Harbour Engineering Department Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 20,700Document Cost
₹ 1,850Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_HED_675128_1Bid Award Id
ViewTender No
02/HEED/2024-25/e-T/STender Authority
Harbour Engineering Department ViewPurchaser Address
-Website
http://etenders.kerala.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group A
4
-
-
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group B
2
-
-
Supplying 16 W LED Tube with box type fixtures Essential LED tube 1200 mm 16W 865 T8 API Philips or equivalent
6
-
-
Supplying surface/suspended mounted smartbrite luminaire SM 270C LED 30S 6500 PSU WH Philips or equivalent
10
-
-
Supply and fix LED Bulk Head fitting 10W with Aluminium die-cast housing and polycarbonate optic materials including connection etc as required. The luminaire shall have IP66 protection, luminous flux 1100 lm, luminous efficiency 110 lumens/watt, cool daylight colour and 6500k colour temperature PHILIPS Endura LED Bulk Head model WT202W LED10S CW PSU S3 PC or equivalent
3
-
-
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade:Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture
1.26
-
-
Engaging labourers for tracing underground cable connection, dismantling the electrical wiring and installations and keeping the same safely at a place as per the direction of the departmental officers at site Wireman
4
-
-
Engaging labourers for tracing underground cable connection, dismantling the electrical wiring and installations and keeping the same safely at a place as per the direction of the departmental officers at site. Beldar
4
-
-
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
541
-
-
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
82
-
-
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
32
-
-
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
23
-
-
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
12
-
-
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
12
-
-
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
4
-
-
Supply and installation of suitable size MS belt type fan clamp fabricated from flat iron 40 x 6 mm, 150mm long x 2 Nos with M.S. rod bent to shape, neatly painted with 2 coats of enamel paint over a coat of red oxide primer as per IS 732 as required.
4
-
-
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm
60
-
-
Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench 63/50 mm or nearest size
60
-
-
Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres.
18
-
-
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required 3.15 mm copper conductor ( 10 SWG)
78
-
-
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
32
-
-
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required
3
-
-
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
1.8
-
-
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper
conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair
178
-
-
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
430
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
47
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
2
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet
6
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
50
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
2
-
-
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required
2
-
-
CAT 6 RJ 45 computer data socket
14
-
-
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.RJ 45 frame
14
-
-
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
26
-
-
Supply and fixing 105 x 50 mm UPVC Cable Management System with base and lid LEGRAND or equivalent along with all required accessories as per the site condition on surface/recess including switch plate
45
-
-
Identifying cables, supply and crimping RJ 45/RJ 11 cable jack on the cable end and giving connection
74
-
-
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way (4 + 24), Double door
2
-
-
Supplying and fixing following Modular base & cover plate on existing existing CMS 105X50mm. As required.1 or 2 Module base and cover plate
20
-
-
Supplying and fixing following Modular base & cover plate on existing CMS 105X50mm etc. as required.3 Module base and cover plate
15
-
-
Supplying and fixing following Modular base & cover plate on existing CMS 105X50mm etc. as required.6 Module base and cover plate
15
-
-
Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
0.08
-
-
Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
2.1
-
-
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
1
-
-
Supply of Cat 6,2 metre patch cord
8
-
-
Supply of Cat 6,1 meter patch cord
6
-
-
Supply of fully digital ISDN PRI EPABX SYSTEM with TDM/PCM technology and IP platfom expandandable model configured to support 04 -Trunk Lines,24 SLT extensions having the following key features. PC/Printer connectivity,internal Voice prompt 134 nos ,Auto Attendant 8 port, Auto fax detection (4 Faxes),ASMDR – 10,000 calls, Call Budgeting/Call Billing, CLI – DTMF, CLI – Restriction, CTI (Computer Telephony Integration), LCR (Least Cost Routing), Name storing, Power on Maintenance, Program/ Master Back up, Time Zone Programming, SMPS With inbuilt battery charger,Customized Music on Hold
1
-
-
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
120
-
-
Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
22
-
-
Supplying and fixing surface /recess mounting 4 way , Double door , dust and water proof IP 66 Hensel make or equivalent FP VN 0410 opaque door, 8+12 VTPN distribution board of polycarbonate inclusive of tinned copper busbar, common nutrel link, earth bar, din bar for mounting MCB's with provision for fixing MCCB /RCCB as incomer
1
-
-
Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
1
-
-
Supply of ceiling fan of 1200 mm sweep Category B Ceiling fan excluding resistance type regulator
6
-
-
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required
10
-
-
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
6
-
-
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1
-
-
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1
-
-
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
4
-
-
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
4
-
-
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2
-
-
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2
-
-
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
1
-
-
Supply, installation, testing and commissioning of 230V AC, 50HZ ,3KVA IGBT based PWM technology microprocessor controlled double conversion true Online UPS(96 V DC or above) capable for automatic changeover from mains to UPS on mains failure and vice versa with built in isolation transformer of make APC/NUMERIC/GE or equivalent suitable to work with 8Nos 12V,100 Ah,rated tubular type battery bank C10 for UPS application suitable for 3 hours backup on full load.Single phase Input Voltage Range 160- 300 V AC, Output Frequency-50 ±. 01Hz,Output voltage Range :230VAC ± 1% ,Output power rating:2400W/3000VA,Interface port:RS232 and com port,Front panel Display: LCD ,input power factor:0.99, input Current THD 10% at full load,Output Voltage THD 3%(Linear Load),THD 5%(Non- Linear load),Overall efficiency =90%,Overload capacity :1min @ 111%-130% of rated load,10 minute @ 105%-110% of rated load,Load power factor: 0.8 lag or better,Load crest factor : 3:1, Noise level: 50 dBA at 1 meter, Continuous Operating Temperature: 0-40 °C,Constant current & constant Voltage with optional Temperature compensated battery charging. Standards: EMC- EN 62040-2, Safety- EN 62040- 1, Performance- IEC 62040-3, Certifications: BIS,OSHAS,CE,PeP, RoHS, ISO 9001 & ISO 14001 ,Warranty :3 years on site warranty from the date of installation
1
-
-
Supply and fixing 80 x 50 mm UPVC Cable Management System with base and lid LEGRAND or equivalent along with all required accessories as per the site condition on surface/recess including switch plate
12
-
-
Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
1
-
-
Supply Push Button Telephone. Preferred make Beetel C-51 CLI or equivalent
2
-
-
Supply Push Button Telephone Preferred make ; Beetel C-11 or equivalent
4
-
-
Supply, installing, commissioning of manageable switch SG350-28-K9 or equivalent 28 PORT GIGABIT manageable switch having 24 x 10/100/1000 + 4 x Gigabit SFP (2 combo) , L3 - Managed, 24x GbE (1000Base-T) | 4x SFP | Managed, VLAN- Rackmount, Enclosure Type:- Rack-mountable Voltage Required :-AC 120/230 V (50/60 Hz), Switching Capacity should be 56 Gbps,4096 active VLAN's ,RAM- 512MB,Flash memory-256 MB flash,switch should be Manageable through CLI, web Interface and SSH
1
-
-
Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
25
-
-
Supply of superior quality copper earth socket for the 3.15mm (10 SWG) earth conductor including crimping etc. as required.
25
-
-
Supply, installation testing and commissioning wall mounting type dust and vermin proof enclosure 9 U rack system with standard accessories patch panel,cable manager , power strip, cooling fan, cable tray (Model 9U) suitable for installing 24port Ethernet switch and patch panel.
1
-
-
Supply, installing HENSEL telephone junction box K9250 size 200x160x98 mm having 20 pair KRONE type telephone wire connector suitable for 0.50 mm dia copper wire of approved quality mounted on a suitable G.I. frame. All the telephone wires are to be identified and terminated on the block as per the colour code using the special crimping tool as per the instruction of the departmental officer.
1
-
-
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
1
-
-
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
10
-
-
Supplying and fixing brass batten/ angle holder including connection etc. as required.
5
-
-
Supply and fixing 7/9 W LED, BC, lamp OSRAM or equivalent
5
-
-
supply of 200 mm sweep 40 W exhaust fan with plastic body with a Speed 1250 RPM,Air delivery 720 CMH Crompton or equivalent
5
-
-
Supply of BIS approved LED Luminaire with system wattage of 35W, made up of pressure die cast Aluminium body and anti UV PC Protector with integrated lenses for increased pole spacing and uniform light distribution, IP66, IK 08, system efficacy of 110 lm/W, CCT 4000K, operating temp range up to 50 degree and designed for efficient thermal management, lumen maintenance L70@ 50000Hrs, Upward Light Output Ratio is 0% at zero degree inclination to avoid light pollution, suitable for side / vertical
mounting up to 48mm diameter, Colour Rendering Index 70, a driver efficiency 85%, with internal surge protection of 4kV and Power factor 0.95.Make: Keselec Cat Ref: Nice-R 35W NW LED or equivalent
2
-
-
Conveyance, installation, testing and commissioning of departmentally supplied flood light / Area light luminaire with lamp on the existing tubular post of height upto 8m from ground level.
2
-
-
Supply and installation of wall mounting cubicle type dust and vermin proof size 4 , 600x300x214 mm, Mi2410 hinged type thermoplastic box with 25A,16 kA,TP MCCB with 32A 2 way porcelain neutral link and rotary handle , one set phase indication lamp,2A C-curve MCB - 3 Nos ,Panel surface mounting 96sq.mm backlit LED Multifunction meter three line display to read V,A,KVA,,PF and frequency of make Schneider or equivalent suitable for 415V ,50Hz - 1 No,30/5 tape wound class 1 CT -3 Nos. Sufficient holes for fixing phase indication lamp,multifunction meter and rotary handle in the thermoplastic box are to be provided.Necessary interconnection with suitably rated copper conductor with copper socket are to be provide
1
-
-
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat
4
-
-
Providing and fixing extra conduit down rod of 20 mm dia, 2X10 cm length wiring with 2 X1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
90
-
-
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc.as required.
6
-
-
Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.
50
-
-
Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
5
-
-
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes
5
-
-
Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
60
-
-
Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
6
-
-
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescentfitting of all types, complete with all accessories and tube etc., including supplying and fixing balland socket arrangement, 2 no. down rods of 20 mm dia X 1.6 mm thick steel conduit upto 30 cm length, painting and wiring the down rods and connection with 1.5 sq. mm FRLS PVC insulated,copper conductor, single core cable and earthing etc. as required.
10
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements