Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 50,000Document Cost
₹ 2,760Tender Fee
Refer Documents
Summary
Nabard-ridf Xxvii - Construction Of Swecb Regulator Cum Bridge Across Shiriya River At Bambrana In Kumbla Gp- Electrification-general Electrical Work
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_Irrig_689491_2Bid Award Id
ViewTender No
PWD/BLDG/TR/552/2022_6_1_1/1Tender Authority
Irrigation Department ViewPurchaser Address
-Website
http://http://www.irrigation.kerala.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Bid submission letter as per item no-1 Part-VI And Integrity pact certificate as per item no-3 PartVI
Preliminary agreement as per item no-2 PartVI
BOQ Items
OD116836/2024-2025:Wiring combined plug point together with the light point/ fan point/ exhaust fan point/ call bell point including 6 A 5 pin modular socket controlled by 6A one way modular switch in the existing switch board and giving connection to the phase,neutral and earth terminal with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable ( Green wire for earthing) etc as required.
5
-
-
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
23
-
-
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
6
-
-
OD116747/2024-2025:Supply and providing the following types and power rated lamps in the existing fittings as required. B22 LED bulb 9W
6
-
-
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
4
-
-
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
4
-
-
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
4
-
-
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
2
-
-
90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture
11
-
-
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
3
-
-
OD105069/2021-2022:Supply, Conveyance, installation , testing and commissioning of 300/305 mm sweep light duty exhaust fans in metal frame in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
3
-
-
90.3.18.1:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.25 mm dia with HG company fabricated clamps
6
-
-
90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
30
-
-
90.15.3.5:Supply installation testing and commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 130 mm bottom diameter thickness 3mm base plate dimensions of 200x200x12 mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc. complete 7 Meters
15
-
-
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
10
-
-
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
12
-
-
OD105722/2021-2022:Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
20
-
-
OD105592/2021-2022:Reinforcement for R.C.C works, bend, tied and placed in position(plain grill requiring bend cold) using tor steel-
90
-
-
OD105590/2021-2022:Supply and fixing Porceline/Bakelite connector 4/2 pole in existing Junction box including connections as required
4
-
-
OD105591/2021-2022:Supply & fixing SMC Junction box with Hinged Door Having Dimension 200X140X95mm or nearest size for Street Lights as required.
2
-
-
OD117981/2024-2025:Supply and fixing Time switch DIN/BASE mounting Analog version in the existing enclosure and giving connection as required
1
-
-
OD117983/2024-2025:Supply and Installation of 4 pole contactor 25A ,440V, 50 Hz. L&T/ ABB/C&S or equivalent make.
1
-
-
OD106176/2021-2022:Supply & fixing 9 A, 2 Pole Mini contactor, AC 3 Rating, in existing enclosure and giving connection ( Make :L&T : MNX 9-2P)
1
-
-
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
150
-
-
90.6.5.12:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 2.50 sq mm
5
-
-
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
4
-
-
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
15
-
-
90.15.4.6:Supply Conveyance, installation, testing and commissioning of 70W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
2
-
-
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
3
-
-
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
4
-
-
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
8
-
-
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
3
-
-
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
8
-
-
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
3
-
-
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
70
-
-
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
15
-
-
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
40
-
-
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
5
-
-
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
20
-
-
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
25
-
-
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
20
-
-
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
10
-
-
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
25
-
-
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
200
-
-
90.12.5.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
900
-
-
90.12.5.2:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 6 sq mm
15
-
-
90.12.5.39:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 6 sq mm
60
-
-
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
650
-
-
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
300
-
-
90.16.2.3:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
12
-
-
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
15
-
-
OD105732/2021-2022:Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required
700
-
-
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
6
-
-
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
36
-
-
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
4
-
-
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.
Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
15
-
-
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
0.5
-
-
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
12
-
-
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
2.5
-
-
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
20
-
-
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
400
-
-
90.14.7:Supply and providing copper earth bus in the panel board
200
-
-
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
5
-
-
OD105757/2021-2022:Supply and installation of switch gear units in existing enclosure complete with handle of the following ratings .. including giving necessary connections as required. (excluding cost of HRC fuse links in case of SDF/ SDFCO) 63 A, 4 pole On load changer switch
1
-
-
90.14.11.1:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 100A with CBCT.
1
-
-
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
1
-
-
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
5
-
-
OD105760/2021-2022:Supply and fixing 50/5 A, 5 VA, accuracy class 1, Tape wound Metering CT in existing panel board and giving connection as required.
3
-
-
90.14.24.1:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.1 KVAr, 3 phase, 440 V, delta connected Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
1
-
-
OD105933/2021-2022:Supply Installation and Testing of DOL Forward and Reversing starter suitable for 3HP/5 HP 3 phase induction motor with D Range Contactor , SPP and LR1D OLR in SS Enclosure, relay range up to 10A, with three numbers push buttons Forward, Reverse, Off C&S ,L&T or equivalent make.
1
-
-
2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N
1
-
-
OD105934/2021-2022:Supply and fixing Flush head Push Button .
2
-
-
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
1
-
-
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2
-
-
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual
current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2
-
-
2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
1
-
-
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
36
-
-
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
3
-
-
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
1
-
-
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2
-
-
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
4
-
-
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5
-
-
OD104480/2021-2022:Providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system
2.5
-
-
OD104487/2021-2022:Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate
20
-
-
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
20
-
-
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
600
-
-
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
900
-
-
90.16.3.3:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 6 mm GI strip
90
-
-
90.16.1.9:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.64 mm GI conductor (12 SWG)
500
-
-
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
8
-
-
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
40
-
-
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
20
-
-
OD104479/2021-2022:Supply and providing 25x3mm brass nut and bolt etc. as required
40
-
-
OD104483/2021-2022:Supply and providing 12x3mm brass nut and bolt etc. as required
10
-
-
OD104485/2021-2022:Supply and fixing 63 A, 2 way neutral link mounted on DMC/ SMC base. in the existing meter board and giving connections etc
1
-
-
OD104482/2021-2022:Supplying and fixing 63, HRC Fuse with HRC Fuse link with connections, in existing meter board
3
-
-
OD104478/2021-2022:Supply and fixing 63 A , 415V , AC 23A , TPN SDF with HRC fuse links in SS Enclosure:with front handle on wall or on existing angle iron framework , giving connections, etc. as required.
1
-
-
OD104486/2021-2022:Supply & installation of dust and vermin proof, 3 Phase Syntex Meter Board( GS-MB-6535) and to fix KSEB LT meters, TVM with CTs/DHD and fuse cut out etc as required including fixing it on wall, making good the damages colour washing etc. as required. 650*350*250mm
1
-
-
OD104481/2021-2022: Supply and providing M8 anchor bolt hook in wall / parapet for binding support for service main
1
-
-
OD118344/2024-2025:Supply, Conveyance, Installation, testing and Commissioning of 15 kVA DG set with integral acoustic enclosure confirming to CPCB 4 and latest amendments with accessories as per the technical details given below :- i. Engine a. Make of Engine : As per Specified in the List of Materials b. Type of Engine : Diesel Engine c. No. of Cylinders : Suitable to develop the required BHP as per manufacturers standard d. Method of Cooling: Water Cooling (with radiator) e. Aspiration : Tubro charged after cooled f. Design : Suitable for generator set application g. Output : BHP ratings specified by the respective manufacturers capable of delivering the required power for alternator. ii. Standard accessories with Diesel Engine a. Flywheel housing and flywheel to suit single bearing alternator (Close coupled arrangement) b. Air Cleaner c. Coolant Kit d. Fuel Pump e. Electronic governor with solid state potentiometer accepting digital pulse input from PLC(backed with mechanical governor supplied as standard with the set by the manufacturer) f. Fuel filter g. Lubricating Oil filter h. Residential type exhaust silencer iii. Engine Instrument Panel a. Starting switch with key or button b. Lubricating oil temperature gauge c. Lubricating oil pressure gauge Water temperature gauge e. RPM Indicator with hour meter f. Battery charging ammeter iv. Safety Controls for Engine a. Trip for low lubricating oil pressure b. Trip for high water temperature c. Providing necessary warning system and other safeties as contemplated in relevant ISS d. Fuel shunt off facility at over speed. iv. Fuel Pipe: Oil resistant flexible hoses 25mm dial or nearest size MS pipe as per manufacturers requirement for fuel line extension with regulator valve. v. Alternator a. Make : As per Specified in the List of Materials . b. Type : Self exited and self regulated c. Capacity : 15 kVA d. System of Voltage : 3 phase, 415V e. Speed : 1500rpm f. Voltage regulation band : +1.00% of rated voltage g. Insulation : Class F/H h. AVR : AVR shall be provided with a motorized or solid state potentiometer. i. IP rating of enclosure : IP 23 j. Waveform distortion : No load < 1.5%, non- distorting, balanced Linear load <5 Total harmonic factor : Better than 2% Standard control panel with suitably rated 4 pole MCCB .m.12V,15A Automatic Battery charger suitable for required Ah Battery, having . Full protection against battery overcharging & reverse polarity. Over voltage, overload & short circuit protection, reverse battery protection The alternator should confirm to IS 4722. Routine tests as per relevant ISS shall be conducted and test reports of the same shall be furnished at the time of delivery. vii. Fuel tank. Integral type fuel tank of adequate capacity including supply and filling 25 litters Diesel viii. Battery: Required number of suitably rated fully charged battery with leads and terminals as required as per manufacturers requirement. ix Operation manual, service manual, list of spares etc x. Acoustic Enclosure with CPCB Norms 4 a. The DG set shall be supplied along with specially designed, company fabricated (to be fabricated in the same company from where the DG set is delivered) acoustic enclosure to meet the CPCB norms 4 ,. b. Sufficient space and clearance shall be maintained inside the enclosure to have optimum serviceability. c. Air inlet louvers shall be designed in such a way as to operate the set at rated load even at 50 degree Celsius enclosure temperature. d. The enclosure shall be with UV resistant powder coating capable to withstand extreme environment. e. Hardware used shall be of only stainless steel make. f. Insulation material shall conform to IS 8183 specifications for better attenuation. xi. Documents to be supplied. a. Engine manual. b. Spares parts book c. Warranty certificate d. Alternator manual & test certificate 1 set control wiring drawing xii. Installation It shall be installed in the pre-constructed concrete bed complying to relevant IS standards, IE rules and as per the direction of the departmental officials. xiii. Testing and Commissioning : xiv. During the 3 year Guarantee period comprehensive maintenance (excluding oil changes) and services as per manufacture recommendation and repairs shall be arranged from date of commissioning .
1
-
-
OD105833/2021-2022:Supply and providing the following size of B class MS pipe conforming to relevant IS specifications complete with heavy guage specials such as bends, flanges etc welded and fixed at appropriate locations, providing cork sheet in between the flanges at the joints, bolting the flanges together, painting the pipe, flange etc with 2 coats of heat resistant paint suitable for outdoor applications, fixing the pipe firmly with fabricated structure/wall/any other mechanical support etc as required.- 80 mm dia B class MS pipe as extended exhaust pipe.
12
-
-
OD105763/2021-2022:Supply and providing 2.00 mm thick, 3.3 kV, Synthetic elastromeric fire retardant insulating sheet
3
-
-
OD118436/2024-2025:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.50 sq mm single run with required sockets.
20
-
-
OD118367/2024-2025:Supply and fixing of Cable alley, 100 x 40 mm aluminium anodised legend plates as required.
1
-
-
OD118368/2024-2025:Supply and fixing of Bus bar chamber, 100 x 40 mm aluminium anodised legend plates as required.
1
-
-
OD118369/2024-2025:Supply and fixing of Danger 415 V, 150 x 100 mm aluminium anodised legend plates as required.
4
-
-
OD118370/2024-2025:Supply and fixing of Blue colour LED indicator, AC/DC, 22.5 mm cut out dia
1
-
-
OD118371/2024-2025:Supply and fixing of Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia
6
-
-
OD117152/2024-2025:Supply and fixing Digital Multifunction meter to read: V, A, F, 3 phase accuracy class 1
1
-
-
OD116855/2024-2025:Supply and Installation of ABC stored pressure type 6 Kg capacity Fire Extinguisher with pressure indication complete conforming to IS 15683 with initial charging and Installation brackets etc as required
4
-
-
OD116858/2024-2025:Charges for Preparation of electrical /fire drawings in A3 sheet as per requirements for submitting electrical inspectorate/ fire department for approvals-First copy
5
-
-
OD116859/2024-2025:Charges for Preparation of electrical /fire drawings in A3 sheet as per requirements for submitting electrical inspectorate/ fire department for approvals- Additional copy
15
-
-