Sq.mm XLPE aluminium armoured Cable

172

-

-

... More
4 Core 6 Sq.mm PVC multistrand Aluminium armoured Cable

36

-

-

... More
4 Core 6 Sq.mm PVC multistrand Copper armoured Cable

4

-

-

... More
4 Core 4 Sq.mm PVC multistrand Copper armoured Cable

4

-

-

... More
4 Core 1.5 Sq.mm PVC multistrand Copper armoured Cable

4

-

-

... More
3 Core 6 Sq.mm PVC multistrand Copper armoured Cable

4

-

-

... More
3 Core 4 Sq.mm PVC multistrand Copper armoured Cable

10

-

-

... More
3 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

6

-

-

... More
2 Core 1.5 Sq.mm PVC multistrand Copper armoured Cable

6

-

-

... More
12 Core 1.5 Sq.mm PVC multistrand Copper armoured Cable

6

-

-

... More
12 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

4

-

-

... More
16 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

4

-

-

... More
24 Core 2.5 Sq.mm PVC multistrand Copper armoured Cable

4

-

-

... More
1Core 185 Sq.mm PVC Copper unarmoured Cable

4

-

-

... More
1Core 25 Sq.mm PVC Copper unarmoured Cable

10

-

-

... More
1Core 50 Sq.mm PVC Copper unarmoured Cable

4

-

-

... More
1Core 6 Sq.mm PVC Copper unarmoured Cable

90

-

-

... More
1 Core 16 Sq.mm PVC Copper Unarmoured Cable

28

-

-

... More
1 Core 10 Sq.mm PVCmultistrand Copper Unarmoured Cable

12

-

-

... More
Screened communciation cable

4

-

-

... More
4 Core 6Sq.mm XLPE aluminium armoured Cable

4

-

-

... More
SECTION – F : EARTHING SYSTEM, MS ITEMS, For all items in section-F, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same.

-

-

-

... More
Supply and installation of earth pipe electrode as per IS 3043 complete with 3000mm long with 100mm dia, 13mm thick, 'B' class C.I. pipe earth electrode with watering funnel and 50 x 10mm GI Strip with 10mm holes for connecting to Grid. Funnel should be Detachable type connection with Main pipe should be threaded. Including construction masonry work and heavy duty CI cover for earth stations.The cover shall be to withstand to suit heavy vehicle movements..The chamber size shall be 450 x 450 mm with C.I. Cover plate. The identification number shall be provided both inside and outside. The earth pit shall be Bore earthing/Compressed Air Breaking and weather coated paints inside and outside with Name Plate in Polycarbonate. The rate inclusive of excavation of hard rock and back filling with alternate layer of salt/Charcoal/Betonite, clay/red sand, ramming and compacting the soil, etc., as required full depth ( For LT-Panel-3 )

3

-

-

... More
Design, supply, erection of “ASHLOK” safe earthing electrode Type-19 (Special), burried in ground, The chamber should be provided with 600mm x 600mm Heavy duty CI Chequered Plate cover with hinge and Stainless steel bolt nuts. The Cover should be painted at site with Black and then Green colour.(UPS-8,LIFT-3,SERVER-4,SPARE-2 )

17

-

-

... More
Supply, installation, testing and commissioning of earth electrode as per IS 3043 complete with 3 mtr long with 40mm dia 'B' class G.I. pipe and Cast iron plate of size 600 mm x600 mm x12 mm or 1200mmx1200mmx6mm including 2 runs of 40 x 10 mm CU. flat upto test link from plate earth electrode, watering funnel and necessary SS bolt, nut and double washer.Including construction masonry work and heavy duty CI cover for earth stations.The cover shall be to withstand to suit heavy vehicle movements..The chamber size shall be 450 x 450 mm with C.I. Cover plate. The identification number shall be provided both inside and outside. The plate electrode shall be filled with alternate layer of salt and charcoal as required full depth. The Cover shall be heavy duty to suit heavy vehicle movements.

2

-

-

... More
Supply, installation, testing and commissioning of earth electrode as per IS 3043 complete with GI pipe 3 mtr long with 40mm dia 'B' class watering funnel and necessary SS bolt, nut and double washer. Including 750mm x 750mm x 3mtr long excavationIncluding construction masonry work and heavy duty CI cover for earth stations.The cover shall be to withstand to suit heavy vehicle movements..The chamber size shall be 450 x 450 mm with C.I. Cover plate. The identification number shall be provided both inside and outside.. The plate electrode shall be filled with alternate layer of salt and charcoal as required full depth. The Cover shall be heavy duty to suit heavy vehicle movements.

2

-

-

... More
Supply, laying of 8 SWG copper wire

600

-

-

... More
Supply and laying of 14 gauge bare copper wire for Gland earthing with copper tap

200

-

-

... More
Supply and laying of 50 x 6 mm G.I flat for Earth grid, Panel Body . The joint shall be provided with welding. The earth grid shall be buried at 600mm depth from finished ground level in the all around the building. The rate inclusive of excavation of hard rock/soil up to 600mm and back filling with sand soil, ramming and compacting the soil, etc., as required.

80

-

-

... More
Supply and laying of 25 x 3 mm G.I flat for eathing. The joint shall be provided with welding. The earthing should be laid all over the tray/above ground level in both sides.(Tray Earth)

1100

-

-

... More
Supply and laying of 25 x 6 mm G.I flat for eathing. The joint shall be provided with welding. The earthing should be laid all over the tray/above ground level in both sides.(Panel Earth)

500

-

-

... More
Supply, Fixing of the following size Copper flat earth Station with 2 Nos DMC supporting Insulator clamp with predrilled machine made holes of 12mm & 6 mm dia at 25mm intervals for fixing earth flat including SS Bolts, Nuts & Washers complete as required. (2Nos DMC supporting insulators shall be used for 400mm distance) (Electrical,Hub room)

-

-

-

... More
600 x 25 x 6mm thick GI earth flat

2

-

-

... More
600 x 25 x 3mm thick GI earth flat

2

-

-

... More
450 x 25 x 6mm thick GI earth flat

5

-

-

... More
Cutting, and fixing of 8 mm thick chequered plate with required MS angles.

10

-

-

... More
Supply and Installation of MS flat / angle iron supports for various purpose if required with various sizes including cutting,welding,grinding,fixing accessories and one coat of primer & two coats of enamel paints, minor civil works etc. as required.(Note: The flat / angle iron weight will be arrived on the basis of theoretical calculation only)

1

-

-

... More
Supply,Installation, testing and commissioning of Ladder Cable Tray, GI, (1.6 mm thick up to 450mm and above 2mm thick) for Electrical Cable with GI Angle/Hitech Suitable threaded rods with Anchor fasteners, Clamps, bolts,nuts including all the necessary fastener etc., to suit site conditions as required. GI Ladder type cable tray :

-

-

-

... More
100mm x 60mm

25

-

-

... More
150mm x 60mm

50

-

-

... More
300mm x 60mm

110

-

-

... More
450mm x 60mm

100

-

-

... More
600mm x 60mm

125

-

-

... More
For Perforated Cable trays designed, tested and confirming to IEC 61537, thickness of cable tray should be according to the manufacturers catalogue.thickness should be 2 mm up to span length of 1.5 meter, 2.5 mm for span length between 2 to 3 meter and 3 to 4 mm for span length between 4 and 10 meter. GI Perforated type cbale tray :

-

-

-

... More
100mm x 60mm

25

-

-

... More
SECTION – G : SAFETY EQUIPMENTS, For all items in section-G, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same.

-

-

-

... More
Supply and laying of class A, 2.0mm thickness 1M X 2M wide chequered rubber mat for 440V installation as per IS 15625 / 2006

15

-

-

... More
Supply and fixing of LT cable route indicator made out of MS flat and angle iron.

15

-

-

... More
Supply and providing St.John make first aid box 18SWG MS sheet duly painted as approved by Indian red cross soceity complete with all first aid medicines.

6

-

-

... More
Supply and providing shock treatment chart in State language, English & Hindi duly framed with 2mm thick glass in front & 6mm thick ply on backas required

6

-

-

... More
Supply and fixing of GI fire buckets with round bottom, each set comprising 4Nos.fire buckets of 9Kg capacity including supply of M.S pedestal stand with hooks suitable for holding of 4Nos of fire buckets, painted with Post Office Red oil paint and letter FIRE on each bucket and filling with sand complete as required.

2

-

-

... More
Supply & Fixing HT danger notice plate 250mm x 200mm made of MS steel 2mm thick & Vitreous enameled white on both sides and with inscriptions in signal Red on front side as required by the electrical authorities.

2

-

-

... More
Supply and erection of fire extinguisher Co2 4.5 Kg. confirm to IS norms.

6

-

-

... More
Supply & Fixing of Artificial Respiratory chart

2

-

-

... More
Supply & Fixing of MS sheet board of size 500mm x 300mm of 16 SWG with Entry Restricted To Authorised Persons Only near the Main entrance of the Substation. The lettering shall be Black painted on Yellow Back ground.

5

-

-

... More
SECTION – H: LIGHTING LUMINAIRES & FANS ,For all items in section-H, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same. Supply, storing, fixing, testing and commissioning of the following lighting luminaires including all necessary accessories.

-

-

-

... More
Recessed LED Downlight similar to Philips Cat. No. RC380B LED34S 6500 W60 L60/Wipro Cat.No.CRCO10R038HP57G1/CGL Cat. No. LCTLRN-36-F0-CDL/ Havells Cat.No. LHEWBPP7PL1W036

4

-

-

... More
Surface mount LED Batten similar to Mirror light LED 9W/Philips Cat. No. BN021 LED10S CDL/Wipro Cat.No.LL20-111-XXX-65-NE/CGL Cat. No. LCL-07-CDL/Mirror Lite

29

-

-

... More
Surface mount LED Batten similar to LED Surface 18W/Philips Cat. No.BN021 LED20S CDL/ Wipro Cat.No.WIO 921208 /Havells Cat. No. LHEAAGP7PL1W015

24

-

-

... More
Surface mount Similar to Philips cat. NO. TCW450 2X18W MASTR TLED /Wipro Cat.No.LE20-491-XXX-57-XX/CGL Cat. No.IPFC112LT8-16+ 2 Nos of LT8-20-865-2/Havells Cat. No. LHEKAWN7UZ6J040

68

-

-

... More
Surface mount LED IP65 Bulkhead /Philips Cat. No. WT140 LED7S/Wipro Cat.No.LW03-850-XXX-57-XX/CGL Cat. No. LBHN-10-CDL/Havells Cat. No. LHEOAOP7UZ6W010

36

-

-

... More
18W LED Recess Mounted down light Similar to Philips Cat.No.DN173B LED12S /Wipro Cat.No.LD90-231-XXX-65-XX/CGL Cat. No. LCDN-18-CDL/Havells Cat. No.LHEBJNP7PV1W018

102

-

-

... More
12W LED Recess Mounted Down lighter Similar to Philips cat. DN172B LED10S/Wipro Cat.No.LD90-141-XXX-65-XX/CGL Cat. No.LCDN-12-CDL/Havells Cat. No. LHEJNP7CPZ1W012

80

-

-

... More
15W LED Recess Mounted down light Similar to Phililps Cat. No.DN173B LED12S /Wipro Cat.No.LD90-231-XXX-65-XX/ CGL Cat. No. LCDN-18-CDL/Havells Cat. No. LHEBJNP7PV1W018

4

-

-

... More
26W LED Recess Mounted down light Similar to Phililps Cat. No. DN173B LED12S /Wipro Cat. No. CRDL11S033HP57/Havells Cat. No. LHEBJNP7PV1W018

29

-

-

... More
36W - 2 X 2 Slim type LED Recess Mounted Similar to Phililps Cat. No. RC375B LED28S/840 PSU W60L60 WH/Wipro Cat. No.CRCO23R036HP40G2

4

-

-

-

-

-

... More
Supply, fixing, testing and commissioning of 1400 RPM heavy duty dia single phase exhaust fan with louvers.

4

-

-

... More
Supply, fixing, testing and commissioning of 1200mm sweep single phase energy efficient ceiling fan with standard down rod similar to Super fan Super 'X' Series. Power : 35W; Speed: 385RPM; Air Delivery: 230CMM

4

-

-

... More
SECTION - I :MISCELLANEOUS ITEMS

-

-

-

-

-

-

... More
Supply, Installation, testing & commissioning of following UPS System with built-in anti-harmonic filter, Preferably with active filter and all parameter in THDi and power factor shall be mentioned for percentage loading from 40% to 100%. , (internal cabling if any) for reducing input thdi to 3 to 5% and improve PF togreater that or equal to 0.95. The same shall be feasible to use in suitable for parallel redundant configuration in future. This UPS shall have 3 phase input and three phase output as per the detailed specification, data sheet, drawings.. and Supply, Installation, testing & commissioning of SMF batteries required for 30 min backup using Global Yuasa / Equivalent make for UPS units, with MS powder coated battery racks. With ventilation louver and covers including Supply, Installation, testing & commissioning of Battery control switch ( MCCB ) at Battery bank . The battery control switch shall be having under voltage provision. The breaker shall be fitted in the battery rack itself.

-

-

-

2

-

-

1

-

-

1

-

-

... More
INVERTERS:

-

-

-

... More
Supply, Installation, testing & commissioning of following INVERTER System with SMF batteries required for 15 min backup, MS powder coated battery racks., ventilation louver and covers, Battery control switch (MCCB) at Battery bank, Battery cable, intercell and cable between inverter and battery. The battery control switch shall be having under voltage provision. The breaker shall be fitted in the battery rack itself.

-

-

-

9

-

-

... More
1.5KVA

1

-

-

... More
SECTION - J : LIGHTNING PROTECTION SYSTEM

-

-

-

... More
For all items in section-J, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same.

-

-

-

... More
Conventional Lightning Protection

-

-

-

... More
25 x 6 mm GI Conductor as horizontal air terminal

200

-

-

... More
Conductor Holder for parapet

153

-

-

... More
Conductor holder for terrace

27

-

-

... More
Vertical air terminal with accessories 16mm rod tapered to 10 mm aluminium rod

2

-

-

... More
2Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load

2

-

-

... More
Fang fix clamp made of SS, lightning tested for 100 KA 10/350 micro sec waveform.

4

-

-

... More
Stand for Fang Fix system 16 kg

6

-

-

... More
cross universal connector: For T and cross connection, to route vertical down conductor /mesh formation made of hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts

20

-

-

... More
Expansion piece with connector

7

-

-

... More
Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised

14

-

-

... More
Down Conductor (15M x 15M)

-

-

-

... More
25 x 6 mm GI Conductor as Vertical air terminal

550

-

-

... More
Conductor Holder for parapet

230

-

-

... More
Test Joint (Saddle Clamp)

9

-

-

... More
Lightnig counter

2

-

-

... More
Earthing

-

-

-

... More
Flat Conductor 32X6mm G.I Strip.

550

-

-

... More
Cross Connector for Flat Suitable for 30mm G.I strip

18

-

-

... More
Conductor Holder for FL 30

9

-

-

... More
Plastic Corrosion protection strip

2

-

-

... More
Copper Earth Rod (20 mm Dia, 3m Length)

9

-

-

... More
universal clamp made of SS to connect rod with flat conductor

9

-

-

... More
Earth Enchancing Compound ( 25kg / Bucket)

9

-

-

... More
Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system

9

-

-

... More
SECTION- K: EXTERNAL LIGHTING & CONNECTED WORKS

-

-

-

... More
For all items in section-K, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same.

-

-

-

... More
STREET LIGHT POLES:

-

-

-

... More
Supply, erection and testing of following 8 mtrs street light poles, Top dia 70mm, Bottom dia upto 155mm, sheet thickness 3mm & base plate size 250x250mm x16mm. with 1000mm length of standard single/ double arm bracket including Supply of M24X750 mm foundation bolts suitable for 8m GI octagonal pole and wiring to the light fittings with 3C X 1.5 PVC insulated FRLS-ZH flexible copper conductor from MCB to light fittings and terminations, coil earthing using 8 SWG GI wire, 50 mm dia PVC pipe for incoming cable loop in and out and necessary cable dressing clamps. supplying and fixing of Bakelite sheet , 10A SP MCB and 8 way terminal connector 30A with all other necessary accessories followed as as per standards.The rate includes excavation and foundation for erecting the above referred street light as required at site and inclusive of necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same

-

-

-

... More
Supply, installation, Testing and commissioing of 8M high Hot Dip Galvanised Octagonal Pole along with single arm bracket- 1000 mm and foundation bolt set

21

-

-

... More
Supply, installation, Testing and commissioing of 8M high Hot Dip Galvanised round Pole along with single arm bracket suitable for 70mm top- 1000 mm and foundation bolt set

5

-

-

... More
Supply, installation, Testing and commissioing of 8M high Hot Dip Galvanised Octagonal Pole along with double arm bracket- 1000 mm and foundation bolt set

5

-

-

... More
Supply, installation, Testing and commissioing of 8M high Hot Dip Galvanised round Pole along with double arm bracket suitable for 70mm top- 1000 mm and foundation bolt set

5

-

-

... More
Supply and drawing of 3 Runs of 1.5 Sqmm copper conductor PVC insulated multistrand flexible copper conductor (FRLS-ZH) wiring to the street light fittings form Junction box to light fittings including making interconnections & terminations etc. as required.

500

-

-

... More
Supply, installation, Testing and commissioing of 4M high Hot Dip Galvanised Octagonal Pole along with single arm bracket- 1000 mm and foundation bolt set

3

-

-

... More
EXTERNAL LIGHTING LUMINAIRES:

-

-

-

... More
Supply, fixing, Testing and commissioning of Any approved make similar to following and not less than 90 W LED with suitable control gear die-cast aluminium housing with weatherproof gasket for LEDs top maintainable street light not less than IP65 along with Driver has protection against over voltage & short circuit including making connections etc., as required

-

-

-

... More
SITC OF STREET LIGHTING LUMINARIES Similar to Similar to Wipro cat no. . LR-02-102-XXX-57-XX WITH 90W LED Similar to philips Cat. No. Green Line V2 ( BRP 410) with 90WPressure die-cast IP 65 LED streetlight suitable for smart lighting.

34

-

-

... More
Supply, fixing, Testing and commissioning of controller suitable for smart lighting

1

-

-

... More
Supply, fixing, Testing and commissioning of Dimmable drive for street light suitable for smart lighting ( to be used for Building -1)

32

-

-

... More
Supply, fixing testing and commissioing of Smart lighting system controlled through centralized only maximum distance 1100mts cable length ( Including feeder piller,Controlls, etc., Cables not included) Communication mode shall be GPRS and Supply and fixing of the computer (Hard disk HDD - 100GB and 2GB ram) with single phase stand alone UPS 500VA. Note: 1. After one year warrenty of server management system from second year onwards AMC (Software) 4% will be charged annually from the Total value of Control system including street light fixture&pole. 2. Only Group dimming shall be done.No Individual dimming of street light.

1

-

-

... More
FASÇADE & LANDSCAPE LIGHTING

-

-

-

... More
Design, Supply, Installation, testing and commissioning of the following decorative/Non decorative light fittings with lamp with all accessories required hardwares. The installation rate shall be including necessary GI Chains, Junction boxes, Ceiling Plate, ceiling hook, terminal blocks, anchor fastener bolts PVC/GI/M.S flexible hose, MS clamp and Supports, GI Pipes etc., with 2 runs of 1.5 runs + 1 run of 1 Sq.mm PVC insulated multistrand copper wire from Light point to Light fitting and making necessary connections, loop in loop out connections, control switches, fixing arrangment supports, earthing etc., for Facade lightings.

-

-

-

... More
Supply, fixing testing and commissioing of Flood light-70W LED fittingEach(Similar to Philips Cat. No. Uniflood BVP 120 LED 70 CW NB FG S1 PSU GR)

5

-

-

... More
Supply, fixing testing and commissioing ofFlood light-150W MH fitting ( Each Conventional Metal Halide Con Tempo 2 MWF 231 1 x MHN TD-150W A )

2

-

-

... More
Supply, fixing testing and commissioing of Flood light-140W LED fitting Each (Similar to Philips Cat. No.BVP122 LED 142 CW HE AK55° FG XTFCL S4 )

6

-

-

... More
Supply, fixing testing and commissioing of Buried uplighter-60W LED fitting Each(Similar to Philips Cat. No. BBP 300 9 x LED HP/WW 220-140 60 IN

5

-

-

... More
Supply, fixing testing and commissioing of Buried uplighter-9W LED fittingEach(Similar to Surya Cat.No. SLE GBL 9W)

5

-

-

... More
Bollard light fitting similar to Philips Cat. No.-BCP400 LED04 U CW PSU GR S1

5

-

-

... More
Bollard light fitting similar to Wipro cat. No.CRLA11008 HP 57-08W IP 65 LED BOLLARD for landscape lighting. Dimension 800(H) x 104mm(dia)

16

-

-

... More
Supply, fixing testing and commissioing of Bollard-9W- LED fitting ( OPTINAL FOR THE ABOVE ITEM NO. 3 b)Each(Similar to Philips Cat. No. BCB 151 LED 150/WW PSU 220-240V 7043)

2

-

-

... More
Supply, fixing testing and commissioing of Bollard-18W- PL fitting instead of above LED fitting.Each(CONVENTIONAL HCS 360 1XPLC/2P 18W GR)

2

-

-

... More
Gate light fitting similar to Philips LED Post Top light Cat. No.- BGP161 LED2500/NW PSU 220-240V 7043 IN

2

-

-

... More
LED City cube Post Top YX light fitting similar to Philips Cat. No.-BGP400 LED50 Y CW PC S1

6

-

-

... More
Pond light fittings with controller similar to Philips Cat. No.C-Splash 2 with PDS-150e

20

-

-

... More
EARTH WORK EXCAVATION

-

-

-

... More
Earth work excavation in soil/soft rock/hard rock/ soft disentegrated rock for the required width 300mm and depth 600mm.The rate shall include refilling compacting and making of good surface to match with the original FGL. After laying the Cables, sand filling to protect the cable inlcuding brick layer. Supplying and laying good quality river sand to a depth of 75mm below cable and also one layer of 75mm river sand above cable. The rate shall include good quality bricks of size 230mmx100mm laid over the sand cushion layer to protect the cables.

1444

-

-

... More
Supply and Fixing of 50mm Dia Rigid/Sleeve PVC conduit for Laying of cable on surface/in recess/ on the existing pole including clamping, painting etc., as required.

300

-

-

... More
Supply, laying of 40 mm dia. GI pipe in ground

100

-

-

... More
Supply, laying of 50 mm dia GI pipe. in ground

100

-

-

... More
EARTHING:

-

-

-

... More
Providing the earth stations with necessary materials, labour, civil works, etc. as per Indian Standard specification IS:3043 etc. complete which includes installation, testing and commissioning using earth electrode testing instruments.Supply and laying of the 8 Swg Copper Spiral/Helical closed coil Earthing for each independent street lighting having with 115 Turns with 50mm dia. atleast 500mm. long (Approximate total length- 18Mtr.) burried below 1 Mtr from ground level.

28

-

-

... More
Supply and Laying of 1No.8 SWG dia GI wire on surface/recess for loop earthing etc. as reqd.

504

-

-

... More
Supply and fixing of the Loop in Loop out Box with terminal block 10A, etc

2

-

-

... More
Professional Charges:

-

-

-

... More
Preparation of the drawing and submission to the chief electrical inspectorate to Govt. of Kerala, Kerala Electricity Board and other statutory authorities for commissioning the system including arranging inspection and also necessary approval / safety certificate from authorities etc. for the ELECTRICAL,STP/ Other services etc,. installation. The necessary statutory fees/charges will be paid by the client against demand advice.

1

-

-

... More
Solar Power Plant

-

-

-

... More
Design, manufacturing, Supply, Packing, forwarding, Transportation & Unloading to site, installation, testing and commissioning of the 315 kWp Solar PV Generation System & connected works consists of the following:i) Solar PV module: 315Wp multicrystalline Silicon (TPS Series)- 25kWpii.a) Module mounting structure( Floor mount with fixed tilt)-1 setii.b) Array Junction box with MOV & Fuses- 4 Nosiii) Grid connect solar inverter( 20 kW, 50 Hz, MPPT, DC-AC=1.3 max ) -1 Nos.iv) Data Logger Monitoring, 1 Setv) 1 C x 4 Sq.mm PVC Copper cable ( Array interconnection & to inverter) in running Mtrs- 1 Lot(Approx:180Mtrs) as requiredvi) 5C, 10 Sq.mm EB XLPE copper cable in running Mtrs- 1 Lot(Approx-40Mtr.) as required.vii) Earth Kit, Earth wires & GI Earth Strip(25x5mm) -1 setviii) Lightning Arrestor - 1 setix) MC-4 Cable couplers(male & Female Pairs)- 1 set as requiredx) 3.5C x 25Sq.mm XLPE Alu. Cable 1.1 kV grade upto LT Panel -Approx: 50Mtrs.(ACDB to LT Panel)xi) Installation kit(Comm. Cable, inverter canopy etc)- 1 setxii)Poly carbonates transparent Bird Spike consists of (Height )5”x (Length)13” & Covering area 6”, Temperature range: -40° C to 110° C, Life of the product (approx) shall be 5 years with required all fixing accessories as required at site. xiii) Liasioning works and statutory fees for Local supply Authority & CEIG/Other statutory authorities approval against demand notice.

2

-

-

-

-

-

... More
VARIABLE REFRIGERANT FLOW SYSTEM

-

-

-

... More
INDOOR UNITS

-

-

-

... More
Design, Supply, Installation, testing and commissioning of BMS Compatible VRF Indoor air conditioning units with direct driven fan, high efficient filter, inbuilt microprocessor thermostat, electronic expansion valve, provision of fresh air duct connection, remote controller including cable, drain pump set (for cessette units and hi-static ductable units), necessary ceiling supports & vibration isolators, refrigerant charging, Refnet joints (Refrigerant branch kit) for both liquid and gas line branch kits, oil charging, control wiring, power cable from the nearest socket including plug, and drain connection, etc. The capacities are as mentioned below:-

-

-

-

... More
Hi Wall Split Unit

-

-

-

... More
Cooling Capacity - 2.0 TR

4

-

-

... More
4 WAY Cassette Units (VRF)

-

-

-

... More
Cooling Capacity - 2.0 TR

2

-

-

... More
Cooling Capacity - 1.6 TR

3

-

-

... More
Cooling Capacity - 1.3 TR

3

-

-

... More
Cooling Capacity - 1.0 TR

9

-

-

... More
Ceiling Mounted Duct Unit (VRF)

-

-

-

... More
Cooling Capacity - 8.0 TR

4

-

-

... More
Cooling Capacity - 6.3 TR

4

-

-

... More
Cooling Capacity - 4.5 TR

2

-

-

... More
Cooling Capacity - 3.0 TR

4

-

-

... More
Floor standing Air Handling unit (VRF)

-

-

-

... More
Design, Supply, installation, testing and commissioning of Double Skin Air Handling Units of Horizontal Configuration, 45±5mm thick panel with PUF insulation, MERV 8 & 13 filter sections, DX coil with single / multiple DX cooling coil suitable for R-410a refrigerant copper tube & aluminium fins, copper header, single/multiple expansion kit, communication kit, backward curved centrifugal fan, belt driven motor, spring vibration isolator for fan and motor, factory assembled volume control damper, internal power and control wiring, required length of power cable from the starter panel/VFD to the equipment, GI base frame complete as per specifications as required. Fan motor shall be suitable for 415±10% volts, 50 cycles, 3 phase AC supply & high efficiency (IE-3) and suitable for VFD operation

-

-

-

... More
Capacity: 24.0 TR, Dehumidified Air: 8400 CFM, ESP: 25mmWC, Motor Rating: 5.5 kW

1

-

-

... More
Capacity: 15.0 TR, Dehumidified Air: 6000 CFM, ESP: 25mmWC, Motor Rating: 3.7 kW

6

-

-

... More
Capacity: 9.0 TR, Dehumidified Air: 3600 CFM, ESP: 20mmWC, Motor Rating: 3.7 kW

2

-

-

... More
Design, Supply, installation, testing and commissioning of AHU Starter Panel with DOL/Star-Delta starter and BMS compatible Variable Frequency Drive with controller with auto bye pass arrangement. The VFD shall have Frequency controller, Microprocessor based logic controller, integrated Software capable to control frequency based on the inputs from sensors, power cable from VFD to AHU, communication cable, Communication card (BACnet protocol) to transfer the entire data available on VFD to the third party BMS System. The VFD shall have IP-20 protection and panel shall have IP42 protection.

-

-

-

... More
Motor rating: 5.5 kW

1

-

-

... More
Motor rating: 3.7 kW

8

-

-

... More
Supply, installation, testing and commissioning of Temperature & RH sensors with transmitters for transferring the signal to the VFD logic controller. The rate shall be inclusive of required length shielded copper communication cable for successful functioning of VFD Logic controller system.

9

-

-

... More
OUTDOOR UNITS

-

-

-

... More
Supply, Installation, testing and commissioning of Outdoor units consists of 100% inverter scroll compressor / Twin Rotary compressors, DC fan motor with aero-spiral fan blade, e-pass heat exchanger, safety valves, solenoid valves, receiver, capillary tube, check valve, electronic expansion valve, high pressure switch, low pressure sensor, pressure regulating valve, refrigerant filter, stop valve, accumulator and refnet kits. Rate inclusive of R-410A refrigerant & oil pre charging, power cable from nearest isolator, vibration isolators, supports, necessary foundation / pedestal works etc. (High COP Models)

-

-

-

2

-

-

1

-

-

1

-

-

1

-

-

1

-

-

... More
Suppy, Installation, Testing and Commissioning of BACnet/Modbus Network Interface and Central Remote Controller for monitoring and Controlling the VRF equipments in third party BMS. Rate shall inclusive of required hardware, software, Auto ON provision for critical areas based on temperature rise, sensors, etc.

1

-

-

... More
Suppy, Installation, Testing and Commissioning of Tenant Billing software with Power Distribution Indicator for all HVAC equipments with the facility to get Total power consumption and individual power consumption of each indoor units & outdoor units, power consumption of each month, with inbuilt power failure proof function including all necessary hardware/software, communication cables upto BMS system for successful installation on the BMS System.

1

-

-

... More
REFRIGERANT PIPING & RELATED WORKS

-

-

-

... More
Supply and erection of 16 Gauge Hard drawn Refrigerant Copper pipes to integrate outdoor / indoor units. The rate shall inclusive of closed cell nitrile rubber insulation for copper pipes and fibre glass cloth covering. The FRP / Polyshield coating shall be applied over the insulation for exposed application. The pipe sizes and insulation thickness as follows.

-

-

-

... More
6.4mm dia with 19mm thick insulation

10

-

-

... More
9.5mm dia with 19mm thick insulation

352

-

-

... More
12.7mm dia with 19mm thick insulation

222

-

-

... More
15.9mm dia with 19mm thick insulation

215

-

-

... More
19.1mm dia with 19mm thick insulation

149

-

-

... More
22.2mm dia with 19mm thick insulation

57

-

-

... More
28.6mm dia with 19mm thick insulation

95

-

-

... More
34.9mm dia with 19mm thick insulation

57

-

-

... More
41.3mm dia with 19mm thick insulation

86

-

-

... More
Supply and erection of following sizes perforated type cable tray made out of 16G thick GI sheet folded to required shape with adequate number of supports for Insulated refrigerant pipe and cable conduits. The tray shall be covered 16G GI sheet at all over the cable tray with screwing to cable tray as shown in the drawing.

-

-

-

... More
150mm wide

353

-

-

... More
300mm wide

163

-

-

... More
450mm wide

28

-

-

... More
Supply and laying of 2C x 1.5 Sqmm PVC Copper Armoured Cable - Communication and Control cabling between indoor and outdoor units. The rate shall be including suitable size MS conduit with conduit accessories and necessary fixing arrangement.

1100

-

-

... More
Supply and laying of 2C x 0.75 Sqmm PVC Copper Armoured Cable - Control cabling for wired remote controller.

573

-

-

... More
Supply and erection of the following UPVC pipe with all joints, reducer, necessary elbows and tees, supporting arrangements, etc. Rate shall inclusive of thermal insulation with 13mm thickness FM approved closed cell nitrile rubber insulation covering with fire resistant fibre cloth fabric as a resistant to Scratch & Mechanical Impact..

-

-

-

37

-

-

119

-

-

146

-

-

... More
AIR DISTRIBUTION SYSTEM Note: The colour shade for the air distribution equipments like ducts, diffusers, grilles, etc shall be approved by the Client / Architects before procurement and execution. The powder coating shall be 50 to 40 microns. The air distribution system comprises with all supports like anchor fasteners and tie-rods, cradles, angle iron supports, bolts and nuts, 4mm thick self-adhesive neoprene rubber gasket, stiffeners, zinc chromate painted angle iron flanges, chipping and plastering of openings made for duct supports etc., filling the gap with fibre glass wool and with fire sealant complete as per specification. The rates quoted shall include turning vanes, straightening vanes, splitters, inspection doors probe, provisions for BAS sensors, inlets with test openings enclosures complete with locking caps, chain, gaskets, insulating plugs, and extension for insulated ductwork etc. Note: The colour shade for the air distribution equipments like ducts, diffusers, grilles, etc shall be approved by the Client / Architects before procurement and execution. The powder coating shall be 50 to 40 microns

-

-

-

... More
Supply, installation, testing and balancing of Air Distribution System consists of factory fabricated Rectangular duct Galvanized Iron sheet metal ducting (Zinc coating 120GSM) with TDF/TDC flanges

-

-

-

... More
1.0mm thick GSS ducting (20G) – factory fabricated

17

-

-

... More
0.8mm thick GSS ducting (22G) – factory fabricated

341

-

-

... More
0.63mm thick GSS ducting (24G) – factory fabricated

1430

-

-

... More
Supply, installation, testing and balancing of Air Distribution System consists of Site fabricated Rectangular duct Galvanized Iron sheet metal ducting (Zinc coating 120GSM) with TDF/TDC flanges

-

-

-

... More
1.0mm thick GSS ducting (20G)

23

-

-

... More
0.8mm thick GSS ducting (22G)

23

-

-

... More
0.63mm thick GSS ducting (24G)

23

-

-

... More
Supply, installation, testing and balancing of GI Round duct as per above specification. The Sheet thickness shall be 24G

21

-

-

... More
Supply, Installation, testing and commissioning of double skin plenum box. The frame work shall be of Extruded Aluminium hollow sections. 23±2 mm thick Double Skin Panels shall be made of 0.6mm Pre-coated GSS on outside and 0.6mm Plain GSS sheet inside with CFC free Polyurethane Foam of 40±2 kg/cum in-house injected in between. These panels shall be screwed from inside on to the frame work with soft rubber gasket in between to make the joints air tight. Framework for each section shall be joined together with soft rubber gasket in between to make the joints air tight. Suitable opening for SA duct shall be made. The plenum box skin colour shall match with the AHU skin colour.

94

-

-

... More
Supply and fixing of Acoustic lining of wall and ceiling of AHU rooms with 50mm thick density 32Kg/Cu.m resin bonded glass fibber insulation friction fixed in 610mm X 610mm frame work made of 25X50X50X50X25mm made out of .6mm thick G.I Sheet U shaped channel and covered with reinforced fibre glass tissue and finished with .80mm perforated aluminium sheet etc. Complete as per Specifications.

583

-

-

... More
Supply and installing of Acoustic insulation, Material shall be processed Nitrile Rubber foam. The material should be fibre free. The density of the same shall be within 140-180 Kg/m3.The material should have a thermal conductivity not exceeding 0.050 W/mK. The maximum surface temperature the material should withstand is 105º C and minimum temperature should be -20ºC. The Thickness of the material shall be 15mm. The material should conform to Class 1 rating for surface spread of Flame as per BS 476 Part 7.

220

-

-

... More
Supply and erection of Thermal Insulation of Supply air duct with 9mm thick closed cell nitrile rubber temperature range from -10ºC to +60ºC, Class O fire category and as per specification.

1166

-

-

... More
Supply and installation of Flexible duct connections between main duct to diffuser plenums and main duct to cassette units shall be 25mm thick fiber glass pre-insulated, single ply/multiply Aluminium construction and with multiple layers of polyester film glass fibber covered with mechanical lock sheets/ Aluminium laminated jackets-Fire resistant complete with Pre-fabricated and powder coated Aluminium angle frame mounting brackets and supports.

-

-

-

... More
300mm dia

110

-

-

... More
250mm dia

25

-

-

... More
100mm dia

22

-

-

... More
Supply and fixing of Spigot damper shall be installed from take off collar to diffuser plenum boxes and at plenum boxes (low leakage) made out of 18G galvanized sheet steel frame and blades of 20G galvanized steel with suitable links.

-

-

-

... More
300mm dia

103

-

-

... More
250mm dia

22

-

-

... More
100mm dia

19

-

-

... More
Supply and fixing of Extruded Aluminium, powder coated Rectangular Supply air diffusers with removable centre core overall size 600x600mm with volume control dampers.

-

-

-

... More
450mm x 450mm neck size

5

-

-

... More
375mm x 375mm neck size

94

-

-

... More
Supply and installation of Acoustic insulated plenum boxes for supply air diffusers with 12mm thick, 48 kg/Cu.m density open cell nitrile rubber insulation to the plenum box with nuts and bolts.

-

-

-

... More
450x450 - 450mm height

5

-

-

... More
375x375 - 450mm height

94

-

-

... More
Supply, fixing and balancing of Extruded Aluminium powder coated circular diffuser with aluminium volume control damper for supply air as per the tender drawing / specifications.

-

-

-

... More
300mm dia

6

-

-

... More
250mm dia

22

-

-

... More
Supply, fixing and balancing of Extruded Aluminium powder coated circular diffuser without aluminium volume control damper for return air as per the tender drawing / specifications.

-

-

-

... More
300mm dia

6

-

-

... More
250mm dia

22

-

-

... More
Supply and fixing of Extruded Aluminium, powder Coated Return air diffusers with removable centre core overall size 600 x 600mm without volume control dampers.

98

-

-

... More
Supply and installation of Powder coated extruded aluminium linear grilles with 15 degree deflection with volume control damper for supply air Grille.

7

-

-

... More
Supply and installation of Powder coated extruded aluminium continuous linear grilles with 0 degree deflection without volume control damper for exhaust /Return air Grille.

8

-

-

... More
Supply, installation, testing and balancing of GI louver volume control damper (low leakage) made out of 1.6mm thick galvanised sheet steel frame and blades of 1.6mm galvanised steel with suitable links, handles, levers and quadrants for manual control of volume of air flow and for proper balancing of air distribution system.

15

-

-

... More
Design, Supply, installation, testing and commissioning of motorized Fire damper in supply air/return air/exhaust air streams. The damper shall be made out of 16G thick galvanized sheet steel frame and blades of 16G galvanized steel with air tight arrangement. The damper shall be provided with control panel, BMS compatible actuator of the motorized Damper shall have required torque to ON / OFF the actuator with 220 V / 24 V transformer duly encased and wired, combined smoke and heat sensor and transmitters, control / communication cables, etc. The control panel shall be suitable for receive/send signal from the Fire Alarm System and status shall be monitored thru BMS.

-

-

-

... More
Smoke & Fire Dampers.

9

-

-

... More
BMS compatible Actuators with Control Panel & Wiring

28

-

-

... More
Supply and installation of Non return damper of gravity type. The damper shall be made up of 16G thick GSS and less leakage type. The rate shall inclusive of necessary fixing and supporting arrangement.

2

-

-

... More
Supply, fixing, testing and balancing of Aluminium powder coated Fresh air and exhaust arrangement with storm proof louvers, volume control damper, MS weld mesh bird screen / mounting frame - 100mm louver spacing and 45 deg angle suitable for protection against splashing rain water fixed within a right aluminium frame.

6

-

-

... More
Supply and installation of Powder coated extruded aluminium Disc Valve of the following diameter for exhaust air. The rate shall be inclusive of volume control damper and necessary fixing and supporting arrangement for the valve . Neck Size : Dia.150mm

107

-

-

... More
Supply and erection of Semi-Rigid aluminium Flexible duct connections between main duct and disc valves. The rate shall be inclusive of mounting brackets and supports and clamping for the both ends. Size : Dia.150mm

55

-

-

... More
Powder coated extruded aluminium air transfer (non vision) door grilles comprising of front section with inverted ‘V’ horizontal blades, borders, countersunk for screw fixing, and matching rear side frame flanges.

3

-

-

... More
Supply and installation of Fire Retardant Canvass connections with GI matching flanges on both sides with a provision of openable zip. The entire assembly shall be factory fabricated.

99

-

-

... More
Supply and laying of Underdeck insulation with Fire Retardant Polyurethane foam (PUF) boards of following thickness and minimum density of 40±2 kg/M3. The Rate shall be inclusive of cleaning the surface of ceiling, fixing of drilling holes of 1.5” long to the ceiling, using rawl plastic plugs, 18 gauge GI wire for cut lacing, 0.5” dia GI washers etc. The overlap on joints and finishes on the supporting arrangements, etc. has to be accounted in the quote. The insulation has to be done completely as per manufacturer specification. 50mm thick

700

-

-

... More
Design, Supply and erection of steel supports like MS plate, angles, channels, etc. Rate shall inclusive of cutting, welding, grinding, fixing accessories and one coat of primer & two coats of enamel paints, etc. as required.

750

-

-

... More
VANE AXIAL FAN

-

-

-

... More
Design, Supply, installation and commissioning of the following capacity Axial Flow Fans for exhaust air. The fan motor shall be suitable for operating on 415±10% V, 3 phase, 50Hz AC supply. The cost shall inclusive of BMS compatible starter panel, required power cabling between the starter panel and fans, mounting arrangements, wall housing, vermin net on both sides, louvers on one end, steel supports required for mounting the fan and bird screen, wire mess and storm proof louvers as required. The fan shall be weatherproof.

-

-

-

... More
Air Qty: 7500 CFM, ESP: 20mmWC, Max Motor Rating: 3.7 kW (3 Phase) - Fresh air fan for Staircase & lift well pressurizaton

4

-

-

... More
INLINE FANS

-

-

-

... More
Design, Supply, installation, testing and commissioning of Cabinet / Ducted-in-Line Ventilation fans consists of GSS rectangular cabinet double skin construction, centrifugal blower with backward/forward and SISW type curved blades, fan motor, removable access door for easy accessibility to motor and fan, flanged inlet and outlet for easy duct work connection, thermally protected motor and necessary supports. The cost shall inclusive of BMS compatible starter panel, required power cabling between the starter panel and fans, mounting arrangements, etc. Motors shall be suitable for 3 Phase (IE-3) AC supply and the capacities are as follows. For Electrical & Hub Room

-

-

-

... More
Air Qty: 5100 CFM, ESP: 30mmWC, Max Motor Rating: 2.2 kW (3 Phase) - Toilet Exhaust (Weatherproof type)

1

-

-

... More
Air Qty: 2750 CFM, ESP: 10mmWC, Max Motor Rating: 1.1 kW (1 Phase) - Electrical Room Exhaust (Weatherproof type)

1

-

-

... More
Air Qty: 2000 CFM, ESP: 10mmWC, Max Motor Rating: 1.1 kW (1 Phase) - Kitchen Exhaust

2

-

-

... More
Air Qty: 550 CFM, ESP: 10mmWC, Max Motor Rating: 0.2 kW (1 Phase) - Hub Room Exhaust

4

-

-

... More
Design, Supply, installation, testing and commissioning of Fresh air Fan Units. The unit shall be single skin, belt driven centrifugal fan, High efficiency motor , spring vibration isolator for fan and motor, Fire retardant canvass connections, internal power and control wiring, GI base frame complete as per specifications as required. The cost shall inclusive of BMS compatible starter panel, required power cabling between the starter panel and fans, mounting arrangements, etc. Fan motor shall be suitable for 1 phase AC supply .

-

-

-

... More
Air Qty: 6250 CFM, ESP: 20mmWC (Weatherproof type)

1

-

-

... More
Air Qty: 4600 CFM, ESP: 20mmWC (Weatherproof type)

1

-

-

... More
Air Qty: 1100 CFM, ESP: 20mmWC (Weatherproof type)

1

-

-

... More
HVAC - BUILDING AUTOMATION SYSTEM

-

-

-

... More
Review and upgrading the existing BMS system of Building-1 for the additional requirements specified under this section of BOQ and as per attached I/O Summary with necessary softwares,hardwares, graphic software, soft points, etc for the successful operation.

1

-

-

... More
DIRECT DIGITAL CONTROLLER:

-

-

-

... More
Supply, installation, testing and commissioning of Autonomous Standalone cum networkable DDC Controller with 32 bit microprocessor with real time clock and historical database of min 1 Mb with panels, peer to peer communicable DDC modules, input or output relays, terminal block, real time clock, power cabling from the nearest power socket, enclosure, networking and inbuilt data buffer for Following requirement as per Enclosed IO summary . (IO Points - Refer Annexure-1 & 2)

-

-

-

... More
B2-DDC-01

1

-

-

... More
B2-DDC-02

1

-

-

... More
B2-DDC-03

1

-

-

... More
B2-DDC-04

1

-

-

... More
B2-DDC-05

1

-

-

... More
B2-DDC-06

1

-

-

... More
Weather proof enclosure for DDC panel to suit external use with suitable floor/wall mounting accessories including necessary civil works if any (IP-54) (for terrace DDCs)

6

-

-

... More
Field Devices

-

-

-

... More
Duct Mounted type Temperature Sensors for return air and supply air with necessary accessories as per the system requirements for BAS system and refer I/O Summary - Annexure-2

33

-

-

... More
Indoor CO2 sensor as per the system requirements for BAS system and refer I/O Summary - Annexure-2

11

-

-

... More
Outdoor Temperature sensor as per the system requirements for BAS system and refer I/O Summary - Annexure-2

3

-

-

... More
Outdoor CO2 sensor as per the system requirements for BAS system and refer I/O Summary - Annexure-2

3

-

-

... More
Duct Mounted type RH Sensors with necessary accessories to monitoring the conditioned area RH as per the system requirements for BAS system and refer I/O Summary - Annexure-2

33

-

-

... More
Indoor Wall Mounted type RH Sensors with LED display with necessary accessories to monitoring the conditioned area RH as per the system requirements for BAS system and refer I/O Summary - Annexure-2

8

-

-

... More
Differential pressure switch to monitor the filter status as per the system requirements for BAS system and refer I/O Summary - Annexure-2

16

-

-

... More
Cables

-

-

-

... More
2 Core 1.0 sq. mm, armoured Annealed Tinned Copper conductor multi stranded Unscreened cable. [For ON / OFF Command & various status, Supply for Field Devices]

660

-

-

... More
4 Core 1.0 sq. mm, armoured Annealed Tinned Copper conductor multi stranded Unscreened cable. [For ON / OFF Command & various status, Supply for Field Devices]

275

-

-

... More
2 Core 1.0 sq. mm, armoured Annealed Tinned Copper conductor multi stranded, screened cable. [For Sensors]

660

-

-

... More
4 Core 1.0 sq. mm, armoured Annealed Tinned Copper conductor multi stranded, screened cable. [For Sensors]

770

-

-

... More
3C x 2.5 sq mm cu. armourd cable for power supply

292

-

-

... More
Bus cable (CAT 6 or CAT 6e) to integrate all DDCs with necessary accessories

396

-

-

... More
Wiring to the BAS equipment using 2 Runs of 2.5 Sqmm insulated copper cable and 1R-2.5 Sqmm of earthing inside the suitable size MS conduits with clamp and fixing accessories -

627

-

-

... More
6A 3-Pin Socket mounted on PVC Box which has to be fixed in wall as required. The Socket should be of modular type

15

-

-

... More
100x50mm PVC raceways with ncessary fittings / accessories and fixing arrangements

176

-

-

-

-

-

... More
PUMP ROOM

-

-

-

... More
Supply, installation, testing & commissioning of Booster pump electrically driven pump set as per specification. Motor TEFC type, 2900 RPM, 415 V 50 cycle, 3 phase Class 'F" insulation, IP - 55 protection, 10 HP starting on DOL. The Pump shall be horizontal, end suction, top discharge. The pump shall be cast iron casing, bronze impeller, steel shaft. with common base frame capable of discharging 54 m3/hour at 35 m head. Pump to be installed at Terrace.

1

-

-

... More
HYDRANT SYSTEM

-

-

-

... More
Supply, installation, testing and commissioning of sluice Gate valve with matching flanges flanged body, gland with square braided non-asbestos packing, cast iron hand wheel, including making necessary flanged joints by providing necessary nuts, bolts, gaskets, etc. all complete as per IS:14846

-

-

-

... More
150 NB

3

-

-

... More
Supply, erection, testing and commissioning of Brass Gate valve (DRAIN) with necessary flanges, supports, bolts, nuts, etc & (Below 50NB) screwed ends.

-

-

-

10

-

-

5

-

-

... More
Supply, erection, testing and commissioning of Cast Iron Non-Return Valves including matching flange joints ,nut, bolt, gaskets etc. All complete as per specifications

-

-

-

... More
65 NB

1

-

-

... More
Under Ground piping - Supply, erection, testing and commissioning of MS pipes conforming to IS 3589 for 200NB & above and IS 1239 for 150NB & below with welded joints including cutting the pipes to correct length, providing fittings like elbow,tee,reducer and welding flanges to pipe, fixing with clamps to GI brackets/ hangers, making flanged joints with necessary nuts, bolts, gaskets,. blank flanges, etc. Rates including all complete as per specifications of the following diameters.

-

-

-

... More
150 NB - Heavy Class C

96

-

-

... More
80 NB - Heavy Class C

12

-

-

... More
Supply, erection, testing and commissioning of MS pipes conforming to IS 3589 for 200NB & above and IS 1239 for 150NB & below with welding joints above 65 NB and socket welding joints below 50 NB including cutting the pipes to correct length, providing fitting like elbow,tee,reducer and welding flanges to pipe, fixing with clamps to GI brackets/ hangers, making flanged joints with necessary nuts, bolts, gaskets,. blank flanges, etc. Rate shall be inclusive one coat of Zinc chromate primer over that 2 coats red enamel paint as per Fire authorities requirement over all above ground pipes.

-

-

-

... More
150 NB - Heavy Class C

124

-

-

... More
100 NB - Heavy Class C

224

-

-

... More
80 NB - Heavy Class C

30

-

-

... More
25 NB - Heavy Class C

30

-

-

... More
Supply, installation, testing and commissioning of courtyard Stainless Steel Single headed hydrant as per IS: 5290 consisting of 63NB single outlet flanged oblique type hydrants valve with instantaneous female plunger type coupling, chained blank cap including making flanged joints by providing necessary nuts, bolts, gaskets all complete as per specifications suitable for 80 NB stand post.

3

-

-

... More
Supply & installation of RRL type-A hose reel of 63mm dia. x 15 meters long with heavy quality gun metal male coupling of IS: 903. combined with 2 Nos of fire chef hoses and 1 Nos of nozzles with ms painted hose tray to accommodate hose reel

15

-

-

... More
Supply & installation of fabricated hose box FRP of size 750x600x250 with glass(4mm thick) fronted door , painted in red out side and white in inside, hose boxes along with GI support angles for courtyard & Internal hydrants. Each box shall be capable to accommodate 2 hose each of 63 mm dia x 15 m long hose pipe, nozzle, branch pipe etc.

3

-

-

... More
Supply, installation, testing and commissioning of 63mm dia. approved make Stainless steel single headed fire hydrant landing valves (with instantaneous female plunger type couplings, chained blank caps) including making flanged joints by providing necessary nuts, bolts, gaskets, etc. painting complete as per specifications.

12

-

-

... More
Supply & Installation of Drum type wall mounting hose reels, swiveling 180o consisting of 19 mm dia. x 30 meters long armored rubber hose pipe with 15 mm dia. bronze shut of type jet nozzle & cut-off valve on the inlet including making connection to the wet riser, by drilling welding, fixing the hose reel to the wall by providing necessary anchor fasteners/ expansion bolts, grouting the same with cement mortar, painting all complete as per drawings, specifications.

12

-

-

... More
Supply and fixing of fire shutter fabricated out of anodised aluminium sheet 2mm and frame,door shall be 900mmx1500mm & fixed with 4mm thick class,suitable rubber beeding and locking arrangement.Quoted rate shall be includes all fateners etc, and complete shutter shall be powder coated of approved colour both inside and outside.

12

-

-

... More
Supply & installation of 4 way Fire Brigade inlet connection with provision for Four male instantaneous coupling fabricated out of 150 mm dia. approved make heavy class MS pipe with non-return valve, for fire fighting system including making connection by providing necessary piping & fittings to the fire storage tank, fire fighting wet riser, sprinkler system painting the same with 3 coats of enamel paint over a coat of Zinc Chromate primer all complete as per drawings, specifications. Connection to Fire Tanks / Yard Hydrants

2

-

-

... More
Supply and fixing of Coating & Wrapping Materials manufactured as per IS 10221 , 4mm thick for underground Pipes as per specification Steel pipelines to be laid underground buried in the soil shall be protected against corrosion by means of coating & wrapping as per IS:10221. The above coating and wrapping shall be carried out in systematic manner such that uniform thickness of coating is obtained as per IS specification. Buried pipelines shall be laid in general with top of pipe 1(one) meter below the ground level. Where soil conditions are not satisfactory, masonry or equivalent supports shall be provided at regular intervals. The rate shall be inclusive of holiday test of underground pipes.

72

-

-

... More
Excavation of earth and refilling with Quarry dust 250 mm above and below of pipe then with earth compaction upto formed ground level.

-

-

-

... More
Soft soil

180

-

-

... More
Soft rock

5

-

-

... More
Hard rock

5

-

-

... More
Supply & installation of Automatic Air Release Valve 20 NB CI to all wet risers all complete as per specifications.

4

-

-

... More
Supply, fabrication and fixing of Test array 150 dia manifold, with valve arrangement as shown in the drawing., Differential Pressure switch - 1no ,IS approved Pressure gauge 100mm dial (Range 0 to 16 ) Kg/cm2 - 1 no.

1

-

-

... More
Supply and installation of Butterfly valve including matching flange joints ,nut, bolt, gaskets etc. All complete as per specifications

-

-

-

... More
150 NB. Gear type

6

-

-

... More
100 NB.

4

-

-

... More
80 NB.

1

-

-

... More
65 NB.

1

-

-

... More
Supply and installation of Pressure gauge 100mm dial size (Range 0 to 16 ) Kg/cm2

9

-

-

... More
Construction of masionry pedastal of 600x450x300 with steel channel (including painting) and clamp for above ground pipes at every 3 mtr interval as per drawing.

55

-

-

... More
Sprinkler System :Supply, erection, testing and commissioning of MS "C" Class pipes conforming to IS 1239 with welding joint above 65NB and socket welding joint below 50NB with including cutting pipes to correct lengths, providing fittings like elbow,tee,reducer and welding flanges to pipe,fixing with clamps to MS brackets / hangers, steel supports as per drawing. Rate shall be inclusive of Zinc chromate primer over that 2 coats red enamel paint as per Fire authorities requirement over all above ground pies. Rates to inclusive of all complete as per specifications

-

-

-

... More
150 NB. -Heavy Class

150

-

-

... More
100 NB. -Heavy Class

108

-

-

... More
80 NB. -Heavy Class

60

-

-

... More
65 NB.-Heavy Class

120

-

-

... More
50 NB.-Heavy Class

150

-

-

... More
40 NB.-Heavy Class

342

-

-

... More
32 NB.-Heavy Class

12

-

-

... More
25 NB.-Heavy Class

492

-

-

... More
Supply and installation of Upright Sprinkler head with the following temperature rating & respond, universal deflector, chromium finish as per specifications with UL &FM approved.Sprinkler standard response K-80 and temperature rating - 68 Deg C.

325

-

-

... More
Supply and installation of pendent Sprinkler head with the following temperature rating & respond, universal deflector, chromium finish as per specifications with UL &FM approved.Sprinkler standard response K-80 and temperature rating - 68 Deg C.

325

-

-

... More
Supply, erection, testing and commissioning of UL approved Metallic stainless steel (SS 304) corrugated or braided Flexible drop pipes of 25mm dia with cross bar assembly support suitable for grid ceiling, reducing fitting, special shoulder Nipple, redcing nipple, T bar braket, braket clip assembly. Flexible length shall be upto 1500 mm long .

325

-

-

... More
Supplying & installing of FM approved make flow switches (flow sensors) suitable to be fixed directly on line of the following diameters, with 1 NO & 1 NC potential free contacts.

-

-

-

... More
150 NB.

3

-

-

... More
100 NB.

2

-

-

... More
Supply & installation of Instrument cables for flow switches to anunciation panel The cable should be 2 core x 1.5 Sq.mm copper armored cable. Complete as per specification.

1600

-

-

... More
Supply and installation of Alarm check valve with full valve trim. The alarm check valve shall be equipped with a removable cover assembly. The alarm valve shall be listed for vertical position. T shall be equipped with gauge connections on the system side and supply side of the valve clapper. The alarm valve trim piping shall be externally galvanized. Maximum water working pressure to 250 PSI. This shall be inclusive of hydraulic powered water motor alarm by way of integral valve alarm line trim piping. Water motor gong shall be connected to a water pressure retarding chamber to limit the propensity of unnecessary alarms. Water motor alarm shall be equipped with a rear closure plate to limit the access of foreign materials of accumulation of debris and as per specification. 150 NB

1

-

-

... More
Supply, fabrication , erection of MS Steel works for pump room platform for cross over and secondary pipe supports in riser pipe etc as per details given in the shop drawings

150

-

-

... More
PORTABLE FIRE EXTINGUISHERS:

-

-

-

... More
Supply & installation of Portable Fire Extinguisher -the extinghser shall be IS 15683

-

-

-

... More
Fire Extinguisher Carbon Dioxide , Capacity - 4.5 Kg,

22

-

-

... More
ABC Fire Extinguisher ,Capacity- 4 kg,

8

-

-

... More
DCP Fire Extinguisher ,Capacity - 6 kg

3

-

-

... More
Clean agent Fire Extinguisher ,Capacity- 2 kg,

8

-

-

... More
FAS & PAS

-

-

-

... More
Supply, installation, testing and Commissioning of the following system as per the technical specification.

-

-

-

... More
Analogue addressable micro Process - controlled Fire Alarm Control Panels with interfacing box, capable of being to the central monitoring System, to monitor and integrated the following quantity of accessories like detectors, MCP's/hooters/control modules, Fault Isolation Modules, hooters, response indicators, fire/fault indicators, audio-visual signals, central processing units, complete with LCD display( (640 nos. of characters 8 lines min), zone indicating LEDs as per the detailed specification: complete with Battery backup for 48 hours in standy mode and 30 minutes in alarm condition. The system should be capable of detecting fire within 3secs as per UL 9th edition/FM/EN-54 approval with charger for each panel. Each loop should provide with minimum 126 detectors and 126 devices. Fire panel should be RS-485 communication port and integrate with other fire panel and Repeater panel.4 loop panel

1

-

-

... More
Rate of Rise Heat Detectors (Thermal Detectors): Addressable analogue type Heat Detectors with solid state design with sensing element combination of fixed type and rate of rise of temperature indicating LED, mounting base etc. as per detailed specifications.

7

-

-

... More
Addressable analogue type smoke detectors with dual chamber, solid state design, indicating LED, mounting base, gland and MS base box(Red Colour) etc. as per detailed specification.(For above False Ceiling & Direct Ceiling)

140

-

-

... More
Addressable analogue type smoke detectors with dual chamber, solid state design, indicating LED, mounting base etc. as per detailed specification.(Below False ceiling)

118

-

-

... More
Hooter with relay module and strobe light with minimum 105 db audible and control relay module, power supply units etc @ 3m for Audible annunciation and 75cd -110cd flashing at 1 Hz for visual indication with Control Module. The Hooter with Control Module shall be flush or surface mountable type with all accessories etc., complete and as per technical specification and shall be of UL listed.

46

-

-

... More
Manual call / pull stations with single action pull down type of approved make with NO/NC contacts slim type and projecting out from the surface of enclosure suitable for addressable function(Resetable Type)

21

-

-

... More
Fault isolation module to electrically isolate different sections of detector loops with necessary back box

14

-

-

... More
Addressable control module to trip the AHUs, triggering the DVR with cover plate and necessary back box

8

-

-

... More
Addressable monitor module for waterflow switches and third party equipments with cover plate and necessary back box

27

-

-

... More
Response indicator for mounting on false ceiling at the entries of the cabin for indicating the operation for detectors in the above areas.

123

-

-

... More
2C 1.5 armoured FRLS with ATC cable in ceiling/tray with suitable clamps and screws (RED colour)

3920

-

-

... More
25mm dia MS conduit with 2mm thick for laying of fire cable including necessary accessories like bend, junction box fixing of clamps etc., complete. The conduit shall be recessed in wall including chipping, roup plastering etc. (only for the Drops - MCPs)

392

-

-

... More
Door position sensor, monitor module with local alarm panel shall have provision for reset key with external Key switch for all Fire Doors

11

-

-

... More
Networkable fire alram active repeater panel at secuirty room. It will reflect all parameters of main panel. The rate shall be inclusive of power supply unit

1

-

-

... More
PUBLIC ADDRESS SYSTEM

-

-

-

... More
Supply, intallation, testing and Commissioning of the following system

-

-

-

... More
System Controller complete with 6 Zone Call Station with key pad, Stem Type Microphone with back box, Dual Tone Control for Speech & Music, integration facility with Fire Alarm System, tone generator & Speech Processor with relays for activating tone & pre-recorded fire alarm messages,(Digital Voice Recorder) for fire activation message, above the whole unit able to fit in rack mounting , facility to integrate with the FAS System as specified in the Tender Specifications . The rate inclusive of Priority module, selector switch, micro phone etc

1

-

-

... More
6 W Wall Mounted Speakers with line matching transformers, metal enclosures and selectedable tap setting as specified in the Tender Specifications for electical rooms and AHU rooms

28

-

-

... More
6 W Ceiling mounted speakers with line matching transformers, metal enclosures with fire dome and selectedable tap setting as specified in the Tender Specifications for false ceiling areas.

93

-

-

... More
25 W Wall Mounted Speakers with line matching transformers, metal enclosures and selectedable tap setting as specified in the Tender Specifications

2

-

-

... More
Rack Mounted minimum 240 W Power Amplifier as specified in the Tender Specifications

4

-

-

... More
2 core twin twisted 48/0.2 ATC with FRLS, Armored, Multi strand, over all PVC sheathed as specified in the Tender Specifications (YELLOW colour)

2220

-

-

... More
DVD player ,AM/FM Tuner with overriding facility, Music Source Selector, with assignable priority on each channel to accept Music, Telephone, Microphone, Recorded message from Voice recorder etc., with in-built comprossor and limiter. -

1

-

-

... More
42U rack for mounting all the above equipments

1

-

-

... More
MISCELLANEOUS ITEMS

-

-

-

... More
Supply, erection of following sizes for Perforated Cable trays as per IEC 61537, thickness of cable tray should be according to the manufacturers catalogue. For locally fabricated and non tested tray, thickness should be 2 mm up to span length of 2 to 3 meter and 3 to 4 mm for span length between 4 and 10 meter. The cable rack shall have runners rugs of suitable size, horizontal elbow, vertical elbow 90 Deg. Up vertical elbow 90 Deg. Down, re-deep, coupler plates, materials. The cable racks shall be suspended from ceiling supported from side walls in columns etc. with adequate size supporting angles / channels with fastners, welding, anchor bolts, nuts etc. The rack shall have suitable cable clamping arrangements etc. Perforated type

-

-

-

... More
100mm x 50mm (Coupler Plate -3mm Thk)

40

-

-

... More
150mm x 50mm (Coupler Plate -3mm Thk)

90

-

-

... More
300mm x 75mm (Coupler Plate -3mm Thk)

30

-

-

... More
110mm dia PVC pipe in existing excavated ground. The rate shall be including necessary coupler, bend etc.

110

-

-

... More
Wiring to the IBMS equipment using 2 Runs of 2.5 Sqmm insulated copper cable and 1R-1.5 Sqmmof earthing the suitable size with FRLS 25mm MS conduits with clamp and fixing accessories

390

-

-

... More
6 A 3-Pin Socket mounted on MS Box which has to be fixed in wall as required. The Socket shall be consider as modular type

40

-

-

... More
PASSENGER LIFT

-

-

-

... More
Supplying, installation, testing & commissioning of 680 Kgs ( 10 persons ) capacity lift of machine room less type elevator design conforming to latest lift act and modern lift with microprocesor including AC-VVVF controller in the existing lift well / shaft having minimum speed of 1.0m/sec with a total travel of 16.8 mtrs , Lower Ground, Ground plus 3 levels servicing 5 stops and 5 landings. on the same side (With floor heights as shown in the drawings) . The lift's Car enclosure, Ceiling Door shall be complete with vandal proof imported stainless steel on all four sides, SS handrail and provision for 150kgs interior etc.( Car floor finish is not in Lift vendor's scope). Inner surface of Car door and the landing door shall be scratch resistant / vandal proof with two hours fire rated door for the landing car door (lift vendor to submit certificates for the fire rating) finish stainless steel and the false ceiling should be SS # 4 Stainless Steel finish. Vendor to submit samples to Client and Architects for review,selection and approval.The lift shall be of excellent quality and shall have push buttons, intelligent group controls , floor announcement system, Gearless traction and other features as per detailed Technical specifications attached.The Machine room less lift equipment will be installed in the shaft at the location above the last landing level as per the drawing. All the lift equipments, i/c car, car doors self-levelling devices, control devices, indicators, landing doors, indicators, buffer ropes safety devices i/c all wiring connection, interconnection and all connected equipments shall be as per detailed Technical specifications. The rate shall include approval / obtaining completion certificate from the electrical / lift inspectorate of Government of Kerala for installation and commissioning of lifts before handing over the lifts to Client.The rates are also inclusive of Electrical works such as bulk head light fixing , socket fixing, MS structural works required on account of additionla head room height etc.The hooks provision based on lift vendors requirement will be arranged by the Client through the Civil vendor.The rates are inclusive of all pocket cuttings, chippings and the lift vendor should carry out the lift installation works as per the final shaft dimensions made available at site and if any civil rectifications are to be carried out,the same should be carried out by Lift contractor at no extra cost to Client. Note: Vendors should give options for car Interiors. The final choice should as per Client's requirement.Before quoting the rates , bidders should peruse the Technical specifications and quote the rates.

2

-

-

... More
COMPREHENSIVE ANNUAL MAINTENANCE FOR TWO YEARS

-

-

-

... More
Comprehensive Maintenance of all lifts on yearly basis after expiry of free maintenance for 36 months under Defects Liability period

-

-

-

... More
1st year after expiry of 36 months of Defects Liability period.

1

-

-

... More
2nd Year after expiry of 36 months of Defects Liability period.

1

-

-

... More
SEWAGE TREATMENT PLANT ( Electro-Mechanical)

-

-

-

... More
BAR SCREEN Providing, installing, testing and commissioning of Bar screen with SS 304 flats size 25 x 5 mm as per site condition Size 1200 mm width and 1200 mm depth of screen proposed of bar spacing 20 mmType : ManualMOC : SS 304

1

-

-

... More
RAW SEWAGE TRANSFER PUMPS FOR EQUALIZATION TANK Providing, installing, testing and commissioning of Non clog Centrifugal Pump of suitable capacity (with PP –Rope for lowering and lifting of pumps) for Sewage transfer from Equalization Tank to Aeration TankCapacity : 6.5 m3/hour @ 10 m headType : Centrifugal, Submersible Non Clog pump, No of pumps :-2 No ( 1Working + 1StandBy )Material of Construction :- The pump housing, motor top and impeller : Cast Iron (Pump housing: EN-GJL-200), (Motor: EN-GJL-200) &(Impeller: EN-GJS-500-7)Type of impeller: Single channelMaximum particle size: 35 -50 mmPrimary shaft seal: SIC/SICInst dry/wet: SubmergedInstallation: VerticalEnclosure class (IEC 34-5): IP68Insulation class (IEC 85): FRated speed: 2830 rpmMains frequency: 50 HzRated voltage: 3 x 400-415 VPump outlet: 65Pressure stage: PN10Make : Refer Technical SpecificationAccessories : Base Plates, Coupling , with necessary ball valve, non-return valve union flange, common header and suction , discharge header as suitable.The valve Pressure ratings PN 16

2

-

-

... More
AIR GRID FOR DISTRIBUTION FOR EQUALIZATION TANK Providing, installing, testing and commissioning of GI fabricated air distribution grid with required piping material, valve and clips to connect air from the blower. The wetted line inside the equalization tank to be provided in UPVC.Pressure Rating : UPVC - 10 kg / cm2 , GI - B Class Medium

1

-

-

... More
AIR BLOWER FOR AERATION TANK & OTHER TANKS, Providing, installing, testing and commissioning of Air blower with following specificationsAir BlowerType : Roots, Twin lobe and Belt DrivenMaterial : Cast IronCapacity : 200 m3 / hr Pressure : 0.5 kg/cm2Material Of Construction : CI FG-260 IS 210Casing / Cover / SidePlates : CI FG-260 IS 210 Lobes : CI FG-260 IS 210Shaft :070 M55 BS :970Gears : 815 M17 BS : 970Base Frame : M.S Fabricated IS 2062Speed : 1400 rpmType of Mounting : Horizontal, Foot Mounted Type Of Enclosure :TEFC AC Motor Class Of Insulation: "F"Degree Of Protection: IP55Make : Refer Technical SpecificationMotorType : Horizontal, TEFC, Squirrel Cage, InductionMake : Refer Technical Specification

2

-

-

... More
COARSE BUBBLE DIFFUSERS FOR EQUALIZATION TANK.Providing, installing, testing and commissioning of Coarse Bubble diffusers for Equalization Tank.Type : Coarse Bubble Diffusers Size of Diffusers : 90 mm Dia MOC : EPDM rubberAccessories : Central PVC Tee with yoke for uniform Air Distributors, SS Clamps,and caps,PVC saddle and internal piping in PVC etc.,Complete

1

-

-

... More
DIFFUSERS FOR AERATION TANK,Providing, installing, testing and commissioning of Diffusers along with air distribution network etc, including following specifications for Aeration Tank.Type : Fine Pore Diffusers Size of Diffusers : 90 mm Dia X 1000 mm long Moc: EPDMAccessories:Central PVC Tee with yoke for uniform Air Distribution, 90 mm Outer Dia X1000mmLong PVC 10 Kg / Sq.cm slotted pipes with uniform Air Distributors, SS Clamps,and caps,PVC saddleand internal piping in PVC etc.,Complete

1

-

-

... More
FEED WELL ASSEMBLY FOR SETTLING TANK,Providing, installing, testing and commissioning of MS feed well drum with required supports and accessories. Provided with two coats of epoxy paint.

1

-

-

... More
SLUDGE TRANSFER PUMP Providing, installing, testing and commissioning of Non clog Centrifugal Pump of suitable capacity for sludge transfer pump with following specificationsType : Horizontal, Centrifugal, Non Clog, No of pumps :-2 No ( 1Working + 1StandBy )Capacity : 6.50 m3/hour @ 15m headType :Horizontal, Centrifugal, Non-ClogSpeed :2900Suction x Discharge:40 x 40Seal Type :MechImpeller Type & Diameter :Semi OpenMaterial Of Construction of:Casing / Cover :CI Impeller :CIShaft :EN 8Speed :2900Type of operation :3ph /415 v /50 HZType of enclosure :TEFC AC Motor Class of Insulation :"F".Degree of protection :IP55,Make : Refer Technical Specification,Accessories : Base Plates, Coupling , with necessary ball valve, non-return valve union flange, common header and suction , discharge header as suitable.The valve Pressure ratings PN 16

2

-

-

... More
CHLORINATION SYSTEMS Providing, installing, testing and commissioning of Chlorination system with following specifications The Dosing system shall consist of Electronic dosing pump with positive displacement type with adjustablealso include PP chemical solution tank Pump Capacity 0 - 6LPHMax. working Pressure = 3.0kg/cm2.Type: Electronic MeteringTankcapacity 100LTS , Make: Refer Technical SpecificationMOC: HDPE/PP

1

-

-

... More
FILTER FEED PUMP,Providing, installing, testing and commissioning of Non clog Centrifugal Pump of suitable capacity for Filter feed pump with following specificationsType : Horizontal Mono block Centrifugal, Non Clog, (2 No ( 1Working + 1StandBy )Capacity : 6.5 .0 m3/hour @ 30 m headMaterial of Construction : Cast IronPump housing: Cast iron ,EN-JL1030 , ASTM 30 BImpeller: Stainless steel ,DIN W.-Nr. 1.4301 ,AISI 304Material code: ARubber: FKMCode for rubber: VSpeed for pump data: 2900 rpmEnclosure class (IEC 34-5): IP55Insulation class (IEC 85): FIE Efficiency class: IE2Rated power - P2: 2.2 kWMains frequency: 50 HzRated voltage: 3 x 220-240D/380-415Y Vshaft seal: AVBVMaximum operating pressure: 10 barIE Efficiency class: IE2Make : Refer Technical SpecificationAccessories : Base Plates, Coupling , with necessary ball valve, non-return valve union flange, common header and suction , discharge header as suitable.The valve Pressure ratings PN 1.6

2

-

-

... More
PRESSURE SAND FILTER Providing, installing, testing and commissioning of Supply, erection and commissioning of Vertical Pressure Sand filter with following specificationsType : Vertical, CylindricalDia :1050 mmHos: 1950mmShell Thick : 6 mmDish Thick : 8 mmMS Plate Make : SAILDesign Pressure : 5.0 kg/cm2Working Pressure : 3.0 kg/cm2Service flow rate :6.50 m3/hour MOC: MS-EpoxyVessel: The filter vessel is made of high grade rolled steel with stamped top and bottom dished ends welded onto it. The vessels inside and outside is painted with rust inhibiting primer and an epoxy paint, for lasting corrosion protection.Internal: Top and bottom internal water collection / distribution systemPiping: Laterals constructed in MS and all frontal piping works constructed in MSFilter media : Graded Pebbles, Silex, Graded filtering Sand. Valves: Butterfly Valves Accessories : Pressure gauges and air vent

1

-

-

... More
ACTIVATED CARBON FILTER: Providing, installing, testing and commissioning of and commissioning of Activated carbon Filter with following specifications.Type : Vertical , CylindricalDia :1050 mmHos: 1950mmShell Thick : 6 mmDish Thick : 8 mmMS Plate Make : SAILDesign Pressure : 5.0 kg/cm2Working Pressure : 3.0 kg/cm2Service flow rate : 6.50 m3/hour MOC: MS-EpoxyVessel: The filter vessel is made of high grade rolled steel with stamped top and bottom dished ends welded onto it. The vessels inside and outside is painted with rust inhibiting primer and an epoxy paint, for lasting corrosion protection.Internal: Top and bottom internal water collection / distribution systemPiping: Laterals constructed in MS and all frontal piping works constructed in MSFilter media : Graded Pebbles, Silex, Graded filtering Sand and Activated Carbon Valves: Butterfly Valves Accessories : Pressure gauges and air vent

1

-

-

... More
FILTER PRESSSupply, installation, testing & commissioning of Mechanical Filter press plate type with screw pump with all accessories, etc, complete.Filter Press UnitType: Manual HydraulicMOC of Plates: PPPlate Size: 470mm x 470mmNo. of Plates : 12No. of Chambers: 10MOC of Structure: MS EpoxyMake: Refer Technical SpecificationScrew PumpType: Single Stage Single ScrewCapacity: 2.0 cum/hrHead: 50 mMOC of Rotor: SSMOC of Stator: EPDMRating: 1.5 HP

1

-

-

... More
MBBR MEDIABiomass carrier Element ( PVC Modules ) for Aeration tank To retain sufficient biomass (MLSS) as required.of virgin plastic material and required with all MSsupporting structures Make : Refer Technical specification

8

-

-

... More
ULTRA FILTRATION SYSTEM :

-

-

-

... More
ULTRA FILTRATION SYSTEM :Providing, installing, testing and commissioning of Horizontal , mono bloc pump fitted with motor suitable capacity for UF feed pump with following specificationsUF FEED PUMP - ( 1Working + 1 Standby )Type : Horizontal , mono bloc pump fitted with motor Material of Construction : Cast Iron Service flow rate : 6.50 m3/hourHead : 30 mts Accessories : Base plates, pipe nipples, fasteners , gaskets, vibration elimination pads, level switches and all other necessary accessories etc. Pump & Motor make : Refer Technical specification

2

-

-

... More
BAG FILTER: Providing, installing, testing and commissioning of Bag Filter with following specificationsCartridge Element: Polypropylene material of construction.Service flow rate : 6.50 m3/hourMoc : SS 304Vessel: The Cartridge filter vessel is constructed of SS and is easy to open for inspection and to replace the filter elements.Cartridge elements: The filter cartridge elements are made of spiral wound polypropylene material.

1

-

-

... More
UF MODULES

-

-

-

... More
UF MODULESProviding, installing, testing and commissioning of UF Modules with following specifications. The flux rate of the membrane should not exceed 40 lmh . The vendor has to design the quantity of the membrane with respect to the flux mentioned. The vendor has to furnish the project chart along with the tender.Type : Tubular Hollow fibre MembranesMake : Refer Technical SpecificationVictaulic Coupling as required Inlet & Outlet interconnectors

1

-

-

... More
UF BACK WASH

-

-

-

... More
UF BACK WASHProviding, installing, testing and commissioning of Horizontal , mono bloc pump fitted with motor suitable capacity for UF Back pump with following specificationsUF BACK WASH PUMP Type : Horizontal, mono bloc pump fitted with motor Material of Construction : CI Capacity : 26 m3 / hr Head : 30 mts Accessories : Base plates, pipe nipples, fasteners , gaskets, vibration elimination pads and all other necessary accessories etc. Pump & Motor make : Refer Technical specification

1

-

-

... More
UF PLANT SKID

-

-

-

... More
UF PLANT SKIDProviding, installing, testing and commissioning of UF plant Skid with following specificationsMS powder coated skid suitable for fixing of UF modules of required size with required supports and accessories piping etc.UF plant piping of CPVC of size 2", 1 1/2", with CPVC fittings and valves etc Pressure gauges in the feed of Ultra filtration feed and rejects with required rota meter for monitor the feed and permeate flow.

1

-

-

... More
DOSING SYSTEM, (HYPO & ACID )

-

-

-

... More
DOSING SYSTEM, (HYPO & ACID )Providing, installing, testing and commissioning of Dosing system with following specificationsTank :MOC: HDPE/PPCapacity: 100 litresPump :Type: MeteringCapacity: 0 - 6LPHMake: Refer Technical Specification

2

-

-

... More
AUTOMATION OF UF SYSTEM

-

-

-

... More
AUTOMATION OF UF SYSTEM Providing, installing, testing and commissioning of Automaton of UF system with following specificationsType : Pneumatic Operated Valves Material of Construction : CI No of Valves : 5 Nos Valve Make : Xtreame / IntervalveActuator Make : Cair/ Aira / EquavaletAccessories : Mini PLC System and Electrical operating valves with required mimics Required Compressor for generation of air of suitable capacity for opening and close of Air Valves

1

-

-

... More
PLC FOR UF AUTOMATION

-

-

-

... More
Providing, installing, testing and commissioning of PLC for UF automation

1

-

-

... More
INTER CONNECTING PIPING WORKS

-

-

-

... More
Supply, Erection, testing and commissioning of Inter Connecting Piping Works in UPVC approved make with required valves and fittings etc.Pressure rating : Schedule 40 / 10 kg/cm2Make : Refer Technical Specification

1

-

-

... More
ELECTRICAL & INSTRUMENTATION WORKS

-

-

-

... More
Supply, Erection, Testing and Commissioning of Electrical works with following specificationsMotor Control CentreDesign, Providing and fixing MCC (Motor Control Centre) cubicle indoor type (IP 42) individual compartment panel with following accessories, incoming MCCB with digital Ammeter, CT’s, Digital Voltmeter, TOD type Energy Meter indicating lamps, outgoing feeder for lighting, pump & and equipments consist of starters shall be with MCB, starter, including bimetal Relay Controls, ON/OFF push buttons, indicating lamps etc., complete with local control push buttons consisting of ON / OFF with power and control cable including cable termination, earthling as per Satutary Requirement, etc,. complete. Quoted rate shall include for testing and commissioning etc. as required as per specifications.MOC : MS (1.6mm thick sheet ) fabricated with powder coating)cable entry : bottomThe Selector switch Auto /Manual to be provided to the MCC PANEL ( Quoted rates to be included for this item)The Panel should have minimum spare feeder of 10% from the total feeder requirements.source of Power supply shall be taken from existing utlity pannel feeder No -2 Cables for STPSupply of cables to connect the control panel and motor within the STP plant equipments and to control in the local mode (local push button).Type : Copper armoured Size : 3C x 2.5 sq. mm, 3C x 4.0 sq.mm Incoming cable from the main electrical panel with suitable feeder to handle the STP Power load.The total distance from main electrical to STP panel is about mts.TerminationsConsists of double compression brass cable glands, ferrules, ties,alumnium cable tags etcCable Trays Cable trays in GI perforated with Cable Tray and GI Cover EarthingConsists of Copper 8 SWG Copper wire for earthing of Motors, MCC etcInstrumentationLevel Controller 3 Sets sutaible for the Tank Depth of Max 4.5 mts from the top level of the tank Timers for Air blower - 2 nosMake : Selectron / VAPL Pressure Gauges - 6 NosSize : 4" SS dial glycerine filled with pressure rating of 0 - 6 Kg/cm2Digital Ph Meter at outlet of STPQty - 1 no, Make : Frobes Marshall / RLTElectro magnatic flow meter at inlet and out let of STP Size : 50 NB suitable to measure minmum 10 m3/hrType : Electro Magnetic Flanged End , Suitable for IBMS integration.Motor Control Centre.

1

-

-

... More
After completion of all installation including mechanical, piping and  electrical works, the contractor has to undertake testing and trial runs of machinery at his own cost with all consumable and labour without any load and ensure that the plant is ready for commissioning. The contractor shall undertake commissioning of the plant once the effluent is provided after the above trial run. After successful completion of the commissioning of the plant, by meeting all design parameters of the treated effluent, the contractor shall run the plant for a period of 3 months at the quoted rate including that for labour, consumables, power etc

1

-

-

... More
Statutory approval for sewage treatment plant

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.