Bharat Sanchar Nigam Limited Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 5,961Document Cost
₹ 590Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_BSNL_136691_1Bid Award Id
ViewTender No
KL CLT-17/13/7/ 2022 - PLG CLT KRL/17Tender Authority
Bharat Sanchar Nigam Limited ViewPurchaser Address
-Website
http://etenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Installation of 1 No cubicle type Meterbox in the new location after transporting the meter box from TE kattippara without making any damage ,painting the meter box, giving cable and earth connections, etc complete as reqd ( Approx 60 Km)(Note; Work involves liasoning with KSEB for shifting of meter and service connections)
1
-
-
... More
Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size 3-1/2 x 25 Sqmm Aluminium conductor armoured UG cable, in the surface/ recess of wall as reqd. ( From MB to COS, EA to COS and COS to VDB)
45
-
-
... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
a) 3 1/2 x 25 sq.mm
6
-
-
... More
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing cable as required.
90
-
-
... More
Dismantling the fire alarm panel, including dismantling the connections to the fire alarm panel, refixing the panel in MDF room, rewiring the dismantled wiring connections to the fire alarm panel , i/c extending connection with the existing 2 x 1.5 sqmm FRLS cable for hooter/ detector/ DC/AC supply etc as reqd ( Approx 22 meter)
1
-
-
... More
Supplying and fixing of following ways surface/ recess mounting,vertical type,415 V, TPN MCB distribution board of sheet steel,dust protected, duly powder painted, inclusive of 125 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. a) 4 way (4 + 12), Double door
1
-
-
... More
S/F following rating MCBs /isolator in the existing MCB DB complete with connections testiong and commissioning etc. as reqd.
-
-
-
... More
(a) 63 A, 415 V, 4 Pole Isolator
1
-
-
... More
(b) 32 A, 415 V, C curve, Triple pole MCB
2
-
-
... More
(c) SP MCB 'C' series 5 to 32 A ,240V
6
-
-
... More
(d) SP MCB Blanking plate
2
-
-
... More
Supplying and fixing 20 W, 4' LED tube without fitting suitable for 240V,50 Hz AC supply in the existing FT fitting, modification in the existing connections, testing, commissioning etc. required (M/s Philips or Sup. Make)
2
-
-
... More
Wiring for Group-"B" light point/ fan point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
2
-
-
... More
Reinstallation of available FT Box fitting in the required location in MDF etc complete as required
2
-
-
... More
S/F of 5/6 A ,5 pin modular type universal socket out let and 5/6A modular switch on the existing switch board without modular cover and plate as reqd.
1
-
-
... More
Supplying and fixing 20 W LED strip type tube with fitting suitable for 240V,50 Hz AC supply , giving connections, testing, commissioning etc. required (Philips Smart bright or Sup. Make)
3
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2.5
-
-
... More
Rewiring with the dismantled circuit wires 2 x 4 sqmm with earth wire of the existing AC units to the TPN vertical DB in medium class 20/25mm dia PVC conduit/ flexible PVC conduit including supplying and fixing PVC conduit (approx. 7 mtr), giving connections, etc as reqd (dismantling of wiring in metal conduit for 5 meter)
1
-
-
... More
S/M cable end termination with brass gland for 2x1.5 sqmm PVC insulated and sheathed FRLS cable as required.
10
-
-
... More
Dismantling and relaying ( aprox. 12 mtrs) of 2 x 1.5 sq mm copper conductor PVC insulated and sheathed armoured (FRLS) cable on the wall/ceiling/ existing cable tray etc as required for extending signal from change over box to alarm converter.
1
-
-
... More
Dismantling and relaying ( aprox. 12 mtrs) of of 4 x 1.5 sq mm copper conductor PVC insulated and sheathed armoured (FRLS) cable on the wall/ceiling/ existing cable tray etc as required for extending signal from change over box to alarm converter.
1
-
-
... More
Dismantling of existing 2 x 2.5 sqmm copper cable from signal converter to EA room (approximate 17 Mtr) and relaying the cable from VDB to EA room SB (approx 30 mtr ) cable on the wall/ceiling/ existing cable tray etc as required (For balance length dismantled fire cable can be used)
1
-
-
... More
S/F of 150mm x 70mm x 60mm deep ms box with phenolec laminated sheet cover on front, i/c painting the box etc to terminate signal cable from EA set and EB, i/c P/F of 8 way backlite connector etc complete as reqd.
2
-
-
... More
TE KAKKATTIL
-
-
-
... More
Dismantling the following items for vacating the space in exchange for reducing the exchange area including making good the damages to the wall, transporting all the items to TE Nadapuram ( Approx. 6 km), stacking the dismantled items as directed by Engineer in charge in exchange premises, i/c loading and unloading etc complete as reqd (a) LT panel of size 1.40m x1.35m x 0.30m with 2 Nos 125A SDF and 6 Nos 63A SDFs including cable connections , earth connections etc complete as reqd (b) Dismantling Wiring in MS conduit in vacating portion of the building (approx. length 140 mtrs), including 4 Nos detectors, hooters, 2 Nos MCPs, 13 Nos light fittings, 4Nos Ceiling fans and 1 Nos. Exhaust fan etc, in the vacating rooms (c) Dismantling the cable connections from meter board to servo panel , Servo Panel to CoS, LTP to AC Panel and DBs (approximate length. 35 mtr of cable size 3 1/2x 70 sq.mm and 4 x 25 sqmm Al. Conductor armoured UG cable) (d) Dismantling of AC Control panel comprising of 6 Nos with control cubicle, TPDB-1 Nos, DC DB-1 No etc. e)Servo bypass panel with 2 Nos changeover switches- f) 1 No 125 A EA to KSEB faulty changeover switch g) 3 Nos 1.5 TR Split type AC units along with copper refrigerant pipes, outdoor support work after pumping down the gas to the compressor Complete of all above
1
-
-
... More
Fixing of 1 No 125 A changeover switch with cable adaptor box at top and bottom after dismantling from the LT panel top i/c removing cable connection , fixing on the wall of EA room etc complete as reqd
1
-
-
... More
Dismantling the cable connection from EA set to LT panel from LT panel side (approx 12 mtr length- 3 1/2 x 70 sq.mm Al conductor armoured UG cable) and relaying 2 meters of cable to the EA change over box in the EA room with earth connection etc., giving connections, etc as reqd
1
-
-
... More
Dismantling KSEB meter board from the existing room, shifting and installing the same in outer wall of building , giving cable and earth connections etc complete as reqd (Note; Work involves liasoning with KSEB for shifting of meter connections)
1
-
-
... More
Providing Rain Guard arrangement for meter board including supply and fixing following Items, providing necessary clamps, tar washers etc for fixing the roofing sheet, painting the iron parts etc complete as reqd
-
-
-
... More
(a) 25x25x5 mm MS angle Iron
3
-
-
... More
(b) 25x 5 mm MS flat
2
-
-
... More
(c ) 0.35 mm Corrugated colour coated GI Sheet
1
-
-
... More
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing cable as required.
76
-
-
... More
Dismantling the cable connection from LT Panel to Light & Fan DB (approx 10 mtr length- 4 x 16 sq.mm Al conductor armoured UG cable) Re- Laying the same from the COS in EA room to TPN vertical DB in switch room, and terminating the connections etc complete as reqd
1
-
-
... More
Rewiring with the dismantled circuit wires 2 x 4 sqmm/ 4 x 4 sqmm with earth wire (Dismantling Approx 13 Metre) of the existing AC units to the TPN vertical DB in medium class 20/25mm dia PVC conduit/ flexible PVC conduit including supplying and fixing PVC conduit (approx. 5 mtrs), giving connections, etc as reqd
1
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
30
-
-
... More
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required
a). Group B
2
-
-
... More
Supplying and fixing 20 W LED strip type tube with fitting suitable for 240V,50 Hz AC supply , giving connections, testing, commissioning etc. required (Philips Smart bright or Sup. Make)
2
-
-
... More
S/F of 5/6 A ,5 pin modular type universal socket out let and 5/6A modular switch on the existing switch board without modular cover and plate as reqd.
2
-
-
... More
Dismantling the fire alarm panel, including dismantling the connections to the fire alarm panel, refixing the panel in switch room, rewiring the dismantled wiring connections to the fire alarm panel in PVC conduit/ flexible PVC conduit including supplying and fixing PVC conduit of 20/25mm (approx. 8 mtr), giving connections, refixing Hooter in SR, Extending supply to hooter using existing wiring, extending AC/DC supply with existing 2 x 1.5 sqmm wire ( Dismantling of wiring in MS conduit approx 28 meter)
1
-
-
... More
Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size 3-1/2 x 25 Sqmm Aluminium conductor armoured UG cable, in the surface/ recess of wall as reqd. ( From Meter Board to COS )
28
-
-
... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-
... More
a) 3 1/2 x 70 sq.mm
1
-
-
... More
b) 3 1/2 x 25 Sq.mm
2
-
-
... More
c) 4 x 16 sqmm
2
-
-
... More
Dismantling of existing alarm cable of 4 x 1.5 sq mm/ 2 x 1.5 sq mm copper conductor PVC insulated and sheathed armoured (FRLS) cable (Approx 22 Meter ) and relaying of the same (Approx 14 Meter) on the wall to the signal converter including dismantling the signal converter from the existing position and refixing in SR including providing gland for cables, giving connection etc as required. (Alarm extension)
1
-
-
... More
Supplying and fixing of following ways surface/ recess mounting,vertical type,415 V, TPN MCB distribution board of sheet steel,dust protected, duly powder painted, inclusive of 125 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. a) 4 way (4 + 12), Double door
1
-
-
... More
S/F following rating MCBs /isolator in the existing MCB DB complete with connections testiong and commissioning etc. as reqd.
-
-
-
... More
63 A, 415 V, 4 Pole Isolator
1
-
-
... More
32 A, 415 V, C curve, Triple pole MCB
2
-
-
... More
SP MCB 'C' series 5 to 32 A ,240V
6
-
-
... More
SP MCB Blanking plate
2
-
-
... More
TE ARUR
-
-
-
... More
Dismantling the following items for vacating the space in exchange for reducing the exchange area including making good the damages to the wall, Transporting all the dismantled items to TE Nadapuram( Approx. 8 km) and stacking the items as directed by Engineer in charge in exchange premises, loading unloading etc complete as reqd. (a)Servo protection panel (b) LT Panel of size 1.20m x 1.35m x 0.30m comprising of 2 Nos 125 A SDF, 6 Nos 63A SDF alongwith cable connections , earth connections etc as reqd (c) Dismantling the cables from meter board to servo panel, Servo panel to Servo, Servo to COS and COS to LTP etc. ( approx. 30 mtrs) (d) Dismantling AC control panel with 6 Nos timer controller, DC DB along with MCBs (e) Dismantling the wiring for the EI &Fans and fire alarm in MS conduit( Aprox. 225 mtrs), including 4 Nos detectors, hooters, MCPs, 14 No light fittings, 2 Nos Ceiling fans and 1 Nos. Exhaust fan etc, in the vacating rooms Complete of all above
1
-
-
... More
Dismantling the fire alarm panel after removing all incoming and outgoing connetion to the fire alarm panel, refixing the panel in opposite wall, including reconnecting wiring to the existing detectors ,hooters , MCP etc complete as required
1
-
-
... More
Dismantling of Changover panel with cable adaptor box for SCV from existing position and refixing on the wall for EA to KSEB changeover ,in the new proposed location including, giving cable connection etc complete as reqd
1
-
-
... More
Dismantling the cable connection from LT Panel to EA set (approx 34 mtr length- 3 1/2 x 70 sq.mm Al conductor armoured UG cable) and relaying on wall entire length of cable from MB to COS and EA set to COS giving connections, etc as reqd
1
-
-
... More
S/F SMC box of approx size 300 x 200 x 105 mm inside dimensions including providing 100A 4 way connector for extending the cable connections etc complete as reqd
1
-
-
... More
Dismantling the cable connection from LT Panel to AC DB (approx 10 mtr length- 3 1/2 x 25 sq.mm Al conductor armoured UG cable) and relaying on wall 8m length of cable from COS to VTPDB giving connections, etc as reqd
1
-
-
... More
Dismantling of existing AC wiring in MS conduit ( Approx 1.4 Meter) and rewiring the same length with the circuit wires 2 x 4 sqmm/ 4 x 4 sqmm with earth wire of the existing AC units to the TPN vertical DB in medium class 20/25mm dia PVC conduit/ flexible PVC conduit including supplying and fixing PVC conduit , giving connections, etc as reqd
1
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
8
-
-
... More
Dismantling of the existing circuit wiring to SR in MS conduit from LDB and relaying to the VDB using new 20 dia PVC pipe (approx 4.60 Meter) and connecting in the switch board etc as required
1
-
-
... More
Dismantling of the existing circuit wiring to EA room in PVC conduit (Approx 16 meters) and relaying to the VDB using existing 20 dia PVC pipe (approx 8 Meter) and connecting in the VDB etc as required
1
-
-
... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-
... More
a) 3 1/2 x 70 sq.mm
8
-
-
... More
b) 3 1/2 x 25 Sq.mm
2
-
-
... More
S/F of 5/6 A ,5 pin modular type universal socket out let and 5/6A modular switch on the existing switch board without modular cover and plate as reqd.
1
-
-
... More
Supplying and fixing 20 W, 4' LED tube without fitting suitable for 240V,50 Hz AC supply in the existing retrofit mirror optic fitting, modification in the existing connections, testing, commissioning etc. required (M/s Philips or Sup. Make)
7
-
-
... More
Reinstallation of available FT Box/MO fitting in the required location in SR etc complete as required
1
-
-
... More
Dismantling (Aprox.22 Mtrs) and relaying ( aprox. 12 mtrs) of 2 Nos Alarm cables of 2 x 1.5 and 4 x1.5 sq mm copper conductor PVC insulated and sheathed armoured (FRLS) cable on the wall/ceiling/ existing cable tray etc as required for extending signal from EA set to alarm converter.
1
-
-
... More
Dismantling meter board from the existing room, shifting and installing the same in corridor of the building, giving cable and earth connections, i/c Pdg necessarry temporary arrangement to extend supply to LT panel etc complete as reqd (Note; Work involves liasoning with KSEB for shifting of meter connections)
1
-
-
... More
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing cable as required.
100
-
-
... More
Providing and fixing 20 mm dia HDPE pipe on surface/ recess of wall for the protection of earth wire as required.
15
-
-
... More
Supplying and fixing of following ways surface/ recess mounting,vertical type,415 V, TPN MCB distribution board of sheet steel,dust protected, duly powder painted, inclusive of 125 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. a) 4 way (4 + 12), Double door
1
-
-
... More
S/F following rating MCBs /isolator in the existing MCB DB complete with connections testiong and commissioning etc. as reqd.
-
-
-
... More
63 A, 415 V, 4 Pole Isolator
1
-
-
... More
32 A, 415 V, C curve, Triple pole MCB
2
-
-
... More
SP MCB 'C' series 5 to 32 A ,240V
6
-
-
... More
SP MCB Blanking plate
2
-
-
... More
Providing and fixing of Earth bus in the EA room using 2 Nos 300mm long 25 mm x 5 mm GI strip on suitable insulators i/c providing nut, bolt, spring washer etc., as required.
1
-
-
... More
Relaying of the existing LA strip of GI of size 25mm x 3 mm including dismantling and relaying 5 meter strip , supply and fixing of 2 meter strip etc as required
1
-
-
... More
TE MUYIPOTH
-
-
-
... More
Dismantling meter board from the existing room, shifting and installing the same in the outwall of TE buildings , giving cable and earth connections, i/c Pdg necessarry temporary arrangement to extend supply to LT panel etc complete as reqd (Note; Work involves liasoning with KSEB for shifting of meter connections)
1
-
-
... More
S/F 50 mm dia PVC pipe along with accessories like bend etc for making service connection cable entry to the meter board including providing 1 no Hook on the wall/ ceiling etc as required
3
-
-
... More
Providing Rain Guard arrangement for meter board including supply and fixing following Items, providing necessary clamps, tar washers etc for fixing the roofing sheet, painting the iron parts etc complete as reqd
-
-
-
... More
(a) 25x25x5 mm MS angle Iron
3
-
-
... More
(b) 25x 5 mm MS flat
2
-
-
... More
(c ) 0.35 mm Corrugated colour coated GI Sheet
1
-
-
... More
Dismantling the cable connection from SCVs Changeover switch to LT Panel (Bypass cable ) (approx 18 mtr length- 3 1/2 x 70 sq.mm Al conductor armoured UG cable) and relaying 14 meters of cable from MB to Change over switch in the EA room with earth connection etc., giving connections, etc as reqd
1
-
-
... More
Dismantling the cable connection from EA Changeover switch to LT Panel (approx 11 mtr length- 3 1/2 x 70 sq.mm Al conductor armoured UG cable) and relaying the entire cable from Change over switch in the EA room to VDB in SR with earth connection etc., giving connections, etc as reqd
1
-
-
... More
Supplying and fixing of following ways surface/ recess mounting,vertical type,415 V, TPN MCB distribution board of sheet steel,dust protected, duly powder painted, inclusive of 125 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. a) 4 way (4 + 12), Double door
1
-
-
... More
S/F following rating MCBs /isolator in the existing MCB DB complete with connections testiong and commissioning etc. as reqd.
-
-
-
... More
(a) 63 A, 415 V, 4 Pole Isolator
1
-
-
... More
(b) 32 A, 415 V, C curve, Triple pole MCB
2
-
-
... More
(c) SP MCB 'C' series 5 to 32 A ,240V
6
-
-
... More
(d) SP MCB Blanking plate
2
-
-
... More
Dismantling the Cubicle type AC panel after disconnecting the incoming and outgoing cable/wire connections, reinstallation of the TPN DB for the AC units in the required locations, relaying of dismantled cables from VTPDB to TPNDB (approx. 6 Meters) giving output connections to AC units i/c supply and fixing of 1.6 mters of PVC /Flexible PVC pipe from TPNDB , giving connections, etc as reqd
1
-
-
... More
Extending of Fire alarm wiring to existing fire alarm panel including supply and fixing of 3 meters of 25 mm PVC conduit and drawing the existing wires to the panel etc as required
1
-
-
... More
Dismantling of the existing input supply cable from DC DB to Fire panel ( Approx 10 Meter) and relaying of 2 meters of cable from VDB to Fire panel etc complete as required
1
-
-
... More
Supplying and fixing 20 W LED strip type tube with fitting suitable for 240V,50 Hz AC supply , giving connections, testing, commissioning etc. required (Philips Smart bright or Sup. Make)
4
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (For SR room and EA room)
16
-
-
... More
Supplying and fixing of following ways surface/ recess mounting,sheet steel enclosure with common neutral link, earth bar, din bar for mounting MCBs (but without MCBs ) as required. a) 2 way
1
-
-
... More
S/F following rating MCBs /isolator in the existing MCB DB complete with connections testiong and commissioning etc. as reqd. a) 40 A 2 Pole isolator
1
-
-
... More
Dismantling (Aprox.22 Mtrs) and relaying the same length of alarm cables of 2 x 1.5 and 4 x1.5 sq mm copper conductor PVC insulated and sheathed armoured (FRLS) cable on the wall/ceiling/ existing cable tray etc as required for extending signal from EA set room to alarm converter.
1
-
-
... More
S/M cable end termination with brass compression gland for 2x1.5 sqmm PVC insulated and sheathed FRLS cable as required.( for signal convertor, Fire)
6
-
-
... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-
... More
a) 3 1/2 x 70 sq.mm
4
-
-
... More
b) 3 1/2 x 25 Sq.mm
4
-
-
... More
Dismantling the following items for vacating the space in exchange for reducing the exchange area including making good the damages to the wall, Transporting all the dismantled items to TE Perambra( Approx. 9 km) and stacking the items as directed by Engineer in charge in exchange premises, loading unloading etc complete as reqd. (a)Servo Changeover panel (b) LT Panel of size 1.40m x 1.30m x 0.30m comprising of 2 Nos 125 A SDF, 6 Nos 63A SDF alongwith cable connections , earth connections etc as reqd C) 8 Zone Fire Alarm Panel d) GI pipe for the service connection cable- 6 Meter (e) Dismantling the cables from meter board to servo panel, Servo panel to Servo, Servo to COS and COS to LTP, DB to LT panel, LT panel to AC DB etc. ( approx. 35 mtrs) (f) DC DB along with MCBs (e) Dismantling the wiring for the EI &Fans and fire alarm in MS conduit( Aprox.120 mtrs), including 4 Nos detectors,3 hooters, 2 Nos MCPs, 8 No light fittings, 2 Nos Ceiling fans and 1 Nos. Exhaust fan etc, in the vacating rooms Complete of all above
1
-
-
... More
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing cable as required.( MB to C/o, C/O to VDB)
60
-
-
... More
S/F 12 SWG dia Copper wire alongwith cable for loop earthing as reqd ( VDB to AC DB)
10
-
-
... More
S/F 20mm dia GI pipe for protection of GI wire for extending earth connections to meter board as reqd( EA room)
8
-
-