Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 35,000Document Cost
₹ 6,195Tender Fee
Refer Documents
Summary
Sitc Of Fire Fighting Equipment Construction Of New Pump Room And Revamping Of Fire Fighting System At Kerafed Kozhikode Unit
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_KFD_684028_3Bid Award Id
ViewTender No
KFD/PROJ/KCCN/FIRE/2024Tender Authority
Kerala Kerakarshaka Sahakarana Federation Limited ViewPurchaser Address
-Website
http://etenders.kerala.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
SITC of Fire fighting equipment construction of new pump room and revamping of Fire fighting system at KERAFED Kozhikode unit
BOQ Items
Centering and shuttering including Straightening etc and removal of form for foundation, footing, base of coloumns ect for mass concrete
100
-
-
Reinforced cement concrete work in walls(any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, coloumns, pillars, piers, abutments, post and struts etc. upto floor five level excluding cost of centering, shuttering, finishing and reinforcement:1:1.5:3(1 cement:1.5 coarse sand: 3 graded stone aggregate20mm nominal size)
18
-
-
Steel reinforce works including straightening cutting, bending, placing and binding all complete as per Thermomechanically treated bars
2200
-
-
BLOCK WORK:Providing and fixing precast cement concrete solid blocks above floor level up to five level in CM 1:6 complete including all charges for scafolding etc complete,
10
-
-
DOORS/WINDOWS/PARTITONS: Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall hall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass pane Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptables, wire mesh and silicon sealant shall be Paid separately)
-
-
-
Two track two panels sliding window made of (big
series) frame 67 x 50 mm & sash 46 x 62 mm both having wall thickness of 2.3 ± 0.2 mm and single glazing bead of appropriate dimension . (Area of window above 1.75 sqm upto 2.50 Sqm).
4
-
-
STEEL WORKS
-
-
-
Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including providing and fixing MS frames for doors with 1.6mm door shutters of mild steel to the existing iron frame , including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer, all complete as per the direction of Engineer-In-charge.
150
-
-
Strucural steel work riveted, bolted or welded in built up sections, trusses and framed work, including, cutting , hoisting, fixing in positions and applying a priming coat of approved steel primer all complete.
2000
-
-
Providing and fixing handrail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer . GI Pipes
40
-
-
Providing corrugate GS Sheet roofing including vertical /curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter with bitumen and GI limpet washers or with GI limpet washers filled with white lead, including a coat of approved steel primer and two caot of approved paint on overlapping of sheet complete ( up to any pitch in horizontal/ vertical or curved surfaces) , excluding the cost of purlins , rafters and trusses and including cutting size to size and shape wherever required 1.00mm thick with Zinc Coating not less than 275gm/m2
70
-
-
Providing and fixing 6mm thick chequerred plate for covering the cable trench including providing anchoring legs, pull out handles and painting with two coats of anti-corrosive paint over a coat of zinc chromate paint
150
-
-
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.
110 mm diameter
12
-
-
Providing & fixing glass panes with putty and glazing clips in windows, clerestory windows, all complete with
5.5 mm thick glass panes
4
-
-
FLOORING
-
-
-
Providing and laying C.C. flooring of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming withwire brush etc. complete as per specifications and directions of Engineer-in-charge.
(The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately).
12
-
-
FINISHING
-
-
-
12 mm cement plaster on single brick/ block or half brick/ block wall of mix: 1:4 (1 cement : 4 coarse sand) to the inside of walls
200
-
-
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface :
200
-
-
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade New work (Two or more coats applied @ 1.43 ltr/ 10 sqm. over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm).
100
-
-
Painting wall with acrylic emulsion paint for interior of approved brand and manufacture to give an even shade after thoroughly cleaning and preparing the old surface: Two or more coats on new work.
100
-
-
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :Two or more coats on new work including two coats of zinc chromate primer complete
15
-
-
LT WIRING
-
-
-
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group-A
8
-
-
Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. 2 x 2.5 sq.mm + 1 x 2.5 sq mm earth wire
35
-
-
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
8
-
-
Supplying & providing 5/6A ,one way modular switch,ISI marked
2
-
-
Supplying & providing 3 pin 5/6A modular socket outlet,ISI marked
2
-
-
Supplying and fixing 5 amps to 32 amps rating, 240 volts, 10kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 16A SP MCB with enclosure
2
-
-
Supply of 36W LED Batten surface mounting luminarire with Industrial box type fitting with powder coated reflector including all necessary accessories complete. (crompton/bajaj/philips/havells).
8
-
-
Supply,Testing and commisioning of 9 watt LED including all necessary accessories complete but excluding the foundation.(Make crompton/Philips/Wipro/havells)
2
-
-
DIESEL ENGINE DRIVEN PUMP
-
-
-
Horizontal centrifugal end suction back pull out type pump capable to deliver 2850 LPM at(171 cum/hr) @80 mtr head. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and S.S. (304) Shaft with mechanical seal. The pump shall coupled to suitable HP of Radiator cooled diesel engine mounted on a common base frame with automatic / manual starting mechanism and other accessories with fuel tank (fabricated from 3 mm MS sheet, painted with two coats of synthetic enamel paint over a coat of primer) of capacity for 8 hours continuous working. The tank shall be fitted with Magnetic oil level indicator, MH with cover, drain valve, air vent including structural supports (painted with approved shade), 24 volt Radiator with necessary piping connections & fittings & exhaust pipe connection complete.MAKE :-KIRLOSKER / LUBE/ CROMPTON
1
-
-
Supply , erection , testing & commissioning of motor control panel for fire pumps incorporating automatic star delta switch gear rated for the motor HP . THE CONTROL PANEL mounting shall include necessary indication lamps for the RYB phase showing the power supply conditions etc . the panel shall dully painted with proper anti corrosive lacquer and is of foot /wall mounted type with all accessories (for diesel pump )
1
-
-
BUTTERFLY VALVE: Supplying, Installing, testing and commissioning of CI butterfly valves with supervisory switch as per BS 5155 (PN 16) slim seal standard gear operated type, with required flanges, nuts, bolts etc. complete.
-
-
-
250MM DIA
2
-
-
200MM DIA
5
-
-
NON RETURN VALVE: Supplying, installing, testing and commissioning of C.I. Non-return valves as per IS:5312 (PN16) swing check type with required flanges, nuts, bolts and gaskets etc. complete.
-
-
-
80MM DIA
1
-
-
200MM DIA
3
-
-
PRESSURE GAUGE: Supplying, Installation, testing, commissioning of Pressure Gauge
4
-
-
PRESSURE SWITCH : Supply installation testing and commissioning of pressure switches of suitable for [pumps sets with ball valves fittings like union /colours /reducers etc for automatic operation
3
-
-
AIR VESSEL: Supplying and fixing air vessel , 4 mm thk , of 1.2 mtr height with all accessories like connecting pipes and valves in the pump house with incorporated in the delivery line,one with upper and lower limit shall be provided for jockey pump and other with only lower limit shall be provided for main electric pump; and priming line from water supply line to header
1
-
-
ABOVE GROUND PIPING: Supply, erection , testing and commissioning of MS ‘B’ class pipes confirming to IS : 1239 part-I with malleable specials confirming to IS: 1239 part –ii , such as elbows ,reducers flanges , etc . including cutting , welding , fixing in/on walls , ceiling by sing suitable supports , the pipes shall be painted with one coat of primer and coats of synthetic enamel paint of approved colour /shade. Make : JINDAL/TATA
-
-
-
250MM DIA
12
-
-
200MM DIA
12
-
-
100MM DIA
6
-
-
80MM DIA
6
-
-
65MM DIA
12
-
-
HYDRANT VALVE: Supplying , installation , testing commissioning of instantaneous pattern SS single headed hydrant valve of 63 mm dia , oblique type , instantaneous hose coupling adapter with pvc blank cap etc Make: KARTAR/NEWAGE
10
-
-
HYDRAULIC HOSE REEL DRUM : Supplying , installation , testing commissioning of hydraulic hose reel drum completed with swinging type drum with 19 mm dia rubber braided hose of 30 M length and shut off nozzle as per EN standards with necessary fittings etc complete Make: KARTAR/NEWAGE
3
-
-
HOSE CABINET : Fire hose cabinet complete in MS, fabricated from 18 SWG CRCA sheet full front glass door and locking arrangement duly painted and suitably mounted on a raised masonry platform / supported from the wall as required (Approx size 750mm x 600mm x 250mm).
16
-
-
FIRE EXTINGUISHERS
-
-
-
CO2 Type 4.5Kg ( the extinguisher must have controllabledischarge mechanism with minimum working pressure 60bar) should have valid BIS certification
6
-
-
Form Type 9Ltrs Capacity ( Preferable agent water mixed with KV Foam) should have valid BIS certification
4
-
-
Removing the existing Main pump, Jockey pump from the existing pump house and Re- installation of these items in new pump house including Cable terminations
1
-
-
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium / Copper conductor power cable confirming to IS 7098 (part 1) ammended upto date.
-
-
-
3.5C x 150 sqmm Aluminium cable
70
-
-
4C x 25 sqmm Aluminium cable
35
-
-
4C x 2.5 sqmm Coppe cable
70
-
-
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall /cable tray/ surface as required.
-
-
-
3.5C x 150 sqmm cable
70
-
-
4C x 25 sqmm cable
35
-
-
4C x 2.5 sqmm Coppe cable
70
-
-
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-
3.5C x 150 sqmm cable
4
-
-
4C x 25 sqmm cable
2
-
-
4C x 2.5 sqmm Coppe cable
8
-
-
Earthing with GI earth pipe 4.5m long,40mm dia including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc without charcoal/coke and salt as required.
2
-
-
Laisoning work with effective approval in writing prepare and submit drawing and other necessary documents, attend all tests and inspections carried out by local fire authorities.
1
-
-