Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.

Kerala State Housing Board - KSHB Tender

Works
Eprocure
Opening Date19 Feb 2021
Closing Date26 Feb 2021
Tender Amount₹ 4,16,310 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Summary

Kshb Bcm College Electrical Renovation Works At Classroom, Kottayam

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
1.15.3 : Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C

18

-

-

... More
od263338/2019_2020 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required.<br>Combined plug point with 6 A, 5 pin plug socket controlled by 6 A switch in the same switch board as that of light points.<br>Group A

10

-

-

... More
od263339/2019_2020 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required (RoHS compliant modular accessories)..<br>Single Control light point with 6A, plate ceiling rose - Short point

18

-

-

... More
od263340/2019_2020 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required (RoHS compliant modular accessories).<br>Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point

3

-

-

... More
od263341/2019_2020 : Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.5 sq mm FRLS PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FRLS PVC insulated wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular type ROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required.<br>Independent plug <br>Group A

1

-

-

... More
1.16 : Rewiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor singlecore cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire inexisting surface/ recessed steel/ PVC conduit including dismantling as required.

4

-

-

... More
1.7.1 : Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire

230

-

-

... More
1.10.1 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A

4

-

-

... More
1.10.2 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B

4

-

-

... More
1.10.3 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C

30

-

-

... More
1.7.2 : Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required2X2.5 sq.mm+1X2.5 sq.mm earth wire

50

-

-

... More
1.7.3 : Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required2x4 sq.mm + 1x4 sq.mm earth wire

40

-

-

... More
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch

20

-

-

... More
1.24.2 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.2 way 5/6 amps switch

4

-

-

... More
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch

4

-

-

... More
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet

5

-

-

... More
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet

4

-

-

... More
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)

2

-

-

... More
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)

2

-

-

... More
1.27.3 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)

2

-

-

... More
1.27.4 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)

4

-

-

... More
1.27.5 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)

4

-

-

... More
1.27.6 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.12 Module (200mmX150mm)

4

-

-

... More
2.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door

3

-

-

... More
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole

40

-

-

... More
2.12.1 : Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

3

-

-

... More
2.14.2 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps

3

-

-

... More
1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden blockincluding connection etc as required.

25

-

-

... More
1.49 : Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.

100

-

-

... More
1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.

40

-

-

... More
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.

10

-

-

... More
90.4.5.2 : Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.

10

-

-

... More
1.43 : Providing and fixing extra conduit down rod of 20 mm dia, 2X10 cm length wiring with 2 X1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)

30

-

-

... More
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm

100

-

-

... More
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm

40

-

-

... More
90.11.1.14 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required

1

-

-

... More
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps

1

-

-

... More
2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps

1

-

-

... More
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole

4

-

-

... More
od37356/2019_2020 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 2x10 sq mm with factory made clamp

120

-

-

... More
od37363/2019_2020 : Supply of superior quality aluminium tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. 10s q mm

10

-

-

... More
od37364/2019_2020 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 2.65 mm copper conductor (12 SWG)

150

-

-

... More
od37367/2019_2020 : Supplying siemens / tropodur type nickel plated Double compression brass cable gland for PVC insulated and PVC sheathed armoured aluminium/ copper conductor cable 1.1 KV grade, and making end termination suitable for 2/ 3/ 3½/ 4 core cable of the following sizes as required. 10 sq mm

10

-

-

... More
od37369/2019_2020 : Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required.4sqmm-16 sq mm with 12 mm wide x 1 mm thick clip

10

-

-

... More
od37371/2019_2020 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4x10 sq mm with factory made clamp

40

-

-

... More
od37396/2019_2020 : Provision for dismantle of existing light / fan / tube /switch board etc

50

-

-

... More
90.3.19.3 : Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required

15

-

-

... More
90.3.19.4 : 1200 mm 2X20W LED Lamp with box type fixture

10

-

-

... More
90.14.1.2 : Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.br Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.

2

-

-

... More
od263363/2019_2020 : SWITCHBOARDS. Design, fabrication, supply, erection, testing and commissioning of following Cubicle type, fully compartmentalized LT Switch boards dust tight and vermin proof, fabricated out of 14/16 SWG CRCA sheet, chemically treated and painted with Powder Coated of approved shade. The Switchboards should have a Set of suitably rated TPN Aluminium busbars with the specified current and fault level, Insulated with heat shrinkable, color coded PVC Sleeves and supported using DMC/ SMC Pillar or Finger type bus bar supports. The design should be as per the standards of the State Electrical Inspectorate& KSEB<br>Incoming 125 AMP 4P CHANGE OVER SWITCH- 1NO , DIGITAL MULTI FUNCTION METER-1 NO , 120/5 AMP CT-1 NO, RYB LED Indicator <br> Out going 32 AMP TPN MCB -1 NO, 63 AMP TPN MCB -2 NOS <br>( Measurement has taken after installation of Panel at site -based on data prepared) <br>

1

-

-

... More
od263362/2019_2020 : Providing and fixing signage, made of casted acrylic (4mm thick) of approved type and colour, duly Laser cut with text and pictograms(3m, LG) PVC Vinyl reverse pasting/double side tape method, electro cut. All fixing arrangements in minor fasteners, stainless steel screws, with cut etc. Or by hanging using SS chain as per design at the required locations as directed by the Engineers in charge. Rate Is inclusive of all materials, labour charges, scaffoldings etc complete (Approved rate of Government medical college Ernakulam Consultancy work )

0.5

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.