Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 1,00,000Document Cost
₹ 8,400Tender Fee
Refer Documents
Summary
Augmentation Of 33/11kv Substation At Tced
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_UAD_701853_1Tender No
TCED/RDSS-3955/24Tender Authority
Directorate Of Urban Affairs ViewPurchaser Address
-Website
http://etenders.kerala.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
SCADA Compatible, 36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker, Jumpers, earthing, supporting structures, bi-metallic clamps, permanent maintenance platform, marshalling box etc required as per technical specifications, scope of works and approved drawings
1
-
-
... More
36kV, 1-Phase, 25kA/3 seconds, 400-200/1-1-1-1 Amps, Cl: 0.2S -5P20 / PX , 3 Nos outdoor type Current Transformers with junction box (1 no junction box for 3 no of 1-phase CTs, Jumpers, earthing, supporting structures, bi-metallic clamps, marshalling box etc required as per technical specifications, scope of works and approved drawings
1
-
-
... More
33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays and other components etc as per approved drawings, specifications and scope of works controlling: Power transformer 33 kV VCB with Static Tri-Vector Energy
Meter
1
-
-
... More
36kV, 630A, 25kA for 3 seconds, 3-ph double break centre rotating type (DBCR), Gang Operated, isolator along with Support Insulators, Operating Mechanism, Base Channel down Pipe and all required accessories complete as per technical specifications, scope of works and approved drawings
2
-
-
... More
30 kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware etc as required as per technical specifications, approved drawings and scope of the works.
3
-
-
... More
9kV, 10kA, 1-ph Station Class Lightening Arrester with mounting platform, jumpering from bus bar, earthing connection using 50x6mm GS flat, hardware, etc as required as per technical specifications, approved drawings and scope of the works.
3
-
-
... More
ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware fittings, hardware, T-claimp etc as per technical specifications, approved drawings and scope of works.
ACSR Kundah
200
-
-
... More
ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including hardware fittings, hardware, T-claimp etc as per technical specifications, approved drawings and scope of works.
ACSR Wolf
300
-
-
... More
Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station with
50 x 6 mm Galvanized GS flat
50
-
-
... More
Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station with
25mm dia GI rod 3 m long
60
-
-
... More
Earthing & Grounding conductor as per Approved Electrical Layout for each sub-station with
Earth Wire 7/ 3.15 mm dia
300
-
-
... More
40 mm dia., 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover plates on GI frame, bantonide powder and other accessories complete as per technical specification. (for Power Transformer Neutral, Station Transformer Neutral and Lightening Arresters direct earthing)
5
-
-
... More
33KV Polymer type Disc Insulators along with Hardware & accessories suitable for Kundah & Wolf conductors as per approved drawings & specifications.
6
-
-
... More
33KV Post Insulators along with Hardware & accessories suitable for Kundah & Wolf conductors as per approved drawings & specifications.
3
-
-
... More
11KV Post Insulators along with Hardware & accessories suitable for Kundah & Wolf conductors as per approved drawings & specifications.
3
-
-
... More
LT Control cables including their termination materials like glands, lugs etc. as per technical specifications, approved drawings and scope of works.
19 Core 2.5 sqmm armored, stranded copper conductor, PVC insulated and PVC sheathed cable
200
-
-
... More
LT Control cables including their termination materials like glands, lugs etc. as per technical specifications, approved drawings and scope of works.
4 Core 2.5 sqmm armored, stranded copper conductor, PVC insulated and PVC sheathed cable
200
-
-
... More
LT Control cables including their termination materials like glands, lugs etc. as per technical specifications, approved drawings and scope of works.
4 Core 4 sqmm armored, stranded copper conductor, PVC insulated and PVC sheathed cable
200
-
-
... More
LT Control cables including their termination materials like glands, lugs etc. as per technical specifications, approved drawings and scope of works.
2 Core 4 sqmm armored, stranded copper conductor, PVC insulated and PVC sheathed cable
200
-
-
... More
LT Control cables including their termination materials like glands, lugs etc. as per technical specifications, approved drawings and scope of works.
12 Core 2.5 sqmm armored, stranded copper conductor, PVC insulated and PVC sheathed cable
200
-
-
... More
LT Control cables including their termination materials like glands, lugs etc. as per technical specifications, approved drawings and scope of works.
12 Core 4 sqmm armored, stranded copper conductor, PVC insulated and PVC sheathed cable
200
-
-
... More
36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential Transformer along with junction box (1 no junction box for 3 no of 1-phase PTs) including earthing connection using 50x6mm GS flat, bi-metallic clamp and required accessories etc., complete as per technical specifications, approved drawings and scope of the works.
1
-
-
... More
11 KV, XLPE, 3 phase power cable armored, aluminium conductor, stranded as per technical specifications, approved drawings and scope of works.
3Cx 300 sqmm
500
-
-
... More
11 KV, XLPE, 3 phase power cable armored, aluminium conductor, stranded as per technical specifications, approved drawings and scope of works.
1Cx 500sqmm
300
-
-
... More
Indoor Cable termination kit suitable for termination in transformer cable box/ breaker panel/ Outgoing feeders complete with all accessories etc. as per technical specifications, approved drawings and scope of works.
3Cx 300 sqmm
6
-
-
... More
Indoor Cable termination kit suitable for termination in transformer cable box/ breaker panel/ Outgoing feeders complete with all accessories etc. as per technical specifications, approved drawings and scope of works.
1Cx 500sqmm
8
-
-
... More
33kV, 400-200-100/1-1-1-1 A Neutral Current Transformer along with required accessories etc., complete as per technical specifications, approved drawings and scope of the works.
1
-
-
... More
11kV, 600-400-200/1-1-1-1 A Neutral Current Transformer along with required accessories etc., complete as per technical specifications, approved drawings and scope of the works.
1
-
-
... More
Supply of SCADA Compatible - 11kV, 5Panel Indoor set with 1 Incomer ( With CTs for Special Protection) Indoor type 12 kV, 1250 A (1 No Incomer) and 630A (4 No Outgoing), 25kA for 3 seconds, 3-ph, Vacuum Circuit breaker (VCB) along with 12 kV, 1-Phase, 800-400/5-5-1-1A (1Set), 400-200/5-5A(4 Set), Cl: 0.2S -5P20 / PX Current Transformers & 11kV/110 Volt Voltage Transformers, I/C & O/G energy meters of smart type IS16444, and required complete accessories as per technical specifications, approved drawings and scope of the works.
1
-
-
... More
Supply of SCADA Compatible - 11kV, 10 Panels Indoor set with 2 Incomers, 2 Bus Couplers,Bus risers and bus trenching arrangement ( With CTs for Special Protection) Indoor type 12 kV, 1250 A (2 Nos Incomer & 2 Nos Bus Coupler) and 630A (6 Nos Outgoing), 25kA for 3 seconds, 3-ph, Vacuum Circuit breaker (VCB) along with 12 kV, 1-Phase, 800-400/5-5-1-1A(2Set), 400-200/5-5A(6 Set) Cl: 0.2S -5P20 / PX Current Transformers & 11kV/110 Volt Voltage Transformers, I/C & O/G energy meters of smart type IS16444, and required complete accessories including indoor cables termination kits as per technical specifications, approved drawings and scope of the works.