Defence Research And Development Organisation Tender

Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.

Defence Research And Development Organisation - DRDO Tender

Works
Eprocure
Opening Date22 Nov 2024
Closing Date12 Dec 2024
Tender Amount₹ 44,37,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 10km initial lead, for all leads including all lifts involved.

2601

458

1191258

... More
Credit for Reinforcement steel obtained form above items

500

-10

-5000

... More
SUBHEAD-II :EARTH WORK & EXCAVATION :

-

-

-

... More
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 Sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. including pumping out water as required or liquid mud,

-

-

-

... More
All kinds of Soils

2103

299

628797

... More
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 Sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. . including pumping out water as required or liquid mud,

-

-

-

... More
All kinds of Soils

3457

203

701771

... More
Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete.

3385

585

1980225

... More
Laying, spreading and compacting stone aggregate of specified sizes to Rubble solling specifications in uniform thickness, hand picking, rolling with 3 wheeled road/vibratory roller 8-10 tonne capacity in stages to proper grade and camber, applying and brooming requisite type of screening / binding material to fill up interstices of coarse aggregate, watering and compacting to the required density .

952

2844

2707488

... More
SUBHEAD-III :ANTI TERMITE TREATMENT :

-

-

-

... More
Supplying chemical emulsion in sealed containers including delivery as specified.

-

-

-

... More
Chlorpyriphos/ Lindane emulsifiable concentrate of 20%

1962

235

461070

... More
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : a) Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc.:With Chlorpyriphos/ Lindane E.C. 15% with 1% concentration.

171

48

8208

... More
Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With Chlorpyriphos/Lindane E.C. 15% with 1% concentration.

3388

271

918148

... More
SUBHEAD-IV : PLAIN & REINFORCED CEMENT CONCRETE :

-

-

-

... More
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :

-

-

-

... More
1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)

657

6927

4551039

... More
Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor,etc., up to floor five level, excluding the cost of centering, shuttering and finishing:

-

-

-

... More
1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)

29

10028

290812

... More
Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth.

557

783

436131

... More
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.

-

-

-

... More
Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement

-

-

-

... More
Concrete of M30 grade with minimum cement content of 350 kg /cum

-

-

-

... More
All works upto plinth level

1594

9573

15259362

... More
All works above plinth level upto floor v level

2578

10265

26463170

... More
Concrete of M25 grade with minimum cement content of 330 kg /cum

-

-

-

... More
All works above plinth level upto floor v level

20

10099

201980

... More
Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). 450 mm dia piles

7310

2254

16476740

... More
Add/ Deduct for using extra/ less cement in the items of design mix over and above the specified cement content therein.

1150

831

955650

... More
Supplying, fabricating and fixing in position reinforcement bars at all levels and positions including the cost of steel, straightening, cutting, bending, binding and placing in position etc., as per drawings and specifications including the cost of binding wire, labour etc., all complete for reinforced concrete.

-

-

-

... More
Thermo-Mechanically Treated bars (Fe 500 Grade or More) at all levels

962

118690

114179780

... More
Centering and shuttering including strutting, propping etc. and removal of form for :

-

-

-

... More
Foundations, footings, bases of columns, etc. for mass concrete

2049

340

696660

... More
Lintels, beams, plinth beams, girders, bressumers and cantilevers

6802

644

4380488

... More
Columns, Pillars, Piers, Abutments, Posts and Struts

3927

850

3337950

... More
Weather shade, Chajjas, corbels etc., including edges

105

946

99330

... More
Suspended floors, roofs, landings, balconies and access platform

5889

815

4799535

... More
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.

860

731

628660

... More
Stairs, (excluding landings) except spiral-staircases

181

733

132673

... More
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured).

-

-

-

... More
Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)

266

332

88312

... More
Vertical load testing of piles in according with IS 2911(Part IV) including installation of loading plateform and Preparation of pile head or construction of test cap and dismantling of test cap arter test etc., complete as per specification & the direction of Engineer-in-charge Single pile upto 50 tonne safe capacity Routine test

2

53295

106590

... More
SUBHEAD-V : STONE & BRICK MASONRY :

-

-

-

... More
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with, Cement mortar 1:6 (1 cement : 6 coarse sand).

183

5539

1013637

... More
Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).

1506

7326

11032956

... More
Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work.

44

9130

401720

... More
SUBHEAD-VI : PLASTERING & SURFACE TREATMENT :

-

-

-

... More
Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) :

-

-

-

... More
Flush/ Ruled Pointing

30

344

10320

... More
6 mm cement plaster of mix cement mortar 1:3 (1 Cement : 3 fine sand).

7310

275

2010250

... More
12 mm cement plaster finished with a floating coat of neat cement of mix 1:4 (1 cement: 4 fine sand).

6210

322

1999620

... More
15 mm cement plaster on the rough side of single or half brick wall of mix 1:6 (1 cement: 6 fine sand).

8700

352

3062400

... More
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand).

6060

465

2817900

... More
Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers.

444

23

10212

... More
Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.

352

79

27808

... More
Providing and fixing 22 gauge chicken mesh wire at the junction of RCC and brick work with overlapping of 100mm on both sides, etc., complete.

2170

70

151900

... More
White washing with lime to give an even shade: New work (three or more coats)

6000

35

210000

... More
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.

21410

135

2890350

... More
Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour (Two or more coats on new work) complete, as per manufacturer’s specification.

21410

99

2119590

... More
Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm

6060

257

1557420

... More
Applying priming coat

-

-

-

... More
With ready mixed pink or Grey primer of approved brand and manufacture on wood work (hard and soft wood)

50

65

3250

... More
With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works.

1480

60

88800

... More
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade, Two or more coats on new work

1530

130

198900

... More
French spirit polishing : Two or more coats on new works including a coat of wood filler.

50

383

19150

... More
SUBHEAD-VII : FLOORING :

-

-

-

... More
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-in charge. (The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately).

441

8616

3799656

... More
Deduct for using of M-20 grade concrete instead of M-25 grade concrete in C.C. pavement.

-

-

-

... More
Making provision for contraction, expansion, construction and longitudinal joints (size 5x20mm) by groove cutting machine.

2065

62

128030

... More
Providing and filling in position at expansion joints (size 5x20mm) with poly sulphate sealants of approved brand.

2065

173

357245

... More
Supply and application of SealArm Tape TPE with adhesive ReArm Bond 4031 for 25mm width expansion joint. Work includes Insert backer rod same or higher dia into the joint and Apply of epoxy adhesive ReArm Bond 4031 first on the flanges of the joint followed by laying tape and press it on the adhesive. Again apply second layer of ReArm Bond 4031 on the tape (sandwiching the tape with adhesive both on top and bottom). Work including surface preparation all incl etc, not incl of joint protection works. Supply and apply of polyurethane sealant to expansion joint. work includes Insert backer rod of same or higher dia into the joint and apply polyurethane sealant - SealArm PU. Ensure that depth of sealant filling is atleast 1/2 of the width of joint as minimum criteria.

101

3115

314615

... More
Providing and placing the 2.0mm thick and 300mm width aluminium plate as a protection for the tape.

-

-

-

... More
Providing and fixing in position 12mm thick bitumen impregnated fiber board conforming to IS: 1838, including cost of primer, sealing compound Grade-A in expansion joints.

542

66

35772

... More
52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc., complete.

649

932

604868

... More
Providing cement skirting in CM (1:3) 18mm thick finished with a floating coat of neat cement etc., complete.

78

598

46644

... More
Supplying and applying Epoxy Flooring System as per the following Specification: Surface Preparation: The concrete surface should be free from dust, laitance, oil and grease. The surface should then be cleaned with copious amounts of water and then allowed to dry. Application of Primer: Supply and application of primer Nitoprime 25, after thoroughly mixing the base and hardener using a heavy duty slow speed drilling machine fitted with a paddle until a homogeneous mix is obtained, over the prepared surface to in a thin continuous film using a stiff brush/roller. Providing Earthing with Copper Strip: Over the cured epoxy underlay surface, supply and application of copper strip of 20mm width and 0.2mm thickness along the periphery

437

2492

1089004

... More
Application of Undercoat: Supply and application of Nitoflor SL Conductive Undercoat, after mixing the base and hardener thoroughly as described above, over the primed surface using roller/brush @ 6-7m2 per kg. Application of Topcoat: Supply and application of Nitoflor SL Conductive Topcoat after mixing the base, hardener, color paste and filler until a homogenous, lump free mix is obtained. The mixed material is poured on the primed surface and spread slowly and evenly to a thickness of 2 mm using a serrated steel trowel. Immediately after spreading, the floor should be firmly rolled with a spike roller to release any entrapped air and level any slight trowel marks

-

-

-

... More
Surface preparation:- Providing and cleaning all floor surface including wall up to required height to make it free from dirt, dust, loose particles, wax, polish, efflorescence, laitance, curing compound and other contaminants by using wire brush, grinding all sharp edges to make it flush with the surface etc and complete as per manufacturer's specification.

437

3807

1663659

... More
Priming:- Prepared substrates to be treated with FloArm SL Conductive system should be primed with FloArm Primer EP. FloArm Primer EP should be mixed in the proportions supplied by adding the entire contents of hardener can to the base can. Once mixed the FloArm Primer EP, should be immediately applied in a thin, continuous filmusing stiff brushes or rollers. Over application and puddles should be avoided. Porous floors may require two coats of FloArm Primer EP. FloArm Primer EP should be allowed to become tack free (over night Air dry) prior to application of Copper tape and subsequent FloArm SL Conductive Undercoat. Copper tape Fixing: - Make a suitable pattern to lay the copper strips of Copper band in a 5/5 m grid.

-

-

-

... More
Screed:FloArm Cempo4 is a three part; epoxy modified cementitious, fine textured mortar for self-smoothing floors creeds in thinlayers of 4mm

-

-

-

... More
Earthing connection: (where needed) should be placed at appropriate locations in consultation with MYK Arment Technical cell. Copper tape needs to be connected with this earthing connection.

-

-

-

... More
Applying undercoat: The mixed undercoat shall be applied with a roller or brush on the primer at a material consumption rate of 6m²/kg for FloArm SL Conductive under coat. Care shouldbe taken to avoid over application or puddles. Theundercoat provides a Conductive system passagetoearth so correct application and strict adherence tocoverage rates are critical to the final electrical propertiesof the completed floor. Adequate ventilation and air movement are necessary for complete curing of undercoat. Thorough covering of earthing connections isessential. The Resistivity of the undercoat needs to bemeasured before applying the top coat (after overnight Air Dry). the surface resistance (FloArm SL Conductiveundercoat) should be: approx. 3x103- 9 x103 Ohm

-

-

-

... More
Applying Topcoat: When mixed, FloArm SL Conductive Topcoat should bepoured immediately on to the surface and spread @2mmwith a steel trowel or a float. Immediately after applicationthe surface should be firmly rolled in perpendicular directions with a nylon spiked roller to help release anyentrapped air in the material and help to spread any slight trowel marks.

-

-

-

... More
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick.

280

2140

599200

... More
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.

141

2592

365472

... More
Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Size of Tile 600 x 600 mm

3889

1383

5378487

... More
Providing and laying Ceramic glazed floor tiles of size 300x300 mm(thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @3.3kg/sqm including pointing the joints with white cement and matching pigments etc., complete.

314

1248

391872

... More
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approvedmake, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.

832

1261

1049152

... More
Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.

170

2919

496230

... More
Polished Granite stone slab of all colour and texture except Black, Cherry/Ruby Red

-

-

-

... More
SUBHEAD-VIII : STEEL & WOOD WORKS :

-

-

-

... More
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete

52

102356

5322512

... More
Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete Fixed to openings /wooden frames with rawl plugs screws etc.

1410

245

345450

... More
Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including MS pressed blet hinges 2.50mm thick with morter guards, lock strike plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:

-

-

-

... More
Profile B, fixing with adjustable lugs with split end tail to each jamb

197

502

98894

... More
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:

-

-

-

... More
35 mm thick

88

1820

160160

... More
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross-section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.

149

550

81950

... More
Providing and fixing to existing door frames, 30 mm thick Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames.

48

3573

171504

... More
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).

195

1467

286065

... More
Providing and fixing the following hardware fittings of approved make:

-

-

-

... More
200mm long SS Tower Bolts

956

309

295404

... More
SS Aldrop 300mm long

302

378

114156

... More
Providing and fixing bright /matt finished Stainless Steel handles of approved quality & make with necessary screws etc all complete.

-

-

-

... More
125mm long

972

203

197316

... More
Providing and fixing aluminium hanging floor door stopper (Single rubber stopper), ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.

486

77

37422

... More
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.

87

981

85347

... More
Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately). Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made.

265

9382

2486230

... More
Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. Three track three panels sliding window with fly proof S.S wire mesh (Two nos. glazed & one no. wire mesh panels) made of (big series) frame 116 x 45 mm & sash 46 x 62 mm both having wall thickness of 2.3 ± 0.2 mm and single glazing bead / double glazing bead of appropriate dimension. (Area of window above 1.75 sqm).

-

-

-

... More
Providing and fixing Motorised Sliding Door of size 6 x 8 m CE Certified As Per European Standard BS EN 13241-1:2003+A1:2011 Single Side 0.50 mm thick GI Cladding Sheet Both Side Automation System : Bottom Drive Inbuilt wicket door with, locking arrangement & auto sensor - (w)1000 x (h)2100 mm Enamel Paint including all necessary fittings,hardwares etc complete as directed engineer in charge.

1

1385660

1385660

... More
Providing and fixing Motorised Sliding Door CE Certified As Per European Standard BS EN 13241-1:2003+A1:2011 Single Side 0.50 mm thick GI Cladding Sheet Both Side Automation System : Bottom Drive Enamel Paint including all necessary fittings, hardwares etc complete as directed engineer in charge.

-

-

-

... More
D1 ( 3.5 x 2.1)

4

310493

1241972

... More
D2 (2.5 x 2.1)

7

265781

1860467

... More
D3 (2 x 2.1)

21

242940

5101740

... More
ED ( 2 x 2.1)

2

242940

485880

... More
Providing and fixing Motorised GI Rolling Shutter CE Certified As Per European Standard EN 13241-1:2003+A1:2011 GI Slat Box Type Guide Powder Coated Motorised System : Indirect Drive With Std. Control Push Button - 1 No. Hood Cover - R/Meter including all necessary fittings,hardwares etc complete as directed engineer in charge.

-

-

-

... More
RS1 (4 x 3)

3

165975

497925

... More
RS2 (3 x 3)

3

141750

425250

... More
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters.

-

-

-

... More
80x1.25 mm M.S. laths with 1.25 mm thick top cover

12

3495

41940

... More
Providing and fixing ball bearing for rolling shutters

8

541

4328

... More
STRUCTURAL STEEL :

-

-

-

... More
Analysis, Design, Engineering, Preparation of Detailed Drawings, MAnufacturing, Fabrication, Supply, Loading,Transporting to SIte, Unloading, Erection of Steel PEB(Pre-Engineered Building)System, Consisting of MS Plates of 345MPa yield strength and Coating Thickness of 275gsm for columns, jack trusses, crane beams, Platforms, canopies, lattice girders, rafter , sub rafters , at all elevations, levels and heights including aligning, leveling, providing and fixing bolts, nuts, washers, comprising MS angles, chann`els, joists, rails, tees, plates, rounds, squares,etc., of various sizes and other structural steel sections conforming to latest IS CODE including straightening, cutting, welding, bending to shape, bolting, and inclusive of Grit / sand blasting and applying two coats of Synthetic Enamel paint over one coats of approved Zinc Chromate primer .

-

-

-

... More
The rate to include the cost of all materials, labours, tools, tackles, cranes, devices and plants, bolts, nuts, washers, clamps, welding electrodes and connection required for work, shims and packing pieces, any cutting, fabrication work required on electrically operated machines in the work shop including transportation to site and erection as per specifications and drawing complete.

-

-

-

... More
a) For trusses , Rafters, gable frame ,lattice girders, Jack Beam, Crane beams, Columns. etc at all heights.

19

151163

2872097

... More
Supplying, fabricating, hoisting and erecting in position Purlins , cladding runners, girts of minium 345mpa jeild strength at all elevations, levels and heights including aligning, leveling, providing and fixing bolts, nuts, washers, comprising MS angles, channels, joists, rails, tees, plates, rounds, squares etc., of various sizes including straightening, cutting, welding, bending to shape, bolting, Acid Pickling / GALVANISING of minium 120gsm & inclusive of following finishes. structural Grit blasting and applying two coats of Synthetic Enamel paint over one coat of Zinc Chromate primer of approved make and colour as per specifications and drawing complete.

6

148879

893274

... More
Providing and fixing in position GI High Strength Foundation Bolts of approved make of with nuts of various diameters and lengths confirming with IS 4000-1992, Class 8.8 Type I for joining of various Structural components like Column, Rafters, Jack Beams, etc., including work at all levels and locations complete all as shown in the drawing

1

199474

199474

... More
TOP SHEET : Supply of 360-degree FORTISS™ 470 standing seam panels shall be 470mm effective cover width, 73mm rib height, with strengthening rib/ flute in the pan for strength. The end lap shall be seamed with 360 degree seeming using Seamer machine. The sheeting material shall be 0.50 mm Base Metal Thickness (BMT), (0.55mm TCT, 0.58mm TPT). The steel sheet is having high tensile strength G300 (Fy=300Mpa), metallic coated with Zinc-Aluminium alloy (i.e. 55% Al, 43.4% Zinc, 1.6% Si - Zincalume), AZ150 (min 150 g/m2 total on both side), pre-painted with NextGen COLORBOND® XRW. The sheet conforms to general requirement of AS/NZS 2728 type 4 / IS 15965 class 3 durability of Tata BlueScope Steel make. The sheet shall be IGBC Green pro, Griha, EPD certified and steel sheet shall have brand marking of coated steel manufacturer (product details, date, mfg. name, etc.) on back side at regular interval confirming genuinity of the material.

2151

3212

6909012

... More
ROOF INSULATION: Insulation shall be 50mm thick, density 48kg/m3 Rockwool with or without facing as per design requirement complying with IS8183 BS - 3958 Part-5. ASTM C592-80, as approved by engineer in-charge shall be laid uniformed over Purlin. SUB GIRTS: LYSAGHT ZED-plus™ purlins and Girts 1.5mm thick high strength galvanized steel with min 345 MPa yield strength, zinc coating of Z275 (275 g/m2 minimum coating mass) confirms to IS 277 / IS 15961 pre-punched to the required dimensions, suitable for roof and wall cladding support and portal framing up to a certain span. The design of cold formed ZED-plus purlins sections shall be subject to the requirement of IS 801 / AISI 1996, cold formed steel structures code. LINER - Bottom Sheet : Pre-painted Zincalume trapezoidal sheets shall be made of 0.45mm BMT (0.50mm TCT, 0.53mm TPT), G550 (min 550 yield strength), 1015mm effective cover width with five major corrugation, 28mm high rib spaced at 203mm c/c with subtle square fluting in the pan and the end rib shall have anti-capillary groove and return leg of Lysaght Trimdek. Color : COLORBOND XRW Standard

-

-

-

... More
OUTER SHEET : Pre-painted Zincalume trapezoidal sheets shall be made of 0.45mm BMT (0.50mm TCT, 0.53mm TPT), G550 (min 550 yield strength), 1015mm effective cover width with five major corrugation, 28mm high rib spaced at 203mm c/c with subtle square fluting in the pan and the end rib shall have anti-capillary groove and return leg of Lysaght Trimdek. Steel should be metallic coated with Zinc-Aluminium alloy (i.e., 55% Al, 43.4% Zinc, 1.6% Si - Zincalume), AZ150 (min 150 g/m2 total on both side), pre-painted with NextGen COLORBOND® XRW. The sheet conforms to general requirement of AS/NZS 2728 type 4 / IS 15965 class 3 durability of Tata BlueScope Steel make. The sheet shall be IGBC Green pro, Griha, EPD certified and steel sheet shall have brand marking of coated steel manufacturer (product details, date, mfg. name, etc.) on back side at regular interval confirming genuinity of the material.

176

2450

431200

... More
Wall INSULATION: Insulation shall be 50mm thick, density 48kg/m3 Rockwool with or without facing as per design requirement complying with IS8183 BS - 3958 Part-5. ASTM C592-80, as approved by engineer in-charge shall be laid uniformed over Purlin. SUB GIRTS: LYSAGHT ZED-plus™ purlins and Girts 1.5mm thick high strength galvanized steel with min 345 MPa yield strength, zinc coating of Z275 (275 g/m2 minimum coating mass) confirms to IS 277 / IS 15961 pre-punched to the required dimensions, suitable for roof and wall cladding support and portal framing up to a certain span. The design of cold formed ZED-plus purlins sections shall be subject to the requirement of IS 801 / AISI 1996, cold formed steel structures code. LINER - INNER Sheet : Pre-painted Zincalume trapezoidal sheets shall be made of 0.45mm BMT (0.50mm TCT, 0.53mm TPT), G550 (min 550 yield strength), 1015mm effective cover width with five major corrugation, 28mm high rib spaced at 203mm c/c with subtle square fluting in the pan and the end rib shall have anti-capillary groove and return leg of Lysaght Trimdek. Color : COLORBOND XRW Standard

-

-

-

... More
Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in true horizontal level, suspended on interlocking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc.

2490

1815

4519350

... More
Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanized butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.

-

-

-

... More
8 mm thick fully perforated calcium silicate board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process to give stable crystalline structure with minimum compressive strength 225 kg/ sq. cm, bending strength 100 kg/sq. cm , of size 595x595 mm, having perforation of dia. 10 mm with minimum perforated area 18 % with non woven tissue on the back side, having an NRC (Noise Reduction Coefficient) of 0.85, with 50 mm thick rockwool of 48 kg /cum backing.

-

-

-

... More
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre,

1454

862

1253348

... More
shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with :

-

-

-

... More
12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) : 2011 (Board with BIS certification marks)

-

-

-

... More
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).

1840

985

1812400

... More
SUBHEAD- IX : MISCELLANEOUS:

-

-

-

... More
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations:

2130

1333

2839290

... More
a) Applying a slurry coat of neat cement using 2.75 kg/Sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment.

-

-

-

... More
b) Laying brick bats with mortar using broken bricks/brick bats 25mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs.

-

-

-

... More
c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ Sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge.

-

-

-

... More
d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement : 4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300mm square 3 mm deep.

-

-

-

... More
e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge, with average thickness of 120 mm and minimum thickness at khurra as 65 mm.

-

-

-

... More
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.

-

-

-

... More
Single socketed pipes of 110mm diameter

473

427

201971

... More
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.

-

-

-

... More
110mm Bend 87.5°

65

160

10400

... More
110mm Shoe (Plain)

65

139

9035

... More
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete.

-

-

-

... More
110mm

130

139

18070

... More
SUBHEAD-X : SANITARY SERVICES:

-

-

-

... More
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :

-

-

-

... More
White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests.

2

8057

16114

... More
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :

-

-

-

... More
W.C. pan with ISI marked white solid plastic seat and lid.

18

10022

180396

... More
Providing and fixing floor mounted, white vitreous china single piece, double traps syphonic water closet of approved brand/make, shape, size and pattern including integrated white vitreous china cistern of capacity 10 litres with dual flushing system, including all fittings and fixtures with seat cover, cistern fittings, nuts, bolts and gasket etc., including making connection with the existing P/S trap, complete in all respect as per directions of Engineer-in-Charge.

2

10850

21700

... More
Providing and fixing G.I. inlet connection for flush pipe connecting with W.C. pan.

20

125

2500

... More
Providing and fixing white vitreous china flat back urinal basin of 430x260x350 mm size.

8

5939

47512

... More
Providing and fixing C.P 15 mm Urinal spreader size 95x69x100 mm with 1/2" BSP thread and shapes, weighing not less than 60 gms.

8

126

1008

... More
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required :

-

-

-

... More
White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar taps.

18

6727

121086

... More
Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings.

2

5359

10718

... More
Providing and fixing toilet paper holder, C.P. Brass.

20

1569

31380

... More
Supply and fixing of 15 mm CP Health faucet Cum bib tap with 1.25 mts long tube with end nuts and hook and 1 no 15 mm CP brass angular stop cock with wall flange, Hook to be fixed with CP brass with suitable counter sunk screws, all of approved make etc., complete.

20

1869

37380

... More
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.

-

-

-

... More
Granite of any colour and shade.

18

4373

78714

... More
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc., complete as per design approved by Engineer-in-Charge.

-

-

-

... More
Granite Work

40

441

17640

... More
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/Granite/stone work, including necessary holes for pillar taps etc., including moulding, rubbing and polishing of cut edges etc. complete.

20

891

17820

... More
Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth.

-

-

-

... More
Granite Stone of approved shade

20

3547

70940

... More
Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.

-

-

-

... More
32mm dia Flexible pipe

40

102

4080

... More
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

20

5400

108000

... More
Providing and fixing CP towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms.

20

1517

30340

... More
Providing, fixing, testing and commissioning of 75 mm pipe diameter uPVC SWR Type B pipe comforming to IS : 13592, including jointing with seal ring conforming to IS : 5382 for vertical pipe & Selfit uPVC Adhesive solvent joint inside in the toilet, including all fittings such as bends, junctions, inspection doors, offests, cowl, clean out, access pieces/plugs etc. complete the job. The rate shall be including all the engineered support at every one Meter (support, hanger, nuts/ bolts, anchor fasteners, fixing clamp/channels with U-bolts, etc) as per detail technical specification etc. complete the job.

-

-

-

... More
100mm dia upvc/ SWR Single socket

65

451

29315

... More
75mm dia UPVC/SWR Single socket

180

255

45900

... More
Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete for UPVC SWG Pipes conform to is 13592-1992.

-

-

-

... More
100mm dia UPVC/SWR Single socket

20

237

4740

... More
75mm dia UPVC/SWR Single socket

20

148

2960

... More
Providing and fixing PVC door bends as per IS - 13592-1992 single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete.

-

-

-

... More
100x100x100 mm

20

295

5900

... More
75x75x75 mm

20

214

4280

... More
Providing and fixing terminal guard, Sand cast iron S&S as per IS - 3989.

-

-

-

... More
100mm dia.

20

412

8240

... More
75mm dia.

20

325

6500

... More
Providing and fixing M.S. stays and clamps for pvc pipes of diameter.

-

-

-

... More
100mm

20

143

2860

... More
75mm

20

143

2860

... More
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors, Sand cast iron S&S as per IS: 3989.

-

-

-

... More
100 mm inlet and 100 mm outlet

10

1789

17890

... More
Cutting chases in brick masonry walls for following diameter sand cast iron/ centrifugally cast (spun) iron pipes and making good the same with cement concrete 1:3:6 ( 1 cement : 3 coarse sand :6 graded stone aggregate 12.5 mm nominal size), including necessary plaster and pointing in cement mortar 1:4 (1 cement : 4 coarse sand) :

-

-

-

... More
100mm dia.

50

643

32150

... More
75 mm dia

50

474

23700

... More
Supply and fixing in position best quality and approved make CP brass coat hooks with flanges fixed to wall/door shutters with necessary screws washers etc., complete.

20

263

5260

... More
SUBHEAD-XI : WATER SUPPLY SERVICES :

-

-

-

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. - External Work.

-

-

-

... More
25 mm dia nominal bore

230

455

104650

... More
32 mm dia nominal bore

128

742

94976

... More
40 mm dia nominal bore

200

515

103000

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc.,

-

-

-

... More
15 mm dia nominal bore

50

542

27100

... More
20 mm dia nominal bore

50

557

27850

... More
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :

-

-

-

... More
25 mm dia nominal bore

5

615

3075

... More
32 mm dia nominal bore

5

682

3410

... More
40 mm dia nominal bore

5

825

4125

... More
Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.

5000

12

60000

... More
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :

-

-

-

... More
25 mm nominal bore

10

613

6130

... More
Providing and fixing CP brass bib cock of approved quality :

-

-

-

... More
15 mm nominal bore

20

867

17340

... More
Providing and fixing CP brass stop cock of approved quality :

-

-

-

... More
15 mm nominal bore

20

836

16720

... More
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931.

-

-

-

... More
15 mm nominal bore

20

728

14560

... More
Making chases up to 7.5x7.5 cm in walls including making good and finishing with matching surface after housing G.I. pipe etc.

50

186

9300

... More
SUBHEAD-XII : INTERNAL ELECTRIFICATION :

-

-

-

... More
Point Wiring for Light/ Fan/ exhaust fan with 2 runs of 1100V grade 1.5 Sq.mm & 1 run of 1.5 Sq.mm PVC insulated multistrand , FRLS , Copper conductor wires , run in and including 25mm dia heavy gauge PVC conduits concealed in wall / ceiling conforming to IS 732 including all accessories such as junction boxes, conduit bends elbows and anodised GI Switch box with modular switch and the box covered with front plate including connections to Earth terminal.

-

-

-

... More
One Light point controlled by one 6 A switch.

120

1963

235560

... More
Two Light point controlled by one 6 A switch.

180

2664

479520

... More
Three Light point controlled by one 6 A switch.

50

3042

152100

... More
Four Light point controlled by one 6 A switch.

30

4439

133170

... More
Ceiling fan point controlled by one 6 A switch and electronic fan regulator of 100 W step type with concealed MS fan hook box.

110

2822

310420

... More
Exhaust fan point controlled by one 6 A switch.

36

1963

70668

... More
Point Wiring for Light/ Fan/ exhaust fan with 2 runs of 1100V grade 1.5 Sq.mm & 1 run of 1.5 Sq.mm PVC insulated multistrand , FRLS , Copper conductor wires , run in and including 25mm dia , 14SWG black enameled MS conduits surface / concealed in wall / ceiling conforming to IS 732 including all accessories such as junction boxes, conduit bends elbows and anodised GI Switch box with modular switch and the box covered with stainless steel front plate including connections to Earth terminal.

-

-

-

... More
One Light point controlled by one 6 A switch.

10

6287

62870

... More
Two Light point controlled by one 6 A switch.

8

5674

45392

... More
Three Light point controlled by one 6 A switch.

6

6339

38034

... More
Four Light point controlled by one 6 A switch.

4

6767

27068

... More
Point Wiring for Light/ Fan/ exhaust fan with 2 runs of 1100V grade 2.5 Sq.mm & 1 run of 2.5 Sq.mm PVC insulated multistrand , FRLS , Copper conductor wires , run in and including 25mm dia , 14 SWG black enameled MS conduits surface / concealed in wall / ceiling conforming to IS 732 including all accessories such as junction boxes, conduit bends elbows etc including connections to Earth terminal.

-

-

-

... More
One Light point controlled by one 6A SP MCB

20

3020

60400

... More
Two Light point controlled by one 6A SP MCB

18

3686

66348

... More
Three Light point controlled by one 6 A SP MCB .

10

4417

44170

... More
Four Light point controlled by one 6 A SP MCB

10

4911

49110

... More
Point Wiring for Light/ Fan/ exhaust fan with 2 runs of 1100V grade 1.5 Sq.mm & 1 run of 1.5 Sq.mm FRLS insulated multistranded Copper wires, run in & including 25mm dia, 14 SWG MS conduits surface / concealed in Slab/ wall after necessary chase cutting with finishing/surface in wall / ceiling conforming to IS 732 including all accessories such as junction boxes, conduit bends, elbows and ceiling rose, anodised GI Switch box with modular switch and the box covered with front plate and also including connections to Earth terminal.

-

-

-

... More
One Light point controlled by one 6A Switch

20

2418

48360

... More
Two Lights point controlled by one 6A switch.

10

2990

29900

... More
Three Lights point controlled by one 6A switch.

4

3656

14624

... More
Four Lights point controlled by one 6A switch.

4

4083

16332

... More
Supply and fixing of 6A, 3Pin Socket outlet with 6A switch in Lighting switch boards. (Dependant).

80

1409

112720

... More
Supply and fixing of 6A, 3Pin Socket outlet with switch of 6A rating with wiring of 2 Runs of 2.5 Sqmm and 1 Run of 2.5 Sqmm FRLS, PVC insulated multistranded Copper conductor wires run in and including 25 mm Dia, 2 mm thick PVC conduit. (Independant).

200

2231

446200

... More
Supplying and fixing suitable size GI box with modular Stainless Steel plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in Clean Room).

20

3946

78920

... More
Supply and Wiring with the following size 1100V grade PVC insulated multistrand FRLS Copper conductor wires in and including suitable size heavy gauge PVC conduit concealed in wall / Ceiling including all accessories such as junction boxes, bends, elbows including end terminated with suitable lugs.

-

-

-

... More
2 runs of 2.5 Sq.mm wires with 1run of 2.5 Sq.mm wire in and including 25 mm Dia PVC Conduit (For Lighting Circuit)

4000

304

1216000

... More
4 runs of 6 Sq.mm wires with 2 runS of 6 Sq.mm wires in and including 32 mm Dia PVC Conduit (For Lighting Sub Mains)

1000

727

727000

... More
Supply and Commissioning of the following type Fluorescent/ Compact fluorescent light fixtures on wall/ Ceiling including all fixing accesssories such as leads, etc complete as required. The Fluorescent/CFL fixtures shall be complete with Low loss copper ballast PF improvement capacitor, Bipin Rotor type lamp holder,starter, starter base, all prewired upto the terminal block. All fixtures shall be supplied with lamps. The Catalogue Numbers refers to Philips Make.

-

-

-

... More
36 W Surface mounted LED 4 Feet Length Luminaire

126

2388

300888

... More
(Philips : BN308C LED40S-6500 L120 PSU WH/or Equivalent as per approved makes)

-

-

-

... More
1 x 12 W Surface Mounted LED Luminaire

70

896

62720

... More
(Philips Cat No : SM250C LED 12S-6500PSU WH or Equivalent as per approved makes)

-

-

-

... More
40 W Recess Mounted LED Light Fixture

180

3582

644760

... More
(Philips Cat No :RC 380 B LED 40S-6500 G4L60W60 PSU OD/Equivalent as per approved makes)

-

-

-

... More
20W Recess mounted Down Light Fixture

170

2239

380630

... More
(Philips Cat No DN296B LED20S-6500 PSU WH S2/Equivalent as per approved makes)

-

-

-

... More
36W Surface mounted Square Light Fixture

6

5971

35826

... More
(Philips Cat No SM36S -6500 G6L54W54 PSU OD/Equivalent as per approved makes)

-

-

-

... More
40 W Bulk Head Light Fixture Indoor

10

746

7460

... More
(Philips Cat No WT 202W LED 10S CW PSU S3 PC/Equivalent as per approved makes)

-

-

-

... More
210W LED High Bay Light Fixture

40

17539

701560

... More
(Philips Cat No BY616P LED200S 5700 WB PSU GR/Equivalent as per approved makes)

-

-

-

... More
104W LED High Bay Light Fixture

15

8142

122130

... More
(Philips Cat No BY225P LED104S CW SYWB PSU FG GR V2/Equivalent as per approved makes)

-

-

-

... More
36W LED 2' X 2' Top openable cleanroom Light Fixtures

30

12213

366390

... More
(Philips Cat No CR652B LED36S-6500 PSU CA BO W30L120 WH /Equivalent as per approved makes)

-

-

-

... More
Supply and Installation Testing and Commisioning of 1200 mm sweep single phase Ceiling fan including fixing accessories etc., complete.( BEE 5 star rated ceiling fan )

110

2296

252560

... More
Supply and Installation Testing and Commisioning of 600 mm dia sweep single phase wall mounted fan including fixing accessories etc., complete.

10

6835

68350

... More
Supply and Installation Testing and Commisioning of 600 mm dia Air circulator single phase wall mounted with metal blades including fixing accessories etc., complete.

20

8101

162020

... More
Supply and commissioning of 305 mm sweep Exhaust fans with Metallic blades and MS gravity louvers including all accessories / Installation materials required.

36

3061

110196

... More
Installtion of Fluorescent/ Compact fluorescent light fixtures on wall/ Ceiling including all fixing accesssories such as leads, etc complete as required.

546

114

62244

... More
Installation of 1200 mm sweep white colour Ceiling fan with standard down rod (600mm length down rod in false ceiling areas) and all accessories as required etc complete.

110

382

42020

... More
Installation of 305 mm sweep Exhaust fans with Metallic blades and MS gravity louvers including all accessories / Installation materials as required.

36

455

16380

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)

-

-

-

... More
8 way (8 + 24), Double door

8

9628

77024

... More
4 way (8 + 12), Double door

2

6840

13680

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
40A

10

5932

59320

... More
Supplying and fixing of 6A to 32A rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.

-

-

-

... More
Single Pole

216

381

82296

... More
Supplying and fixing following way, vertical type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)

-

-

-

... More
8 way (4 + 24), Double door

3

18060

54180

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, molded case circuit breaker (MCCB), having a breaking capacity 25 KA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
160A 4P MCCB, 25 kA

3

16311

48933

... More
Supplying and fixing of following rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.

-

-

-

... More
40A Three Pole MCB 10 kA

24

2502

60048

... More
SUBHEAD-XIII : AIR CONDITION:

-

-

-

... More
HVAC SYSTEM

-

-

-

... More
All works should include supply, installation,testing, commissioning and handling over.

-

-

-

... More
The equipment shall be five star rated where were mentioned

-

-

-

... More
All Techincal data sheet & drawing shall be submitted and get approved by department before supply

-

-

-

... More
All equipment factory inspection shall be carried out by department

-

-

-

... More
First prefers as per BOQ followed by Techincal specification

-

-

-

... More
VARIABLE REFRIGERANT FLOW (VRF) / VARIABLE REFRIGERANT VOLUME (VRV)

-

-

-

... More
Supply, Installation, Testing & Commissioning & Handing over of the following:

-

-

-

... More
HIGH SIDE VRF/VRV EQUIPMENT

-

-

-

... More
VRF/VRV HI BRID AIR-CONDITIONING EQUIPMENTS: (100% INVERTER TYPE ONLY TO BE QUOTED) - R410A Refrigerant

-

-

-

... More
Supply, Lifting, Shifting, Positioning, Installation, Testing , commissioning & handing over of VRV/VRF air conditioning system unit suitable for cooling and heating mode having all hermetically sealed inverted type screw compressor with 5 Star and above Rating as per OEM comprising of Modular type high efficiency Twin Rotary Multiple Compressor with inverter, High efficiency heat transfer Cooling Coil suitable for Environment friendly R410a refrigerant,Air cooled propeller type condenser fan with DC motor drive,interconnecting piping, suction line insulation etc., Micro-processor control panel suitable for automatic operation,High speed calculation inverter control, active oil control mechanism incorporating all safety functions as per equipment specifications & other points as listed below:

-

-

-

... More
The unit mounted starter panel shall be complete with IP-65 protection consisting of power disconnecting switches with fuses, soft starters, for compressor motors, under/over voltage trip, single phase preventers, communication card which can accept 4-20 mA or 2-10 Vdc analog signal.

-

-

-

... More
All components shall be mounted on welded steel base frame, structural steel profiles/panels made out of galvanized sheet steel, protected with primary coat & finished with epoxy paint.

-

-

-

... More
Modular type outdoor units equipped with highly efficient scroll compressors, with inverter type compressor(s),special acryl precoated heat exchanger,low noise condenser fan,auto check function for connection error, auto address & UNIT Price shall be inclusive of outdoor stand price. Shifting & Installing of ODU as per shop drawing is part VRV vendor scope.(ODU Location & Capacity mentioned below). Shifting of Out door units from GF to repective location is part of VRF vendor scope . ODUs shall have service valve station for easy operations and monitoring of system

-

-

-

... More
All VRV units should be compatible for third party BMS integration .necessary integrator should be consider in part HVAC VRF/VRV vendor scope (Bacnet over MSTP protocol to be considered for BMS compatibility requirement). Centralized controller shall be considered combined for all the VRF/VRV indoor and outdoor units and same to be located in a specific location as per client requirement.

-

-

-

... More
Supply & providing of MS stand for VRF/VRV ODU along with proper supports-suitable for above configuration

-

-

-

... More
Installation and pressure testing with nitrogen Gas, Vaccumising including all consumables for all system shall be part of scope of supply (Pre commissioning )

-

-

-

... More
First Filling, testing, commissioning including topping up of R410 A Refrigerant Gas.

-

-

-

... More
Factory acceptance test to be conducted for all the units and cost of the same to be included

-

-

-

... More
Testing tools and instruments of approved make and required quantity tobe maintained by Contractor

-

-

-

... More
Contractor shall engage dedicated commissioning manager for project and shall coordinate for all testing activities and documentations

-

-

-

... More
Central remote controller should be considered and provided along with VRF/VRV units

-

-

-

... More
With all necessary accessories including vibration insolation i.e fixing etc complete.

-

-

-

... More
Lifting, shifting and positioning of VRF/VRV System as per design location

-

-

-

... More
Outdoor unit suibtable for both cooling & heating mode having all hermetically sealed inverted type scroll compressor, minimum two compressors for above 14hP Modules, microprocessor based controller.

-

-

-

... More
The unit shall be delived the rate capacity at AHRI conditions and work even at 50c ambient temperature with out tripping

-

-

-

... More
The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5.The motor shall be by IEE3 Rated

-

-

-

... More
(*Note:The cost includes the maintenance granttee includes 24months from the date of Commissioning without any additional cost) MAKE: Daikin, Blue star, Voltas, Carrier, Trane.

-

-

-

... More
Outdoor Unit (ODU) : Cooling Capacity : 218HP

1

3194921

3194921

... More
Outdoor Unit (ODU) : Cooling Capacity : 56HP (CLEAN ROOM)

1

820714

820714

... More
INDOOR UNITS

-

-

-

... More
Indoor Unit (IDU): Cooling type All the units should be supplied with thermostat control. The following Indoor unit capacities are required for each type of Room. considered for Auto change over,failure status,overload sequencing etc. Along with proper supports-suitable for above configuration With all necessary accessories i.e fixing etc complete.

-

-

-

... More
It should be suitable for BMS connectivity with necessary accessories.

-

-

-

... More
4-WAY CASSETTE UNIT

-

-

-

... More
Four way Cassette 1.6TR

2

36680

73360

... More
Four way Cassette 2.0TR

20

37461

749220

... More
Four way Cassette 2.6TR

33

41076

1355508

... More
Four way Cassette 3.2TR

4

42542

170168

... More
HI-WALL SPLIT UNIT

-

-

-

... More
Hi-wall Unit 1.0TR

4

24019

96076

... More
Hi-wall Unit 1.6TR

1

26462

26462

... More
Hi-wall Unit 2.0TR

3

28986

86958

... More
Hi-wall Unit Drain Pump

8

2931

23448

... More
AIR HANDLING UNITS

-

-

-

... More
Supply, installation, testing, commissioning and handing over of following capacity floor mounted Thermal Break Double skin construction with internal and external sheets of 1.0 mm thickness with galavanizing of 120 gm/m2 ,Air handling unit made out of extruded aluminium structural frame work. Panels shall be made of 50 mm PUF injected panels having density 43 Kg/m3 in galvanised sheet casings having scratch free preplasticised coating on galvanised sheet on external side and plain GI inner sheet. The whole unit shall be mounted on spring isolators

-

-

-

... More
i) The Air handling unit shall comprise of fan section with Plug Fan/ Backward curved fan with limit load characteristics , spark proof fan. fan mounted on the scroll and not on the casing, coil section comprising of vrv/vrf water coil,stainless steel drain pan under coil section, Filter section comprising of prefilter 10 micron and 3 micron fine filters,mixing box along with RA and FA dampers etc. complete in all respect whether specifically spelt or not but required to complete the system works.

-

-

-

... More
The entire unit casing shall be weather proof , made out of 50 mm thk. 43 Kg/ cum density double skin PUF panels. The entire assembly of the unit shall be mounted on a rigid GSS base frame. Inner skin of the panel shall be 1 mm thick GSS plain and the outer skin shall be with 1 mm thk. Pre plasticized powder coated. The total unit along with VRV/VRF coils and hot water coil shall be AHRI certified. The face velocity of the coils shall not exceed 500 FPM . The face velocity across the filters shall not exceed 500 FPM.

-

-

-

... More
The coils and filters shall be full face of the unit. The fan and motor shall be mounted on a common base frame with cushy foots / spring isolator to avoid vibration transmission to the base of the unit. The motor shall be effiency 1 and with VFD compatable.

-

-

-

... More
The fan shall be AMCA certified and motor shall be energy efficient EFF1. The fan out let velocity shall limit to 12 m/ sec. The fan access door shall have safety door interlock arrangement with motor. The unit shall be supplied with fire retardant double canvass connection between the fan out let and supply air flange.

-

-

-

... More
Variable frequency drives including harmonic filters and surge suppresors to be installed in independently with bypass starter panel and also differential pressure sensor with cabling from the sensor located on the duct to the VFD for Air handling units of following capacity Motors including necessary fittings and fixing accessories etc., complete

-

-

-

... More
The unit shall be supplied with an outlet flange at the the supply air side along with opposed blade volume control damper. The damper casing and blades shall be made out of 16 G Aluminum.

-

-

-

... More
The scope includes one set of commissioning filters along with the VFD & Starter panel with Bypass and control panels with MCB,MCCB.

-

-

-

... More
The AHU unit shall outdoor type with all season weather proof protection

-

-

-

... More
The noise level at all-round the unit shall limit to 60 dBA from 1 m distance to the unit.

-

-

-

... More
The fan curves, coil selection and technical data sheet shall be submitted by vendor for scrutiny.

-

-

-

... More
The unit shall be included with AHU & VFD DRIVE STATER & CONTROL PANEL

-

-

-

... More
The unit shall be included with AHU CONTROLL KITS WITH CORDED REMOTES

-

-

-

... More
Unit shall be ultra violet lamp to kill germs/fungus

-

-

-

... More
AHU1 - 20 TR capacity , total air qty 15200 cfm, 65mm Static pressure with suitable High efficency motor, 30.4sqft area of 6 row coil,

1

498535

498535

... More
Heater section should be with 8kW electric strip heater in 2 banks.

1

13027

13027

... More
AHU1 - 45 TR capacity , total air qty 50000 cfm, 150mm Static pressure with suitable High efficency motor, 100 sqft area of 6 row Dx coil

1

1034685

1034685

... More
Heater section should be with 10kW electric strip heater in 2 banks.

1

16284

16284

... More
Imported fittings like Y-Joints and headers etc as per the layout (additional supports should consider for both ends of the Y joint) With all necessary accessories i.e fixing etc complete.

90

4470

402300

... More
CENTRAL CONTROLLER & REMOTE SYSTEM (FOR VRF UNITS)

-

-

-

... More
Centarl controller integrating advanced I Touch screen display Controller type (System controller) for floor Indoor units with necessary software & spare parts. It shall be BMS compatible with BACNet over MSTP output to connect to the main IBMS system and showes real time data for both temperature Limitation and RH% in screen display. This Controller shall be stand-alone controller with features like visual navigation, graphical report, Multi-PC access and have the capability to program for sequential operation of indoor units etc.,complete.

1

65136

65136

... More
LOW SIDE VRV/VRF EQUIPMENT

-

-

-

... More
REFRIGERANT PIPING

-

-

-

... More
Interconnecting copper refrigerant pipe work duly insulated with elastomeric nitrile rubber type tubular insulation between indoor & outdoor units as per specifications . All piping inside the room shall be properly supported with hanger and all piping should be run in perforated cably tray.Cable tray qty specified seperately.. MS supports for refrigerant piping & cables, using angles, channels, Tees, flats, etc should be considered as part of scope.All MS supports shall be given a coat of red-oxide primer and two coats of synthetic enamel paint of approved colour. Class O insulation to be considered for the piping insulation. Cu.pipes shall be supported with PVC sleeves with clamps around and all wall/partition crossings shall have PVC sleeves

-

-

-

... More
41.3mm OD (insulation =19 mm thick)

20

2964

59280

... More
38.1mm OD (insulation =19 mm thick)

25

2459

61475

... More
34.9mm OD (insulation =19 mm thick)

20

2215

44300

... More
31.8mm OD (insulation =19 mm thick)

18

1873

33714

... More
28.6mm OD (insulation =19 mm thick)

200

1596

319200

... More
25.4mm OD (insulation =13 mm thick)

35

1262

44170

... More
22.2mm OD (insulation =13 mm thick)

40

1091

43640

... More
19.1mm OD (insulation =13 mm thick)

55

961

52855

... More
15.9mm OD (insulation =13 mm thick)

650

953

619450

... More
12.7mm OD (insulation =13 mm thick)

60

708

42480

... More
9.5mm OD (insulation =13 mm thick)

500

529

264500

... More
6.4mm OD (insulation=13mm thick)

60

415

24900

... More
DRAIN PIPE

-

-

-

... More
Supply & Installation of CPVC drain pipe insulated with 6 mm thick closed cell FM approved class O nitriler rubber insulation. Necessary U trap for units with clean out plugs to be provided

-

-

-

... More
32 mm dia

150

218

32700

... More
25 mm dia

350

179

62650

... More
Providing & fixing of 2 Cx 1.5 sqmm cu. cable for control cum trans-mission between Indoor unit and Out Door Unit through PVC Conduit.

800

194

155200

... More
Supply & providing of MS stand for VRV ODU along with proper supports-suitable for above configuration

3

2544

7632

... More
Supply and installing following size of perforated Hot Dipped Galvanised iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections,joined with connectors,suspended from the ceiling with G.I. suspenders including including Cover on above tray, G.I. bolts & nuts, etc. as as required and also inculding 14 SWG GI cover sheet with 40x5mm GI strip on both sides.

-

-

-

... More
150mm wide x 75mm Height, 1.6mm thick

460

900

414000

... More
300mm wide x 75mm Height, 1.6mm thick

150

1271

190650

... More
450mm wide x 75mm Height, 1.6mm thick

60

1648

98880

... More
MECHANICAL VENTILATION SYSTEM

-

-

-

... More
Supply, Installation, Testing & Commissioning & Handing over of the following:

-

-

-

... More
Supply, Installation, Testing & Commissioning & Handing over of the Circular Inline fan Supplying, installing, testing and commissioning of low noise silent type Inline fan with @15mm WC static pressure. The motor shall be suitable for 220 volt single phase 50 cycles AC supply, 6/15 Amp plug and wiring between the fan and the socket and low sound level exceeding not more than 50dBA. Fan should be complete with all accessories, gravity louver/ shutter as required etc., as per manufacturer specification including transportation to site, all mounting arrangements like brackets etc., as per specification including transportation to site, all mounting arrangements like brackets etc. It should be suitable for BMS connectivity with necessary accessories and cost of all accessories and all labour charges complete.

-

-

-

... More
Circular Inline fan 100CFM/15mm WC static pressure

3

8549

25647

... More
Circular Inline fan 200CFM/15mm WC static pressure

6

9200

55200

... More
Circular Inline fan 400CFM/15mm WC static pressure

1

10178

10178

... More
Circular Inline fan 500CFM/15mm WC static pressure

3

11073

33219

... More
Circular Inline fan 600CFM/15mm WC static pressure

3

11724

35172

... More
Circular Inline fan700CFM/15mm WC static pressure

5

12408

62040

... More
Circular Inline fan 800CFM/15mm WC static pressure

1

16843

16843

... More
CLEAN ROOM

-

-

-

... More
CLEAN ROOM FALSE CEILING

-

-

-

... More
Supply, Installation, Testing & Commissioning & Handing over of the False ceiling panels are designed to fit within each other and suspended by threaded tension bars to the overhead support at fixed intervals , Standard Ceiling Panels have a composite construction of two skins of powder coated GI over an GI frame work with a sealed and insulated interior. 150-200 Kg per sq. mtr load bearing

-

-

-

... More
50mm double Skin Walkable False Ceiling made of 0.45 mm both Top & Bottom with pre coated GI Sheets with mounting accessories PUF as in fill (40 +/-2 kg./m3). False ceiling support rods length suit to site condition. Note: 1.All ceiling joints and gaps between panel to panel, ceiling elements (such as HEPA module, diffusers, pipe & electrical drops etc.) etc. to be sealed usingApproved food grade silicon sealant of same or nearest colour as panel. The gap above panel to civil wall shall be properly closed with aluminium 'L' - angle secured properly between civil wall and panels. All the gaps between panel to panel shall be closed with GI pre coated External Flashing . All the gaps between ceiling elements and ceiling panel shall be sealed using food grade silicon sealant of the same colour as the panel.

400

2470

988000

... More
CLEAN ROOM PANELS

-

-

-

... More
Standard wall partitions are a composite construction of two skins over an GI frame work with a sealed and insulated interior. Standard panel dimensions are 1200 mm. Standard panels have an overall thickness of 80 mm.Including Silicon Sealant. The self supporting internal walls are constructed with an interior floor Flashing to suit panel thickness. The Partition seams are sealed by silicone(Food grade) with a perfectly flush finishing. The panels should be factory manufacture

1000

2605

2605000

... More
CLEAN ROOM COVINGS

-

-

-

... More
Extruded Aluminum Powder Coated /Anodized clip on type covings of 60mm radius for Panel to Panel and Panel to Ceiling.

-

-

-

... More
Horizontal & Vertical Coving

200

611

122200

... More
3D Corner Powder Coated

8

375

3000

... More
2D Corner Powder Coated

8

318

2544

... More
AL powder Coated TEE Support for Ceiling Panels with threaded Rods and clamps

300

700

210000

... More
CLEAN ROOM DOORS

-

-

-

... More
Doors are designed to fit flush into the wall panel / civil walls system on both sides and are supplied in different dimensions. Doors are fabricated from Pre Coated GI sheets & Puf as infill(48 +/-2 kg./m3). Shutter has sheet thickness of 1mm and the frame of 1.2mm. jam depth of door shutter inline with adjacent panel thickness and shutter width of 40mm. Doors are available in various sizes as per the requirement. The following accessories are a part of the door: Note: 1.All joints between view panel and door panel to be sealed using approved food grade silicon sealant of the same or nearest colour as the panel. 2.Colour of the door panel:Same as Panel Colour or Blue 3.Double face VHB tapes of required thickness or silicon sealant to be provided on the periphery of the view panel frame to avoid any play between view panel frame and the slot in the door leaf.

-

-

-

... More
Shutter Thickness: 40 mm thick

-

-

-

... More
Stainless steel hinges (Any reputed Make)

-

-

-

... More
Stainless Steel 'D' type of handles on pull side

-

-

-

... More
Stainless steel push plates on push side.

-

-

-

... More
Heavy duty Concealed door closure

-

-

-

... More
concealed double glazed Vaccumized View panel along with self adhesive tape and silicon sealant (500mmWx750mmH) with toughened glass with 6mm thick and black border

-

-

-

... More
Mortice dead lock (ML100D) with both Side Key Operation Cylinder-Dorset

-

-

-

... More
Concealed Flush Bolt Body with rod

-

-

-

... More
Gasket at bottom for Single Door

-

-

-

... More
Gasket at bottom for Double Door

-

-

-

... More
Stainless Steel kick plates on both sides of Door of 1.2mm thick with 300mm height for material transfer doors for Single Door.

-

-

-

... More
Stainless Steel kick plates of 1.2mm thick with 300mm height for material transfer doors for Double Door.

-

-

-

... More
DOOR SIZE

-

-

-

... More
900 X 2100 mm Single Door

1

26869

26869

... More
1200X2100 mm Double Door

2

33382

66764

... More
Emergency Doors

-

-

-

... More
Doors are designed to fit flush into the wall panel / civil walls system on both sides and are supplied in different dimensions. Doors are fabricated from Pre Coated GI sheets & PUF as infill. Shutter has sheet thickness of 1mm and the frame of 1.2mm. jam depth of door shutter inline with adjacent panel thickness and shutter width of 40mm, stainless steel hinges (Any reputed make), door shutters should be with min leakages, without any View Panels, Panic Bar with all the accessories to be included. Doors are available in various sizes as per the requirement. Note: 1.All joints between view panel and door panel to be sealed using approved food grade silicon sealant. 2. Colour of the door panel: RED

-

-

-

... More
1500 X 2100 mm Emergency Door

1

50480

50480

... More
VIEW PANELS ON MODULAR PARTITION

-

-

-

... More
SINGLE GLAZED

-

-

-

... More
All Viewpanel units are Double glazed and round profiled Epoxy based powder coated GI wall panel system. Thickness of 6/8 mm Tougened glass. The window system is completely of food grade Silicone sealed. All veiw panels to have black border. Approx Size of view panels will be 800 x 1000mm

-

-

-

... More
View Panel on 80mm wall panel

4

10340

41360

... More
FALSE CEILING CUTOUTS FOR ELECTRICAL & HVAC GRILSS,LIGHT FIXTURES ETC.

-

-

-

... More
Frame Work for Wall Panel Cutouts

8

594

4752

... More
Back Boxes for Electrical Sockets includes 3M, 2M, 6M, 8M, Single Phase, Three Phase industrials sockets respectively of apprvoed makes like Anchor, MK, North West & Legrand.

8

896

7168

... More
Frame work for False Ceiling Cutouts for Electrical & HVAC

30

594

17820

... More
PVC Conduit for Electrical Cables / Data Cables 24mm dia / 40 mm dia respectively

50

399

19950

... More
INBUILT RETURN RAISER

-

-

-

... More
Supply and Installation of wall panel inbuilt Return Air Risers of 0.8 mm thick GI sheet & G4 Filter in aluminium frame work with proper fixing arrangement & fastening using SS 304 Dome nuts. to be provided up to the top of the false ceiling for HVAC duct connection. along with Butter fly Dmpers on the Top side.

-

-

-

... More
Inbuilt raiser 600 x 600

8

10340

82720

... More
GI RETURN AIR FILTER WITH SS PERFORATED SHEET MODULE

-

-

-

... More
Supply & installation of Return Air Raisers SS PERFORATED SHEET MODULE WITH 20 MICRON FILTER ASSEMBLY TO FLUS FIT THE RETURN AIR RISER PANEL. The RA raiser shall be adequately supported to ensure the rigidity.

-

-

-

... More
450 mm x 450 mm x 450 mm

8

2915

23320

... More
Supply and Laying of Self levelling Expoxy flooring with Floor Preparation work and application ofone coat primer, screed and finishing with Self levelling Epoxy up to a max of 2mm of approved Colour

400

1979

791600

... More
INSULATED FLEXIBLE DUCT WITH NECESSARY FIXING CLAMPS ON BOTH SIDE FOR TERMINAL HEPA MODULE

-

-

-

... More
Supply, Installation, Testing and Commissioning of The insulated flexible duct of class 1 air duct, light weight, strong, fully flexible & made of double lamination of films permanently bonded to a coated spring tough steel wire helix. The thermal efficiency is ensured with a blanket of fiberglass wool insulation in between. Necessary Fixing Clamp on both side shall be considered. (With Spigot Connection & Rigid GI Round Duct). Note: Rigid GI Round Duct area shall be part of GI Ducting. Each Flexible connection shall not be more than 1 Mtr.

-

-

-

... More
200 mm Dia

200

692

138400

... More
TERMINAL HEPA FILTER WITH MODULES

-

-

-

... More
Supply, Installation, Testing and Commissioning of H14 HEPA Filter with Housing & Damper (Bottom Discharge Module Type with SS304 perforated grille of 16 SWG sheet along with SS chain link). Complete Housing (Sides + Top) made of extruded aluminium anodized material and low leakage aluminum collar damper with operating bevel gear arrangement, Diffuser Plate, Housing shall be suitable for fixing the Gel Seal type (Polyurethane gel) terminal HEPA filter (H-13) with Protective Expanded Metal Screen. The Filter Housing shall have provision for smoke aerosol test point and differential pressure measuring point. The filter mounting box shall have a provision to replace filter & control the airflow from inside conditioned space. The HEPA filter modules are of the following sizes:

-

-

-

... More
Plenum box size of 485x485x220H (530X530mm Flange to Flange) inlet collar with Diffuser plate & TOP entry 305 Sq / dia Collar with necessary clamps complete with gel seal filter minipleat H-13 of Size: 450X450X70mm with DOP port and bevel gear arrangement room side operation damper.

20

26054

521080

... More
PRESSURE MONITORING SYSTEM

-

-

-

... More
Supply, Installation, Testing and Commissioning of Compound Magnahelic gauges housed in a SS304 front cover (50-0-50 Pa) complete with PVC tubing and SS perforated nozzle (For Installation in Clean Room Panel for Classified Areas)

2

8793

17586

... More
MISCELLANEOUS

-

-

-

... More
Commissioning of Classified Areas with Validation reports comprising of :

-

-

-

... More
AHU & Duct leakage testing with pressurization (As per SMACNA air duct leakage standards). This process to be documented.

-

-

-

... More
HVAC testing adjusting and balancing as per ASHRAE standard.

-

-

-

... More
Air balancing with flow hood meter

-

-

-

... More
Room Temperature & Humidity mapping for 24 hours and monitoring for 3 days.

-

-

-

... More
Room pressure balancing with monitoring for 3 days.

-

-

-

... More
HEPA Filter Integrity Test.

-

-

-

... More
Particle count test

-

-

-

... More
Providing all documentation of DQ, IQ, OQ & PQ in approved formats.

-

-

-

... More
The Validation has to be carried out for minimum 3 working days continuously for Air flow, Temperature and Humidity. For Room Pressure Differential continuously for 3 working days. In case of any non compliance the system has to be set right and the Validation has to be carried out once again as per the above schedule. Validation has to be carried out by valued Certification ISO 14644-1 is a widely recognized certification .It's should issued by the International Organization for Standardization (ISO) or The FDA, Health Canada, and the EU recognize this certification.

1

162840

162840

... More
Clean Air Devices Equipments

-

-

-

... More
Supply,erection, testing and commissioning of personal Air shower , single entry and single exit,high velocity, low pressure system SS304 nozzles,pre and HEPA fillers, completely self contained unit, utilizing low wall return (floor grill type not accepted)

-

-

-

... More
The Unit shall be consisting of ISO class 8 clean room compatible pre-fabricated units built up, in place having fluorescent lamp with acrylic cover, electronic ballast , both side red and green indicators, elector-magnetic latches on both sides of Dorma make to ensure both doors do not open simultaneously, 5.0 mm thick viewing glass, SS304 finish handles of Dorma make, door closer with hold open arm of Dorma make, blower, control wiring, emergency stop switch etc.

-

-

-

... More
For 3 persons entry

1

528465

528465

... More
Supply, installation, testing and commissioning and placing of stainless steel centrifugal air curtain having following specification. The product should be made up stainless steel 304Grade having 3 Blowers(in M.Steel), 2 Motors operating on three phase , Power =1650 Watt having RPM (Max/Min = 2700) and CFM. Overall Dimension of 6000X230X212(mm) with Noise level 66 db. Air Curtain should be provided with velocity control switch and a Door sensor. The product should carry manufacturers warranty of one year from the Date of Supply. Along with Fabrication work of providing 2/1 MS Pipe , Tin Sheet as cover, Bracked and screws*Variations acceptable in parameters above - 5-10% The Product should be Supplied along with PVC curtains & SS Bracket for PVC Support. Supply, installation, testing and commissioninging of transparent blue PVC Strip curtain,these medium weight strip will help with temperature control or dust exclusion without impeding access, It is suitable for the door is the main entry gate of the premises, means exposed to air. .The Product should be complete in all aspect as per Engineer incharge instructions

2

42338

84676

... More
Supply, installation, testing and commissioning and placing of stainless steel centrifugal air curtain having following specification. The product should be made up stainless steel 304Grade having 2 Blowers(in M.Steel), 2 Motors operating on three phase , Power =1650 Watt having RPM (Max/Min = 2700) and CFM. Overall Dimension of 3500X230X212(mm) with Noise level 66 db. Air Curtain should be provided with velocity control switch and a Door sensor. The product should carry manufacturers warranty of one year from the Date of Supply. Along with Fabrication work of providing 2/1 MS Pipe , Tin Sheet as cover, Bracked and screws*Variations acceptable in parameters above - 5-10% The Product should be Supplied along with PVC curtains & SS Bracket for PVC Support. Supply, installation, testing and commissioninging of transparent blue PVC Strip curtain,these medium weight strip will help with temperature control or dust exclusion without impeding access, It is suitable for the door is the main entry gate of the premises, means exposed to air. .The Product should be complete in all aspect as per Engineer incharge instructions

2

37453

74906

... More
SS/PP Furniture

-

-

-

... More
Design, engineering, fabrication, supply, erection and testing of Cross over bench made up of 10 mm thick PP sheets of size which has to fully fixed in the designated place in the changeroom, with heat welding .Bottom of bench will have pegion holes for keeping dayshoes/CR sleepers of equal size 250 mm X182 mm in two rows.

4

36567

146268

... More
Design, engineering, fabrication, supply, erection,testing and commissioning of garment cubicle compatible for ISO class 8 cleanroom either SS304 sheet material for keeping maximum 15 cleanroom garments, sliding doors, glazing , UV light,pre filter, HEPA filter and blower for recirculation of air, complete ready to use.

1

185231

185231

... More
ELECTRICL LIGHTS AND ACCESSORIES

-

-

-

... More
LIGHT FIXTURES

-

-

-

... More
Supply,Installation, Testing & commissioning of following LED light fittings for lighting fixture with accessories and LED chip. The Luminaire shall be with CRCA housing and Luminaire and an operating Voltage Range of 120 - 277V,  Internal Surge Protection 2.5KV.

-

-

-

... More
40W 2'x2' (600mmx600mm) LED Screw less Clean room recess mounted bottom opening luminaires with toughed glass with diffused acrylic cover, construction of the housing with engineering push back mounting arrangement system of Approved make. System output 4000 lumens to be considered.(Philips or equivenlant)

10

4193

41930

... More
Electrical Cabling with PVC Conduiting for the Lights 3 Core 1.5 Sqmm

60

134

8040

... More
POWER SOCKETS

-

-

-

... More
Supply, Installation, Testing & Commisioning of following Plug sockets & Push buttons. The assembly shall be housed in metal box / on partition / on wall concealed type. Rate shall include the internal wiring, terminations, GI back box and front face plate, enclouser with fixing accessary like lugs, screws, blot nuts, ferruls etc. as per tender technical specifications. Necessary wall chipping, drilling & fixing of back box in concelead type. Rate shall be included backbox fixing concelead on the wall and chipping along the wall fixing chicken mesh and making good surface of wall as required at site. Note : Modular sockets Back box should be considered 45mm depth only.

-

-

-

... More
Emergency stop push button station with enclosure fixed on wall or on required MS angle support with all its accessories of approved make.

3

1900

5700

... More
EARTHING

-

-

-

... More
GI Plate Earthing

-

-

-

... More
Supply and Laying of following earthing strips / earth wire of the following sizes with required accessories like clamps, bolts & nuts, painting. Two numbers of earth strips should run along with cable tray/civil wall with proper using bolt and nuts for strips connectivity and two earth points shall be end terminated for all equipments, motors, all Electrical and ELV panels, DB etc., refer the earthing schematic for considering the earth strips.

-

-

-

... More
50mmx6mm GI Strip

50

456

22800

... More
AIR COOLED SYSTEM

-

-

-

... More
HVAC WORKS: Supply, Transportation, Lifting, Shifting, Installation ,Testing, Commisioning & handed over of the following:

-

-

-

... More
Supply , transportation , Lifting , Shifting ,installation ,testing,Commissioning & handed over of Air Cooled Screw Chillers with the following technical parameters complying with the technical specifications. The chiller shall be with independent refrigerant circuits, having R-134a / Eco friendly refrigerant. The unit shall comprise of mutiple Semi- hermetically sealed Compressors with VFD, having independent refrigerant circuits , suction & discharge valves , relief valves, oil filter, suction filter,dual pressure switch, oil safety switch,crank case heaters & relay integrated with compressor motor, insulated shell and tube DX/flooded chiller, electronic expansion valve,VFD starter with related wiring,Microprocessor panel , First charge of refrigerant and oil and necessary automated and safety controls. The chiller shall be provided with Victaulic couplings/ Flanged connectors for connecting the chilled waterlines. The air cooled condenser complete with copper condenser coil with aluminium fins, coil guard, condenser fans & motors , inter connecting refrigerant piping, fittings, suction line insulation etc. The entire chiller package shall be mounted on a rigid common base frame. The base frame shall be provided with two coats of anti corrosive primer and two coats of epoxy paint.The units including with flexible connections (Bellows)suitable for working pressure of PN16. The chillers shall be mounted on a MS framed structure with necessary vibration mount. The compressors shall be provided with acoustic jackets . The dB(A) of the chillers with acoutic jackets shall not exceed 78dB(A) at 1 Mtr Distance. The microprocessor panel Shall be BMS compitable and has Backnet/IP protocol for sharing the chillers information/ data with BMS System. Motor shall be suitable for 415+/-10 V,50 cycles, 3 phase, 4 wire AC supply. The chillers shall be compitable to Bacnet/IP protocol. The chillers shall operate on varying part loads in stepless mechnism ( infinite ) from 10% to 100% with capacity control slide valve mechanism. The shall be included flexiable bellows including accessores. The Chiller shall meet Min. COP, EER, IPLV as per ECBC & ASHRAE 90.1 -2010(S) standards requirement Evaporator LWT/EWT :43/52 Deg F , Evaporator Fouling factor :0.0001 hr-sft/deg F/Btu, Ambient temprature - 33.3Deg F,Mounted on a Spring Vibration isolaters,Chiller should be filled with required amount of Refrigerant & Oil which shall be as per OEM's standards., Transportation,Lifting, shifting of the chillers to the required allocated space at Chiller plant room., consider first charge & second charge of water in offer for commissioning,C.O.P minimu 3.0 and IPLV not less than 4.4, 120TR Actual Capacity for Thiruvanathapuram

-

-

-

... More
The chiller shall be designed based on

-

-

-

... More
Ambient : 33.3º C

-

-

-

... More
Chiller inlet : 11º C

-

-

-

... More
Chiller Outlet : 6º C

-

-

-

... More
60TR Chiller (2W+1S))

3

3616603

10849809

... More
CHIILED WATER PUMPS- SKID MOUNTED PUMPING SYSTEM PRIMARY CHILLED WATER PUMPS: Supply , transportation , Lifting , Shifting ,installation ,testing, Commissioning & handed over of Factory prefabricated skid consisting of externally sealed type vertical inline split coupled centrifugal pumps with suction guide with inbuilt stainer, , valves as per P&ID on suction and discharge risers and suitable size headers. Pumps should be with cast iron body, bronze impeller ,coupling,coupling guard,mechanical seal including SS316 gland plate. The motor shall be of TEFC Squirrel cage induction type , IP-66, Class F insulation with IE2 Efficiency . The rate quoted shall also include the cost for structure to mount supply and discharge header with related MS C class piping , bends & elbows, flotrex valve ( triple duty valve) , butterfly valves for suction and discharge side, pressure gauges , temparature gauges, drain valves etc. The units including with flexible connections (Bellows)suitable for working pressure of PN16. The shall be included flexiable bellows including accessores.The skid will be complete in all terms and ready for inlet and out let connections at the site.insulation with 50 mm thick, 18 kg/cum density TF quality expanded polyesterenepre formed sections upto 80 mm dia pipes and 75 mm thick insulation for above 80 mm dia pipes finished with vapour barrier,chickenwire mesh and two coats of 12 mm thick sand cement plaster on above wrap with 26 g aluminium cladding Pump flow rate : 324 usgpm head : 20 m ( 2 working + 1 stand by) (consider head is tentative actual calculate as per site conditions)

3

116072

348216

... More
SECONDARY CHILLED WATER PUMPS : Supply , transportation , Lifting , Shifting ,installation ,testing, Commissioning & handed over of Factory prefabricated skid consisting of vertical inline pumps with integrated drives with sensorless feature, valves as per P&ID on suction and discharge risers and suitable size headers. Pumps should be with cast iron body, bronze impeller ,coupling,coupling guard,mechanical seal including SS316 gland plate. The motor shall be of TEFC Squirrel cage induction type , IP-66, Class F insulation with IE2 Efficiency . The integrated drive shall be PWM type , having a graphical userinterface with IP 55protection. The rate quoted shall also include the cost for structure to mount supply and discharge header with related MS C class piping , bends & elbows, isolation valves, y stainer,rubber bellows, pressure gauges, temparature gauges, drain valves etc. The units including with flexible connections (Bellows)suitable for working pressure of PN16. . The shall be included flexiable bellows including accessores.The skid will be complete in all terms and ready for inlet and out let connections at the site.insulation with 50 mm thick, 18 kg/cum density TF quality expanded polyesterenepre formed sections upto 80 mm dia pipes and 75 mm thick insulation for above 80 mm dia pipes finished with vapour barrier,chickenwire mesh and two coats of 12 mm thick sand cement plaster on above 26 g aluminium cladding also required.Pump flow rate : 486 usgpm head : 30 m ( 2 working + 1 stand by) (consider head is tentative actual calculate as per site conditions)

3

193894

581682

... More
VARIABLE FREQUENCY DRIVES & LOGIC CONTROL PANEL: (PRIMARY PUMP & SECONDARY PUMP)

-

-

-

... More
Supply, Installation, Testing ,Commissioning & handed over fo variable speed pumping system comprising of following accessories. The system shall be complete in all respects including electrical components for motor of primary chilled water pumps. Each pump shall have an independent adjustable frequency drive. Common Panel with suitable controller to control 4 Nos. Pumps separately. as per specs and drawing. Including sensor, transmiter, control wiring etc complete in all respect. It shall be also BMS compatible. Panel should be IP 55 Rated.

-

-

-

... More
For chilled water pumps

-

-

-

... More
Variable frequency drive (VFD) : 2 Nos

-

-

-

... More
Micro processor based pump controller : 1 No

-

-

-

... More
Differential pressure sensors/Transmitters : 2 Nos

-

-

-

... More
Software down loaded in pump controller : Job

-

-

-

... More
Control wiring : Lot

-

-

-

... More
Variable speed pumping system described above

1

70763

70763

... More
PRESSURIZATION SET:

-

-

-

... More
Supply, Installation, Testing,Commissioning & handed over of Insulated Pressurisation Unit (1000 L) of requisite capacity with necessary makeup, quick fill, drain and over flow connection, valves, fittings, suitable rating pump(1W+1S),expansion vessel (1000 L), necessary pump connection along with valves,stariner and compleate panel etc. All pump's shall be mounted with necessary vibration isolators, etc. as per the specifications and approved drawings. {Closed loop Expansion tank + booster pumps}.Data sheets to be submitted by department.

1

194236

194236

... More
AIR & DIRT SEPERATOR

-

-

-

... More
Supply Installation Testing ,Commissioning & handed over of 125mm dia In-line Air & Dirt Separator. removing of free air, bubbles and microbubbles in combination with separation and removal of dirt particles within chilled water system.The acceptable design shall incorporate a separating element to force water into tranquillity zones for air and dirt removal. A nozzle shall force de-aerated water into the main flow to divert contaminated water through the separating element. A high capacity, conical brass automatic air vent shall be installed on the top of the vessel for air discharge. Drain valve for removal of floating debris and dirt. Heavier than water dirt particles shall be removed via a blow down valve on the base of the vessel whilst ferrous particles down to 4 µm shall be captured by a magnetic device in the lower part of the vessel.Manufactured and designed in accordance with European Pressure Equipment Directive. The Microbubble Air and Dirt Separator shall be sized appropriate to the maximum operating pressure and flow velocity 324USGPM of the system. as per the specifications and approved drawings.

1

44501

44501

... More
CHILLED WATER PIPING

-

-

-

... More
Supply, laying on Above ground testing,Commissioning & handed over of MS class 'C' ERW Pre insulated Chilled water piping complete with Elbows , reducers , bends , supports,and pressure testing of Pre Insulated pipes. Insulation of piping shall be with Polyurethane foam injected of minimum 50mm thick 36 Kg/m3 density for all size covered with GI Sheet of 26 Gauge for the following sizes with all the accessories hardware complete as per TS :

-

-

-

... More
100 mm dia

250

791

197750

... More
125 mm dia

400

981

392400

... More
150 mm dia

50

1230

61500

... More
Supply , transportation , Lifting , Shifting ,installation ,testing ,Commissioning & handed over of Motorised Butterfly valve of PN 16 Rating, cast iron body with 32mm thickness Nitrile rubber insulation as per specifications , SGI (Nylon coating) disc,EPDM seat,SS hand lever operated , wafer Type etc.The Valve shall be insulated to the same specification as that of piping.The Valve shall be insulated to the same specification as that of piping.

-

-

-

... More
Butterfly Valves

-

-

-

... More
100 mm dia

12

2780

33360

... More
125 mm dia

9

3569

32121

... More
150 mm dia

6

4104

24624

... More
Supply , transportation , Lifting , Shifting ,installation ,testing,Commissioning & handed overof Manual Balancing valves of PN 16 for sizes upto 50mm, valve shall have Gun Metal body, stem brass, brass pressure test port, threaded ends, & for valves 65mm dia & above, valve shall have cast iron body, Stainless steel 410 stem, EN- 3 Disc, EPDM Seal & steel chrome plated pressure test ports, Installed with pair of Table E Flange ,nuts, bolts, gasket etc. The Valve shall be insulated to the same specification as that of piping.

-

-

-

... More
Balancing Valves

-

-

-

... More
100mm dia

6

26734

160404

... More
Supply, Installation, Testing and Commissioning of Non return valves with matching flanges , bolt, nuts, insulation and suitable for working pressure of PN16. The insulation covered with treated woven glass fiber reinforced covering & finished with 24G Aluminium cladding, all etc., complete as per specifications and approved drawings. .

-

-

-

... More
Non Return Valve

-

-

-

... More
125mm dia

3

13434

40302

... More
150 mm dia

3

16416

49248

... More
Supply , transportation , Lifting , Shifting ,installation ,testing and commissioning of Y- strainers of PN 16 made of Cast Iron body, SS filter having 3mm perforationX 24G SS rings on top with flanged ends & permanent Magnet. Flanges as per ANSI 16.5.valve shall be installed with Table 'E' flanges , bolts, nuts, gasket and complete with all accessories. The Valve shall be insulated to the same specification as that of piping.

-

-

-

... More
Y' Strainers

-

-

-

... More
100mm dia

2

12589

25178

... More
125 mm dia

3

18727

56181

... More
150mm dia

3

21169

63507

... More
Supply , transportation , Lifting , Shifting ,installation ,testing and commissioning of 2-way ball type chacterised control valve with internal thread IS07/1,ISO7005-2, equal percentage flow characterstic, PN 25, body nickel plated brass with stainless steel ball, Non spring return rotary type modulating actuator , power supply 24 V AC/DC, control signal 2- 10 V DC , Feed back signal 2- 10 V Dc,IP54 and related cabling:modulating type temparature controller,power supply 24 V AC, control signal 0-10 V DC,set point 0-40 deg C, NTC senser, IP20.The Valve shall be insulated to the same specification as that of piping.

-

-

-

... More
2 way mixing valves with actuvator

-

-

-

... More
100mm dia

2

41264

82528

... More
6 inch dia Pressure gauges with syphon & cock and isolation valve etc complete.

22

1313

28886

... More
6 inch dia Dial type Thermometers with syphon & cock and isolation valve etc complete.

10

2408

24080

... More
Water flow switch with stem type sensing element probe for flow sensing.

3

3032

9096

... More
Supply, Installation, Testing and commissioning of Double float Auto Air vents 20mm dia

8

458

3664

... More
AIR HANDLING UNITS

-

-

-

... More
Supply, installation, testing, commissioning and handing over of following capacity floor mounted Thermal Break Double skin construction with internal and external sheets of 1.0 mm thickness with galavanizing of 120 gm/m2 ,Air handling unit made out of extruded aluminium structural frame work. Panels shall be made of 50 mm PUF injected panels having density 43 Kg/m3 in galvanised sheet casings having scratch free preplasticised coating on galvanised sheet on external side and plain GI inner sheet. The whole unit shall be mounted on spring isolators

-

-

-

... More
i) The Air handling unit shall comprise of fan section with Plug Fan/ Backward curved fan with limit load characteristics , spark proof fan. fan mounted on the scroll and not on the casing, coil section comprising of Chilled water coil, stainless steel drain pan under coil section, Filter section comprising of prefilter 10 micron and 3 micron Hepa filters, mixing box along with RA and FA dampers etc. complete in all respect whether specifically spelt or not but required to complete the system works.

-

-

-

... More
The entire unit casing shall be weather proof , made out of 50 mm thk. 43 Kg/ cum density double skin PUF panels. The entire assembly of the unit shall be mounted on a rigid GSS base frame. Inner skin of the panel shall be 1 mm thick GSS plain and the outer skin shall be with 1 mm thk. Pre plasticized powder coated. The total unit along with chilled water coils shall be AHRI certified. The face velocity of the coils shall not exceed 500 FPM . The face velocity across the filters shall not exceed 500 FPM.

-

-

-

... More
The coils and filters shall be full face of the unit. The fan and motor shall be mounted on a common base frame with cushy foots / spring isolator to avoid vibration transmission to the base of the unit. The motor shall be effiency IE3 and with VFD compatable.

-

-

-

... More
The fan shall be AMCA certified and motor shall be energy efficient IE3. The fan out let velocity shall limit to 12 m/ sec. The fan access door shall have safety door interlock arrangement with motor. The unit shall be supplied with fire retardant double canvass connection between the fan out let and supply air flange.

-

-

-

... More
The unit shall be supplied with an outlet flange at the the supply air side along with opposed blade volume control damper. The damper casing and blades shall be made out of 16 G Aluminum.

-

-

-

... More
The scope includes one set of commissioning filters along with the VFD & Starter panel with Bypass.

-

-

-

... More
The units including with flexible connections (Bellows) suitable for working pressure of PN16.

-

-

-

... More
The AHU unit shall outdoor type with all season weather proof protection

-

-

-

... More
The noise level at all-round the unit shall limit to 60 dBA from 1 m distance to the unit.

-

-

-

... More
The fan curves, coil selection and technical data sheet shall be submitted by vendor for scrutiny or approval.

-

-

-

... More
The unit shall be included with AHU & VFD DRIVE STATER & CONTROL PANEL

-

-

-

... More
The unit shall be included with AHU CONTROLL KITS WITH CORDED REMOTES

-

-

-

... More
Unit shall be ultra violet lamp to kill germs/fungus

-

-

-

... More
AHU1 - 60 TR capacity, total air qty 24000 cfm, 65mm Static pressure with suitable High efficency motor, 48 sqft area of 6 row Chilled water coil.

2

1180753

2361506

... More
Supply and fixing of thyristor control Duct Heater Bank for humidity control 32kw capacity & necessary accessories to maintain RH.

2

17326

34652

... More
DRAIN PIPE

-

-

-

... More
Supply & Installation of PVC drain pipe insulated with 9 mm thick closed cell FM approved class O nitriler rubber insulation. Necessary U trap for units with clean out plugs to be provided

-

-

-

... More
40mm dia

20

254

5080

... More
Sheet Metal Work using Factor Fabricated Duct with Ductmate (TDF) Flanges for all sizes of the duct. Fabrication as per SMACNA Standards

-

-

-

... More
Galvanizing shall be Class VIII – light coating of zinc, nominal 120 gm / sqm surface area and Lock Forming Quality prime material alongwith mill test certificates. In addition, if deemed necessary, samples of raw material, selected at random by owner’s site representative shall be subject to approval and tested for thickness and zinc coating at contractor’s expense.

-

-

-

... More
All duct construction and installation shall be in accordance with SMACNA standards. In addition ducts shall be factory fabricated utilizing the following machines to provide the requisite quality of ducts.

-

-

-

... More
All ducts shall be fabricated and installed in workmanlike manner, conforming to relevant SMACNA codes.

-

-

-

... More
To ensure the air tightness, all ducts shall be checked with Duct pressure Test after completion of duct installation but before applying insulation

-

-

-

... More
Guide vanes to be installed in elblow, reducers and other accessories

-

-

-

... More
Stiffernner to be considered for ducts with more than 1200mm wide ducts

-

-

-

... More
Duct joining shall completed with adhesive type gasket and sealant

-

-

-

... More
All ducts needs to properly supported with suitablewire supports as per makes given in make list. The cost shall be inclusive of anchor fastners/wedge supports suiting to steel structure.

-

-

-

... More
With all necessary accessories i.e fixing etc complete.

-

-

-

... More
Rectangular Ducting

-

-

-

... More
Sheet Metal Ducting As per Specification. Pressure 500 Pa

-

-

-

... More
24 G Ducting with Factor Fabricated Duct/ TDF flanges

800

944

755200

... More
22 G Ducting with Factor Fabricated Duct/ TDF flanges

1000

1050

1050000

... More
20 G Ducting with Factor Fabricated Duct/ TDF flanges

450

1225

551250

... More
Thermal & Acoustic insulation

-

-

-

... More
Thermal Insulation for ducts

-

-

-

... More
Supply, installation and testing of Class- O, 25 mm thick Closed cell elastomeric insulation for thermal insulation for indoor supply air ducts with density not less than 50 kg / cum. Microban antimicrobial protection insulation material to be fire retardant. Joining tapes & low VOC adhesive to be supplied with the insulation material by the insulation material manufacturer.

750

993

744750

... More
Supply, installation and testing of Class- O, 19 mm thick Closed cell elastomeric insulation for thermal insulation for indoor supply air / return air ducts with density not less than 50 kg / cum. Insulation material to be fire retardant. Joining tapes & low VOC adhesive to be supplied with the insulation material by the insulation material manufacturer.

940

660

620400

... More
Supply, installation and testing of Class- O, 13 mm thick Closed cell elastomeric insulation for thermal insulation for indoor supply air / return air ducts with density not less than 50 kg / cum. Insulation material to be fire retardant. Joining tapes & low VOC adhesive to be supplied with the insulation material by the insulation material manufacturer. Refer method statement in technical specification for insulation works.

550

539

296450

... More
Acoustic Insulation for ducts

-

-

-

... More
Supply, transportation , Lifting , Shifting ,installation ,testing and commissioning of Acoustic insulation for ducting with 50mm TF quality thermocole, density 18kg/cum, chicken wire mesh and 2 coats of 12mm thick sandcement plastering for exposed ducting.

40

1252

50080

... More
Air Terminal Devices

-

-

-

... More
Supply, installation, testing and balancing Powder Coated extruded aluminium grilles with collar damper for supply and return distribution (colour for the grill to be confirmed by department before placing the order) . Deflection of the grille shall be 0 / 15 / 30. same will be confirmed later. Single / 2 way / 4 way deflection shall be confirmed later.

35

4478

156730

... More
Supply, Fixing, Testing and commissioning of Aluminium powder coated 4-Way Diffusers with Anti smudge ring and all fixing accesseroies as per standard specifications and practice.

15

2768

41520

... More
Supply, installation and testing of Jet diffuser with fire resistance flexible double canvas Connection for supply distribution (colour for the Jet to be confirmed by consultant/ PMC team before placing the order)

-

-

-

... More
Ø 315

30

2280

68400

... More
Supply and fixing of 18G circular butterfly damper with provision to fix to the rectangular duct with GI circular flanges.

30

497

14910

... More
Supply and fixing of Insulated Aluminum flexible duct with 25mm thick glass wool insulation covered with aluminum foil suitable to connect the ducting including necessary clamps at both ends of size

90

489

44010

... More
Acoustic Insulation for AHU rooms

-

-

-

... More
Supply, installation and testing of acoustic insulation on walls & ceilings for the AHU Rooms with 50mm thk. 24 kg/ cum density Resin bonded fiber glass covered with 24 G GI perforated sheet as per specification. The FG slabs shall be placed in the grid of 600mmx600mm centers formed out of GI channels.

171

651

111321

... More
Supply and Fixing of Fresh Air / Exhaust air Louvers with brass wire mesh backing with Pre filter along with Dampers for all AHU room fresh air wall openings.

15

4478

67170

... More
Supply, installation and testing of Factory fabricated Rectangular shape - GI Volume control dampers, 1.6-mm GI Steel Frame, 1.6-mm GI blades, 150-mm width, with required hardware and accessories. Stiffen damper blades for stability. Include locking device to hold single-blade dampers in a fixed position without vibration & engraved marking on position of damper.

45

3623

163035

... More
Supply, installation and testing of Aluminium powder coated fresh air intake / exhaust air louvers backing with pre filters complete with HDPE insect mesh with cowl mounting frame and 45 deg angle suitable for protection against splashing rain water fixed in a powder coated Aluminium angle mount frames as required for all AHU ROOM fresh air wall openings.

15

6921

103815

... More
Supply, installation and testing of Motorized Fire dampers (MSFD) with ON/OFF type actuator. The dampers to be fire rated for 120 minutes at 250Deg C. Fire damper to be provided with matching flanges on both sides. Fire dampers should be supplied with extended fire rated sleeves. Actuators shall be for spring return type & shall be fire rated for 120 minutes @ 120Deg C. Actuators to be internally mounted. Actuators should be suitable for BMS connectivity with necessary accessories.

-

-

-

... More
Note:Duly factory fitted and tested at manufacturers works and certificate to this effect produced along with delivery of fire damper.

-

-

-

... More
Fire damper

45

4844

217980

... More
Actuator,Sensor,Control panel and relay/communication module, interlinking cabling

4

2972

11888

... More
Supply, installation and testing of GI Non Return Dampers at suction & discharge side, suitable for duct mounted including mating galvanized angular iron flanges.

36

4315

155340

... More
Supply, Installation, Testing and Commissioning of Fire Retardant Canvass Connections with MS Eoxy painted / Al powdercoated finish angle flanges on both sides as per the specifications and approved drawings.

4

4967

19868

... More
Supply, installation, testing and commissioning of FM approved 32mm thickness of closed cell nitrile rubber without aluminium foil temperature range from -10ºC to +60ºC, Class O fire category and as per specification. for Underdeck insulation, as per technical specifications and as shown in approved drawings. Adhesive shall be used as recommended by insulation manufacturer for applying over concrete structures and it shall be green building complaint. Makes: Galaxy, sheth insulation, ALP Aeroflex,neothermalinsulation.

350

407

142450

... More
MS structural Steel for supports of Unit, Piping, Control cabling supports including fabrication,erection with GI clamps and brackets with adequate number of supports for pipes every 2.5 mts interval and at bends for Insulated refrigerant pipe for exposed areas etc

2500

106

265000

... More
FALSE CEILING WORK

-

-

-

... More
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre,shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I.

-

-

-

... More
wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint , all as per manufacturer's specification and also including the cost of making openings for light fittings, grills,diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : (a)12.5 mm thick tapered edge gypsum moisture resistant board. (Make : Gproc , L Strong , Armstrong)

500

1111

555500

... More
ELECTRICAL WORKS:

-

-

-

... More
MV Panels

1

390816

390816

... More
Supply, installation,Testing and Commissioning of 3 phase and Neutral 415V, 4 wire Free Standing Floor mounted MV panel made out of 14 SWG MS sheet after seven tank process and painting with Epoxy powder coating.

-

-

-

... More
The panel shall consist of suitable rating TPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and color coded with Heat shrinkable sleeves.

-

-

-

... More
The Metering shall be provided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below.

-

-

-

... More
The panel shall be got fabricated from manufacturers with CPRI Test certificate only. The PCC shall have at least two spare cubicles of the maximum rating. The size of all Panel Mounting Meters shall be 96X96mm.

-

-

-

... More
The Panels shall be mounted on U channels including supply and fixing of the same. Every ACB shall be provided with ON/OFF /Trip Indication lamps of LED type. For all Electrically operated Breakers, Local Remote Selector switches shall be provided for controlling the Breakers remotely.

-

-

-

... More
M.V.PANEL ( OUTDOOR ) - CHILLER PLANT

-

-

-

... More
Incoming : 800A FP 50KA EDO ACB with Microprocesser Based releases for Overload, S/C and earth fault- 1 set

-

-

-

... More
BUSBARS : 800A, TPN Aluminium busbars – 1set

-

-

-

... More
Metering for Incomer

-

-

-

... More
Phase indicating lamps - 1 set with toggle switch

-

-

-

... More
Voltmeter (0-500V) with selector switch - 1 set

-

-

-

... More
Ammeter (0-800A) with selector switch - 1 set

-

-

-

... More
Multifunction Meter -1Set

-

-

-

... More
800/5A, CL-1, 15VA CT's with resin cast- 3Nos.

-

-

-

... More
Outgoing Feeders :-

-

-

-

... More
250A TP 36KA MCCB As Outgoing Feeder (Air Cooled Screw Chiller) -2Nos

-

-

-

... More
100A TP 25KA MCCB As Outgoing Feeder (Dehumidifier 1,2,3 and 4) -4Nos

-

-

-

... More
15KW Star delta /DOL Feeder with Type II Coordination MCCB, Contactor, OLR, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (AHU Feeder) - 1Set

-

-

-

... More
15KW Star delta /DOL Feeder with Type II Coordination MCCB, Contactor, OLR, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (AHU Feeder) - 1Set

-

-

-

... More
10KW Star delta /DOL Feeder with Type II Coordination MCCB, Contactor, OLR, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (AHU Feeder) - 1Set

-

-

-

... More
5.5KW DOL Feeder with Type II Coordination MpCB, Contactor, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (Primary Chilled Water Pumps) - 4Sets

-

-

-

... More
5.5KW DOL Feeder with Type II Coordination MpCB, Contactor, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (Secondary Chilled Water Pumps) - 4Sets

-

-

-

... More
2.2KW DOL Feeder with Type II Coordination MpCB, Contactor, SPP, ON/OFF Push Button, ON/OFF/TRIP Indication Lamps, Auto/Manual Selector Switch with Ammeter & CTs (Pressurisation set) - 1Set

-

-

-

... More
250A TP 36KA MCCB As Outgoing Feeder (Spare) -2Nos

-

-

-

... More
100A TP 25KA MCCB As Outgoing Feeder (Spare) -2Nos

-

-

-

... More
VRF/VRV HVAC PANEL - OUTDOOR

1

309396

309396

... More
Supply, installation, Testing and Commissioning of 3 phase and Neutral 415V 4 wire Free Standing Floor mounted outdoor type weather proof double door with canopy on top MV panel made out of 3mm thick CRCA/Galvanised steel enclosure for main frame and 2mm thick partitions for mechanical strength/ruggedness, after seven tank process and painting with Epoxy powder coating. The panel shall consist of suitable rating TPN Aluminium busbar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and color coded with Heat shrinkable sleeves. The Metering shall be provided as specified. The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below. Outdoor panels shall have IP-55 degree of protection wiith external door . Enclosure shall be modular with bolted design. Enclosure shall be powder coated with RAL-7035 coat with matt finish. Design ambient temperature shall be 50 degree centrigrade. No use of hygroscopic material like FRP/Hylam/Bakellite sheet inside the panel for partitions or any other purpose.

-

-

-

... More
The PCC shall have at least two spare cubicles. The size of all Panel Mounting Meters shall be 96X96mm. The Panels shall be mounted on U channels including supply and fixing of the same. Every ACB shall be provided with ON/OFF /Trip Indication lamps of LED type. For all Electrically operated Breakers, Local Remote Selector switches shall be provided for controlling the Breakers remotely.ACB's shall have built-in All ACBs shall be provided with Digital type Ammeter of suitable range along with CTs. All ACBs shall be provided with ON/OFF/TRIP indication lamps and shunt trip coils. All MCCB/ACBs of rating 160A and above shall be with Micro processor releases All MCCBs below 160A shall be with adjustable thermal magnetic based releases. All MCCBs shall be with spreader links and rotary handle. All MCCBs shall be over load & short circuit releases with Icu=100% Ics. All CTs/CBCT shall be resin cast type. All Controlling wiring shall be FRLS cables, all the bus bar sleeves shall be Heat shrinkable kits. Panels shall have form 4b/form 3b construction as per the requirement. ACBs shall conform to IEC 60947 (part 1&2), shall be suitable for rated system voltage 690V, Insulation voltage 1000V and Impulse withstand of 12KV.

-

-

-

... More
For MCCB with Microprocessor based release : A common indication LED for internal temp/ fault/alarm . MCCB should have in-built feature of logical selectivity by which it can give a time delay of 50msec between upstream and downstream MCCB The microprocessor based release should have the following settings: • Overload Settings: 0.4 to 1 times of Ir • Short Circuit Settings: 1.25 to 10 times of Ir. • Earth fault Settings: 0.2 to 1 times of In. • Neutral protection settings: 0 – 50% – 100%Ir. • Manually closing mechanism should be accommodated in a Moulded housing of robust and vermin-proof construction. • MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open) • The tripping devices shall be ambient temperature compensated type. The insulating case shall be made of high strength heat resistant and flame retardant thermosetting insulating material.

-

-

-

... More
OUTDOOR MAIN PCC PANEL

-

-

-

... More
Incoming :

-

-

-

... More
400A FP, 50kA, Moulded Case Circuit Breaker and micro processor based protection release having adjustable over load, short circuit and earth fault protection. - 1No.

-

-

-

... More
Busbars :400A TPN Aluminium busbars - 1 set

-

-

-

... More
Outgoings :

-

-

-

... More
63A TPN, 16kA, Moulded Case Circuit Breaker and Electromagnetic based protection release having adjustable over load, short circuit and earth fault protection. - 20 No.

-

-

-

... More
63A TPN ,16kA MCCB - 2 Nos - Spare

-

-

-

... More
Metering :

-

-

-

... More
0-500V Digital Voltmeter with selector switch and Fuses - 2 sets

-

-

-

... More
0-400A Digital Ammeter with CTs of ratio 400/5A,Class 1 Accuracy and 15VA burden and selector switch - 2sets

-

-

-

... More
LED Phase indication lamps with individuals Fuses and control with toggle switches- 2sets

-

-

-

... More
CT Operated Load Manager with RS 485 port ( Similar to EM-6400) – 2sets

-

-

-

... More
Suitable Earth strip at bottom of the panel of GI Strip

-

-

-

... More
Supply, Installation, Testing and Commissioning of following size 1.1 KV Grade Aluminum / Copper conductor XLPE insulated PVC sheathed armoured cable and shall be laid on cable tray with all installation materials. the cable shall conform to IS 7098 / part-I.

-

-

-

... More
4Core X 50Sqmm (Copper) ( un Armoured) (for Chillers) - 2No's

120

6609

793080

... More
3.5C X 35Sqmm (Aluminimum) (for dehumidifier) - 2No's

400

4978

1991200

... More
4Core X 10Sqmm (Copper) (Armoured) (for Ahu's ) - 1No

50

5216

260800

... More
4Core X 16Sqmm (Copper) (Armoured) (for Ahu's ) - 1Nos

100

5415

541500

... More
4Core X 16Sqmm (Copper) (Armoured) (for Ahu's ) - 1Nos

50

5496

274800

... More
3Core X 4Sqmm - (Copper) (Armoured) (for Primary Pumps ) - 4Nos

90

4983

448470

... More
3Core X 4Sqmm - (Copper) (Armoured) (for Secondary Pumps ) - 4Nos

90

4983

448470

... More
1R X 3Core X 4Sqmm - (Copper) (Armoured) (for Pressurisation Set ) - 1No

50

4983

249150

... More
Supply, Installation, Testing and Commissioning of following size ELECTRICAL TERMINATIONS WITH SINGLE COMPRESSION GLANDS / LUGS:

-

-

-

... More
3.5Core X 50Sqmm . - (Copper) (for Chillers)

6

409

2454

... More
3Core X 4Sqmm - (Copper) (for chilled water Primary & Secondary Pumps )

12

60

720

... More
3.5C X 35Sqmm (Aluminimum) (for dehumidifier )

8

177

1416

... More
3Core X 10Sqmm (Copper)

2

167

334

... More
3Core X 16Sqmm (Copper)

4

167

668

... More
3Core X 16Sqmm (Copper)

2

167

334

... More
3C x 4 Sq.mm. - (Copper)

2

60

120

... More
SITC of GI Earthing for equipment

-

-

-

... More
8 SWG G.I. Wire

30

76

2280

... More
SUBHEAD-IVX : POWER WIRING :

-

-

-

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)

-

-

-

... More
12 way (8 + 36), Double door

2

14168

28336

... More
8 way (8 + 24), Double door

6

9628

57768

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
63A

8

6513

52104

... More
Supplying and fixing of 6A to 32A rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.

-

-

-

... More
Single Pole

216

358

77328

... More
Supplying and fixing following way, vertical type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)

-

-

-

... More
12 way (4 + 24), Double door

1

28143

28143

... More
8 way (4 + 24), Double door

6

18060

108360

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, molded case circuit breaker (MCCB), having a breaking capacity 25 KA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
200A 4P MCCB, 35 kA

7

30063

210441

... More
Supplying and fixing of following rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.

-

-

-

... More
63A Three Pole MCB 16 kA

60

2502

150120

... More
Supply,erection,testing and commissioning of the following switch sockets with anodised G.I. Box, front plate and fixing screws etc .

-

-

-

... More
6/16 Amps, 5-pin (250 Volts) single phase modular type socket controlled by 16 Amps SP Switch.

259

1280

331520

... More
Supply and fixing of factory made 20A, 1Ph Metalclad socket with plug top & 20A SPMCB in MS box including all fixing accessories

30

2139

64170

... More
Supply and fixing of factory made 25A, 1Ph Metalclad socket with plug top & 25A SPMCB in MS box including all fixing accessories

30

2509

75270

... More
Supplying and fixing 32A, 415V, TPN industrial type socket outlet with 4 pole and earth metal enclosed plug top alongwith 32A C Curve, TP MCB in sheet metal enclosure on surface/recess with chained metal cover for the socket outlet and complete with connections ,testing and commissionining etc complete as required.

25

7330

183250

... More
Supplying and fixing 63A, 415V, TPN industrial type socket outlet with 4 pole and earth metal enclosed plug top alongwith 63A C Curve, TP MCB in sheet metal enclosure on surface/recess with chained metal cover for the socket outlet and complete with connections, testing and commissionining etc complete as required.

26

16983

441558

... More
Supply,erection,testing and commissioning of the following switch sockets with anodised G.I. Box, Stainless steel front plate and fixing screws etc .

-

-

-

... More
6/16 Amps, 5-pin (250 Volts) single phase modular type socket controlled by 16 Amps SP Switch.

30

1456

43680

... More
Supply and Wiring with the following size 1100V grade PVC insulated multistrand, FRLS Copper conductor wires in and including suitable size heavy gauge PVC conduit concealed in wall / Ceiling including all accessories such as junction boxes, bends, elbows including end terminated with suitable lugs.

-

-

-

... More
2runs of 4Sq.mm wires with 1run of 4 Sq.mm wire in and including 25mm dia PVC Conduit(For 16A Sockets).

2400

353

847200

... More
2runs of 6Sq.mm wires with 1run of 6 Sq.mm wire in and including 25mm dia PVC Conduit(For AC Sockets).

1500

493

739500

... More
4runs of 10Sq.mm wires with 2run of 6 Sq.mm wire in and including 25mm dia PVC Conduit.

1500

941

1411500

... More
4 X 16 sq. mm + 2 X 16 sq. mm earth wire in existin PVC / Floor raceways

700

1482

1037400

... More
Supply and Wiring with the following size 1100V grade PVC insulated multistrand, FRLS Copper conductor wires in existing MS/PVC conduit / Floor race way including all necessary interconnections etc complete.

-

-

-

... More
2runs of 2.5Sq.mm wires with 1run of 2.5 Sq.mm wire in existing PVC Conduit(For 6A Sockets & Switch boards), ferrules incliding all labour charges etc., complte. .

500

128

64000

... More
2runs of 4Sq.mm wires with 1run of 4 Sq.mm wires in existing PVC Conduit(For 16A Sockets), ferrules incliding all labour charges etc., complte. .

600

188

112800

... More
2runs of 6Sq.mm wires with 1run of 6 Sq.mm wires in existing PVC Conduit(For AC Sockets), ferrules incliding all labour charges etc., complte. .

500

275

137500

... More
4runs of 6Sq.mm wires with 2run of 6 Sq.mm wires in existing PVC Conduit. for run of mains, ferrules incliding all labour charges etc., complte.

400

540

216000

... More
4runs of 10Sq.mm wires with 2run of 6 Sq.mm wire in existing PVC Conduit.for run of mains, ferrules incliding all labour charges etc., complte.

700

759

531300

... More
4 X 16 sq. mm + 2 X 16 sq. mm earth wire in existin PVC / Floor raceways for run of mains, ferrules incliding all labour charges etc., complte.

500

1329

664500

... More
Providing and fixing of maintenance free earthing which consists of 40mm Dia, standard length (as per Equipment Supplier) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Earth enhancing compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.

4

8673

34692

... More
Supply and laying of following size strips including all necessary inter connections with earth station and equipments

-

-

-

... More
50 X 5 mm Hot dip GI strip

200

329

65800

... More
25 X 5 mm Hot dip GI strip

200

220

44000

... More
Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.

2000

58

116000

... More
Supply and fixing of following size GI Perforated type cable tray made out of 2mm thick G.I sheet including MS supports for fixing the tray, anchor fasteners etc., laid including 2runs of 25x5 GI strip etc including with 2 mm thick GI covers.

-

-

-

... More
300 mm wide x 50 mm Height

150

1598

239700

... More
150 mm wide x 50 mm Height

200

1209

241800

... More
100 mm wide x 50 mm Height

200

1076

215200

... More
Supply, laying, jointing GI pipes of medium quality including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.

-

-

-

... More
50mm Dia

30

717

21510

... More
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor cable. The cable shall conform to IS 7098/ Part-II.

-

-

-

... More
3.5C X 400 Sq.mm

50

1614

80700

... More
3.5C X 300 Sq.mm

200

1284

256800

... More
3.5C X 240 Sq.mm

50

1070

53500

... More
3.5C X 185 Sq.mm

50

859

42950

... More
3.5C X 150 Sq.mm

200

686

137200

... More
3.5C X 70 Sq.mm

600

365

219000

... More
3.5C X 25 Sq.mm

900

175

157500

... More
4C X 16 Sq.mm

300

140

42000

... More
Copper armoured control cables

-

-

-

... More
i) 4C X 2.5 Sq.mm

100

144

14400

... More
ii) 7C X 2.5 Sq.mm

100

218

21800

... More
iii) 19C X 2.5 Sq.mm

100

509

50900

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

-

-

-

... More
Upto 35 sq. mm

50

422

21100

... More
Above 35 sq. mm and upto 95 sq. mm

30

441

13230

... More
Above 95 sq. mm and upto 185 sq. mm

30

454

13620

... More
Above 185 sq. mm and upto 400 sq. mm

100

507

50700

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.

-

-

-

... More
Upto 35 sq. mm

50

38

1900

... More
Above 35 sq. mm and upto 95 sq. mm

20

59

1180

... More
Above 95 sq. mm and upto 185 sq. mm

20

80

1600

... More
Above 185 sq. mm and upto 400 sq. mm

100

139

13900

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

-

-

-

... More
Upto 35 sq. mm

2200

40

88000

... More
Above 35 sq. mm and upto 95 sq. mm

350

72

25200

... More
Above 95 sq. mm and upto 185 sq. mm

150

110

16500

... More
Above 185 sq. mm and upto 400 sq. mm

1050

179

187950

... More
Providing Indoor ordinary end terminations for the foollwing 1.1 KV grade XLPE insulated armoured alluminium conductor cables with compression type steel gland, Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland with 8SWG GI Wire.

-

-

-

... More
3.5C X 400 Sq.mm

4

3572

14288

... More
3.5C X 300 Sq.mm

38

2875

109250

... More
3.5C X 240 Sq.mm

6

2555

15330

... More
3.5C X 185 Sq.mm

2

1944

3888

... More
3.5C X 150 Sq.mm

2

1717

3434

... More
3.5C X 70 Sq.mm

2

1096

2192

... More
3.5C X 25 Sq.mm

32

822

26304

... More
4C X 16 Sq.mm

8

535

4280

... More
End terminations of Copper armoured control cables including supply and fixing of crimping type copper lugs.

-

-

-

... More
i) 4C X 2.5 Sq.mm

2

336

672

... More
ii) 7C X 2.5 Sq.mm

2

357

714

... More
iii) 19C X 2.5 Sq.mm

2

870

1740

... More
SUBHEAD-XV : SHOP ELECTRIC:

-

-

-

... More
Supplying and fixing 20A, 415V, TPN industrial type socket outlet with 4 pole and earth metal enclosed plug top alongwith 20A C Curve, 4 P MCB in sheet metal enclosure on surface/recess with chained metal cover for the socket outlet and complete with connections ,testing and commissionining etc complete as required.

30

7111

213330

... More
Supplying and fixing 32A, 415V, TPN industrial type socket outlet with 4 pole and earth alongwith 32A C Curve, TP MCB in sheet metal enclosure on surface/recess with chained metal cover for the socket outlet and complete with connections ,testing and commissionining etc complete as required.

20

7330

146600

... More
Supplying and fixing 63A, 415V, TPN industrial type socket outlet with 4 pole and earth alongwith 63A C Curve, TP MCB in sheet metal enclosure on surface/recess with chained metal cover for the socket outlet and complete with connections ,testing and commissionining etc complete as required.

15

16983

254745

... More
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor cable. The cable shall conform to IS 7098/ Part-II.

-

-

-

... More
4C X 10 Sq.mm

200

103

20600

... More
4C X 16 Sq.mm

2500

140

350000

... More
3.5C X 25 Sq.mm

1000

174

174000

... More
3.5C X 35 Sq.mm

1000

209

209000

... More
4C X 50 Sq.mm Cu Armoured Cable

500

1826

913000

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

-

-

-

... More
Upto 35 sq. mm

50

422

21100

... More
Above 35 sq. mm and upto 95 sq. mm

10

441

4410

... More
Above 95 sq. mm and upto 185 sq. mm

50

454

22700

... More
Above 185 sq. mm and upto 400 sq. mm

50

507

25350

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.

-

-

-

... More
Upto 35 sq. mm

100

38

3800

... More
Above 35 sq. mm and upto 95 sq. mm

10

59

590

... More
Above 95 sq. mm and upto 185 sq. mm

50

80

4000

... More
Above 185 sq. mm and upto 400 sq. mm

50

139

6950

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

-

-

-

... More
Upto 35 sq. mm

4550

40

182000

... More
Above 35 sq. mm and upto 95 sq. mm

480

72

34560

... More
Above 95 sq. mm and upto 185 sq. mm

50

110

5500

... More
Above 185 sq. mm and upto 400 sq. mm

50

179

8950

... More
Providing Indoor ordinary end terminations for the foollwing 1.1 KV grade XLPE insulated armoured alluminium conductor cables with compression type steel gland, Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland with 8SWG GI Wire.

-

-

-

... More
4C X 10 Sq.mm

6

281

1686

... More
4C X 16 Sq.mm

160

535

85600

... More
3.5C X 25 Sq.mm

6

656

3936

... More
3.5C X 35 Sq.mm

4

663

2652

... More
4C X 50 Sq.mm Cu Armoured Cable

8

2874

22992

... More
Supply and fixing of following size GI Perforated type cable tray made out of 2mm thick G.I sheet including MS supports for fixing the tray, anchor fasteners etc., laid including 2runs of 25x5 GI strip etc including with 2 mm thick GI covers.

-

-

-

... More
600 mm wide x 50 mm Height

150

2375

356250

... More
450 mm wide x 50 mm Height

100

1983

198300

... More
300 mm wide x 50 mm Height

150

1598

239700

... More
150 mm wide x 50 mm Height

250

1209

302250

... More
Providing and fixing of maintenance free earthing which consists of 40mm Dia, standrad length (as per Equipment Supplier) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Earth enhancing compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.

4

8673

34692

... More
Supply and laying of following size strips including all necessary inter connections with earth station and equipments.

-

-

-

... More
50 X 5 mm Hot dip GI strip

200

329

65800

... More
25 X 5 mm Hot dip GI strip

500

220

110000

... More
Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.

100

58

5800

... More
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)

-

-

-

... More
12 way (8 + 36), Double door

2

28143

56286

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
250 A, 35KA 4P MCCB

4

40778

163112

... More
200 A, 35KA 4P MCCB

4

30063

120252

... More
63 A, 4P RCBO

24

6513

156312

... More
100 A, 4P ,25ka MCCB (

2

7803

15606

... More
125 A, 4P ,25ka MCCB (

1

10730

10730

... More
Supply,Installation Testing Commissioning of following TTA PANEL. Supply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 c/s Main LT Panel at Substation fully compartmentalized cubical type, as per the standards IEC61439-1&2 as tested assembly (TTA) ,tested for impulse voltage 8 KV,IP 42 fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having required capacity extensible type FP bus bars of high conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35KA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, Form of separation shall be form 4b with metallic separation only entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of bus bars, interconnection, interlocking between feeders etc.,with indication lamps, push buttons necessary accessories, complete with following incoming and outgoing switchgears with protection and metering etc. as per specification and schematic diagram including provision to be made for interfacing with BMS etc. complete as required, with incoming & outgoing cable entry from bottom/top and bus-duct entry from top, wiring with 2.5sq. mm. FRLS insulated copper conductor , cable alleys, PLC cable gland i/c providing following switch gears

-

-

-

... More
All ACBs should have Ics=Icu=Icw for 1 sec All MCCBs shall be rating for 25kA (Ics=Icu). All MCCBs above 63A should be provided with Copper Spreader Terminals Marshalling Bay To Be Provided for BMS Operation Approval shall be taken for each panel before fabrication. PLC based control with 100% hot redundant PLC arrangement with touch-screen LCD / LED display board (min. 8" Diag size) along with all accessories for complete automatic, manual and HMI controls & indication. Energy Management Software wth necessary cabling shall be in scope, nos. of breaker / Meters to be connect with energy management software shall be inform by Engineer In Charge.

-

-

-

... More
USER EQUIPMENT PANEL

1

514235

514235

... More
Incomer

-

-

-

... More
630 A, 50KA, 4P , MCCB, Should be supplied with Microprocessor based S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No

-

-

-

... More
2A, control MCB - 3 Nos.

-

-

-

... More
Outgoings :

-

-

-

... More
200A ,35KA TP, MCCBs - 9 Nos

-

-

-

... More
125A ,25KA TP, MCCBs - 3 Nos

-

-

-

... More
100A ,25KA TP, MCCBs - 3 Nos

-

-

-

... More
63A ,16KA TP, MCCBs - 3 Nos

-

-

-

... More
Surge Protection Device - 1 No

-

-

-

... More
Bus Bar : 630 A TPN Alluminium Bus Bar-1 Set

-

-

-

... More
Metering Incomer :

-

-

-

... More
0-500V Digital Voltmeter with selector switch and MCB-1set

-

-

-

... More
CT Operated Load Manager (similar to EM-6400) - 1 No

-

-

-

... More
0-630A Digital Ammeter with resin cast CTsof ratio 630/5A Class 1 Accuracy and 15VA burden and selector switch -1set

-

-

-

... More
LED phase indication lamps with toggle switch -1set

-

-

-

... More
Main LDB

1

205694

205694

... More
Incomer

-

-

-

... More
250 A, 35KA, 4P , MCCB, Should be supplied with Microprocessor based S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No

-

-

-

... More
2A, control MCB - 3 Nos.

-

-

-

... More
Outgoings :

-

-

-

... More
160A ,35KA TP, MCCBs - 5 Nos

-

-

-

... More
63A ,16KA TP, MCCBs - 2 Nos

-

-

-

... More
Surge Protection Device - 1 No

-

-

-

... More
Bus Bar : 250 A TPN Alluminium Bus Bar-1 Set

-

-

-

... More
Metering Incomer :

-

-

-

... More
0-500V Digital Voltmeter with selector switch and MCB-1set

-

-

-

... More
CT Operated Load Manager (similar to EM-6400) - 1 No

-

-

-

... More
0-250A Digital Ammeter with resin cast CTsof ratio 250/5A Class 1 Accuracy and 15VA burden and selector switch -1set

-

-

-

... More
LED phase indication lamps with toggle switch -1set

-

-

-

... More
Main PDB

1

241655

241655

... More
Incomer

-

-

-

... More
630 A, 50KA, 4P , MCCB, Should be supplied with Microprocessor based S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No

-

-

-

... More
2A, control MCB - 3 Nos.

-

-

-

... More
Outgoings :

-

-

-

... More
200A ,35KA TP, MCCBs - 5 Nos

-

-

-

... More
63A ,16KA TP, MCCBs - 2 Nos

-

-

-

... More
Surge Protection Device - 1 No

-

-

-

... More
Bus Bar : 630 A TPN Alluminium Bus Bar-1 Set

-

-

-

... More
Metering Incomer :

-

-

-

... More
0-500V Digital Voltmeter with selector switch and MCB-1set

-

-

-

... More
CT Operated Load Manager (similar to EM-6400) - 1 No

-

-

-

... More
0-630A Digital Ammeter with resin cast CTsof ratio 630/5A Class 1 Accuracy and 15VA burden and selector switch -1set

-

-

-

... More
LED phase indication lamps with toggle switch -1set

-

-

-

... More
COMPRESSOR PANEL

1

582560

582560

... More
Incomer

-

-

-

... More
250 A, 35KA, 4P , MCCB Should be supplied with Microprcessor based S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No

-

-

-

... More
2A, control MCB - 3 Nos.

-

-

-

... More
Outgoings :

-

-

-

... More
160A ,25KA TP, MCCBs - 2 Nos

-

-

-

... More
63A ,16KA TP, MCCBs - 1 Nos

-

-

-

... More
40A ,16KA TP, MCCBs - 1 Nos

-

-

-

... More
Surge Protection Device - 1 No

-

-

-

... More
Bus Bar : 250 A TPN Alluminium Bus Bar-1 Set

-

-

-

... More
Metering Incomer :

-

-

-

... More
0-500V Digital Voltmeter with selector switch and MCB-1set

-

-

-

... More
CT Operated Load Manager (similar to EM-6400) - 1 No

-

-

-

... More
0-250A Digital Ammeter with resin cast CTs of ratio 250/5A Class 1 Accuracy and 15VA burden and selector switch -1set

-

-

-

... More
LED phase indication lamps with toggle switch -1set

-

-

-

... More
SUBHEAD-XVI : TELEPHONE AND LAN :

-

-

-

... More
Supply and laying of 25mm dia, 16 SWG black enamelled M.S. conduit concealed in wall/ ceiling/ floor including all accessories such as junction boxes, conduit bends, etc., complete as required for Telephone etc.,

300

262

78600

... More
Supply and laying of 25mm dia, heavy gauge PVC . conduit concealed in wall/ ceiling/ floor including all accessories such as junction boxes, conduit bends, etc., complete as required for Telephone etc.,

1600

178

284800

... More
Supply and laying of 25mm dia, heavy gauge PVC . conduit concealed in wall/ ceiling/ floor and drawing of 12 SWG GI Wire as fish wire for laying of LAN Cables at a later stage and supply of all fixing accessories such as junction boxes, conduit bends, etc., complete as required.

1400

175

245000

... More
Supply and fixing of Telephone outlet (RJ11) with anodised GI box with front plate and fixing screws.

150

716

107400

... More
Supply,Installation,Testing and commissioning of RJ 45 socket(FOR LAN) with flush mounting G.I. box, with front plate and fixing screws etc complete.

250

1156

289000

... More
Supply and laying of 2pair 0.5mm dia PVC insulated Copper conductor Telephone wire conforming to DOT Specifications in already laid PVC Conduit including necessary interconnections.

600

34

20400

... More
Supply and laying of Cat 6 LAN cable conforming to DOT Specifications in already laid PVC Conduit Floor Race way including necessary interconnections.

12000

45

540000

... More
Supply and installation of 100 pair Krone connectors in MS junction box complete as required.

3

2346

7038

... More
Supply and installation of 50 pair Krone connectors in MS junction box complete as required.

2

1531

3062

... More
Supply and installation of 20 pair Krone connectors in MS junction box complete as required.

1

1043

1043

... More
Supply, laying, jointing GI pipes of medium quality including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.

-

-

-

... More
50mm Dia

10

717

7170

... More
SUBHEAD-XVII : UPS WIRING :

-

-

-

... More
Supply and fixing of 2 Nos of 6/16A, 5Pin Socket outlet with 2Nos of switch of 16A rating including Modular G.I Box, Front Plate and also including all fixing accessories etc complete. ( For UPS Socket)

250

1652

413000

... More
6/16 Amps, 5-pin (250 Volts) single phase modular type socket controlled by 16 Amps SP Switch including Modular G.I Box, Front Plate and also including all fixing accessories etc complete.

150

1280

192000

... More
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)

-

-

-

... More
4 way (4 + 12), Double door

4

23269

93076

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, molded case circuit breaker (MCCB), having a breaking capacity 25 KA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
200A 4P MCCB, 35 kA

4

30063

120252

... More
Supplying and fixing of following rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.

-

-

-

... More
63A TPN MCB 10 kA

16

2502

40032

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).

-

-

-

... More
8 way (8 + 24), Double door

6

9628

57768

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
63 A

6

6519

39114

... More
Supplying and fixing of 6A to 32A rating 240/415V, 10kA, C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections, testing and commissioning etc complete.

-

-

-

... More
Single Pole

144

358

51552

... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC/MS/Floor race way as required including necessary interconnections etc complete.

-

-

-

... More
2runs of 4Sq.mm wires with 1run of 4 Sq.mm wire

50

178

8900

... More
4 X 10 sq. mm + 2 X 6 sq. mm earth wire in existing PVC / Floor raceways /MS Conduit

50

703

35150

... More
4 X 16 sq. mm + 2 X 10 sq. mm earth wire in existing PVC / Floor raceways

50

1276

63800

... More
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required including excavation in all types of soil.

6

12992

77952

... More
Supplying and laying following copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets(Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm).

-

-

-

... More
25 mm X 5 mm copper strip

120

845

101400

... More
50 x 5 mm copper strip below ground.

200

2574

514800

... More
Supply and Installation of 300 x 38 mm height G.I Floor raceway including supply and installation of Junction Boxes ,bends and fixing accessories etc complete.The scope also includes civil work for installation of Raceways i.e chipping of flooe wherever required and also laying of sand and cement mortar for alignment of Floor raceways etc complete.The minimum thickness of the floor raceways and junction boxes shall be 2 mm (Make : Legrand )

400

3168

1267200

... More
Supply and Installation of 150 x 38 mm height G.I Floor raceway including supply and installation of Junction Boxes ,bends and fixing accessories etc complete.The scope also includes civil work for installation of Raceways i.e chipping of flooe wherever required and also laying of sand and cement mortar for alignment of Floor raceways etc complete.The minimum thickness of the floor raceways and junction boxes shall be 2 mm (Make : Legrand )

600

1765

1059000

... More
Supply,Installation Testing Commissioning of following TTA PANEL. Supply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 c/s Main LT Panel at Substation fully compartmentalized cubical type, as per the standards IEC61439-1&2 as tested assembly (TTA) ,tested for impulse voltage 8 KV,IP 42 fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having required capacity extensible type FP bus bars of high conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35KA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, Form of separation shall be form 4b with metallic separation only entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of bus bars, interconnection, interlocking between feeders etc.,with indication lamps, push buttons necessary accessories, complete with following incoming and outgoing switchgears with protection and metering etc. as per specification and schematic diagram including provision to be made for interfacing with BMS etc. complete as required, with incoming & outgoing cable entry from bottom/top and bus-duct entry from top, wiring with 2.5sq. mm. FRLS insulated copper conductor , cable alleys, PLC cable gland i/c providing following switch gears All ACBs should have Ics=Icu=Icw for 1 sec All MCCBs shall be rating for 25kA (Ics=Icu). All MCCBs above 63A should be provided with Copper Spreader Terminals Marshalling Bay To Be Provided for BMS Operation Approval shall be taken for each panel before fabrication. PLC based control with 100% hot redundant PLC arrangement with touch-screen LCD / LED display board (min. 8" Diag size) along with all accessories for complete automatic, manual and HMI controls & indication. Energy Management Software wth necessary cabling shall be in scope, nos. of breaker / Meters to be connect with energy management software shall be inform by Engineer In Charge.

-

-

-

... More
UPS INPUT PANEL INDOOR

1

215763

215763

... More
Incomer

-

-

-

... More
200 A, 50KA, 4P , MCCB Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No

-

-

-

... More
2A, control MCB - 3 Nos.

-

-

-

... More
Outgoings :

-

-

-

... More
100A ,25KA 4P, MCCBs - 3 Nos

-

-

-

... More
Surge Protection Device - 1 No

-

-

-

... More
Bus Bar : 200 A TPN(100%) Alluminium Bus Bar-1 Set

-

-

-

... More
Metering Incomer :

-

-

-

... More
0-500V Digital Voltmeter with selector switch and MCB-1set

-

-

-

... More
CT Operated Load Manager (similar to EM-6400) - 1 No

-

-

-

... More
0-200A Digital Ammeter with resin cast CTsof ratio 200/5A Class 1 Accuracy and 15VA burden and selector switch -1set

-

-

-

... More
LED phase indication lamps with toggle switch -1set

-

-

-

... More
UPS OUTPUT PANEL INDOOR

1

170884

170884

... More
Incomer

-

-

-

... More
200 A, 35KA, 4P , MCCB, Should be supplied with S/C, E/F, O/C Protection.(70 - 100% Plug setting) – 1No

-

-

-

... More
2A, control MCB - 3 Nos.

-

-

-

... More
Outgoings :

-

-

-

... More
63A ,10KA 4P, MCBs - 5 Nos

-

-

-

... More
Bus Bar : 200 A TP+N Alluminium Bus Bar-1 Set

-

-

-

... More
Metering Incomer :

-

-

-

... More
0-500V Digital Voltmeter with selector switch and MCB-1set

-

-

-

... More
CT Operated Load Manager (similar to EM-6400) - 1 No

-

-

-

... More
0-200A Digital Ammeter with resin cast CTsof ratio 200/5A Class 1 Accuracy and 15VA burden and selector switch -1set

-

-

-

... More
Surge Protection Device - 1 No

-

-

-

... More
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor cable. The cable shall conform to IS 7098/ Part-II.

-

-

-

... More
4C X 50 Sq.mm Cu Armoured Cable

100

1826

182600

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

-

-

-

... More
Above 35 sq. mm and upto 95 sq. mm

5

441

2205

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.

-

-

-

... More
Above 35 sq. mm and upto 95 sq. mm

5

59

295

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

-

-

-

... More
Above 35 sq. mm and upto 95 sq. mm

90

72

6480

... More
Providing Indoor ordinary end terminations for the foollwing 1.1 KV grade XLPE insulated armoured alluminium conductor cables with compression type steel gland, Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland with 8SWG GI Wire.

-

-

-

... More
4C X 50 Sq.mm Cu Armoured Cable

2

2874

5748

... More
SUBHEAD-XVIII : SPECIAL EARTHING :

-

-

-

... More
Providing and fixing of maintenance free earthing which consists of 65 MM Dia ,2.5 mtr long electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Earth enhancing compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.

20

11185

223700

... More
Supply and laying under ground/above ground of following size strips including all necessary interconnections between earth station and equipments including earth excavation, back filling, intermediate supports for strips as applicable and directed by engineer in charge.

-

-

-

... More
25 x 3 mm copper strip on DMC insulators

1000

980

980000

... More
25 x 3 mm copper strip below ground.

500

1066

533000

... More
50 x 5 mm copper strip below ground.

100

2574

257400

... More
Supply and fixing of Static Discharge Handles made out of 40 mm dia Copper rod 600 mm Long fixed on wall with brass spacers and connected to 25 x 3 mm copper strip by brazing.

5

4487

22435

... More
Supply, laying, jointing GI pipes of medium quality including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.

-

-

-

... More
50mm Dia

20

717

14340

... More
SUBHEAD-XIX : LIGHTNING PROTECTION :

-

-

-

... More
Providing and fixing of maintenance free earthing which consists of 40mm Dia ,standrad length (as per Equipment Supplier ) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Earth enhancing compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.

10

8538

85380

... More
Supply and laying of following size strips including all necessary inter connections between earth station and equipment. supports for strips as applicable and directed by engineer in charge.

-

-

-

... More
32 X 6 mm Aluminium strip conductor with DMC Insulator Supports

800

260

208000

... More
50 X 5 mm GI strip conductor including excvation and back filling.

700

330

231000

... More
25 X 5 mm Hot dip GI strip

200

230

46000

... More
Supply and installation of vertical air termination with 100mm dia copper hollow sphere with spikes, fixed on 1500mm length 50mm dia Class C GI pipe including all fixing accessories.

22

4467

98274

... More
Providing and fixing of Test links for Lightning protection system.

22

2087

45914

... More
SUBHEAD-XX : FIRE ALARM SYSTEM :

-

-

-

... More
Supply, erection, testing and commissioning of Intelligent Addressable Fire Alarm Control Panel (a minimum of 159 detectors/ 159 modules per loop )with Network Communication Module expandable to 2 loop, to monitor loop Devices located in all floor with dual stage alarm facilities,built in buzzer,built in NAC Circuits & RS 485 port on CPU board with optional net work software connectivity, fire/fault indicators, audio-visual signals, battery, battery charger, central processing unit,80 character display unit, fibre optic converter and networking card etc complete in all respects .

-

-

-

... More
2 - Loop Panel ( One Loop for Integration )

1

274064

274064

... More
Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches etc complete.

1

210056

210056

... More
Supply, Installation, Testing and commissioning of Online UPS of 1 KVA capacity with built-in SMF Batteries (12V 7Ah X 3nos) for battery back up and regulated AC supply to the FAS.

1

39938

39938

... More
COMIBINATION/MULTI SENSOR DETECTORS (Photoelectric + Heat Sensing)

-

-

-

... More
Supply, fixing, testing and commissioning of Addressable anlogue type multi sensor detectors (Photo electric + Heat sensing) with dual chamber, solid state design,Rotatable DIP Switch Setting indicating lamp, mounting base etc. .

180

3692

664560

... More
Supply, fixing, testing and commissioning of Response Indicators with all required accessories etc complete.

50

225

11250

... More
Supply, fixing, testing and commissioning of Addressable anlogue type Beam Detector with transmitter and receiver including short circuit isolator including connections with remote test features etc complete. Range 100 Mtr

3

43070

129210

... More
MANUAL CALL POINTS:

-

-

-

... More
Supply, erection, testing and commissioning of Addressable analogue type manual call point for indoor installtion.

22

3516

77352

... More
Supply, Installation, Testing and commissining of Addressable analogue type manual call point stations weather proof with 1500 mm Length ISMC 100 standing Post.

2

8930

17860

... More
FAULT ISOLATION MODULE:

-

-

-

... More
Supply, fixing, testing and commissioning of Fault Isolation module.

9

3516

31644

... More
Supply, installation, testing & commissioning of addressable fire control module complete as required.

4

3611

14444

... More
Supply, installation, testing & commissioning of addressable fire Monitor module complete as required.

10

4200

42000

... More
CABLE:

-

-

-

... More
Supply, laying , testing and commissioning of 1100 V grade FIRE RESITANCE LOW SMOKE PVC insulated copper conductor control cables as per specification.

-

-

-

... More
Armoured Twisted pair 2C x 1.5 sq. mm. shielded FRLS insulated copper conductor cable to be laid on cable tray /to be clamped to wall including supply and fixing of clamps etc complete.

2000

150

300000

... More
Armoured Twisted pair 2C x 1.5 sq. mm. shielded FRLS insulated copper conductor cable to be laid in cable trench including excavation and backfilling.

400

181

72400

... More
3 core x 2.5 Sq.mm armoured sheilded twisted pair copper conductor cable on cable tray/on wall including clamping etc complete and including cable end termination with double compression weather proof cable glands and copper lugs.

150

191

28650

... More
Supply and Installtion of 12 Way Elmex terminal powder Coated junction Box including all terminations and Necessary Glands.

2

7139

14278

... More
Supply, Installation, Testing and commissioning of Weather proof siren to be operated on Single Phase 230 V, 50 Hz ,A.C.Supply with a range of 2/3 km distance including fixing clamps and accessories.complete.

1

42971

42971

... More
Supply, laying of 50mm dia, class-B GI pipe including specials of approved make fixed to wall/to the required lengths, threading jointing chasing the walls and floor, making holes, clamping of clamps and making good the same, necessary excavation, etc., complete as specifed and directed.

10

717

7170

... More
Supply and laying of of 6 core 9/125 micro meters armored single mode optical fiber cable with suitable dia HDPE pipe (1300nm wave length) including splicing & terminations and laid in ground at 750 mm below ground including excavation and sand, brick protection and refilling of earth and cable route markers at every 50 meters intervals. 6C SM ARM-OFC - 6 C Armoured Single Mode Optical Fiber Cable networking card and fibre optic converter etc., complete.

1000

440

440000

... More
Supply and laying of 25mm dia, 16 SWG black enamelled M.S. conduit concealed in wall/ ceiling/ floor including all accessories such as junction boxes, conduit bends, etc., complete as required duly coated with two coats of red colour enamel paint etc., complete.

2000

266

532000

... More
SUBHEAD-XXI : FIRE FIGHTING SYSTEM :

-

-

-

... More
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :

-

-

-

... More
Single headed Gunmetal

18

9055

162990

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze /gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :

-

-

-

... More
80 mm dia

18

6220

111960

... More
150 mm dia

6

11216

67296

... More
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required :

-

-

-

... More
80mm dia

10

13030

130300

... More
150mm dia

2

27183

54366

... More
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts,washers etc.as required :

-

-

-

... More
80mm dia

2

9645

19290

... More
150mm dia

3

22759

68277

... More
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :

-

-

-

... More
Gun Metal

36

5096

183456

... More
Supply, installtion, testing and commissioning off Hose Box to accommodate 2sets of CP hoses of 15 mtr length each and with 1 pair of Male and female coupling, and one branch pipe with nozzle. The cabinet shall be made of 16 SWG MS Sheet with double door glass front and painted with Scarlet Red colour of size 30"x24".

18

33660

605880

... More
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :

-

-

-

... More
Gun metal

18

2430

43740

... More
Supply, Installation, Testing and Commissioning of Swinging type fire hose reel drum of Rubber hose 30mtrs length.

8

11691

93528

... More
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :

-

-

-

... More
4 way - 150 mm dia M.S. Pipe

2

14912

29824

... More
Providing, laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts,gaskets etc. in ground including welding, as supports, anticorrosive treatment with coaltar/asphalt/bitumen tape as per IS 10221, refilling the trench etc. of following sizes complete as required.

-

-

-

... More
150 mm dia. Pipe

800

2866

2292800

... More
80 mm dia. Pipe

100

1656

165600

... More
50 mm dia. Pipe

100

1232

123200

... More
Supply, errect, jointing, testing and commissioning of heavy class MS pipes (as per IS-1239). The pipes being fixed on to the wall or suspended from the ceiling/ truss with angle iron supports complete with bends, tees, flanges and with all other required accessories including painting of the pipeline with two coats of approved enamel paint over a coat of primer etc. complete.

-

-

-

... More
150 mm dia.

200

2291

458200

... More
100 mm dia.

300

1630

489000

... More
80 mm dia.

300

1186

355800

... More
65 mm dia.

200

992

198400

... More
50 mm dia.

200

826

165200

... More
40 mm dia.

200

651

130200

... More
32 mm dia.

250

592

148000

... More
25 mm dia.

1000

512

512000

... More
Supply and installation , Testing and commissioing of approved make 15mm orifice quartzoid bulb pendent type sprinklers, 68°C rating, recessed

360

333

119880

... More
Supply and installation, Testing and commissioing of approved make 15mm orifice quartzoid bulb side wall pendant type sprinklers, 68°C rating.

160

373

59680

... More
Supply installation and fixing of flow switches in the following Pipe line with 1NO+1NC Contacts

-

-

-

... More
a) 150/100mm dia

5

5446

27230

... More
Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m : Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.

-

-

-

... More
In ordinary soil.

1250

718

897500

... More
Excavating trenches of required width for pipes, cables, etc, including excavation for sockets, depth upto 1.5 m, including getting out the excavated materials, returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layers by ramming, watering etc., stacking serviceable material for measurements and disposal of unserviceable material as directed, within a lead of 50 m : Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia

-

-

-

... More
Hard rock (blasting prohibited)

50

1415

70750

... More
Ordinary rock :

50

1331

66550

... More
Construction valve chamber 1.8 Mtrs x 1.2 Mtrs x 1.2 Mtrs in first class brick (table moulded) masonry in CM 1:6 on PCC bed to 100mm thick plastering with CM 1:4 internal and providing CI Cover with stiffness lifting arrangement frame work etc. complete with providing anticorrosive paint on both side for steel works. Cover should be in two halfs fixed to frame work by means of hinges.

2

13052

26104

... More
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :

-

-

-

... More
300 mm dia. R.C.C. pipe

30

1024

30720

... More
Supply, laying, jointing, testing and commissioning heavy class M.S pipe (as per IS-1239) in Pump room with MS supports including two coats of red oxide and two coats of Red coloure enamel paint . Rate quoted shall include for necessary specials like long radius bends, tees, including cutting, welding/ flanged joints with necessary washers, nuts, bolts etc., complete.

-

-

-

... More
250 mm dia. Pipe

54

4868

262872

... More
200 mm dia. Pipe

24

3909

93816

... More
150 mm dia. Pipe

24

2717

65208

... More
100 mm dia. Pipe

12

1992

23904

... More
80 mm dia. Pipe

12

1507

18084

... More
Supply, Installation,Testing and Commissioning of air cussion vessel of capacity 250 litres with air release valve and ball valve.

1

21675

21675

... More
Supply,Installation,Testing and Commissioning of PN 16 Sluice valves with gate of the following sizes.

-

-

-

... More
a) 250mm dia

1

61491

61491

... More
b) 200mm dia

3

42625

127875

... More
c) 100mm dia

2

18621

37242

... More
Supply,Installation,Testing and Commissioning of PN 16 Butterfly valves of the following sizes including flanges and hardware ,nuts and bolts etc complete.

-

-

-

... More
a) 200mm dia

3

17997

53991

... More
b) 80mm dia

2

6220

12440

... More
Supply, Installation, Testing and Commissioning of CI Non Return valves of the following sizes.

-

-

-

... More
a) 200mm dia

3

38360

115080

... More
b)80mm dia

2

9645

19290

... More
Supply, installation, testing and commissioning of approved make brass "Y" strainer with necessary flanges which should include nuts, bolts, washers, gaskets.

-

-

-

... More
a) 200 mm dia.

3

48127

144381

... More
c) 100 mm dia.

2

33707

67414

... More
Supply,Installation,Testing and Commissioning of electrical control panel for diesel engine, main motor and for jockey pump comprising of following.

1

331466

331466

... More
Incoming : 800A,50KA TPNMCCB - 1SET

-

-

-

... More
800A TPN aluminium busbars - 1set

-

-

-

... More
Outgoings:

-

-

-

... More
Main Fire Pump 250 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 100 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets

-

-

-

... More
(with built in single phase preventor) and ON/OFF/TRIP

-

-

-

... More
indication lamps for motor-2set

-

-

-

... More
Jockey Pump 125 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets

-

-

-

... More
Diesel Engine Control

-

-

-

... More
Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification

-

-

-

... More
Supply installation testing and commissioning of Instrumentation Board on type pressure gauges for pumps in delivery line and common delivery header

4

2072

8288

... More
Supply fabrication and erection of MS angle supports for Pipe lines

1.5

109000

163500

... More
Supply and fixing of G.M. ball type valves Conforming to IS

-

-

-

... More
a) 25mm dia

12

1506

18072

... More
b) 15mm dia

12

313

3756

... More
Supply, Installation, Testing and Commissioning of Pressure Switches. Make: Indfoss/Donfoss

5

2198

10990

... More
Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required : Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered with anti vibration pads. 2280 lpm at 70 m Head with 70% of Pump efficiency.

2

313671

627342

... More
Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 2280 lpm at 70 m Head with 70% of Pump efficiency.

1

486892

486892

... More
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads. 180 lpm at 70 m Head

2

98627

197254

... More
Supply, Installation of following Fire extinguishers & accessories:

-

-

-

... More
CO2 6.5 kg capacity trolley mounted

4

11399

45596

... More
CO2 22.5 kg capacity trolley mounted

4

48852

195408

... More
DCP 5 kg capacity (potassium bi-carbonate Uria reaction)

4

7057

28228

... More
Water buckets with stand

4

1303

5212

... More
Sand buckets with stand

4

1303

5212

... More
Showels

4

1303

5212

... More
Fire Beater

4

489

1956

... More
Fire gong/ hand siren

4

1575

6300

... More
Ceiling Hook

4

272

1088

... More
Supplying, installation, testing & commissioning of 1000 MM sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.

150

1569

235350

... More
Supplying, installation, testing & commissioning of 1500 MM sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.

150

1813

271950

... More
Supplying Installation Testing & Commissioning of Ceiling Mounted exit sign/emergency lighting unit uses high-performance led lamps.

10

4446

44460

... More
SUBHEAD-XXII : WATER COLLERS

-

-

-

... More
Supply and fixing of 40 (cooling)/ 80 (storage) ltrs water cooler with water purifier (RO system) and voltage stabilizer etc. complete.

4

65007

260028

... More
SUBHEAD-XXIII : LIFTS :

-

-

-

... More
Supply, erection, testing and commissioning of Machine room less gear less 1000Kgs Goods lift with a speed of 0.75 meters per second, suitable for (Ground + 2floors) floors operation with 3 phase AC VVVF drive of suitable HP to operate on 415 volts 50 HZ with base including 1100X 1300X2300 mm car made of all stainless steel body, heavy duty cabin suitable for one number car entrance and landing entrance doors ( Center operated doors ) , SS hairline finish , with clear opening of 800x2100mmn height suitable for simplex selective and collective operation with or without attendant including call register and other parameters as per specification

1

2714000

2714000

... More
SUBHEAD-XXIV : EOT CRANES

-

-

-

... More
Design, Manufacture, supply , erection, testing and Commissioning of Tandem operator (1 set consist of 2 nos of cranes) Double Girder Non FLP EOT Crane with all speeds "VVVF drive control and micro speed arrangement for hoist, CT & LT and confirming to IS 807/IS 3177 /4137c and other relevant IS standards of the latest revisions as shown below complete with all taxes, duties and other charges such as transportation to site, loading and unloading at stores / building, where to be installed etc., movement of material to work spot including the cost of paint as required loaded testing at factory and at site. The crane shall be designed for earthquake and sesmic qualification. Span to be measured by the the Bidder at Site and it shall be its sole responsibility to provided Span suitable . Design drawings and list of materail to be submitted to department duly approved checked by Govt., agency/ reputed technical institute as approved by department. VVVF drive controls with along travel and cross travel movement and with pendent control opeartion as per IS807 &IS3177(including festool cable, 60 lb rails, third party inspection, transportation, design proof check) Double Girder Box Type. 25% overload ,Duty class- III, head Room 2.5mtr,side clearence 300.indoor operation. AC Control Supply , Floor operated via pendant push button,All drives should be provided with alternative parallel path with DOL starter for Main Speed only

-

-

-

... More
MOTORS- Conforming to IS 325-1978& 900-1965,

-

-

-

... More
GEAR BOX- Electro Hydraulic Thrusters type, 3Ph, 440V, A.C. Conforming with IS 3938 - 1983

-

-

-

... More
WIRE ROPE- 6X 36 Cont. Hempcore(IS 2365-1963)

-

-

-

... More
Rope Drum- made from Seamless/ms rolled

-

-

-

... More
Hook- Forged Material EN-3A

-

-

-

... More
WHEEL ASSEMBLY- Made from forged steel- Double flange hardened to BHN 275 Conforming with IS 807-1976.

-

-

-

... More
BEARING- All bearings are of anti Friction Ball/ Roller Conforming, with IS 6455-1972

-

-

-

... More
COUPLING- AlI Couplings will be Geared Coupling

-

-

-

... More
SHAFT- All Shafts will be of EN - 9

-

-

-

... More
RESISTANCE BOXES- AlI resistance boxes will be stainless steel, Wire grid and 15 min. Rated heavy duty, (IS 1822 -1967 )

-

-

-

... More
LIMIT SWITCH- Rotary Limit Switch for Hoisting & Lever Type for L.T &C.T. Conforming with IS- 3936 - 1983

-

-

-

... More
PANEL BOXES - All panel boxes will be of steel febricated

-

-

-

... More
CONTROL TRANSFORMER- 750 VA, 44OV / LLOV.

-

-

-

... More
POWER CONTROL CABLE -Sheet Metal housing, DustlVermin Proof having BCH/Siemens Contactors & Overload ReIays' BCH time delay Relay

-

-

-

... More
PAINT- Two coats of Red Primer & Two coats of Golden Yellow.

-

-

-

... More
Full platform on driving side & two small platform on non driving side.(Monkey ladder &side railing shall be provided by civil)

-

-

-

... More
PART- I : SUPPLY

-

-

-

... More
Supply of Non-Flameproof Tandem Operated ( 1 set consist of 2 Nos of 5 Ton capacity cranes) 5 Ton capacity Double Girder Crab type EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 31774137 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. Span:16.0 mts. ± 0.5 mtrs.to be checked as per site condition ± Lift: 8.5 mts. Bay length: 86 ± 0.5 mtr (to be checked as per site condition ±

1

4317296

4317296

... More
Crane operating speeds

-

-

-

... More
Main speed Micro speed

-

-

-

... More
Main hoist : 2.5m/min 0.25m/min

-

-

-

... More
Cross travel : 10m/min 1.0m/min

-

-

-

... More
Long travel : 15m/min 1.5m/min

-

-

-

... More
Micro speed for all motions : 10% of main speed through VVVF drives.

-

-

-

... More
Provision of inching is to be incorporated in the drives.

-

-

-

... More
Supply of shrouded bus bar system with double shoe copper current collections system complete with support tracks, cable loops, junction boxes and cable from main supply point to crane festoons with all necessary fixtures etc complete as per site condition (For 5 ton capacity crane as per above BOQ EOT 1.1)

172

3306

568632

... More
Supply of material for Gantry Rails section 60 Lb of prime material in length of 10 mts and above complete with mounting arrangement at the building over the crane girder including painting of rails with approximate colour code as approved by the dept as per site condition (For 5 ton capacity crane as per above BOQ EOT 1.1)

172

1831

314932

... More
Supply of Non-Flameproof Tandem Operated ( 1 set consist of 2 Nos of 2 Ton capacity cranes) 2 Ton capacity Double Girder Crab type EOT Crane with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 31774137 and other relevant IS standards of the latest revision. All drives should be provided with alternative parallel path with DOL starter for Main Speed only. Span:12.0 mts. ± 0.5 mtrs.to be checked as per site condition ± Lift: 8.5 mts. Bay length: 26 ± 0.5 mtr (to be checked as per site condition ±

1

2988128

2988128

... More
Crane operating speeds

-

-

-

... More
Main speed Micro speed

-

-

-

... More
Main hoist : 2.5m/min 0.25m/min

-

-

-

... More
Cross travel : 10m/min 1.0m/min

-

-

-

... More
Long travel : 15m/min 1.5m/min

-

-

-

... More
Micro speed for all motions : 10% of main speed through VVVF drives.

-

-

-

... More
Provision of inching is to be incorporated in the drives.

-

-

-

... More
Supply of shrouded bus bar system with double shoe copper current collections system complete with support tracks, cable loops, junction boxes and cable from main supply point to crane festoons with all necessary fixtures etc complete as per site condition (For 2 ton capacity crane as per above BOQ EOT 2.1)

104

3306

343824

... More
Supply of material for Gantry Rails section 50 mm sqr bar of prime material in length of 10 mts and above complete with mounting arrangement at the building over the crane girder including painting of rails with approximate colour code as approved by the dept as per site condition (For 2 ton capacity crane as per above BOQ EOT 2.1)

104

1831

190424

... More
Part-II: - ERECTION, TESTING AND COMMISSIONING

-

-

-

... More
Erection, testing and commissioning of Non FLP EOT Tadem Opereated following Double Girder EOT Cranes including loaded testing and others mentioned in item S.No.EOT-1.1 to EOT-2.3 of Part-I as per the relevant IS standards and as mentioned in the technical specifications.

-

-

-

... More
Erection, testing and commissioning of Non Flameproof Tadem Opereated Double Girder EOT Cranes of 5 Ton capacity ( 1 set consist of 2 Nos of 5 Ton capacity cranes) mentioned in Items .No.EOT-1.1 of Part-I with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. including loaded testing All drives should be provided with alternative parallel path with DOL starter for Main Speed only. Span:16.0 mts. ± 0.5 mtrs. Lift: 8 mts. Bay length: 86 ± 0.5 mtr to be checked as per site condition ±

1

4317296

4317296

... More
Erection testing and commissioning of shrouded type current collection system complete as per the item Sl No.EOT-1.2 of Part I over the crane bay including tapping of supply for electrical panel testing & handing over the crane as per the approved QA plan etc complete as per site condition.

172

1308

224976

... More
Erection, testing & commissioning of Gantry rail section 60 Lb mentioned in item Sl No.EOT-1.3 of Part -I with mounting arrangement and fixing hardware etc., complete over the bay length to match the span of the crane within the permissible accuracy levels for span in height variation as per the QA Plan etc complete as per site condition.

172

3775

649300

... More
Erection, testing and commissioning of Non Flameproof Tadem Opereated Double Girder EOT Crane of ( 1 set consist of 2 Nos of 2 Ton capacity cranes) mentioned in Items .No.EOT-2.1 of Part-I with VVVF drive complete with long travel and cross travel movements as per technical specifications and as per IS: 807 / IS: 3177 and other relevant IS standards of the latest revision. including loaded testing All drives should be provided with alternative parallel path with DOL starter for Main Speed only. Span:12.0 mts. ± 0.5 mtrs. Lift: 8 mts. Bay length: 26 ± 0.5 mtr to be checked as per site condition ±

1

2988128

2988128

... More
Erection testing and commissioning of shrouded type current collection system complete as per the item Sl No.EOT-2.2 of Part I over the crane bay including tapping of supply for electrical panel testing & handing over the crane as per the approved QA plan etc complete as per site condition.

104

1308

136032

... More
Erection, testing & commissioning of Gantry rail section 50 mm sqr bar mentioned in item Sl No.EOT-2.3 of Part -I with mounting arrangement and fixing hardware etc., complete over the bay length to match the span of the crane within the permissible accuracy levels for span in height variation as per the QA Plan etc complete as per site condition.

104

3775

392600

... More
Supply of Test loads of 5 Ton along with Slings and 'D'-shakles (Suitable for 5 Ton, loads of 5 ton -1 no, 1 ton-1 nos, 0.25 ton -1 nos

1

172593

172593

... More
Supply of Test loads of 2 Ton along with Slings and 'D'-shakles (Suitable for 2 Ton, loads of 2 ton -1 no, 0.5 ton -1 nos

1

111140

111140

... More
SUBHEAD-XXV : BOOM BARRIER:

-

-

-

... More
Supply,Installation,Testing and commissioning of 6 mtr length Boom Barrier electromechanical hydraucally operated opening and closing times can be adjusted between 3 to 6 seconds and speeds can be adjusted seperately through hydraulic adjusters in a closed circuit system optional emergency close option 2 seconds shall be available with 100% duty cycle with power supply unit,photo sensors,flashing lights on the boom ,push button for entry,exit & Remote control.This shall be along with safety features like Induction and safety loop etc with remote operating facility with remote control unit,along with 4 nos of photo cells with each boom barrier.The system shall be complete in all respects along with all fixing accessories and civil works

1

165554

165554

... More
SUBHEAD-XXVI : ROADS/HARDSTANDING & DRAINS :

-

-

-

... More
Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.

3810

195

742950

... More
Banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with ½ tonne roller, or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up, in embankments for roads, flood banks, marginal banks, and guide banks etc., lead upto 50 m and lift upto 1.5 m in all kinds of soils.

800

573

458400

... More
Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge.

792

3253

2576376

... More
Providing and laying Bituminous concrete using crushed stone aggregates of specified grading, premixed with bituminous binder and filler, transporting the hot mix to work site by tippers, laying with paver finisher equiped with electronic sensor to the required grade, level and alignment and rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction and density as per specification, complete and as per directions of Engineer-in-Charge.

162

12819

2076678

... More
40/50 mm compacted thickness with bitumen of grade VG-30 @ 5.5% (percentage by weight of total mix) and lime filler @ 3% (percentage by weight of Aggregate) prepared in Batch Type Hot Mix Plant of 100-120 TPH capacity.

-

-

-

... More
Providing and applying tack coat using bitumen emulsion conforming to IS:8887, using emulsion pressure distributer including preparing the surface & cleaning with mechanical broom.With rapid setting bitumen emulsion. On W.B.M / W.M.M. @ 0.4kg/Sqm.

3240

17

55080

... More
Providing and laying seal coat of premixed fine aggregate ( passing 2.36 mm and retained on 180 micron sieve) with bitumen using 128 kg of bitumen of grade VG - 10 bitumen per cum of fine aggregate and 0.60 cum of fine aggregate per 100 sqm of road surface, including rolling and finishing with road roller all complete.

3240

84

272160

... More
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).

41

9518

390238

... More
SUBHEAD-XXVII : EXTERNAL WATER SUPPLY SERVICES :

-

-

-

... More
Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.

-

-

-

... More
25 mm dia nominal bore

100

430

43000

... More
40 mm dia nominal bore

150

561

84150

... More
50 mm dia nominal bore

100

758

75800

... More
100 mm dia nominal bore

200

1019

203800

... More
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :

-

-

-

... More
50 NB

15

1016

15240

... More
Making connection of G.I distribution branch with G.I main of folloeing size by providing and fixing tee, inclding cutting and threading the pipe etc. complete:

-

-

-

... More
25 to 40 mm nominal bore

1

786

786

... More
50 to 80 mm nominal bore

1

1699

1699

... More
Providing and fixing gun metal non- return valve of approved quality (screwed end) :

-

-

-

... More
25 mm nominal bore

6

485

2910

... More
40 mm nominal bore

6

969

5814

... More
50 mm nominal bore

5

1246

6230

... More
Supply,erection, testing and commissiong of C.I Air release valves flanged end type with bolts,nuts and rubber insertions etc., complete and of following sizes:

-

-

-

... More
25 mm nominal bore

1

2990

2990

... More
50 mm nominal bore

1

4983

4983

... More
Supply and Fixing of cast iron pipe line Route Marker for water supply Network system

100

382

38200

... More
Borewells

-

-

-

... More
Geological Survey by specialist Agencies and submitting the report for number of poit surved and yield available

4

10695

42780

... More
Drilling and developing of 61/2 inch dia Bore Wells by DTH method in any type of soil, Conducting yield test as per V Notch method and submission of yield report, including filling of filter media clamps, MS Cover etc., complete.

-

-

-

... More
a) 0-60 mtrs

40

936

37440

... More
b) 61-100 mtrs

60

936

56160

... More
c) 101-200 mtrs

200

1471

294200

... More
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 150 mm Dia.

50

2591

129550

... More
Providing HDPE pipe PE-80 grade (12.5 kg/ sq.cm) of 63 mm OD for bore wells.

500

3809

1904500

... More
Supply, erection, testing and commissioning of 3 Cu.m/hr at 70 m head submersible pump set 3Phase-415V, 50 Hz, 2 HP/ 12 stages, 2900 rpm as approved by Engineer in charge at site.(As per depth of base)

2

26266

52532

... More
Supply, erection, testing and commissioning of Gun metal Check valve (Non return valve PN-10) conforming to IS 778 with screwed ends type with bolts, nuts and rubber insertions etc., complete and of following sizes:

-

-

-

... More
a) 50 NB

4

1920

7680

... More
Supply, erection, testing and commissioning of Brass / GM / Bronze Air Release valves with threaded ends of following sizes:

-

-

-

... More
a) 25 NB

2

3383

6766

... More
Supply, erection, testing and commissioning of pressure gauges with range of 0-10 bar along with isolation cock and pipe for bore wells.

2

1553

3106

... More
Supply, installation, testing and commissioning of weather proof type box (IP-55) made out of 2 mm thick CRCA sheet including painting with epoxy powder coating. The box shall be consisting of star-delta starter suitable for 3 Cu.m/hr and 200 meters head pump motor with MPCB, contactor, overload relay, ON/ OFF push button. ON/ OFF/ TRIP indications. Ammeter with resin cost Cts and selector switch, Voltmeter with selector switch. The box shall be suitable for terminating suitable cable. The box shall be mounted on suitable angle frame work of 450 mm height on a PCC pedestal including all materials, complete.

2

28043

56086

... More
Providing maintenance free Earth station with consisting of 40 mm dia pipe standard length (as per equipment supplier) electrode capsule, filled with earth enhancing compound, sealed at both ends and brazed lead for connection at one end, suitable for direct installation at site, at a depth of 2.5 mtrs. Bentonite compound (as per equipment supplier) upto a depth of 2.0 meters around the electrode capsule. Brick chamber & CI Cover complete.

2

30266

60532

... More
Supply and laying of following size strips including excavation and refilling of each when laid in ground and with all fixing accessories when laid inside the building including all necessary interconnections with earth station and equipments.

-

-

-

... More
a) 25 x 5 mm hot dip galvanized iron strip

30

162

4860

... More
b) 8 SWG GI Wire

20

12

240

... More
Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m in All kinds of soils

-

-

-

... More
Supply, Laying, testing and commissioning of Medium grade G.I. Pipes conforming to IS 1239 Part - I including all necessary fittings etc., complete for sizes

-

-

-

... More
a) 65 NB (Borewell to sump)

200

599

119800

... More
b) 50NB (Borewell)

100

462

46200

... More
c) 40NB (Borewell to sump)

20

339

6780

... More
d) 32NB

20

298

5960

... More
e) 25NB

20

246

4920

... More
Supply, Erection, testing and commissioning of Cast Iron Butterfly valves (Wafer type) (PN-10) above nd upto 50mm dia with necessary flanges, bolts, nuts etc., and gun metal gate valves from 40mm dia and below

-

-

-

... More
a) 65NB (GM Gate Valve)

6

3773

22638

... More
b) 50NB (GM Gate Valve)

6

2212

13272

... More
c) 40NB (GM Gate Valve)

6

1524

9144

... More
d) 32NB (GM Gate Valve)

2

1158

2316

... More
e) 25NB (GM Gate Valve)

2

708

1416

... More
Constructing of Valve Chamber of size 750 x 750 x 1000mm deep comprising of 230mm thick brick walls in cement mortar 1:5 over a bed of 150mm thick PCC 1:4:8 alround beyond the masonry faces plastered with CM 1:3 mixed with approved water proofing compound as per manufacturer's specifications, 13mm thick on internal, external, top surfaces, finished smooth with a floating coat of neat cement, providing and fixing painted light duty double seal CI frame and cover of size 600 x 450mm weighting not less than 52 kgs conforming to IS 1726 with locking arrangements, fixing the frame in RCC 1:2:4 including fabrication, form work, curing etc., complete all as specified and directed.

2

12339

24678

... More
Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete (a) 50 to 80 mm nominal bore:

2

1743

3486

... More
Providing and fixing gun metal non- return valve of approved quality (screwed end) :Vertical (a) 50 mm nominal bore .

2

1531

3062

... More
Supply, laying and commissioning of following size 1.1KV grade PVC insulated flexible Copper conductor in the bore with all installation materials. The cable shall conform to IS 694

-

-

-

... More
a) 3C x4sqmm (copper ), pvc Flat Water proof cable.

500

206

103000

... More
Conducting water yield test without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by "V" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge.

2

808

1616

... More
Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete.

-

-

-

... More
200mm clamp

2

1564

3128

... More
SUBHEAD-XXVIII : EXTERNALELECRIFICATION

-

-

-

... More
11 KV HT SWITCHGEAR INDOOR

-

-

-

... More
Supply,Installation,Testing and commissioning of the following indoor floor mounted 11 kv Rated VCB Panel in Metal Enclosure fabricated out of 14 swg sheet steel to be operated on 11KV,Three phase,50HZ A.C Power supply .The panel is to be compartmentalised with individual compartments for Bus bars, Cable and CTs and Instrument and relay control Panel. The VCB shall be horizontal draw out single break as per IS 13118.The short circuit fault level of the system shall be 350MVA- Indoor

-

-

-

... More
11 KV- H.T SWITCH GEAR PANEL - INDOOR

-

-

-

... More
11 KV VCB panel with one no of 1250 A vcb -Indoor as Incomer and 3 Nos 800A VCB as out goings.

1

1892371

1892371

... More
11 KV H.T Switch Gear Panel (INDOOR TYPE) With 1 No. OF 1250 Vaccum Circuir breaker as Incomer.

-

-

-

... More
CONSTRUCTION - The Switch Gear Panel shall be compartmentalised Designed with cubicles fabricated out of High Quality Sheet Steel . The panels shall be designed having the Following Segregations separately.

-

-

-

... More
a) Busbar compartment

-

-

-

... More
b) Cable and CT compartment

-

-

-

... More
c)) Instrument and Relay Compartment

-

-

-

... More
The clearances between phase to phase and phase to earth shall be provided in accordance with the relevant standards. The bus bars shall be supported by bus support insulators placed at regular intervals.

-

-

-

... More
The panels shall be powder coated with epoxy base paint to give an aesthetically pleasing appearance. The paint shade shall be as per the requirement.

-

-

-

... More
SAFETY FEATURES:

-

-

-

... More
a) Mechanical Interlock and earth switch for out goings

-

-

-

... More
b) Door interlock in service position.

-

-

-

... More
INCOMING VCB PANEL

-

-

-

... More
11 , KV, 1250A, 26.2 KA, Horizontal Draw out type Vaccum Circuit breaker with motor/manual spring charge mechanism and also with mechanical indications for breaker on /off/trip indications and also with Local Remote selector switch and with breaker TNC Switch.

-

-

-

... More
CURRENT TRANSFORMER: (3 No’s) Cast Resin

-

-

-

... More
Ratio 200-100 - 5/5 A , Core 1: 15 VA, CI – 0.2 for Metering and 5P10 for protection.

-

-

-

... More
METERING: ( 1set)

-

-

-

... More
96 Sq.mm Digital Ammeter with selector switch Digital type 0-200A.

-

-

-

... More
POTENTIAL TRANSFORMER : (3 No’s) Cast Resin

-

-

-

... More
Ratio 11000 V/ rt 3 / 110 v / rt 3 , 100 VA, CI – 0.2 for Metering and 3 P for Protection and also with 2 numbers of Under Volage relays.

-

-

-

... More
OUTGOING VCB PANEL

-

-

-

... More
11 , KV, 800A, 26.2 KA, Horizontal Draw out type Vaccum Circuit breaker with motor/manual spring charge mechanism and also with mechanical indications for breaker on /off/trip indications and also with Local Remote selector switch and with breaker TNC Switch.-Outgoing-3No's

-

-

-

... More
CURRENT TRANSFORMER: (3 No’s) Cast Resin

-

-

-

... More
Ratio 75 /5 A , Core 1: 15 VA, CI – 0.2 for Metering and 5P10 for protection.

-

-

-

... More
METERING: ( 1set)

-

-

-

... More
96 Sq.mm Digital Ammeter with selector switch Digital type 0-100A.

-

-

-

... More
Digital Multi function Meter for KW,KWH,KVA, KVAR , COS PHI Parameters reading.

-

-

-

... More
INDICATION LAMPS:

-

-

-

... More
1) TCH, Battery failure , Spring charge, discharge, ON, OFF and Trip Indication Lamps, Phase indication Lamps for RYB. - (1 set)

-

-

-

... More
CONTROL SWITCHES/PUSH BUTTON

-

-

-

... More
Bus Bar with 1250 Amps Copper - (1 set)

-

-

-

... More
COMMON FOR SWITCHGEAR:

-

-

-

... More
Heater ON and OFF Switch with Space heater, single Phase switch socket and cubicle lamp for panel illumination, MCB's for AC/DC Control - (1 set)

-

-

-

... More
MS sheet enclosure suitable for Indoor installation with outgoing cable entry. - (1 set)

-

-

-

... More
Relays Incomer ; Undervoltage relays 2 nos,IDMT relay ,TCH and Master trip relay and also with 12 window annunciator

-

-

-

... More
Power Pack - 1 No with necessary Interconnections.

-

-

-

... More
Supply and commissioning of 11 KV earthed HT cable of size 3 c x 300 sqmm XLPE insulated armoured alluminium conductor cable as per IS 7098 - Part 2 - 1983

750

2241

1680750

... More
Supply and commissioning of 11 KV earthed HT cable of size 3 c x 185 sqmm XLPE insulated armoured alluminium conductor cable as per IS 7098 - Part 2 - 1983

80

2002

160160

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

-

-

-

... More
Above 120 sq. mm and upto 400 sq. mm

670

418

280060

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.

-

-

-

... More
Above 120 sq. mm and upto 400 sq. mm

50

139

6950

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size on cable tray as required.

-

-

-

... More
Above 120 sq. mm and upto 400 sq. mm

50

118

5900

... More
Supply, Installation, Testing and commissioning of 11 KV earthed heat shrinkable end termination kit of 11 KV earthed XLPE insulated armoured alluminium conductor HT Cable of size 3 c x 300sqmm ( Indoor Termination Kit).

2

12350

24700

... More
Supply, Installation, Testing and commissioning of 11 KV earthed heat shrinkable end termination kit of 11 KV earthed XLPE insulated armoured alluminium conductor HT Cable of size 3 c x 185sqmm ( Indoor Termination Kit).

6

11746

70476

... More
Supply and Installation ,Commissioning of HT Straight through Joint Kit for 3 C x 300 Sqmm Earthed XLPE insulated armoured alluminium conductor cable.

2

31000

62000

... More
Supply, Installation, Testing and commissioning of 1000 KVA, 11kv / 433 v, 3 PHASE, 50 Hz, Dyn 11 INDOOR ANAN Resin cast dry type Transformer with on load tap changer, RTCC panel, AVR and HT Side marshalling box for termination of 11 kv grade , 3 c x 300 sqmm XLPE insulated alluminium conductor screeened cable and LT side provision for connecting sandwich type of Alluminium bus trunking system of 1600 A capacity as per IS 11117 etc

3

2861812

8585436

... More
LT SANDWICH TYPE BUS DUCT

-

-

-

... More
Supply, Installation, Testing and commissioning of 415 V, 50 Hz, A.C, 1600 A, Three phase and neutral Sandwhich type Alluminium bus bars Bus trunking system with necessary fixing Clamps and Jointing accessories including all required horizontal and vertical bends, tees for outdoor Application Ip -65 ( Transformer feeder Incomer ) .As p-er IS ; 8623 Part 1 & 2.

45

24087

1083915

... More
M.V.PANELS

-

-

-

... More
Supply,Installation Testing Commissioning of following TTA PANEL. Supply, erection, testing and commissioning of 415V, 3 phase 4 wire 50 c/s Main LT Panel at Substation fully compartmentalized cubical type, as per the standards IEC61439-1&2 as tested assembly (TTA) ,tested for impulse voltage 8 KV,IP 42 fabricated CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having required capacity extensible type FP bus bars of high conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 35KA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, Form of separation shall be form 4b with metallic separation only entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of bus bars, interconnection, interlocking between feeders etc.,with indication lamps, push buttons necessary accessories, complete with following incoming and outgoing switchgears with protection and metering etc. as per specification and schematic diagram including provision to be made for interfacing with BMS etc. complete as required, with incoming & outgoing cable entry from bottom/top and bus-duct entry from top, wiring with 2.5sq. mm. FRLS insulated copper conductor , cable alleys, PLC cable gland i/c providing following switch gears All ACBs should have Ics=Icu=Icw for 1 sec All MCCBs shall be rating for 25kA (Ics=Icu). All MCCBs above 63A should be provided with Copper Spreader Terminals Marshalling Bay To Be Provided for BMS Operation Approval shall be taken for each panel before fabrication. PLC based control with 100% hot redundant PLC arrangement with touch-screen LCD / LED display board (min. 8" Diag size) along with all accessories for complete automatic, manual and HMI controls & indication. Energy Management Software wth necessary cabling shall be in scope, nos. of breaker / Meters to be connect with energy management software shall be inform by Engineer In Charge.

-

-

-

... More
MAIN MVPANEL - 1 - Indoor

1

3020682

3020682

... More
Incomer 1,3,4 : 3 Nos of 1600 A, 4P. EDO ACB, 50KA, shall be supplied with S/C,E/F,O/C AND INSTANTANEOUS TRIP RELAY UNIS WITH TIME DELAY SETTINGS.

-

-

-

... More
2A, control MCB - 9 Nos.

-

-

-

... More
RYB indicating lamps - 3 sets

-

-

-

... More
Voltmeter (0-500V) with selector switch - 3 sets

-

-

-

... More
Ammeter (0-1600A) with selector switch - 3 sets

-

-

-

... More
1600/5A, CL-1, 15VA CT's with resin cast- 3 nos.

-

-

-

... More
A Single CT with ratio of 1600 / 5 A , 15 VA, 5 P 10 ,CT for feeding APFC relay of APFC panel. ( For 3 Nos of Incomers )

-

-

-

... More
Bus Coupler : 3 Nos of 1600 A, 4P. EDO ACB, 50KA, shall be supplied with S/C,E/F,O/C AND INSTANTANEOUS TRIP RELAY UNIS WITH TIME DELAY SETTINGS.

-

-

-

... More
Incomer 2 : 1 No of 1250 A, 4P. EDO ACB, 50KA, shall be supplied with S/C,E/F,O/C AND INSTANTANEOUS TRIP RELAY UNIS WITH TIME DELAY SETTINGS.

-

-

-

... More
2A, control MCB - 3 Nos.

-

-

-

... More
RYB indicating lamps - 1 sets

-

-

-

... More
Voltmeter (0-500V) with selector switch - 1 sets

-

-

-

... More
Ammeter (0-1250A) with selector switch - 1 sets

-

-

-

... More
1250/5A, CL-1, 15VA CT's with resin cast- 1 nos.

-

-

-

... More
A Single CT with ratio of 1250 / 5 A , 15 VA, 5 P 10 ,CT for feeding APFC relay of APFC panel.

-

-

-

... More
Outgoing

-

-

-

... More
800A, 3P, 50KA, EDO ACB - = 2 Nos

-

-

-

... More
630A, 3P, 50KA, EDO ACB - = 3 Nos

-

-

-

... More
400A, 3P, 50KA, MCCB - = 2 Nos

-

-

-

... More
250A, 3P, 35KA, MCCB, - = 2 Nos

-

-

-

... More
200A, 3P, 35KA, MCCB, - = 5 Nos

-

-

-

... More
160A, 3P, 25KA, MCCB, - = 4 Nos

-

-

-

... More
63A, 3P, 16KA, MCCB, - = 6 Nos

-

-

-

... More
Surge Protection Device - 1 No

-

-

-

... More
63 A, 3P, 16KA, MCCB, - = 1 No and also with 20 A TPNMCB as outgoings 3 Nos with timer circuit for controlling of street lights and the timer should be with required 24 hors clock settings.

-

-

-

... More
Bus Bars : 1600A, 3Ph, 4 wire TPN , 50Hz, aluminium bus bars

-

-

-

... More
Metering Instruments ; Load Manager in the Incomer and ACB/ MCCB on , off , Trip Indication Lamps and with Breaker Status indication Lamps and also with Phase indication Lamps.

-

-

-

... More
Earth Bus; To be provided at the bottom of the Panel of Gi Strip

-

-

-

... More
APFC PANEL INDOOR TTA PANEL - 300KVAR

-

-

-

... More
Supply,Installation,Testing and Commissioning of APFC PANEL with Automatic power factor control relay and with 2 nos of 50 kvar capacitor banks and 25 kvar capacitor banks 8 nos with the following incoming and out goings.. The Panel is to be installed in Indoor. The panel is to be supplied with necessary power and control wiring required for the automatic operation of Power factor control.

3

517832

1553496

... More
INCOMER

-

-

-

... More
630 A, 4 P , 50KA MCCB with O/c, S/c,E/f Protection Microprocessore Relay Unit

-

-

-

... More
2A, control fuse - 3 Nos.

-

-

-

... More
RYB indicating lamps - 1 set

-

-

-

... More
Voltmeter (0-500V) with selector switch - 1 set

-

-

-

... More
Ammeter (0-630A) with selector switch - 1 set

-

-

-

... More
630/5A, CL-1, 15VA CT's with resin cast- 3 nos.

-

-

-

... More
Outgoing

-

-

-

... More
125 A, 3P, SDF , - 2No

-

-

-

... More
63 A, 3P, SDF , - 8 No

-

-

-

... More
Bus Bars : 630A, 3Ph, TPN, 50Hz, aluminium bus bars

-

-

-

... More
Metering Instruments ; Multi Function Meter in the Incomer and SDF on , off , TRIP Indication Lamps and with Breaker Status indication Lamps and also with Phase indication Lamps

-

-

-

... More
Earth Bus; To be provided at the bottom of the Panel of copper

-

-

-

... More
The panel is to be supplied with Required capacity Capacitor Banks as per BOQ quantity and also with required capacity over load relays,contactors ,Switch disconnecting fuses and also with APFC relay control wiring for manual and Auto operation.

-

-

-

... More
EARTHING

-

-

-

... More
Providing and fixing of maintenance free earthing which consists of 40 mm Dia, 3 mtr length (as per Equipment Supplier) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Bentonite compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.

16

8673

138768

... More
Providing and fixing of maintenance free earthing which consists of 65 mm Dia, 3 mtr length (as per Equipment Supplier) electrode capsule,filled with earth enhancing compound,sealed at both ends and brazed lead for connection at one end suitable for direct installation at site at a depth of 2.5 mtr.Bentonite compound upto a depth of 2.0 mtr around the electrode capsule and also wih brick chamber and cast Iron cover etc complete including excavation in all types of soil.

6

11185

67110

... More
Supply and fixing of following earth strips/ conductors. The scope incudes supply and fixing of copper lugs wherever found necessary, brass bolts, nuts and washers for fixing arrangement etc., (from earth station to main panel).

-

-

-

... More
50 x 5 MM G.I. Flat

300

329

98700

... More
25 x 3 MM GI Flat

200

220

44000

... More
50 x 6 MM Copper Flat

150

2574

386100

... More
6SWG G.I.Wire

200

58

11600

... More
Cable Trays

-

-

-

... More
Supply and fixing of following size GI Perforated type cable tray made out of 2mm thick sheet including MS supports for fixing the tray, anchor fasteners etc complete as required.Including with GI covers.

-

-

-

... More
600mm wide

150

2375

356250

... More
300mm wide

200

1598

319600

... More
SAFETY ITEMS

-

-

-

... More
Supply, Installation, Testing and commissioning of the Follwing Safety items as per standrads and specification.

-

-

-

... More
Fire Extinguishers - 5 KG CAPACITY CO 2 Confirming to IS 2878 fitted with discharge bend pipe and horn

3

11724

35172

... More
Rubber Mats 11 KV , 2 Mtr x 1 Mtr

6

3500

21000

... More
Rubber Mats 415 V , 2 Mtr x 1 Mtr

20

679

13580

... More
Shock treatment Chart with frame and glass

1

475

475

... More
First Aid Box

1

339

339

... More
Sand Bucket with stand with 3 Nos of buckets and also with canaopy.

2

2036

4072

... More
415 V Danger Boards

4

271

1084

... More
11 kv Danger Boards

3

339

1017

... More
Single Line Diagram with frame and glass.

1

206

206

... More
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor cable. The cable shall conform to IS 7098/ Part-II.

-

-

-

... More
3.5C X 400 Sq.mm

200

1614

322800

... More
3.5C X 300 Sq.mm

500

1284

642000

... More
3.5C X 240 Sq.mm

50

1070

53500

... More
3.5C X 185 Sq.mm

50

859

42950

... More
3.5C X 150 Sq.mm

500

686

343000

... More
3.5C X 70 Sq.mm

1600

365

584000

... More
3.5C X 25 Sq.mm

1200

175

210000

... More
4C X 16 Sq.mm

1000

140

140000

... More
Copper armoured control cables

-

-

-

... More
i) 4C X 2.5 Sq.mm

100

144

14400

... More
ii) 7C X 2.5 Sq.mm

100

218

21800

... More
iii) 19C X 2.5 Sq.mm

100

509

50900

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

-

-

-

... More
Upto 35 sq. mm

50

422

21100

... More
Above 35 sq. mm and upto 95 sq. mm

30

441

13230

... More
Above 95 sq. mm and upto 185 sq. mm

30

454

13620

... More
Above 185 sq. mm and upto 400 sq. mm

50

507

25350

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.

-

-

-

... More
Upto 35 sq. mm

50

38

1900

... More
Above 35 sq. mm and upto 95 sq. mm

20

59

1180

... More
Above 95 sq. mm and upto 185 sq. mm

20

80

1600

... More
Above 185 sq. mm and upto 400 sq. mm

50

139

6950

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.

-

-

-

... More
Upto 35 sq. mm

2400

40

96000

... More
Above 35 sq. mm and upto 95 sq. mm

1550

72

111600

... More
Above 95 sq. mm and upto 185 sq. mm

500

110

55000

... More
Above 185 sq. mm and upto 400 sq. mm

650

179

116350

... More
Providing Indoor ordinary end terminations for the foollwing 1.1 KV grade XLPE insulated armoured alluminium conductor cables with compression type steel gland, Bi-metallic lugs using crimping tool, Insulation tape, Identification tags etc., including end termination and Earthing of Gland with 8SWG GI Wire.

-

-

-

... More
3.5C X 400 Sq.mm

8

3572

28576

... More
3.5C X 300 Sq.mm

44

2875

126500

... More
3.5C X 240 Sq.mm

12

2555

30660

... More
3.5C X 185 Sq.mm

4

1944

7776

... More
3.5C X 150 Sq.mm

4

1717

6868

... More
3.5C X 70 Sq.mm

52

1096

56992

... More
3.5C X 25 Sq.mm

48

822

39456

... More
4C X 16 Sq.mm

24

535

12840

... More
End terminations of Copper armoured control cables including supply and fixing of crimping type copper lugs.

-

-

-

... More
i) 4C X 2.5 Sq.mm

6

336

2016

... More
ii) 7C X 2.5 Sq.mm

6

357

2142

... More
iii) 19C X 2.5 Sq.mm

6

870

5220

... More
SUBHEAD-XXIX : AREA LIGHTING :

-

-

-

... More
Supply and erection of steel stepped and swaged tubular poles of 9 mtr long (410 SP25) (1.5 mtr below ground) with base plate earthing studs 1.5 mtr out reach single /Double arm , FRP terminal Box 2 Nos of 40 mm Dia Class B G.I Pipe ,0.5 mtr Long for incoming and outgoing cables including excavation in all types of soil ,PCC 1:2:4 ,PCC Pedestal with painting with black bitumen paint inside the coping for embedded portion and two coats of Zinc chromite primer and two coats of Alluminium paint externally for length above the ground.The pole shall be with FRP junction box consisting of 10A MCB.The wiring from Junction box to Light fixture shall be carried out with 3 Core 2.5 Sqmm Copper conductor flexible cable.

10

21378

213780

... More
The Street Light Pole shall be fixed with 70W LED street Light fixture including supply of controlgear / driver and lamp(Make : Cat No.LR02-102-XXX-57-G2,WIPRO MAKE / CAT NO - Greenline V2 (BRP410) Philips/equivalent make.)

-

-

-

... More
Supply and erection of 65 mm Dia, Class B GI Pipe of 3 mtr. long with base plate, earthing studs, 3 phase and neutral loop-in and loop-out box as per specifications, 2nos 50mm dia,1.5mtr. long GI bent pipes for incoming and outgoing cables, including excavation , 1 :2 : 4 PCC Pedestal etc complete. The pole shall be with Junction box consisting of MCB. The Junction box shall be of weather proof. The wiring from Junction box to Light fixture shall be carried out with 3core 2.5sq.mm flexible copper conductor cable. The Pole shall be fixed with weather proof 72W LED ( Philips Cat No :BRP046 LED 30 CW MR S1 PSU GR/equivalent) Light fixture including supply of driver and fixing clamps etc complete.

5

9935

49675

... More
Supply, testing and commissioning of following size 1.1KV grade XLPE insulated armoured aluminium conductor underground cable. The cable shall conform to IS 7098/ Part-II.

-

-

-

... More
4Core 10sq.mm

1000

103

103000

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required

-

-

-

... More
Upto 35 Sqmm

900

422

379800

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.

-

-

-

... More
Upto 35 Sqmm

100

38

3800

... More
Providing End terminations for the following size of 1.1 KV grade XLPE insulated armoured alluminium conductor cable with compression type steel gland, alluminum lugs using crimping tool, Insulation tape, Identification tags etc.,complete

-

-

-

... More
4Core 10 sq.mm

30

596

17880

... More
Providing Spiral coil earthing with 8 SWG GI wire including spreading of salt and charcoal as per IS 3043/87 with latest amendments.

13

2880

37440

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, weather proof MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)

-

-

-

... More
4 way (8 + 12), Double door

1

16576

16576

... More
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
40A

1

5932

5932

... More
Supplying and fixing of 6A to 32A rating 240/415V,10kA , C Curve miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections ,testing and commissioning etc complete.

-

-

-

... More
Single Pole

12

381

4572

... More
Supply and Commissioning of the following type Fluorescent/ Compact fluorescent light fixtures on wall/ Ceiling including all fixing accesssories such as leads, etc complete as required. The Fluorescent/CFL fixtures shall be complete with Low loss copper ballast PF improvement capacitor, Bipin Rotor type lamp holder,starter, starter base, all prewired upto the terminal block. All fixtures shall be supplied with lamps. The Catalogue Numbers refers to Philips Make.

-

-

-

... More
40 W Bulk Head Light Fixture Outdoor

30

1493

44790

... More
(Philips Cat No WT1 40W LED 7S NW PSU S1 PC /Equivalent as per approved makes))

-

-

-

... More
150W LED Flood Light Fixture outdoor with alluminium die cast housing and also includind driver with fixing clamps etc complete

4

13434

53736

... More
SUBHEAD-XXX : SEWAGE DISPOSAL :

-

-

-

... More
Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m in All kinds of soils.

-

-

-

... More
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.

100

437

43700

... More
PVC SWR PIPES

-

-

-

... More
Providing, laying and jointing PVC/ SWR Pipes conform to IS:13592-1992 of Type-B on sand cushion at bottom and around the pipw and testing of joints etc. complete :

-

-

-

... More
100 mm dia PVC/SWR Single Socket

100

256

25600

... More
150 mm dia PVC/SWR Single Socket

100

462

46200

... More
Providing and fixing square-mouth PVC gully trap conform to IS:13592-1992 complete with brick masonry chamber around as per standard design :

-

-

-

... More
100x100 mm PVC Gully trap with Sewer bricks conforming to IS : 13592-1992.

10

1112

11120

... More
Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design :

-

-

-

... More
Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), With Sewer bricks conforming to IS : 4885.

5

12781

63905

... More
Extra for depth for manholes :

-

-

-

... More
Size 90x80 cm, With Sewer bricks conforming to IS : 4885

2

8040

16080

... More
Providing M.S. foot rests including fixing in manholes with 20x20x10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) as per standard design, With 20x20 mm square bar.

30

534

16020

... More
Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design, With common burnt clay F.P.S. (non modular) bricks of class designation 3.5.

2

42456

84912

... More
Supply and positioning of ready made polyethylene septic tank of size 2.3M long 1.3M dia 16mm shell thickness with 2/3 chambers and 2Nos manholes of size 550mm dia and 100mm/160mm dia inlet outlet pipe and airvent pipe 50mm dia of make United Septic tank Design Reg.No 173352 Type-4

1

53906

53906

... More
SUBHEAD-XXXI : ARBORICULTURE :

-

-

-

... More
TREE PLANTATION

-

-

-

... More
Digging pits in all type of soils and refilling the same with the good earth (excavated / imported) & manure (organic manure/cow dung/sludge) in the ratio of 3:1 (03 part of stacked volume of manure). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth &8% stacked volume of manure. Each pit to be mixed with antitermite chemical / granules, Thimet 10G @100-200 am/pit

-

-

-

... More
(I) AVENUE / FLOWERING TREES / Palms

-

-

-

... More
a) 1mts x 1mts x 1mts (L X W x D )

10

352

3520

... More
b) Each pit to be added with 100gms of Thimet 10 g granule, to control termite attack. (Repeat the treatment after 06 months, if termite persists). Flooding the pit basin with water, dressing including removal of rubbish & surplus earth, if any, with all lead & lifts

10

39

390

... More
c) Supply and plantation of approved varieties of healthy, disease free, stout stem & well developed root system tree sapling of, 5'-6' height, with a clear minimum height of 4'-5' from basin / ground level, after plantation. Staking the tree sapling upto 3/4 height with appropriate strength of bamboo stick. Lower 1 feet of stake portion should be treated with antitermite chemical

-

-

-

... More
i) Phonix Palm

10

286

2860

... More
ii) Red Palm

2

1047

2094

... More
iii) Golden Palm

2

1144

2288

... More
iv) Fox Tail Palm

2

719

1438

... More
v) Areca Palm

5

222

1110

... More
d) Maintenance of tree sapling, after plantation for 30 days or more as minimum guarantee period, for well establishment of tree sapling. Stacking to be continued till tree sapling attains the stem strength. Replacement of saplings casualties immediately

40

39

1560

... More
LAWM PLANTATION

-

-

-

... More
a) Preparation of ground by trenching in all type of soils upto a depth of 30cm including removal & stacking of serviceable material than disposing the surplus soil with all lead & lifts, by spreading and leveling neatly. Making up the trenched area well leveled by filling with additionally supplied earth (if needed).

25

69

1725

... More
b) Now rough dressing of trenched ground including breaking clods & flooding with water.

25

62

1550

... More
c) After 10-15 days removal of weeds / unwanted grass (motha etc) with roots & disposal of uprooted material, stone rubbish etc., with all lead & lifts.

25

5

125

... More
d) Then fine dressing of ground. Spreading and mixing with the good earth (excavated / imported) & manure (organic manure / cow dung / sludge) in the ratio of 8:1 (08 part of stacked volume of good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth & 8% stacked volume of manure. The area to be mixed with antitermite chemical / granules, Thimet 10G @ 100-200gm / sqmts. If termite persists repeat the treatment after 06 months by surface spreading the chemical.

25

49

1225

... More
e) Supply of grass and planting by dibbling the area including watering & maintenance of lawn for 30 days or more till grass forms a thick lawn cushion free from weeds

-

-

-

... More
i) With Bermunda grass (15cm x 15cm apart)

10

67

670

... More
ii) Carpet of grass turfing

10

186

1860

... More
iii) Supply & turfing of artificial lawn

10

1038

10380

... More
iv) After ward maintenance of lawn area, green & weed free for 01 year with standard specification

100

83

8300

... More
SHRUB PLANTATION (SOLO)

-

-

-

... More
Digging pits in all type of soils and refilling the same the good earth (excavated / imported) & manure (organic manure / cow dung / sludge) in the ratio of 5:1 (05 part of stacked volume of manure). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth & 8% stacked volume of manure. Each pit to be mixed with antitermite chemical / granules thimet 10G @50-100gms / pit

-

-

-

... More
i) Pit size 0.60mts x 0.60mts (Dia x Depth)

25

51

1275

... More
ii) Pit size 0.45 dia x 0.60mts Depth

25

30

750

... More
b) Supply & plantation of shrub and / or rose sapling to pit, appropriate stacking & initial maintenance for 30 days. Replacement of sapling casualties immediately.

25

94

2350

... More
c) Afterward 01 year maintenance as per standard specification

25

24

600

... More
SHRUBBERY PLANTATION - (SHRUBS IN GROUPS)

-

-

-

... More
Digging beds in all type of soils and refilling the same with the good earth (excavated / imported) mixed with antitermite chemical / granules @100gm/sqmts) & manure (organic manure / cow dung / sludge) in the ratio of 5:1 by volume (05 part of staked volume of good earth & 1 part of stacked volume of manure). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth &8% stacked volume of manure

-

-

-

... More
i) L X W X 0.60 mts depth

25

179

4475

... More
b) For roses, rose mixture @500gms / sq mts to be used additionally, before plantation

25

86

2150

... More
c) Termite treatment - Thimet 10G granules @100 gms / Sqmts

25

39

975

... More
d) Supply & plantation of shrub sapling to pit, appropriate stacking & initial maintenance

25

138

3450

... More
e) Afterward 01 year maintenance as per standard specification

50

83

4150

... More
HEDGE PLANTATION

-

-

-

... More
a) Digging trenches of approved / desired size of L X W (45-50cms) X D (30-60cm) in all type of soil. Refilling the trenches with good earth (excavated / imported) mixed with manure (cowdung / sludge / dump) in the ration of 5:1 (05 part of good earth and 01 part of manure by stacked volume). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth &8% stacked volume of manure. Fore Termite treatment add Thimet 10G granules @ 100gms / running mts. Flooding the trench with water and than rough & fine dressing of trenched area including removal of undesirable weeds & vegetation.

25

81

2025

... More
b) Supply & plantation of approved varieties of hedge plant saplings. It should be well grown, fully established & disease free. Sapling height & density as follows

25

81

2025

... More
i) Hedge with sapling height -0.45 mts to 0.60mts (After Plantation)

-

-

-

... More
ii) Density - @07 Nos plants / running meters (staggered condition)

-

-

-

... More
c) Maintenance the hedge by regular watering, trimming & pruning etc for 30 days initially. Replacement of sapling casualties immediately

25

13

325

... More
d) Afterward maintenance of hedge length for 01 (one) year as per standard maintenance specification

25

155

3875

... More
GROUND COVER

-

-

-

... More
Digging of ground cover marked area upto a depth of 30 cms in all type of soils. Refilling the same with (excavated / supplied) good earth mixed with manure (organic / cow dung / sludge) in the ration of 8:1 (08 part of good earth *01 part of manure by stacked volume). Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth & 8% stacked volume of manure. For Termite treatment add Thimet 10G granules @100 gms/Sq mts. Flooding with water the entire area. Rough & fine dressing of the ground cover bed area and removal of weeds & unwanted vegetation & its disposal

25

93

2325

... More
b) Supply and plantation of approved / desired ground cover plant varieties, well established, fully grown, disease free and good foliage. Plantation density should be @36 ground cover plants / square metre, or less as desired or decided by site incharge. Maintenance of all the ground cover area for 30 days till the plants establish well.

25

37

925

... More
c) Regular maintenance afterward for 01 year as per standard specification

25

155

3875

... More
FLOWER BED PREPARATION

-

-

-

... More
Digging of FLOWER BED marked area upto a depth of 30 cms (Canna Beds - 60cms depth) in all type of soils. Refilling the same with (excavated / supplied) good earth mixed with manure (organic / cowdung/ sludge) in the ration of 5:1 (05 part of good earth & 01 part of manure) . Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% by stacked volume of stacked volume of good earth & 8% stacked volume of manure. For Termite treatment add Thimet 10G granules @100gms / sq mts. Flooding the entire with water. Rough & fine dressing the flower bed area and removal of weeds & unwanted vegetation & its disposal with all lead and lifts

-

-

-

... More
a) SEASONAL FLOWERING BED SIZE FORMAL STYLE - Lx1.0mts width, INFORMAL STYLE - Any style as desired

20

221

4420

... More
b) Supply & plantation of seasonal flowers sapling @36 seedlings / sq mts (minimum three times in a year)

-

-

-

... More
i) BUL BOUS / CUTTINGS - FLOWERING - Dahalia Plants @16 plants / Sqm) Winter

40

221

8840

... More
c) Maintenance of flower beds regularly upto 1 year as per standard specifications. Replacement of casualty immediately

40

55

2200

... More
MOUND

-

-

-

... More
Preparation of mounds of various size and shape by available excavated / supplied earth in a layers not exceeding 20cm in depth, breaking clods, watering of each layer, dressing etc with all lead & lifts complete as per direction of Officer in charge. Cost of manure / sludge and good earth if needed to be paid separately, after reduction of 20% of stacked volume of good earth and 8% stacked volume of manure

40

200

8000

... More
BRICK EDGING

-

-

-

... More
Edging with bricks (Class I) laid in PCC (1:2:4) length wise, including required excavation, refilling, consolidating withhand packing and spreading surplus earth neatly within all lead and lifts

40

39

1560

... More
Brick Paving : Supply and Paving of wire cut bricks on sand bed

20

581

11620

... More
Terracotta Pot : Terracotta Pots of height 4' & width 1m made with 8mm rod chicken mesh with cement mortar complete

2

1384

2768

... More
PVC Pipe Line : Supply & laying of 63mm dia PVC pipeline of ISI including excavation of outlet back filling of trenches of 0.60m depth fixing with all accessories and providing outlet wherever required backfilling of trenches etc complete

10

277

2770

... More
Supply & erection of 2 Hp pump with all accessories including panelboard etc

1

35991

35991

... More
Supply, erection, testing and commissioning of 1.5sqmm 3 core copper cable

1

305

305

... More
GOOD EARTH / AGRICULTURE SOIL

-

-

-

... More
a) Supply and stacking of good earth / agriculture soil from approved source / field ; of approved quality / pH & suitable for plantation work with all leads, lifts, carriage and royalty / taxes etc. Cost of good earth to be paid separately, after reduction of 20% of stacked volume of good earth

5

346

1730

... More
b) Cattle manure : Supply of cattle manure

5

485

2425

... More
Note:- Where Ever Written for Sand Should be Read as Manufacture Sand

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.