Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 50,000Document Cost
₹ 2,760Tender Fee
Refer Documents
Summary
Construction And Renovation Of Building For Panchajanyam Annexe-fire Security System
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_GD_676657_1Bid Award Id
ViewTender No
E7-2438/24Tender Authority
Guruvayur Devaswom ViewPurchaser Address
-Website
http://https://guruvayurdevaswom.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Construction and Renovation of building for Panchajanyam Annexe Guruvayur Temple- Fire Security System..
BOQ Items
Supply and Laying of below sized XLPE insulated PVC sheathed Aluminium conductor armored cabling to the incoming and outgoing of fire pump panel including necessary termination, glanding, necessary connections etc
HAVELLS/POLYCAB/FINOLEX
-
-
-
3 x16 sq mm on wall floor
50
-
-
Supplying, installing , testing and commisioning CI Non-Return (PN 20) valve as per IS 5312 swing check type with required flanges, nuts, bolts and gaskets etc.complete. (Make: Audco, Intervalve)
-
-
-
100 mm nominal dia
1
-
-
Supplying, installing , testing and commisioning CI butterfly valve (PN 16) slim seal standerd lever operated type confirming to BS:5155 (IS 13039) with required flanges, nuts, bolts etc complete. (200mm and above Gear Operated type) (Make: Audco, Intervalve)
-
-
-
100 mm nominal dia
3
-
-
80 mm nominal dia
5
-
-
FLOW SWITCH
-
-
-
Supplying installing testing and commissioning flow switch on sprinkler distribution header on each floor and shall be connected to fire alarm panel
5
-
-
Supplying and erecting 20/25 mm Ø G.M. air release valve, with necessary G.I coupling to be fitted on top of air vessel or on wet riser.
1
-
-
Supplying, fabricating, structural steel supports such as MS channels, angles, flats, rods as required at site with anchor fasteners, clamps, threaded rods, nuts, bolts, washers etc. complete with painting.
220
-
-
Supplying, fixing, testing and commissioning above / under ground piping of heavy grade ISI marked class 'C' MS pipes confirming to IS: 1239 Part - 1 with maleable specials confirming to IS 1239 P1 and II such as tees, elbows, checknuts, unions flanges, nipples, etc. including cutting welding fixing in/on walls, celling by using suitable supports at standard spacing and priming and painting with two coat of red colour synthetic enamal etc. as per drawing. The quoted rate shall include for chasing the walls, marking bore in walls/ floos and making good with filler material and finished in cement morter etc. complete.( Make: Jindal / Tata)
-
-
-
100 mm nominal dia
42
-
-
80 mm nominal dia
24
-
-
65 mm nominal dia
66
-
-
50 mm nominal dia
102
-
-
40 mm nominal dia
36
-
-
32 mm nominal dia
24
-
-
25 mm nominal dia
152
-
-
Providing, anti corosive pipe protection bituminous tape after painting with anti corossive black paint as required.
30
-
-
Suppling, installing, testing and commisioning conventional sprinkler quartzoid bulb type with 15 mm screwed end connection of 58oC temperature rating. Sprinkler shall be UL listed / FM approved.(Pendant sprinkler) (Make: Tyco / Viking)
-
-
-
Pendant type sprinkler
65
-
-
Side wall type sprinkler
73
-
-
Supply, installation, testing and commissioning of hydrant valve Single headed GM obligue suitable for 63 mm flanged inlet, female instantaneous outlet, complete with cap chain etc, as per IS : 5290. (Make: NewAge / Safex )
6
-
-
GM branch pipe with 63 mm female instantaneous inlet male threded outlet completewith hex. Basednozzle heavy quality as per IS : 903. (Make: NewAge / Safex )
6
-
-
Supply and fixing of 63 mm dia CP hose tested to a bursting pressure of 32 Kg / sq.cm made of superior quality cotton and nylon jacket beaming seamless woven and rot proofed each of length 15 mtrs. confirming to IS :4297 (8423) Complete with heavy quality GM coupling as per IS:5290. Hoses shall be rolled & hug to suitable M.S. structural support fixed inside the Fire duct wall. (Make: NewAge / Safex )
12
-
-
Hose reel complete with 20 (19) mm dia high bursting pressure rubber hose (textile reinforced) type-2 as per IS:12585 of 30 mtr long with nozzle and 20mm ball valve. Hose reel mounted in a 16SWG MS construction of revolving type drum with swinging up to 170 degree friction less rotaton with painted in post box red colour confirming to IS:884. The rate includes 20mm (nominal) dia gun metal nozzle mounted at the end. Brackets for fixing the equipments on wall. (Make: NewAge / Safex )
5
-
-
Hose boxes of size 30"X24"X10" made of 16 swg CR sheet with two glass fronted door,3mm thick glass the box shall be painted red outside and white inside with MS support/ stand to hydrant. Structual support fixed inside the fire hose cabinet for hanging 2nos. 15m length of 63mm dia RRL hose with couplings and one Branch pipe nozzle. The cabinet shall be supported proper manner as per approved drawings. (Make: NewAge / Safex )
6
-
-
Supplying, fixing, testing and commissioning of 0-15 Kg/sq cm100mm dia Dial type pressure gauge with isolation cock and pipe at hydrant station as per specification.Make: FEBIG/HGURU
1
-
-
Supply, installation, testing and commissioning of 3way Fire Brigade Inlet connection of 63 mm dia. built - in Gun metal Non- return valves instantaneous coupling type arrangement to be connected to wet riser main.Make:ARIHANT/NEWAGE
1
-
-
Supply, installation, testing and commissioning of industrial type pressure switch having 1/4" BSP(F) connection IP:32 enclosure protection, phosphor bronze bellows as sensing element, SDPT contact system, switch rating 6A Inductive/lOA resistive 380 V AC, 0.2A Inductive/10A resistive 250V DC suit with ball valve etc. complete as required.
1
-
-
Fire Alarm System
-
-
-
Supply & installation of networkable Two loop Micro processor based 2 wire fault tolerant loop with optional redunadant network module, each loop shall have the capability of connecting 250 devices. The panel should have inbuilt TCP/IP communication for Panel Program and Remote Monitoring option . The panel shall be able to give location of all fire, fault and Isolation conditions of addressable units via the address codes and must be able to automatically activate respective module when ever any alarm is triggered. The panel should have inbuilt common Alarm, Fault and monitored sounder output. Also the panel should have the option to operate in manned and unmanned mode.The panel shall have as per specifications and Duly Approved by EN/UL Listed
Make: Ravel/Cooper
1
-
-
Supply installation testing and commissioning of Active Repeater Panel: Supply ofRepeater Panel with 640 Character LCD Display or Touch Screen LCD with all functionality of Main Panel having Reset / Alarm Silence and Acknowledgement Buttons . On the Active Repeater over Serial Interface or Network there shall be Annuciation Panels as well for all Control stations. Individual Active Repeater shall be able to take care of upto minimum 16 nos Annunciation LCD Indicator Panels . Approval Standards : UL/ FM
1
-
-
Supply and Inatallation of Addressable Multi detector with base with Binary coded address setting. Dual LED’s for 360° visibility. Sleek low-profile housing design. Regular 100mm base. IP Rating : IP - 42. Approval: UL Listed, Make: COOPER/GST/EDWARD
107
-
-
Supply of addressable analogue type manual call points,Adjustment of the Manual Call Point after alarm triggering, Automatic or manual detector addressing via rotary switch possible,Indicator LED for alarm or for inspection evaluation, Call point query routines with evaluation and multiple transmission, Individual call point identification. ( MAKE :RAVEL/COOPER/GST/EDWARD)
5
-
-
Supply and Installation of Control Relay Module, Maximum switching current of 5 A (type DIN rail) /1 A (type in-built), Low current consumption, Maintains LSN loop functions in the event of wire interruption or short-circuit thanks to two integrated isolators. ( MAKE :Ravel/ BOSCH /Cooper/Eaton)
5
-
-
Supply & installation ofAnalog Addressable type Addressable Input/Output module with LED indication for Normal, Fault, test, and activation.The module shall have the option for configuration as fail safe operation and duly approved by EN/UL Listed Ravel/COOPER/GST/EDWARD
5
-
-
Supply and installaiton of 2C x 1.5 sq.mm PVC insulated FRLS copper armoured cable confirming to IS 694 for Fire Alarm System. MAKE : VERSHA/Kflex/Polycab/Finecore
3000
-
-
Supply, erection, testing and commissioning of Public Addressing cum Talk back pael 8 zone Selector control with controller , power supply including call selector, suitable Amplifier Unit 5 mic input.AGNI/ASES AGNI
1
-
-
Supply & erecion of MICROPHONE for Intelligible, crisp and bright sound suitable for all type of PA applications. Supplied with quick detachable holder with 3-pin professional XLR connector & 6 mtrs. Twin core shielded low noise cable.
1
-
-
Supply, installation, of public address speaker 5W
5
-
-
Supply, installation, of Medium Class PVC Conduit, FRLS Grade, with proper MS brackets and clamps/saddles in the shaft and vertical run through walls or partitions. (Fire alarm system) 25MM DIA… Make:VIP/marcoplast/Geo
200
-
-
Supply and fixing of GI Perforated Cable tray strip galvanized with horizontal & vertical bends, reducers, Tee's, cross over , suitable supports and bracketsbrand other accessories as required confirming to IEC-61537. The Tray shall be galvanised for corrosion protection confirming to DIN ENbr10346 / ISO 1461 .The trays should be tested for a max. safe working load of 185 Kgs with a span distance of 1.5 meters and the deflectionbrshould be within the limits as per standard. The safety factor shall be 1.7 times of the safe working load.
-
-
-
150mm x 60mm
10
-
-
Fire Extinguishers
-
-
-
Carbon-di-oxyde type fire extinguisher of 4.5 kgs. capacity CO2 gas filled in brand new seamless cylinder with power coated finish, made out of manganese steel, with wheel type valve, discharge nozzle, bend and Horn, wall-mounting bracket etc. Complete confirming to IS: 2878. (Make; Ceasefire, Safex)
5
-
-
ABC type fire extinguisher of 5 kgs. capacity filled in brand new seamless cylinder with power coated finish, made out of manganese steel, with wheel type valve, discharge nozzle, bend and Horn, wall-mounting bracket etc. Complete confirming to IS: 2878 (Make; Ceasefire, Safex)
10
-
-
Signages and Drawing
-
-
-
Supply and providing emergency fire escape lighting system IP42 60lm consisting 2 nos lamp ,7Ah battery charging unit ,exit sign display etc in MS enclosure with 3 years warranty.(Cooper /Eaton)
10
-
-
Supply & erection of Glow Sign Boardmade of 3mm thick PVC foam board for each floor 12" x 4" (Fire Lift, Passenger Lift, Electrical Duct, Fire Station, Main Stair, Fire Exit, Floor Display & Pump Room)
25
-
-
Supply & erection of Assembly Point sign board 16" x 16"
1
-
-
Supply & erection of Fire Escape rout in each floor having size 12" x 16"
5
-
-
Preparation of fire fighting system drawing and check list as per new fire rules inlduing printing in colour, conducting fire force inspection and obtaining Final NOC from Fire Fprce Department
1
-
-
CIVIL SCOPE OF WORKS TOWARDS FIRE FIGHTING WORKS
-
-
-
Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
175
-
-
Filling available excavated earth (excluding rock) in trenches, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 metre
175
-
-
Providing and laying in position cement concrete 1 :2:4 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) including form work etc. as required.
1
-
-
Providing brickwork (in width225mm or more) with F.P.S bricks of class designation 7.5 in cement mortar 1:4 at all levells
2
-
-
Supplying, laying, and laying 25X6mm GI Strip
55
-
-