HLL Infra Tech Services Limited Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 1,00,000Document Cost
₹ 11,800Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HITES_681842_1Bid Award Id
ViewTender No
HITES/IDS/CHTKD-HVAC/24/02_1Tender Authority
HLL Infra Tech Services Limited ViewPurchaser Address
-Website
http://http://www.hllhites.com/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
204 HP
1
-
-
Indoor Units
-
-
-
Supply, installation and commissioning of 4-way cassette type direct expansion indoor units with individual blade control for all the four directions including blower, TEFC blower motor, suitable for operation on 240 ± 10% volts, 1 phase, 50 Hz A.C. supply, copper tube aluminium finned direct expansion cooling coil, pre filters, electronic expansion valve with cordless remote and control wiring, drain connections with anti-vibration mountings, Fresh Air connection etc., as required and as per schedule of equipment and specifications.
-
-
-
2 TR
1
-
-
2.5 TR
3
-
-
4 TR
1
-
-
Supply, installation, testing & commissioning of VRV/VRF High Wall indoor unit complete with cordless remote control, cooling coil, washable type filter, DC fan motor, electronic expansion valve, vane control , decorative panel all complete as required. The blower shall be dynamically balanced and designed for silent operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required.The cost shall include power wiring from nearest power socket
-
-
-
1.0 TR
10
-
-
1.5 TR
18
-
-
Supply, installing, testing and commissioning of ductable FAN COIL UNITS for VRF, with corded remote control, each complete with 3 / 4 rows deep Coil, cleanable fabric filters, main condensate extended SS drain pans, as described in specifications, casing, coil piping connections, through copper pipes, condensate drain connections, wiring, control wiring in conduit upto thermostat boxes.
-
-
-
1.5 TR
1
-
-
2.5 TR
3
-
-
3.0 TR
2
-
-
3.5 TR
3
-
-
4.0 TR
1
-
-
Supply installation testing and commissioning of double skin draw through type air handling unit with mixing plenum, Filter, DX Coil and Fan sections of 40 mm panel thick duly sandwiched with PUFand with thermal bridging having outer skin made out of 0.8 mm GI preplasticised with plug fan with VFD having efficiency more than 60%, coil section with 6RD copper coil having fins 5fins per cm, with provision of prefilter . The drive unit comprising of TEFC Class F motor shall be installed on a common base and isolated from the bottom casing through spring mounts complete as detailed in Data sheet. with corded remote control. Fan outlet velocity not to exceed 2000fpm. The zinc coating on GI sheet to be 120 GSM Necessary AHU KIT for VRF/VRV connection to be added.Contractor to select suitable static and select the AHU fan accordingly. The cost shall include corded remote with ESP control, starter panel with power and control cabling between nearest isolator to starter panel and fan, etc. as required.
-
-
-
3.0Tr 1200 CFM with 2 stage Filteration
1
-
-
4.0 Tr 1600 CFM with 2 stage Filteration
2
-
-
4.5 Tr 1800 CFM with 2 stage Filteration
1
-
-
5.5 Tr 2200 CFM with 2 stage Filteration
1
-
-
7.0 Tr 2800 CFM with 2 stage Filteration
3
-
-
8.5 Tr 3400 CFM with 2 stage Filteration
1
-
-
12.0Tr 4800 CFM with 2 stage Filteration
1
-
-
16.5 Tr 6600 CFM with 2 stage Filteration
1
-
-
Supply installation testing and commissioning of double skin draw through type air handling unit with mixing plenum, Filter, DX Coil and Fan sections of 40mm panel thick duly sandwiched with PUFand with thermal bridging having outer skin made out of 0.63mm GI preplasticised and inner skin of 0.63mm prepainted complete with plug fan with VFD having efficiency more than 60%, coil section with 6RD copper coil having fins 5fins per cm, with provision of prefilter & fine filter . The drive unit comprising of TEFC Class F motor shall be installed on a common base and isolated from the bottom casing through spring mounts complete as detailed in Data sheet. with corded remote control. Fan outlet velocity not to exceed 2000fpm. The zinc coating on GI sheet to be 120 GSM. 9KW (3*3KW) capacity of strip heater(complete with fixing arrangements digital humdistat and safety thermostat including separate control panel and all supports, terminations, power and control wiring) and factory fitted UV light shall be installed.
-
-
-
9.0TR 3600 CFM with 2 stage Filteration(OT AHU with 125mmWG Esp)
6
-
-
Supply, installation, testing and commissioning (SITC) of 11 TR capacity (5.5 TR + 5.5 TR double circuit)aircooled inveter type Outdoor condensing unit with single/multi scroll compressor as per specifications complete with suitable capacity drive motor, air cooled condenser with all accessories, hermetically sealed scroll compressor, electronic microprocessor pendant controller with digital display, first charge R 407A/R410A refrigerant gas, vibration isolator pads, contro panel with associated cabling work and saftey devices like thermal protector, pressure relief valve, over load relays single phase preventor, high-low pressure cut out, suitable for three phase 440V supply.br
6
-
-
Supply, installation, testing and commissioning of suitable hard drawn copper refrigerant piping for 11 TR (5.5 TR+ 5.5 TR) machine with 13 mm nitrile rubber insulation interconnecting the condensing unit to evaporating unit for packaged units as per site condition .
90
-
-
SITC of factory fabricated Plenum box made of 18G Aluminium sheet with Terminal HEPA Filters having filtering efficiency of 99.7% down to 0.3 microns with SS frame works and grilles and provision of access door for removing the HEPA Filters for cleaning and replcaement .The size shall be to suit.br1800x2400x400
6
-
-
Supply, Installation, testing & commissioning Touch screen controller for managing VRV / VRF system,with individual temperature control, fan speed control, ON/OFF function and error code display. Control should be capable of handling up to 60 IDUs and 12 ODUs
1
-
-
Supply, installation, testing and commissioning, Transmission/Communication cabling, of 2 core 1.5 Sqmm (or as per OEM standards) non polar shelied cable for interconnecting the Indoor and Outdoor Units of all the VRV/VRF Units for proper performance , Communication cable must be routed throgh PVC conduit.
1500
-
-
Supply, installation, testing and commissioning of interconnecting insulated copper tubing, for refrigerant liquid and suction lines between the Outdoor and Indoor Units complete, including fittings like elbows, reducers etc. and suitable wall / ceiling clamps as required for the complete installation and proper functioning of the VRV/VRF system. The suction lines shall be insulated with 19 mm thick and discharge lines shall be insulated with 13mm closed cell antimicrobial nitrile rubber flexible hose insulation.
1000
-
-
Supply, installation, testing and commissioning of special refrigerant connection joint kits for taking branch connections to the various Indoor Units, as required, for the complete installation and proper functioning of the VRV/VRF system.
57
-
-
Supply Installation testing and commissioning of Branch / Outdoor connection Kit
5
-
-
Supply,installation,testing and commissioning of drain piping of hard PVC pipe and fittings,insulated with 12mm thick nitrile rubber.
-
-
-
25mm
250
-
-
32mm
200
-
-
40mm
50
-
-
Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction. inlet air louvers with bird screen, volume damper & filter for fresh air as per specifications and approved shop drawings.
4
-
-
Supply, installation balancing and commisnioning of factory fabricated GSS sheet metal ducts rectangular ducting complete with neoprene rubber gaskets,elbows,splitter,dampers,vanes,hangers,supports etc as per approved drawings & specification of following sheet thickness
-
-
-
Thickness 0.63 mm sheet
900
-
-
Thickness 0.80 mm sheet
100
-
-
Supply, installation balancing and commisnioning of site fabricated GSS sheet metal ducts rectangular ducting complete with neoprene rubber gaskets,elbows,splitter,dampers,vanes,hangers,supports etc as per approved drawings & specification of following sheet thickness
-
-
-
Thickness 0.63 mm sheet
250
-
-
Thickness 0.80 mm sheet
150
-
-
Supply, Installation, Testing and Commissioning of GI VOLUME CONTROL DAMPERS complete with neoprene rubber gaskets,nuts,bolts,screw linkages,flanges etc. as per specifications.
2
-
-
Supply,fixing ,testing and commissioning of SUPPLY AIR DIFFUSERS of powder coated aluminium with aluminium volume control dampers with anti smudge ring and removable core..
38
-
-
Supply,fixing,testing and commissioning of RETURN AIR DIFFUSERS of powder coated aluminium without volume control dampers with anti smudge ring and removable core.
23
-
-
Supplying and fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
4
-
-
Supply, installation, testing & commissioning of thermal insulated FLEXIBLE DUCT of following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications.
-
-
-
200 mm Dia
30
-
-
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
-
-
-
Damper
10
-
-
Actuator
34
-
-
Supply, installation and testing of site fabricated Aluminium sheet metal ducts as per SMACNA in accordance with the approved shop drawings and as required by the specifications.
-
-
-
Thickness 22G
670
-
-
Thickness 20G
80
-
-
Supplying and fixing of following thickness closed cell Anti Microbial Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
-
-
-
19 mm
1600
-
-
Supply, installation, testing and commissioning of Acoustic duct lining using 10mm nitrile rubber insulation open cell type inside the ducts, antimicrobial protection at the outlets of all indoor units upto 4m distance from fan outlet as per spec provided
230
-
-
Supply, fabrication, installation and testing the Flexible connections constructed of fire resistant double resin sleeve for AHUs & Exhaust Fans with zip fastener for measuring temperature at the outlet of AHU.
13
-
-
Supply and fixing of Underdeck insulation with 13 mm thick Fire retardent class nitrile rubber stuck with synthetic adhesive and held in position with GI screw, washer and cross braced with GI 20SWG wire netting
1600
-
-
Supply, installation and testing of Protective layer for Copper piping with woven fibre glass cloth wrapped around copper piping tubular inuslation and finished with PVAC based high strength glue with anti fungal property of approved colours
150
-
-
Supplying, installing, testing and commissioning of Inline fans(Exhaust Air) suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller . The motor shall be suitable for 220±5% volt AC supply & meeting criterion as per ASHRAE standard 90.1-2010 and high efficiency (IS 12615). HEPA filter having filtering efficiency of 99.97% down to 0.3 microns and UV lamp with flow switch integration suitable for fixing in the exhaust air duct/plenum boxe shall be considered.
-
-
-
Quoted price shall be inclusive of electronic speed regulatorfor single phase fans.In case of 3 phase fans quoted price shall be inclusive of VFD starter panel , power and control wiring between power supply, fan & speed regulator/VFD panel, suitable enclosure, ,relay for integration of flow switch and UV lamp, suitable raing MCB etc. including all necessary accessories as required.The enclosure should meet all the requirements of statutory authority. The incoming power supply will be provided. Contractor to select suitable static and select the inline fan accordingly.
-
-
-
3250 CFM
1
-
-
2700 CFM
1
-
-
1500 CFM
1
-
-
Supplying, installing, testing and commissioning of Inline Fans (Exhaust Air) suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller . The motor shall be suitable for 220±5% volt AC supply & meeting criterion as per ASHRAE standard 90.1-2010 and high efficiency (IS 12615).
-
-
-
Quoted price shall be inclusive of electronic speed regulatorfor single phase fans.In case of 3 phase fans quoted price shall be inclusive of VFD starter panel , power and control wiring between power supply, fan & speed regulator/VFD panel, suitable enclosure, plug top for connecting to the socket etc. including all necessary accessories as required. The enclosure should meet all the requirements of statutory authority The incoming power supply will be provided. Contractor to select suitable static and select the inline fan accordingly.
-
-
-
1100 CFM
1
-
-
900 CFM
1
-
-
700 CFM
1
-
-
600 CFM
1
-
-
450 CFM
1
-
-
400 CFM
2
-
-
350 CFM
2
-
-
300 CFM
1
-
-
Supplying, installing, testing and commissioning of Inline Fans (Fresh air) suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller . The motor shall be suitable for 220±5% volt AC supply & meeting criterion as per ASHRAE standard 90.1-2010 and high efficiency (IS 12615).
-
-
-
Quoted price shall be inclusive of electronic speed regulatorfor single phase fans.In case of 3 phase fans quoted price shall be inclusive of VFD starter panel , power and control wiring between power supply, fan & speed regulator/VFD panel, suitable enclosure, plug top for connecting to the socket etc. including all necessary accessories as required. The enclosure should meet all the requirements of statutory authority The incoming power supply will be provided. Contractor to select suitable static and select the inline fan accordingly.
-
-
-
2700 CFM
1
-
-
2400 CFM
1
-
-
1200 CFM
1
-
-