Bharat Sanchar Nigam Limited Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 11,101Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_BSNL_224660_1Tender No
KRLCO-13/16(11)/49/2024-ELETender Authority
Bharat Sanchar Nigam Limited ViewPurchaser Address
-Website
http://https://www.bsnl.co.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Recharging the breather using fresh silica gel after removing the hydrated gel ,cleaning the assembly, refilling with new gels, refixing etc as reqd.
2
-
-
... More
Servicing the existing 11 KV, 3 Panel load break switch 400Amps (make : uni power) with 1 incoming & 2 Outgoings HT Panel i/c cleaning the entire panel, and removing the dust, rust, and moisture contents, tightening nuts and bolts of the Bus bars, cable terminals and spouts, and improving the IR value by heating with a hot air blower after cleaning of accumulation of carbon deposits with CTC (Carbon Tetra Choride ), heating the interior of the panel board to expell moisture, applying two coats of moisture resistant winding varnish for all HT spouts and resin cast CTs, applying petroleum jelly in the fixed contacts of LBS , greasing the moving parts of LBS , reconnecting properly, etc i/c checking the control wiring and trip circuit, testing etc. i/c cleaning & removing the rust on surface of panel , providing one coat of superior quality spray enamel paint on accessible area of panel, sign writing etc complete as reqd.
1
-
-
... More
Servicing of existing ACB in the LT panel i/c cleaning / checking all componets, mechanical parts, all moving and fixed contacts, auxilary contacts, all connections of CTs, control wiring, replacement of the minor components like springs , mechanical parts etc . i/c Lubricating all mechanical parts, cleaning contact tips, applying petroleum jelly on all contacts, refixing testing etc as required ( work should be carried out by a qualified and skilled technician)
4
-
-
... More
Spray painting the outside of the 500 KVA Oil cooled indoor transformer i/c complete cleaning, removing dust, dirt, rust etc i/c pdg One coats of enamel paint on accessible surface area i/c checking the tightness of HT & LT cable terminations and all terminal connections for any occured overheating, tightening if required replacing the defective LT side gaskets of transformer terminal box, etc complete as required
2
-
-
... More
Servicing of following Electrical panels including cleaning the inside dust, checking and tightening all the connections such as busbar, cables etc, tightening switch terminals/ busbar taping etc I/c removing dust deposit using vacuum cleaner and pdg minor repairs of switches etc, replacement of fused indication lamps/defective indication lamp holders and control fuse , replacing the damaged gaskets,i/c cleaning & removing the rust on surface of panel , providing one coat of superior quality spray enamel paint on accessible area of panel, sign writing etc complete as required. ( excluding servicing of ACBs)
-
-
-
... More
Main MV panel of approximate size (size 4.80mtr x 2.30mtr x 1.0 mtr ) comprising 4 Nos 800A ACBs as incomers, 17Nos SFU/ SDF/MCCBs out goings, Bus bars, indication lamps, castle key arrangemnt setc. (Excluding servicing of ACBs )
1
-
-
... More
11 stage APFC panel with APFC Controller & capcitors, contactors etc
1
-
-
... More
Power room LT panel of approximate size (size 2.1mtr x 1.90mtr x 0.35 mtr ) comprising 2 Nos 630A switches as incomers, 13Nos SFU/ SDF/MCCBs out goings, Bus bars, indication lamps etc.
1
-
-
... More
Power room LT panel of approximate size (size 3.0mtr x 1.90mtr x 0.45 mtr ) comprising 2 Nos 630A switches as incomers, 10Nos SFU/ SDF/MCCBs out goings, Bus bars, indication lamps etc.
1
-
-
... More
Light and Power Rising mains from ground floor to second floor wall made of sheet steel enclosure with PVC insulated 4 Nos aluminium bus bars suitable for 415 V, 3 phase, 4 wire, with extension joints , insulations and earthing with all accessories, TPN tap off boxes and SFUs etc associated with rising mains i/c opening the sheet steel covers, complete cleaning servicing the busbars and accessories, tightening all terminations , providing new fastners / minor spares if reqd, resetting the rising main / tap off boxes / SFUs, i/c painting the accessible area etc. as required
1
-
-
... More
Checking, correcting and testing of pick up time and closing time of IDMT relay 2 Nos of over current and 1 No of earth fault relay by injecting 5 amps current using testing kit i/c checking and correcting connected control wiring in the LT/HT panel, Checking shunt trip circuit, auxiliary switch, trip healthy indication , trip push button etc as required.
2
-
-
... More
Checking, meggering for earth resistance of the existing earth pits, cleaning the joints and reconnecting, replacing corroded nut and bolts, washers etc with new ones etc as required.
12
-
-
... More
Supply following accessories for 11KV substation etc as required.
-
-
-
... More
Supply of ISI MARKED rubber mat suitable for HT supply as required.
3
-
-
... More
Supply of 6 mm nominal thick rubber mat suitable for MV supply as required.
4
-
-
... More
a) Rubber gloves of 11KV grade.
1
-
-
... More
Replacing the existing defective flourescent tube light fittings on surface of wall / ceilng in substation room with new 20W LED tube light fittings i/c dismantling the defective, Supplying and fixing of new lights with all accessories testing etc as required.
6
-
-
... More
Supply and fixing 450mm sweep 1400 RPM exhaust fans with suitable louvre on existing wall opening in substation room testing etc as required.
2
-
-
... More
Dismantling existing defective 18" dia exhaust fans with accessories from substation room etc as reqd.
6
-
-
... More
Making the existing castle key arrangement of the 2 Nos MCCB incomers operational in the power room panel i/c providing suitable handles for the existing 400Amps capacity 4 pole L&T make MCCB, providing suitable castle key arrangements to the 2 Nos 400Amps MCCBs , carry out necessary minor modification if required , testing commissioning etc complete as reqd.
1
-
-
... More
Replacing the existing defective HRC fuse units / links in the existing tap off boxes / distibution boxes in the rising main i/c dismantling the defective, Supplying and fixing of following spares with all accessories, providing connections testing etc as reqd
-
-
-
... More
HRC fuse units up to 63 amps
15
-
-
... More
HRC fuse links up to 63 amps
15
-
-