HLL Lifecare Limited Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
HLL Lifecare Limited - HLL Tender
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date9 Feb 2024
Closing Date28 Feb 2024
Tender AmountRefer Documents
Costs
EMD
₹ 2,00,000Document Cost
₹ 1,770Tender Fee
Refer Documents
Summary
Tender For Capacity Enhancement And Modernization Of Electrical Substation
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HLL_185182_1Bid Award Id
ViewTender No
HLL/AFT/PUR/CEMS/2023-24Tender Authority
HLL Lifecare Limited ViewPurchaser Address
-Website
http://http://www.lifecarehll.com/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Acceptance Letter Declaration and Indemnity Clause
Specification Compliance sheet
Buyback Offer for Old 630 kVA Transformer
BOQ Items
Sub panel board - 1
Aluminium bus bar & cable entry as per site condition, CPRI/ERDA tested panel boards
Incomer: 800A 4P Isolator - 1 No
Metering: 2A SP MCB - 6 Nos, RYB LED indicating lamp -1 set, Multi function meter (voltage, current and frequency) - 1no, 800/5A Class:1 15VA CT - 3 nos, Neutral link - 1 No
Outgoings: 320A TPN 36kA thermal magnetic based MCCB with 1 no of earth fault and 3 nos of over cureent relay, ROM ,spreaders and interphase barriers - 1 no, 250A TPN 36kA thermal magnetic based MCCB with 1 no of earth fault and 3 nos of over current relay, ROM, spreaders and interphase barriers - 4 nos, 200A TPN 36kA thermal magnetic based MCCB with 1 no of earth fault and 3 nos of over current relay, ROM, spreaders and interphase barriers - 2 nos
1
-
-
Sub panel board - 2
Aluminium bus bar & cable entry as per site condition, CPRI/ERDA tested panel boards
Incomer: 800A 4P Isolator - 1 No
Metering: 2A SP MCB - 6 Nos, RYB LED indicating lamp -1 set, Multi function meter (voltage, current and frequency) - 1no, 800/5A Class:1 15VA CT - 3 nos, Neutral link - 1 No
Outgoings: 320A TPN 36kA thermal magnetic based MCCB with 1 no of earth fault and 3 nos of over cureent relay, ROM ,spreaders and interphase barriers - 1 no, 250A TPN 36kA thermal magnetic based MCCB with 1 no of earth fault and 3 nos of over current relay, ROM, spreaders and interphase barriers - 4 nos, 200A TPN 36kA thermal magnetic based MCCB with 1 no of earth fault and 3 nos of over current relay, ROM, spreaders and interphase barriers - 2 nos
1
-
-
Supply and laying of 11 kV XLPE 3 core, armoured, aluminium cable of 185sq.mm size of approved make in concrete trench
20
-
-
Supply and termination of 3x185sq.mm,11KV XLPE cable using heat shrinkable type indoor termination kit.
2
-
-
Dismantling of existing MSB
1
-
-
Dismantling of 630kVA Oil type transformer
1
-
-
Dismantling of 3x185Sq.mm 11kV XLPE Cable and its terminations
20
-
-
Dismantling of LT cables in following sizes including its terminations at the time of dismantling the existing MSB
-
-
-
3.5 x 400 Sq.mm
180
-
-
3.5 x 300Sq.mm
30
-
-
3.5 x 240 Sq.mm
85
-
-
3.5 x 185 Sq.mm
80
-
-
3.5 x 150 Sq.mm
40
-
-
3.5 x 120 Sq.mm
30
-
-
3.5 x 70 Sq.mm
40
-
-
Supply and Laying of:
a) Aluminium conductor, [Sl. No 1 to 7] XLPE insulated, PVC Sheathed, armoured, cable for working voltage up to 1.1KV, through wall/tray,in existing trench etc. b)Copper conductor, Cable for [Sl. No 8 to 10]
-
-
-
3 .5 x 400 Sq.mm (Transformer to MSB ,MSB to DG,MSB to Sub panels)
750
-
-
3 .5 x 300 Sq.mm (MSB to Chiller, MSB to capacitor panel)
140
-
-
3 .5 x 240 Sq.mm(For extending existing cables)
80
-
-
3 .5 x 185Sq.mm (For extending existing cables)
80
-
-
3 .5 x 150Sq.mm(For extending existing cables)
65
-
-
3 .5 x 120Sq.mm(For extending existing cables)
25
-
-
3 .5 x 70Sq.mm(For extending existing cables)
25
-
-
24 x 2.5Sq.mm(Cu Cable) (RTCC panel to Transformer)
60
-
-
7 x 2.5Sq.mm(Cu Cable) (DG control wiring)
200
-
-
2 x 2.5Sq.mm(Cu Cable) (Control wiring of EPB and Capacitor panel)
110
-
-
Supply of materials and termination for cable of following size using brass siemens type gland and Aluminium Palm/banana type socket.
-
-
-
3 .5 x 400 Sq.mm.(Transformer to MSB ,MSB to DG,MSB to Sub panels)
52
-
-
3 .5 x 300 Sq.mm (MSB to Chiller, MSB to capacitor panel)
8
-
-
3 .5 x 240 Sq.mm (For extending existing cables)
4
-
-
3 .5 x 185Sq.mm ( MSB to capacitor panel)
6
-
-
3 .5 x 150Sq.mm (For extending existing cables)
6
-
-
3 .5 x 120Sq.mm (For extending existing cables)
2
-
-
3 .5 x 70Sq.mm (For extending existing cables)
2
-
-
24 x 2.5Sq.mm (Cu Cable) (RTCC panel to Transformer)
8
-
-
7 x 2.5Sq.mm (Cu Cable) (DG control wiring)
10
-
-
2 x 2.5Sq.mm (Cu Cable) (Control wiring of EPB and Capacitor panel)
4
-
-
Supply and termination of following size LT cable using heat shrinkable type straight joint kit.
-
-
-
3.5 x 400Sq.mm
4
-
-
3.5 x 300Sq.mm
2
-
-
3.5 x 240Sq.mm
2
-
-
3.5 x 185Sq.mm
2
-
-
3.5 x 150Sq.mm
2
-
-
3.5 x 120Sq.mm
2
-
-
3.5 x 70Sq.mm
1
-
-
Supply and laying of following size copper earth strip /wire through walls, trench etc. including giving terminations
-
-
-
50x 6mm (Interlinking of earth pits and earthing of new transformer and MSB)
350
-
-
25 x 6mm ( Earthing of subswitch board)
80
-
-
25 x 3mm (Gland earthing/Earth plates)
90
-
-
10 SWG
60
-
-
Supply and providing efficient plate earthing using 1200x1200x10mm CI earth electrode with necessary earth pit pipe connection including filling the pit with charcoal salt etc. cement concrete or equivalent construction,chequered sheet cover etc. complete as required.
4
-
-
Fabrication,supply and fixing cable trays, supports etc using angle iron and flats including painting using 2 coats of synthetic enamel paint over zinc chromate metal primer.
500
-
-
Supply,providing and fixing of 5mm thick chequered plate over the both sides of slab, fixing of the angle iron beading on the sides of the duct and trenches, etc
3
-
-
Supply and laying of 150mm GI pipe for road crossing
24
-
-
11kV/440V cable route marker with angle support including concreting
5
-
-
Excavation of cable trench including for tar/soil cutting of depth 0.7m and width of 60cm providing sand cushioning and protective covering with country burnt bricks laid and refilling the trench as required.
40
-
-
Preparation of all drawings/documents submitting and getting approval from Central Electrical Inspectorate,submitting of Completion certificates and arranging inspection ,getting sanction and energization certificate etc from Central Electrical Inspectorate.
1
-
-
Preparation and submitting completion report and 7 set agreement to KSEBL for energising the entire sytem. Any Statutory fee for KSEBL or other department is not included.
1
-
-
Stickering of Panel Boards
1
-
-
Civil work for
-
-
-
a)Transformer plinth Modification,
1
-
-
b) Sock pit construction
1
-
-
c) Supply & installation of 2.5 KL tank with necessary basement at designated area. (Optional item - Rate only item)
1
-
-
d) Arranging drain pipe to oil tank provided at designated area. (Optional item - Rate only item)
1
-
-
Bus duct (Optional item - Rate only item) a) 1600A compact sandwich aluminium bus duct, type tested to IEC 61439-6 guidelines, KEMA/ASTA certified, 3 PHASE + 100% NEUTRAL +50% INTEGRAL EARTH without external earth strip, IP 54 rated, electro galvanised sheet steel enclosure with epoxy painting - 15 Meters
b) 1600A flanged end - 2 Nos
c) 1600 A 90 degree bend - 2 Nos
d) Copper Flexible connection - 1 Set
e) Adaptor box - 2 Nos
1
-
-
Installation of advanced Multifunction Energy Meters and Gateways for EMS (Energy Management System). (Optional item - Rate only item)
a) For Transformer & DG incomers the MFM used shall be of model PM2230 / Equivalent. All other outgoing feeders shall have MFM with suitable CT and RS 485 communication provision.
b) The gateway to installed and configured shall be MODBUS/ETHERNET/ZIGBEE GATEWAY: PAS600/equivalent
1
-
-