Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Repair/replacemet Transformer, Ht Cable And Overhead Line And E/m Installation At ,south Camp, North And Mutaga Campat Ats Belagavi in Belagavi, Karnataka, with an estimated contract value of Rs. 25,98,000. The bid opening date for this tender is 22-10-2026 and the last date for bid submission is 16-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - Karnataka Tender
Opening Date22 Oct 2026
Closing Soon16 Nov 2026
Tender Amount₹ 25,98,000
Costs
EMD
₹ 52,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Repair/replacemet Transformer, Ht Cable And Overhead Line And E/m Installation At ,south Camp, North And Mutaga Campat Ats Belagavi
Contact
Tender Id
2026_MES_788866_2Tender No
81269/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply & Fix cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections conforming to Grade E-165 (Fe 290) including nuts, bolts, washers, welding, bending cold or hot, drilled holes for bolts, in any shape or size for 33 KV/ 11 KV over head structure with & including two coats of aluminium paint over a coat of red oxide zinc chromate primer, fixed as in repairs, complete all as specified & as directed. Notes :- (i) Size, section and shape of steel sections shall be as directed. (ii) Weight of paint shall not be considered for payment purpose and quoted rate shall deemed to be included this aspect.
5
16
-
... More
Inspecting, servicing, testing and calibration of 11 KV SF 6 / VCB Breaker with control relay Panel as recommended by OEM by deploying expert inspector cum engineer and helper of authorised associates of M/s Crompton Greaves Company for the followings :-
(a) Properly clean the VCB with a CRC-226 & ensure proper lubrication in VCB (Electrical contact cleaner).
(b) Removal of old grease & regreasing the same eith recommened frease.
(c) Check condition of SIC contacts, alignment jaw contacts, proper tightening of hardware, proper closing of all poles together.
(d) Check & adjust gap between hyleum sheet and side plate.
(e) Check pressure of all circlips.
(f) (i) Check IR between Phase-Phase (VCB closed condition) (ii) Phase-Earth (VCB closed condition) (iii) Phase-Earth (VCB in open condition)
(g) Any faulty spares/parts to be replaced with new one.
9
16
-
... More
Supply & fix in repair porcelain vitreous HT 11 KV bushings with brass studs suitable for out door distribution transformers of capacity 63 KVA - 300 KVA after removing the old u/s studs/bushings and draining out the transformer oil from the top level up to conservator of the transformer and removing the top cover of the carefully and refixing and refilling the oil complete all as specified and as directed.
Note - The transformer repair / servicing works shall be carried out only by engaging specialized and experienced technicians. The rate shall be included making necessary arrangements to remove the oil in the conservator in safe drums and refilling after the repair works.
5
16
-
... More
Supply & fix in repair porcelain vitreous LT 11 KV bushings with brass studs suitable for out door distribution transformers of capacity 63 KVA - 300 KVA after removing the old u/s studs/bushings and draining out the transformer oil from the top level up to conservator of the transformer and removing the top cover of the carefully and refixing and refilling the oil complete all as specified and as directed.
Note - The transformer repair / servicing works shall be carried out only by engaging specialized and experienced technicians. The rate shall be included making necessary arrangements to remove the oil in the conservator in safe drums and refilling after the repair works.
5
16
-
... More
Surface dressing in hard / dense soil /aggregate not exceeding 15cm deep and clearing all the grass weeds etc at E/M installations as directed after removing and spreading back the aggregate twice a month or as directed upto the completion of work in each sub station and E/M installation as directed.
450
16
-
... More
Re-straining/ re-stringing/tightening of existing HT 11 KV over head Aluminium Conductor Steel Reinforced (ACSR) and GI earth wire of any size/ type upto permissible sag in between existing span carefully without damaging other components such as insulators etc of HT distribution system with & including repair to broken conductor where required and replacement of binding wire with new 2mm dia aluminium binding wire complete all as specified and as directed. Note :- Unit for measurement and payment for this item “RM” is comprising of 3 Nos ACSR conductors and one GI earth wire in line.
2
16
-
... More
Material and labour for fixing lightning arrester for out door use expulsion type with all fittings suitable for 11000 volts HT line transmission class of discharge capacity 65 KA including taking out the unserviceable lightening arrester, complete all as specified and as directed.
5
16
-
... More
Material and labour for Pin type, porcelain, vitreous, white brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm height, 150mm dia for 11000 volts grade complete including taking out the unserviceable all as specified and as directed.
20
16
-
... More
Supply and fix disc insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown on green suitable for HT 11 KV complete including taking out the unserviceable all as specified and as directed.
15
16
-
... More
Material and labour for repair to existing switch air break, gang operated outdoor, vertical / horizontal mechanically operated type, HT 11 KV, Triple pole by cleaning and servicing to operating mechanism, greasing etc of all joints for smooth operation replacement of defective parts where as required to make it fully functional with smooth operations and testing, complete all as specified and as directed.
Note : (i) Labour component required for the replacement of unserviceable parts shall deemed to be included in the quoted rates in this schedule.
(ii) Major parts where required to be replaced shall be measured and paid for separately as 'Supply Only' under relevant items of this schedule.
(iii) All T&P and minor parts such as nuts, bolts, washers etc shall be arranged by the contractor and the cost thereof shall be demeed to be included in the quoted rate of this item.
15
16
-
... More
Supply only moving contact blades copper, complete all as specified & directed.
15
16
-
... More
Supply only Fixed contact jaw copper, complete all as specified & directed.
15
16
-
... More
Supply only tinned copper flexible jumper, complete all as specified & directed.
15
16
-
... More
Supply only MS Jumper carrier guide, complete all as specified & directed.
15
16
-
... More
Supply only Back connecter plate, complete all as specified & directed.
15
16
-
... More
Supply only PG clamp, complete all as specified & directed.
15
16
-
... More
Supply only GOD insulator with base assembly, complete all as specified & directed.
5
16
-
... More
Material and labour for jumper connections (RYB) between GOD and drop out fuses and transformers with ACSR conductor 6/1 x 3.35 mm (rabbit) not exceeeidng 2 mtrs all as specified and as directed
15
16
-
... More
Material and labour for painting of four pole structure complete including chanels, GODs, cross arm, scraping the old painted surfaces, cleaning and painting with two coats of aluminium paint over a coat of red oxide primer for steel tubuler pole and cement colour for PCC pole upto 1.2 mtr height from top of copping and then 03 nos of each black and yellow alternate strip of 20 cm width upto GL/Copping complete including writing pole numbers all as specified and as directed.
3
16
-
... More
Material and labour for painting of two pole structure complete, scraping the old painted surfaces, cleaning and painting with two coats of synthetic enamel paint of silver colour over a coat of red oxide primer for steel tubuler pole and cement paint for PCC pole upto 1.2 mtr height from top of copping and then 03 nos of each black and yellow alternate strip of 20 cm width upto GL complete all as specified and as directed.
3
16
-
... More
Disconnecting and taking out old defective HT jointing kits of any size and type, complete all as specified and as directed.
12
16
-
... More
Material and labour for heat shrinkable cable jointing kit for 11 KV earthed grade cable for out door termination complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm 3 core complete including taking down the old burnt joint joint complete all as specified & directed.
4
16
-
... More
Material and labour for heat shrinkable cable jointing kit for 11 KV earthed grade cable for out door termination complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size120 to 185 sqmm 3 core complete including taking down the old burnt joint joint complete all as specified & directed.
2
16
-
... More
Material and labour for heat shrinkable cable jointing kit for 11 KV earthed grade cable for out door termination complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm 3 core complete including taking down the old burnt joint joint complete all as specified & directed.
2
16
-
... More
Material and labour for heat shrinkable cable jointing kit for 11 KV earthed grade cable for out door termination complete with jointing materials and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size120 Sqmm to 185 Sqmm 3 core complete including taking down the old straight through joint complete all as specified & directed.
2
16
-
... More
Supply and fix Tap changeover mechanism for 125 to 500 KVA step down transformer as per existing make, complete all as specified & directed.
2
16
-
... More
Supply and fix Tap changeover mechanism for 50 to 100 KVA step down transformer as per existing make, complete all as specified & directed..
2
16
-
... More
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm, complete all as specified & directed.
2
16
-
... More
Supply and laying, testing and commissioning on fixing or passing through pipes, cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (Heavy duty) with aluminium conductor 11 KV (E) volts grade screened of size 95 Sqmm 3 core, complete all as specified & directed.
50
16
-
... More
Supply, Laying, testing and commissioning of HT UG cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armored electric power cable (heavy duty earthed) with stranded aluminium conductor,11000 volts grade of size 3 core 120 Sqmm complete laid in trenches or fixed on walls /floors etc, all as specified and as directed.
50
16
-
... More
Supply and laying, testing and commissioning on fixing or passing through pipes, cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (Heavy duty) with aluminium conductor 11 KV (E) volts grade screened of size 240 Sqmm 3 core, complete all as specified & directed.
75
16
-
... More
Excavation in trenches for laying underground cables, poles and stays in hard / dense soil not exceeding 1.5M wide and not exceeding 1.5 M deep and getting out, complete all as specified & directed.
66.5
16
-
... More
Excavation in trenches for laying underground cables, poles and stays in hard / dense soil not exceeding 1.5M wide and exceeding 1.5 M deep but not exceeding 3.0 m deep and getting out, complete all as specified & directed.
1.55
16
-
... More
Supply & Fix DWC Pipe IS-16205, outer dia 120 mm for cable protection in wall/under gorund laying of UG cables including SNAP-FIT Coupler and all fittings as required at site, complete all as specified and as directed by Engr-in-Charge.
80
16
-
... More
Supply & Fix DWC Pipe IS-16205, outer dia 160 mm for cable protection in wall/under gorund laying of UG cables including SNAP-FIT Coupler and all fittings as required at site, complete all as specified and as directed by Engr-in-Charge.
65
16
-
... More
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25cms thick, complete all as specified & directed.
56.49
16
-
... More
Removing surplus excavated material to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 M above the starting point, complete all as specified & directed.
11.56
16
-
... More
Supply and fix HT RCC pole 11 mtr long 152 x 152 mm at top and 152 x 260 mm at bottom class 9 erecting in vertical position incl cement colour upto 1.2 mtr height from top of copping and then 03 nos of each black and yellow alternate strip of 20 cm width upto GL/Copping & including removing broken pole from site, complete all as specified & directed.
4
16
-
... More
Material and labour for stay assembly with complete accessories as shown in electrical plate No. 1 using 20 mm dia stay rod including taking down old stay assembly complete all as specified & directed. (Note - loop type isolator, stay clamps, excavation and concrete will be measured and paid separately)
3
16
-
... More
Material and labour for Galvanised iron stay strand of size 7/4.00 mm including taking down old stay strand, complete all as specified & directed
0.15
16
-
... More
Material & Labour for providing cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation filling & mass concrete, complete all as specified and directed
0.49
16
-
... More
Material & Labour for providing cement concrete 1:3:6 type C-2 (using 40 mm graded crushed stone aggregate) as in foundation filling & mass concrete, complete all as specified and directed
8.86
16
-
... More
Material & Labour for providing cement concrete PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) as coping around poles etc complete including necessary formwork and finishing the exposed surfaces even and smooth without using extra cement all as specified and as directed.
0.43
16
-
... More
Supply and fix in repair of silica Gel container (breather) including silica Gel suitable for the transformers of capacity 50 KVA to 200 KVA after dismantling the old U/S breather, complete all as specified and directed.
5
16
-
... More
Supply and fix in repair of silica Gel container (breather) including silica Gel suitable for the transformers of capacity 250 KVA to 500 KVA after dismantling the old U/S breather, complete all as specified and directed.
5
16
-
... More
Material and labour for replacement of silica gel including disconnecting of silica gel from body of any capacity of transformer and refixing the same, complete all as specified & directed.
10
16
-
... More
Supply and fix in repairs of simplex type overcurrented Earth fault relay features (04 Points) (a) IDMT and High set unit provides both inverse Definite minimum time(IDMT) protection for overload and high Set instantenous protection for severe faults, (b) Overcurrent and eart fault protection detects both phase overcurrent faults and earth ground fault to ensure reliable system protection, (c) No external Auxiliary support required: The relay is self powered from the current transformer (CT) circuit and does not require an external auxiliary DC/AC supply for operation, (d) Adjustable settings pickup current time multiplier setting (TMS) and High set values can be adjusted to suit the protection requirement of the electrical system complete all as specified & directed.
1
16
-
... More
Supply and fix in repairs of 2 Element High speed Electrochemical Tripping relay features(Four Points), (a) Two independent tripping elements equipped with 2 independent high speed electrochemical tripping elements for reliable and fast circuit breaker tripping, (b) Auxiliary suppply operates on 110 V DC auxiliary voltage, (c) Output contacts provides 6 normally open (6No) and 02 Normally closed(2NC) output contacts for tripping, alarm and interlocking functions , (d) Fast and reliable operation ensures high speed, dependable tripping with robust electrochemical construction suitable for protection schemes in HT/EHT substations.
1
16
-
... More
Material and labour for servicing of servo controlled volatge stabilizer of capacity 100 KVA of make : Servo, situated at AF NET by disconnecting the LT cables and draining out oil complete and taking out the core and checking the continuity and insulation values of all three phases, reinsulating if required and inspecting and replacing the PCB in case of repair, repair and servicing of breaker, removing and cleaning the sludge from the tank, refilling the oil after filtering by using online centrifuge machine and obtain the dielectric strength of oil not below 100 KV at 2.5 mm gap including testing of volatge stabilizer by reconnecting the disconnected cables and calibrating complete all as specified and as direcrted.
Note : (a) The rate shall also deemed to be included the rate for (i) Technician, Electrician and labours (ii) Supply and fixing of drain valve to the voltage stabilizer suitable for of make : Servo.
(b) Filtration of oil by using online centrifuge machine and top up of oil will be measured and paid separately under relevant items of the schedule
1
16
-
... More
Material and labour for fixing earth pit indicators made out of 3 mm thick MS sheet of size 200mm x 150mm duly fixed in MS angle iron 25mmx25mm of 450 mm long to be fixed to ground by means of cement concrete including painting with two coats of synthetic enamel paint over a coat of red oxide primer and writing the earth resistance complete including excavation and earth work PCC type C1, 1:3:6 of size 150 x 150 x 150mm all as directed, including dismantling and taking out the old rusted / out lived earth indicators all as specified and as directed .
5
16
-
... More
Material and labour for Earthing complete with galvanised steel earth plate electrode 600mmx600mmx6mm size burried directly in ground vertically to a depth not less than 2.25 mm below ground level with top edge of the plate not less than 1.5 metre below normal ground level, connected to galvanised earth strip 32x6 mm size protected by 40 mm light grade pipe upto 7.5 m length by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part-1 including necessary excavation earth work, drilling of holes for electrode, PCC 1:3:6 type C1, RCC cover slab, 50 mm thick with 1:2:4 type B1, using 8 mm CTD bars 140 mm C/C both- way with suitable handle, watering pipe 20 mm dia light grade GI, funnel, charcoal, salt all as specified and as directed by Engineer in charge including taking down old u/s earthing assembly all as specified and directed.
5
16
-
... More
Material and labour for PVC alkathene sleeving 15mm dia as per IS standard for Jumper connection on HT/LT poles heavy duty all as directed .
50
16
-
... More
Supply and fix in repairs switch air break gang operated, triple pole, mechanically operated, mounted on insulators & steel frame with operation mechanism worked from ground level for current rating 200 Amps, 11000 volts complete all as specified and as directed. Note - GOD shall be vertical type / horizental type which ever is suitable as per site requirement.
2
16
-
... More
Supply & fix of drop out expulsion fuse single pole 11000 volts, above 25 Amps and upto 50 Amps complete including taking out old U/S one all as specified and as directed.
2
16
-
... More
Material and labour for spray painting of transformer upto 300 KVA capacity with two coats of synthetic enamel paint of smoke grey colour over a coat of red oxide primer after thoroughly preparing the surface, complete all as specified and as directed.
10
16
-
... More
Material and labour for painting of GOD cross arms and channel with clamps by scrapping rusted surface by applying one coat of aluminium paint including support GOD handle, complete all as specified and as directed.
20
16
-
... More
Supply only distilled water for lead acid battery of Main receiving station, complete all as specified and as directed.
50
16
-
... More
Cutting tree branches below, top and around the OH conductors not less than two metre around the line and keeping the line clearance through out the contract period by trimming the branches repeatedly as many times as required, depending on the growth of new branches including clearing the site by removing the branches to a distance not exceeding 50 m all as directed .
200
16
-
... More
Supply & Fix Aluminium Conductor Steel Reinforced (ACSR) of any size as directed, stringing for overhead line on HT poles including jointing with and including aluminium binding wire 2 mm dia, jumpers, line tapes, conducting jelly, stretching properly and connecting with suitable PG clamps, etc including dismantling and taking down old existing unserviceable aluminium conductor steel reinforced (ACSR) of any size/ type / capacity, complete all as specified and as directed.
Notes : (i) The ACSR conductors shall conforming to IS-398 (Part-II) and as specified in SSR Part-I. (ii) The unit rate quoted shall also deemed to include for supply and fixing of binding wire, aluminium tapes, etc which shall not be included in the weight of conductors for payment. (iii) Weight of conductors shall be determined by measuring the horizontal distance between centers of two adjacent poles and compounding the weight of conductors of that size and length and 3% extra shall be added for sag, jointing, jumpers etc. (iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS code.
3
16
-
... More
Material and labour for spreading 40 mm coarse graded aggregate (blue metal) in the substation yards at a thickness not exceeding 150 mm complete all as specified and as directed.
Note:- Aggregate should be layed after scrapping of existing aggregate and levelled at various transformer yard as indicated.
50
16
-
... More
Disconnecting HT/LT Connection of 33/11 KV Power transformer 2.0 MVA capacity and identifying the leakage by visual inspection and other available technique and rectifying the leakage by welding/brazing etc after draining out transformer oil including refilling of transformer oil after dehydration complete including testing and commissioning complete all as specified and directed by Engr-in-Charge. Note - Contractor shall responsible for:- (i) Arranging the drum for storing Transformer oil. (ii) Any damage during leakage arrest.
(iii) Refilling the existing transformer oil after filtration to remove moisture carbon particle and to achieve dielectric strength of oil minimum up to 60 KV. (iv) Testing of transformer oil and the payment will be made under the relvant item.
2
16
-
... More
Supply & Fix in repairs insulated synthetic mat nominal 6.0mm thick confirming to IS: 15652-2006 ISI marked suitable upto 33 KV Colour blue standard roll from 5m / 10m to minimum joints and width of Each mat shall be 1.0m complete all as specified and directed by Engineer-in-Charge. [Make: PREMIER POLYFILM LTD / SUNTEX INSULATICA / DUNLOP]
10
16
-
... More
Overhauling and Servicing of OLTC unit for HT transformer of capacity 33KV/11KV, 2 MVA comprising of the following:-
(i) Servicing of all mechanical gear wheels and moving parts, latches and releasing parts, over driven stopping and restarting mechanism complete
(ii) Cleaning of complete OLTC control chamber and fault finding and rectification
(iii) Repairing to control wiring, replacement of burnt wires, lugs, etc
(iv) Lubricating, greasing of all mechanical parts
(v) Servicing to electrical auxillary contactors and limit switches and HRC fuses complete
2
16
-
... More
Painting of old painted surface of chain link fencing of mesh size 50 x 50 mm by scrapping rusted surface by applying one coat of aluminium paint inside and out side of 33 KV yard & other sub station including cement paint of cement pillar compelete all as directed
300
16
-
... More
Overhauling and Servicing of CT - 12 Nos and PT- 06 Nos for HT transformer of capacity 33KV/11KV.
Note :- Quoted rate is inclusive of necessary sapres parts complete.
1
16
-
... More
Material and labour for Galvanised Iron pipes 80 mm dia, light grade with all fitting and fixed to poles/route/drains, ceillings or laid in floors, complete all as specified and as directed.
30
16
-
... More
Cutting the tar macadam road / hard standings for laying cable and excavating not exceeding. 1.5 wide and not exceeding 1.5m in depth and getting out all as directed including filing back and finishing it with PCC 1:3:6 type C-1, complete matching with the surroundings.
6
16
-
... More
Material and Labour for HT cable Route Indicator with a welded/riveted disc of 4 inch dia and engraved with cable route maker made out of angle iron 40 x40 x 4 mm thick , inserted in ground with PCC 1:3:6 type C1 concrete using 20mm graded aggregate at approx distance of 100mtrs including necessary earth work etc. complete all as specified and directed.
10
16
-
... More
Supply and installation outdoor type current transformer rated 33 KV, Insulation Class-A, frequency-50 HZ, Higest Voltage- 36 kv REF-IS-2705, Rated STC-35KA RMS For 1 Sec, IDY-62.5 KA, insulation level 70/170 KV, Qty of Oil-25 Ltrs, Crappage- 900 mm, Total weight- 110 Kgs, Ratio 200-100/1-1A,
3
16
-
... More
Supply & Fix GI continuous earth wire or guard/cradle made to shape of 3.15mm or 4mm dia as directed including Galvanized mild steel binding wire 1.63mm dia including dismantling & taking down old existing unserviceable GI continuous earth wire, guard, cradle, etc of any size from HT poles including disconnecting from the existing system complete all as specified & as directed.Note :- Galvanized wire shall be measured & paid for under this item and clamps, eye hooks where provided shall be measured and paid for separately.
0.5
16
-