Karnataka Urban Water Supply And Drainage Board Tender

Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.

Karnataka Urban Water Supply And Drainage Board - KUWSDB Tender

Opening Date22 Jul 2021
Closing Date30 Jul 2021
Tender Amount₹ 36,04,20,986 

Costs

  • EMD

    NA
  • Document Cost

    NA
  • Tender Fee

    NA

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents

No Documents Available

Report Missing Document

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Earth work excavation by manual means for pipeline trenches (except building works) including depositing on bank with all lead including shoring, strutting, barricading, danger lighting and using sight rails and boning rods at every 100 meters wherever necessary as directed in the following strata. - Do- In all soils mixed with boulders upto 30cms. size and exclusive of disintegrated rocketc., complete with all lead and lift as directed by the Engineer In-Charge.

39436

-

10332232

... More
In disintegrated rock, soft rock, soft shale and medium hard rock comprising of Lime stone, sand stone, hard shale, schist, fissured rock without resorting to blasting with all lead and lift etc., complete with all lead and lift as directed by the Engineer In-Charge.

15168

-

8979456

... More
in Hard Rock by Chisteling etc., complete with all lead and lift as directed by the Engineer In-Charge.

6064

-

14462640

... More
Providing Murrum / Gravel Bedding for the pipeline trenches including watering and consolidation by punners etc., complete with all lead and lift (In Black Cotton soil and rock reaches) etc., complete with all lead and lift as directed by the Engineer In-Charge.

7851.37

-

2033504.83

... More
Supplying HDPE pipes conforming to IS 4984:2016 with latest amendments and conveying to work site including loading and unloading at both destination and rolling, lowering into trenches, laying true to line and jointing of pipes and specials by electrofusion welding, as per standard procedure and guidelines including encasing the pipe around to a depth not less than 15cms with soft gravel or selected earth available from the excavation etc., complete giving hydraulic test as per relevant ISS with all lead and lift including testing and commissioning. The rate is inclusive of required specials and fittings etc., complete with all lead and lift as directed by the Engineer In-Charge. (Contractor will make his own arrangement for procuring water for testing) HDPE Grade-PE-100, PN-8 -Do- for 75mm dia

39670.47

-

7789296.78

... More
- Do- for 90mm dia

15582.99

-

4074172.74

... More
- Do- for 110mm dia

6026.49

-

2195751.63

... More
- Do- for 160mm dia

4148.19

-

2948740.86

... More
Supplying Ductile Iron pipes conforming to IS 8329:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line, level and perfect linking at joints, testing and commissioning, including loading and unloading at both destinations and cuts of pipes wherever necessary including jointing of DI pipes and specials, (excluding cost of specials) with rubber gaskets including cleaning the socket and spigot ends with soap solution and applying soft soap to the spigot and socket ends before insertion of rubber gaskets, jacking and fixing in perfect conditions including cost of soap solution, soft soap, waste etc. and giving necessary hydraulic test to the required pressure as per ISS with all lead and lift including cost of jointing materials. Contractor will make his own arrangements for procuring water for testing) etc., complete with all lead and lift as directed by the Engineer In-Charge. - Do- for 200mm dia K-7

5613.32

-

10328508.8

... More
- Do- for 250mm dia K-7

1445.63

-

3465175.11

... More
- Do- for 300mm dia K-7

1305.55

-

3962344.25

... More
Supplying and fixing of DI Special with ISI mark conforming to IS 9523/200- suitable for jointing 100mm to 600 mm dia DI pipes Coated with rust prevention coatings as below,etc., complete with all lead and lift as directed by the Engineer In-Charge. A) External coating : a) metalic zinc with finishing layer of bituminous as per Annexure "A" of IS :9523/2000 b) Zinc rich paint with finishing layer of bituminous as per Annexure "A" of IS :9523/2000 c) Bituminous paint as per Annexure "C" of IS :9523/2000 B) Internal lining : a) Portaland Cement (with or without additives) mortar as per Annexure "B" of IS :9523/2000 b) Cement mortar with coat as per Annexure "B" of IS :9523/2000 c) Bituminous paint as per Annexure "" of IS :9523/2000

26000

-

2002000

... More
Manufacturing, providing, transporting, rollilng, lowering, laying and jointing, testing and commissioning of ERW (Electric Resistance Welded) /SAW (Sub-merged Arc Welded) MS pipes,(Fe-410 grade) conforming to IS 3589-2001 with latest amendments, including perfect linking and welding of joints to correct position including cost and conveyance of pipes and materials with all lead and lift, cost of all labour and giving satisfactory hydraulic test as per IS 3589-2001 with latest amendments for test pressure and working pressure both at factory and site etc complete as per detailed specifications with inside CM 1:1:5 lining of minimum 10mm thick upto 610 mm OD & minimum 12 mm thick beyond 610 mm OD and out side minimum 25 mmm thick coating in unloading of pipes for the following diameters and specified thickness of plate as noted below, including bailing out of water wherever necessary (Contractor will make his own arrangement for procuring water for testing) etc. complete with all lead and lift as directed by the Engineer Incharge 219 mm dia M.S. pipe (6.4 mm thick)

500

-

1619500

... More
Manufacturing, providing, transporting, rolling, lowering, laying and jointing, testing, commissioning of MS specials of minimum 8mm thick, conforming to IS 7322:1985 with latest amendments, perfect linking and welding of joints to correct position including cost and conveyance of materials with all lead and lifts, cost of all labour and giving satisfactory hydraulic test as per IS 3589: 2001 with latest amendments for test pressure and working pressure both at factory and site etc. complete as per detailed specifications with inside lining two coats of food grade epoxy painting pf approved make with each coat 250 microns thick (after dry) over one coat of food grade epoxy primer of approved make with minimum of 50 micron thick (after dry) and outside 25mm thick coating in CM 1:3 by providing 50mmx50mm weld mesh including loading and unloading of pipes for the following category to suit PSC/MS/DI/ AC/CI/ PVC pipes. (The weight of the MS shell only be considered before lining and coating for arriving at the rate). The thickness of plate will be specified by the Engineer. (contractor will make his own arrangement for procuring water for testing) etc., complete with all lead and lift as directed by the Engineer In-Charge.

5000

-

815000

... More
Supply and delivery to work site, loading, unloading, stacking and fixing of Resilient seated soft sealing DI Sluice valves with body bonnet of ductile iron of Grade GGG50, wedge fully rubber lined with EPDM and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face dimensions as per BS 5163-89/IS 14846-2000/ DIN/3202 F4/F5. The stem sealing should be with toroidal sealing rings (Minimum 2 O-rings) All the valves should be with Electrostatic powder coating both inside and outside with pocket less body passage. The valves shall be supplied with suitable size galvanized bolts and nuts of required numbers as per relevant IS etc., complete with all lead and lift as directed by the Engineer In-Charge. -Do- for 80mm dia PN 1.6

80

-

684160

... More
-Do- for 100mm dia PN 1.6

15

-

162570

... More
-Do- for 150mm dia PN 1.6

12

-

227580

... More
-Do- for 200mm dia PN 1.6

6

-

180492

... More
-Do- for 250mm dia PN 1.6

2

-

90550

... More
-Do- for 300mm dia PN 1.6

2

-

127664

... More
Providing and laying cement concrete 1:2:4 proportion (excluding cost of reinforcement) with 20mm and down size metal of approved gradation hard broken granite, trap, basalt or with any other approved hard aggregate including cost and conveyance of all materials with all lead and lift and placing the same above or below ground level including plywood / steel form work, machine mixing, laying, tamping, curing, etc., complete including smooth finishing the exposed faces with CM 1:4 proportion 12 mm thick wherever necessary, etc., complete with all lead and lift as directed by the Engineer In-Charge. for Anchor Blocks/Thrust Blocks

54.96

-

356797.57

... More
Supply and Labour charges for fabricating TMT steel bars of all sizes for reinforcement of RCC works including cleaning straightening, bending, fabricating, placing in position, tieing as per designs including cost of binding wire hoisting etc., complete with all lead and lift as directed by the Engineer in charge.

3.85

-

245914.9

... More
Construction of valve chamber Earth work excavation for pipeline trenches (except building works) including depositing on bank with all lead including shoring, strutting, barricading, danger lighting and using sight rails and boning rods at every 100 metres wherever necessary as directed in the following strata etc., complete with all lead and lift as directed by the Engineer In-Charge. - Do- In all soils mixed with boulders of upto 10cms. size and exclusive of disintegrated rock

660

-

172920

... More
-do- In disintegrated rock, soft rock, soft shale and medium hard rock comprising of Lime stone, sand stone, hard shale, schiest, fissured rock wihtout resorting to blasting.

440

-

260480

... More
-do- In Hard Rock by chiseling

367.5

-

876487.5

... More
Providing and laying C.C. 1:1.5:3 proportion for foundation (Screed layer) with 20 mm and down size of approved gradation hard broken granite, trap basalt or with any other approved hard aggregate including cost and conveyance of all materials with an all lead & lifts including plywood / steel form work, machine mixing, laying, tamping, curing etc., complete with all lead and lift as directed by the Engineer In-Charge.

126.25

-

739017

... More
Providing and laying vibrated M30 design mix for R.C.C. Works with 20 mm and down size of approved gradation hard broken granite, trap, basalt or any other approved haraggregate, including, cost and conveyance of all materials with all lead & lift, including plywood/steel form work, centering, scaffolding, cement mortar, plastering in CM 1:3 proportion, 20mm. thick for inside with admixture of water proof compound of requisite proportion of proved quality including weigh batch plant mixing, curing, making construction joints wherever necessary and giving satisfactory water proof testing etc., complete (excluding cost of reinforcement) for floor slab, resting on ground. contractor will make his own arrangements for procuring water for testing) etc., complete with all lead and lift as directed by the Engineer In-Charge.

167.5

-

1280370

... More
Providing and laying vibrated M30 design mix for R.C.C. Works with 20 mm and down size of approved gradation hard broken granite, trap, basalt or any other approved haraggregate, including, cost and conveyance of all materials with all lead & lift, including plywood/steel form work, centering, scaffolding, cement mortar, plastering in CM 1:3 proportion, 20mm. thick for inside with admixture of water proof compound of requisite proportion of proved quality including weigh batch plant mixing, curing, making construction joints wherever necessary and giving satisfactory water proof testing etc., complete (excluding cost of reinforcement) for vertical side walls, alround effluent channel, baffels, etc. complete with outside form finishing etc., complete with all lead and lift as directed by the Engineer In-Charge.

293.75

-

3983250

... More
Providing and laying vibrated M30 design mix for RCC work with 20 mm and down size of approved gradation hard broken granite, basalt, trap or any other approved hard aggregateincluding cost and conveyance of all materials with all lead and lift including weigh batch plant mixing, centreing plywood / steel form work, scaffolding tamping, curing, cement mortar plastering in C.M. 1:3 proportion 12 mm. thick for inside surface etc., complete (excluding cost of reinforcement) for R.C.C. covering slab (Flat slab) etc., complete with all lead and lift as directed by the Engineer In-Charge.

91.25

-

1187162.5

... More
Providing TMT steel reinforcement for RCC work including straightening, cutting, bending, hooking, placing in position, lapping and or welding wherever required, tying with binding wire and anchoring to the adjoining members wherever necessary complete as per design (laps, hooks and wastage shall not be measured and paid) cost of materials, labour, HOM of machinery complete as per specifications.

55

-

3513070

... More
Supplying and fixing of SFRC frame and cover heavy duty etc., complete with all lead and lift as directed by the Engineer in charge.

125

-

184500

... More
Supply and installation of water connections to individual houses upto water meter point (which shall be fixed about one meter from customer boundary) and includes civil works like Earthwork excavation for the pipeline trenches for laying of MDPE/GI pipes for the house connections in all types of soils , disintegrated rock, soft rock, hard rock, including cutting of any road using machine cutter, crossing drains, compound, cutting any surfaces along the pipelines such as tiles/floor/concrete/ or any other surfaces using machine cutter, boring the wall surfaces comprising of BBM or SSM for conveying the pipelines to customer property, restoring the damaged portions inside or outside the property premises, refilling etc. complete. Supply and laying of MDPE PE-80, PN 12.5 pipes with specials such as Electrofusion tapping Tee or saddles of Virgin Compounded PE 100 material, Black colour of pressure rating PN 16 /SDR 11 or higher grade of approved make conforming to standard specifications with brass cutter, flow regulator, water tight cap with "O" ring, long spigot, cutting edges for making hole tapping suitable to HDPE distribution mains by electro fusion welding as per BS EN 12201-3 & EN 1555-3 Standards. The Product should be tested to comply with BS 6920 for drinking water service in WRC NSF, UK and DVGW certificate. Germany. Tapping Tee or Saddles with coupler and compression fittings with cost of Gl pipes, all specials such as GI tee, Gl elbow GI coupler, stopper etc, and brass or SS tap as shown in Fig. no. 2.1, 2.2 & 2.3 for the following diameters etc., complete with all lead and lift as directed by the Engineer in charge. . -do- for 15mm dia

8321

-

48378294

... More
Supply of Gunmetal Ball valve of non-rising stem, screwed in bonnet, inside screw, integral seats, screwed female ends to IS: 554/BS 21/IsO 7, unbreakable sheet metal Hand wheel conforming to IS:778 Class-1 including provision of re-packing under pressure etc., complete.(BSR 2018-19 P-68, I-53) etc., complete with all lead and lift as directed by the Engineer in charge. .

8321

-

1580990

... More
Providing 50 mm Dia HDPE Sleeve pipe with allied accessories at ferrule point of HSC to assist in regulating flow with allen key etc., complete with all lead and lift as directed by the Engineer in charge. .

8321

-

1913830

... More
Supply and fixing of HDPE water meter box with locking arrangements to protect the water meter of Class "B Multijet type of size 15 to 32 mm including HDPE box with base dia 300mm x lid dia 200mm x height 250mm with openable lid and the cover is buried below GL with lid flush with GL including earth work excavation for 600mm x 600mm and base sand filling for 100mm thick over which the cover is placed and enclosed by PCC 1:2:4 Using 12-20mm BG jelly for an height of 150mm and refilling wIith excavated earth for balance 100mm height, disposal of excess carth with all lead and lifts etc complete as per drawing enclosed.etc., complete with all lead and lift as directed by the Engineer in charge. .

8321

-

4160500

... More
Supplying and fixing multijet class B inferential type, AMR compatable water meters with IP 68 protection totalizer confirming to IS 779 with its latest amendments of following size to service connections including conveying and fixing of necessary G.I. specials etc.complete, with all lead and lift as directed by the Engineer in charge. . -Do- for 15mm dia

8321

-

13696366

... More
Restoration of Road Providing, laying, spreading and compacting crushed stone aggregates of granite / Trap / basalt of specific sizes to water bound macadam specifications including spreading in uniform thickness, hand packing, rolling with 3 wheeled steel / vibratory roller 8-10 MORTH specification No.404 tonnes in stages to proper grade and camber, applying and brooming requisite type of screening / binding Materials to fill up the interstices of coarse aggregates, watering and compacting to the required density. Complete as per specification.using crushable type such as Moorum or Gravel for Grading - II etc.complete, with all lead and lift as directed by the Engineer in charge. .

11143.9

-

25341228.6

... More
Providing, laying, spreading and compacting crushed stone aggregates of granite / Trap / basalt of specific sizes to water bound macadam specifications including spreading in uniform thickness, hand packing, rolling with 3 wheeled steel / vibratory roller 8-10 MORTH specification No.404 tonnes in stages to proper grade and camber, applying and brooming requisite type of screening / binding Materials to fill up the interstices of coarse aggregates, watering and compacting to the required density. Complete as per specification.using Type B 11.2 MM Grading - III etc.complete, with all lead and lift as directed by the Engineer in charge. .

11143.9

-

26567057.6

... More
Providing and applying tack coat using 80/100 grade bitumen (VG-10) in boiler fitted with spray set distributor at the rate of 0.20 kg per sqm on the existing prepared bituminous surface cleaned with mechanical broom. Complete as per specifications including cost of all labour, HOM of machineries complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

27750

-

333000

... More
Providing and laying bituminous macadam on prepared surface with crushed coarse aggregates as per design mix with formula for base /binding course including loading of aggregates of F.E. loader, hot mixing of stone aggregates and bitumen in hot mix plant, transporting the mixed material in tipper to paver and laying mixed materials with paver finisher to the required level and grade, rolling by smooth wheeled, vibratory & tandem rollers to achieve the desired density, but excluding cost of primer / tack coat & including lead, lift and cost of all materials, labour, HOM complete as per specifications. -do- using 120 TPH capacity Asphalt batch mix plant with sensor paver Gr-1 (80 to 100 mm) with 3.3% VG-30 bitumen etc.complete, with all lead and lift as directed by the Engineer in charge. .

1387.5

-

8812012.5

... More
Providing and Laying 20mm thick mix seal surfacing type 'B' on prepared surface in a single course composed of specified graded crushed aggregates 5.6mm to 13.2mm size 0.027 cum/sqm premixed with bitumen binder at 1.90 kg/sqm of VG-30 (60/70) in a minimix plant 6/10 tone capacity, laying manually and rolling with power roller 8-10 tone excluding cost of tack coat including cost of all materials, labour, HOM complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

27750

-

4800750

... More
Providing and laying in position plain cement concrete of mix 1:2:4 with OPC @ 240Kgs with 20mm and down size graded granite metal coarse aggregates @ 0.878 cum and fine aggregates @ 0.53cum, machine mixed, concrete laid in layers not exceeding 15 cms. Thick, well compacted, in foundation and plinth & cills, including cost of all materials, labour, HOM of machinery, curing complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

7201.72

-

43684193.18

... More
Dismantling of existing structures like culverts, bridges, retaining walls and other structure comprising of masonry, cement concrete, wood work, steel work, including T & P and scaffolding wherever necessary, sorting the dismantled material, disposal of unserviceable material and stacking the serviceable material with all lifts complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. . -do- for Lime/Cement Concrete. By manual means. Lime concrete, cement concrete grade M-10 and below.

81

-

36774

... More
Dismantling of existing structures like culverts, bridges, retaining walls and other structure comprising of masonry, cement concrete, wood work, steel work, including T & P and scaffolding wherever necessary, sorting the dismantled material, disposal of unserviceable material and stacking the serviceable material with all lifts complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. . -do- for Lime/Cement Concrete. By manual means. Cement concrete grade M-15 & m-20.

36

-

20052

... More
Dismantling of existing structures like culverts, bridges, retaining walls and other structure comprising of masonry, cement concrete, wood work, steel work, including T & P and scaffolding wherever necessary, sorting the dismantled material, disposal of unserviceable material and stacking the serviceable material with all lifts complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. -do- for Prestressed / Reinforced Cement concrete grade M-15 & m-20.

36

-

57204

... More
Providing and constructing granite / trap / basalt size stone masonry in foundation with cement mortar 1:6 stone hammered dressed in courses not less than 20 cms high, bond stones at two m. apart in each course including cost of materials, labour, curing complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. --do-- cement mortar 1:6

81

-

380246.4

... More
Providing and laying C.C. 1:1.5:3 proportion for foundation (Screed layer) with 20 mm and down size of approved gradation hard broken granite, trap basalt or with any other approved hard aggregate including cost and conveyance of all materials with an all lead & lifts including plywood / steel form work, machine mixing, laying, tamping, curing etc.complete, with all lead and lift as directed by the Engineer in charge. .

36

-

210729.6

... More
Providing and laying in position reinforced cement concrete of design mix M25 with OPC cement @ 340Kgs, with 20mm and down size graded granite metal coarse aggregates @ 0.70 cum and fine aggregates @ 47cum, with superplastisiser @ 3lts confirming to IS 9103-1999 Reaffirmed -2008, machine mixed, concrete laid in layers not exceeding 15 cms thick, vibrated for all works in ground floor level for roof slabs, staircase, lintels and beams retaining walls, return walls, walls (any thickness) including attached pilasters, columns, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window cills, fillets etc., including cost of all materials cost of reinforcement as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

36

-

240832.8

... More
Providing and removing cantering, shuttering, strutting, propping etc., and removal of form work for flat surface such as suspended floors, roofs, landings, balconies and likes, thickness upto 200mm including cost of all materials, labour complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

480

-

211200

... More
Supply and Labour charges for fabricating TMT steel bars of all sizes for reinforcement of RCC works including cleaning straightening, bending, fabricating, placing in position, tieing as per designs including cost of binding wire hoisting etc., complete with all lead and lift as directed by the Engineer in charge.

4.32

-

275935.68

... More
Restoration of water supply pipeline: Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading and unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (including cost of specials) with jointing of approved type, with all labour, with all lead and lift including encasing the pipe alround to a depth of not less than 15cms with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (contractor will make his own arrangements for procuring water for testing) etc., complete with all lead and lift as directed by the Engineer in charge. -Do- for 63 - 6 Kg/cm2 (Class3)

2100

-

227115

... More
-Do- for 75 - 6 Kg/cm2 (Class3)

4500

-

661500

... More
-Do- for 90 - 6 Kg/cm2 (Class3)

5600

-

1064280

... More
-Do- for 110 - 6 Kg/cm2 (Class3)

3500

-

922425

... More
-Do- for 160 - 6 Kg/cm2 (Class3)

1500

-

685125

... More
Supply, erection and commissioning of suitable pressure rating Board approved make Battery operated full bore Electro-magnetic flowmeter with 2 internal batteries, signal convertor as per the specification complete including 8 mm thick M.S Specials, RCC M20 valve chamber, data, signal and supply cables. The meter shall be supplied with suitable size galvanized bolts and nuts of required numbers of approved brand. (Construction drawing & QAP of the Flowmeter to be got approved from the employer by the contractor) etc., complete with all lead and lift as directed by the Engineer in charge. -Do- 200mm dia 5KSC

1

-

202856

... More
- Do- for 250mm dia - 5 KSC

2

-

449372

... More
-Do- for 300mm dia - 5KSC

1

-

237076

... More
Supplying, installing and commissioning of Pressure monitoring point (PMP) which includes supply, fixing and installation of dual channel data logger within built battery, C/W flexible pressure lose and quick fit connector and digital cable (bare wire) with required accessories, required size of electro fusion saddle and compression elbow consumables etc., complete with all lead and lift as directed by the Engineer in charge.

8

-

640000

... More
Providing & laying reinforced cement concrete pipes NP-2 for culverts including pointing ends & fixing collars with CM 1:2 including cost of all materials, labour, curing complete as per specifications. for encasing HDPE pipes coming across Box drain; C.D; culverts; road crossings etc., complete with all lead and lift as directed by the Engineer in charge. - Do- for 300mm dia

500

-

528000

... More
- Do- for 450mm dia

585

-

842400

... More
Providing & fixing DI dismantling joints etc., complete with all lead and lift as directed by the Engineer in charge. -Do- for DN 150PN 10 ISO 700

5

-

37398.5

... More
-Do- for DN200PN 10 ISO 700

3

-

29364.9

... More
Providing & fixing DI Flanged adopters etc., complete with all lead and lift as directed by the Engineer in charge. -Do- for DN 80 PE 90

80

-

104217.6

... More
-Do- for DN 100 PE 160

15

-

26461.5

... More
- Do- for DN 150 PE 160

12

-

32822.88

... More
- Do- for DN 200 PE 200

6

-

22571.04

... More
Supply and laying Detector Tape for HDPE Pipes & It should detect & identify the buried HDPE PIPE & the tape should be 3" wide, green in colour & should be written lettered message "CAUTION" over it repeating at every 0.5m c/c. Detector tape should be laid 0.6m above the pipe line. It should consist of Aluminium foil encased between two layers of virgin polyethylene plastic etc., complete with all lead and lift as directed by the Engineer in charge.

65428.14

-

697463.97

... More
Refilling pipeline trenches and foundation with selected available earth from trench excavation and foundation including watering, consolidation in layers of 15 cms., thickness including disposing off the surplus earth etc, complete with all lead and lift as directed by the Engineer Incharge.

60716.39

-

6253788.17

... More
Chlorination plant (Gravity feed type) Chlorination plant shall be of 0 - 5 Kg/hr size and have open design. Due to open design more specious arrangement for all parts shall be made which shall be very helpful for easily accessible for control, adjustment and replacement or repairs of parts. Material of Construction: Components required for Chlorination plant shall be as described for individual component as below and shall be erected as per drawing.1) Cylinder connecting pipe both end connect with brass nut and nipple 4 to 5 feet copper pipe both end connect with brass nut and nipple.2) Primary filter made from chemically treated PVDF rod which resist 10 Kg/cm2 pressure. Inside of rod MS pipe of 25 mm shall be fixed and inside MS pipe necessary glass wool shall be filled which will be helpful to arrest all possible chlorine impurities with necessary moisture glass tube and PVC nut.3) Diaphragm type pressure gauge shall be with teflon packing having range 0 - 14 Kg/cm2 / 0 - 200 psi.4) Chlorine control valve / needle valve shall be made from brass and having ISI and explosive test.5) Gas bend pipe shall be of PVC chemically treated 20mm dia pipe to resist 10 Kg/cm2 pressure from primary filter to secondary filter.6) Secondary filter shall be made from chemically treated PVC rod of 63 mm dia which resist moisture by having inside glass wool and having glass non return valve, PVC moisture nut and moisture glass tube.7) Gas bend having glass Non-return valve (PVC NRV bend) to connect secondary filter and mixing chamber made from 20 mm pipe PVC.8) Mixing chamber is made from 90 mm chemically treated PVC pipe, borosilicate glass tube of 75 mm dia, glass orifice tube, rubber O ring and rubber bush.9) PVC T with diaphragm valve for inlet of water and drainage of chlorinated wastage from mixing chamber shall be fixed at bottom of mixing chamber.10) PVC water bend made from chemically treated PVCpipe of 20 mm dia and connect mixing chamber and solutionizer.11) PVC solutionizer made from PVC pipe of 63 mm dia and bottom - outlet connection to join chlorine solution line.12) Panel board from phylum sheet - thickness 7 to 8 mm / size - 36" x 18". etc., complete with all lead and lift as directed by the Engineer in charge.

4

-

134400

... More
Supply, Erection and testing of Chlorine tonner cylindrical in shape including all lead and lift Chlorine toner of 930Kg etc., complete with all lead and lift as directed by the Engineer in charge.

4

-

386400

... More
Filling of cylindrical Chlorine tonner etc., complete with all lead and lift as directed by the Engineer in charge.

4

-

84000

... More
Trenchless technology for laying of distribution pipeline Horizontal Directional Drilling for steel Ducts/ pipes. Installation of steel product pipe by HDD method including preparing and setting up the plant and equipment, preparing new pipe-work material, installing new pipe work and commissioning system or making the system ready for commissioning by HDD operation including all related civil and mechanical works like excavation, shoring/strutting, etc., drilling,stringing, reaming and pulling back new pipe work on the designed bore path alignment, proper disposal of drilling fluid and restoration of site after completion all inclusive as per IndSTT:101-2007:Code of practice for Horizontal Directional Drilling Techinique suiting Indian Conditions Steel pipes above 450 mm and upto 700 mm etc. complete with all lead and lift as directed by the Engineer Incharge -Do- In Hard Soil

50

-

732000

... More
-Do- In Hard Rock

35

-

1645875

... More
-Do- In Mixed Soil

35

-

779660

... More
Manufacturing, providing, transporting, rolling, lowering, laying & Jointing, testing, commissioning of ERW(Electric Resistance Welded)/ SAW(Submerged Arc Welded) MS pipes (Fe-410 grade) conforming to IS 3589-2001with latest amendments incluidng perfect linking and welding of joints to correct position including cost and conveyance of pipes and materials with all lead and lifts, cost of all labour and giving satisfactory hydraulic test as per IS 3589-2001 with latest amendments for test pressure and working pressure both at factory and site etc complete as per detailed specifications. with inside CM 1:1.5 lining of minimum 10 mm thick upto 610 mm OD & minimum 12 mm thick beyond 610 mm OD and out side minimum 25 mm thick coating in CM 1:3 over 50 x 50 mm weld mesh of 13 gauge, including loading and unloading of pipes for the following diameters and specified thickness of plate as noted below, including bailing out of water wherever necessary. (Contractor will make his own arrangement for procuring water for testing) etc. complete with all lead and lift as directed by the Engineer Incharge -Do- for 559 mm dia, 8.70 mm thick

120

-

1080480

... More
Manufacturing, supplying, installing and commissioing of automation system at Tapping point includes the following: GPRS RTU: manufacturing, supply, assembly at site, erection, testing, trail run & commissioning of brand new RTU (Remote Terminal Unit) including reputed make, integrated PLC and display unit (monocolour), keypad for user interface, with 12 digital inputs, atleast 12 Digital relay outputs and 4 analog inputs ( settable as voltage or current analog inputs), atleast 2 serial ports configurable for RS 232 and RS 485, with GPRS modem dual band with RS 232 or RS 485 port with external antenna for GPRS communication, Modbus TCPIP configurable, to be supplied with all necessary lifetime activated licensed programming software and application software in soft copies, including all standard panel accessories like protection fuses, MCBs, interfacing relays for valve operation and other logical operations. RTU instrument and installation-1 set Hardware and networking- 1 set Protective cabinet for RTU- 1 job Network Operator charges for each RTU- 12 months Installation with necessary accessories.- 1 job GPRS RTU at Canal Offtake point & 350 HP pump house.

1

-

92500

... More
Providing , installing & commissioning of Power Backup unit conforming to relavant ISS with latest ammendments including a) 1 KVA inverter Backup with 2 Hrs Backup- 1 Nos. b) Installation and commissioning- 1 job c) Power Wiring MCBs DB Box etc- 1 job d) Power Backup unit

1

-

49000

... More
Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new best efficient Electro Magnetic Bulk Flow water meters to measure both Raw & Pure water having minimum conductivity of 5uS/cm, of approved make or equivalent make & conforming to BIS or ISO standards based on the origin of the goods including the sensors, acceptance / routine tests shall be either conducted by M/S Fluid Control Research Institute, Palghat, Kerala or any of the laboratories approved by the National Accreditation Board for calibration laboratories[NABL] or EEC pattern approval certificates, Further the meters should satisfy following specifications. Accuracy Class & Display: ± 0.5% of measured flow; 2 Line LCD Indicator Converter Type: Remote, field mounted Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz Otput: 4 to 20mA Communication Interface’s 485 (MODBUS RTU) Cable Entry: 1/2"NPT Sensor Size (mm): 350 mm Pressure Rating(Kg/cm2):10 Kg/cm2 Design of the Measuring Sensor:Flanged-DIN Flange Material:CS Sensor Lining: Rubber/ PTFE Electrode Material: SS316 Earthing ring :None. With built-in earthing electrode. Measuring Tube: SS304 Coil Housing: CS Protection Class for Sensor: IP68 Electromagnetic Flow meters 350mm size as per required specifications-1 Nos. Power Wiring-1 job Signal Wiring- 1 job Elctromagnetic flow meter

1

-

498200

... More
Electrical Actuators for existing sluice Gate at Canal Offtake point: Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new Three Phase Rotary Electrical Actuators , Three Phase Electrical Actuator, To operate tapping point Sluice gate, Output Motion- Rotary (Multi Turn), Output Speed -20 RPM effective, Out Put Coupling- Bore & Keyway, Class of Protection- IP 65, Manual Over-ride, Travel Limit Switches-2NO + 2 NC-Potential Free Type. Qty: 2 Nos, Torque Limit Switches-2NO + 2 NC-Potential Free Type. Qty: 2 Nos, Local Position Indicator, Sq. Cage Induction Motor or surface cooled motor of required torque, 1.5 KW/ / 2 HP rating or higher. Supply (V AC), 415 VAC, 50Hz’s. ±10% 50 Hz, ±5 %(combined ±10), Local Control Panel Consists of Contactors , OLR , MCB, Control Transformer , Selector Switch 3 way 3 position (Local /off/Remote), Push Buttons (Open/stop/Close), Respective Indications etc including all necessory accessroies for indirect mouning with couplings with onsite fabrication work and electrical work, necessory three phase wiring and electrical connections for PLC panel including digital inputs, outputs and analog output for feedback. a) Actuator for sluice valve at tapping point for remote operation, monitoing and control.- 1 No b) Installation , commissioning , onsite fabrication , eletrification-1 Job c) Electrical Actuator for Tapping point including power cable Note: Tapping point shall consist of a Remote Terminal unit with Automated gate operations and Realtime flow monitoring. The system should perform remote operations from control centre situated at pump house or any other location. The remote terminal unit shall have PLC based along with GPRS data transmitters to enable communication with the control station. The RTU should be supported with the power back up. The System should be able to communicate with the control centre through GSM/GPRS based Remote terminal unit to record and generate the report of the instantaneous and Cumulative Flow.

1

-

342500

... More
Providing, installing, testing, and of the following as control station for the SCADA automation: supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new satellite Communication system with static IP for control centre including 1.2 m dia Satellite antena/Dish and satellite Router Physical Interfaces One 10/100BaseT Ethernet LAN RJ45 port Satellite & Antenna Specifications Outbound transmission format: DVB-S2 Information Rate: Up to 121 Mbps (Receive or Outbound Channel) Information Rate: Up to 3.2 Mbps (Transmit or Inbound Channel) Symbol Rate (Receive): 1 to 45 Msps (in 1 Msps steps) Symbol Rate (Transmit): 256, 512, 1024, 2048 ksps Encoding (Receive): DVB-S2 LDPC/BCH Encoding (Transmit): Turbocode FEC 1/2, 2/3 and 4/5 Frequency Range: Ka-/Ku-band Modulation (Receive): QPSK, 8PSK, 16APSK Modulation (Transmit): OQPSK Bit Error Rate (Receive): 10-10 or better Bit Error Rate (Transmit): 10-7 or better Antenna: 74 cm, 89 cm, 98 cm, 120 cm, 180 cm,Radio: 1 and 2 watt Ka- or Ku-band Note: satellite communication system will provide means of reliable internet connectivity for control centre for data accumulation and control of all the distribution OHT RTU'S & other RTUs installed at remote locations. Satellite internet connections will consists of all the necessary harwares like dish, setellite communication modem, power and signal wiring etc and will also be installed in a 2.5 m x 2.5 m protective cage for avoiding any interference. a) Instrument and installation-1 set b) Hardware and networking- job c) Large Protective Cage for dish antenna - 1 job d) Network Operator charges (months)- 1 job Satellite Comminication System at Control station

1

-

520000

... More
Control station at Impounding Reservoir housing chamber near Basapur village PLC Panel at Pump house: Manufacturing, Supplying, Installing, and successful commissioning of brand new PLC panel for Pump house Pumphouse should be provided with the instrumentation panel which will be a PLC panel along with software to be programmed for automatic and manual commands,which should integrate with the pumps, valve actuators, installed sensors and hence the Control station panel for data acquisition and control such as current, voltage, power consumption by pumps, outlet flow, valve actuators at pumphouse and other sensors installed. which will be programmed for automated and remote pump operations, controlling valves at pumphouse etc. consisting following. PLC reputed make, operating voltage 24VDC, with USB port for programming, Ethernet port configurable for MODBUS TCP IP, programming and PC communication, with 14digital inputs and 10 digital outputs with add on card for atleast 8 analog inputs for pressure sensor and other nalog signals, RS 232 or RS 485 port with lifetime activated licensed programming software and application software in soft copy, including atleast 7" HMI with 64K coloured TFT display with touch and hard key, including ethernet port, RS485 and configurable RS 232 422 485 port with programming software and application software for user defined display screens. All panel accessories of standard make and as per electrical standard including protection fuses, auto manual key switch, emergency stop switch, and other keys and push buttons for manual operation and auto operationn from PLC and remote operation through SCADA over modbus TCP IP network, housed in IP 65 metal enclosure with atleasted 3 mm thick zinc plated mounting plate, lock and key arrangement for PLC panel, mounting on plinth.a) PLC unit -1 Nos b) Power Wiring- 1 Job c) Control Wiring-1 Job d) Switch Gear Items, SMPS etc- 1 set e) Panel with accessories- 1 Nos f)Panel Wiring- 1 Job g)Analog to Modbus converter- 1 Nos h) Relay Module - 1 Set i) Energy Meter with CT and PT- 1 set j) Modbus TCP IP module- 1 set k) PLC Panel at Pump house

1

-

447500

... More
Power Backup Unit with online ups: Providing 2 KVA power backup unit shall be provided to power Entire PC console panel and installed sensors except valves and pumps to run in absense of power and continue its operation and data accumulation from the distribution OHT's/ installed sensors and hence provide platform to observe and monitor the system in absence of power: a)2KVA Online ups with Batteries for Compouter and PLC Panel Unit- 1 Nos b) Installation and commissioning- 1 Job c)Power Wiring MCBs DB Box etc- 1 Job d) Power Backup Unit for Control station

1

-

154500

... More
Computer Unit:-Supply , delivery at site brand new reputed brand server with all licensed operating software, MS office 2010 or higher with latest application software necessaory for SCADA software, database software my SQL etc complete, hardware configuration as intel Xeon processor latest 2/4 core, 8GB DDR2 RAM, 2 USB ports, Ethernet port, and all other accessories , atleast 22" LCD / LED display with HDMI cable, accessories like key board mouse, 8GB pendrive, laser printer of reputed make, the display unit shall be housed in an industrial grade PC enclosure panel to be supplied with all standard accessories like plint door lock and drawer for keypad and mouse

1

-

168000

... More
SCADA Runtime and Development Key conforming relevant standards with latest amendments

1

-

100000

... More
Design Development of SCADA application software: Development of software for data storage; communication with all instruments; to provide run / stop instruction for all motors / actuators, providing automatic logical operating sequence of all systems as per the instructions of the Engineer in Charge Note: constrol station will consist of centralized control panel for monitoring, control, data accumulation and report generation platfrom hosting SCADA software on server. The control station shall operate on reliable sattellite internet source for reliable connectivity. Control Centre shall be able to support and perform the following functions: • Displaying the entire data of Field Control Unit / RTU such as reservoir level, flow rate and accumulated flow, smart valve status, pressure reading , pump parameters etc in the form of tables and graphical screens • Displaying Field Control Unit's events and alarms and ability to report them utilizing SMS & Email technology. • Display the communication healthiness of field units. • The user shall be able to operate valve from screens • Control centre shall be callable of Downloading data from all FTU / RTU for each reservoir level, flow , pump houses etc. • The Control Center shall have a program to design and display an event report for each reservoir in the water network & pump houses in bulk water supply . • This should be based on the operating periods (schedules) of the valves, theirs flow rates, vs. a nominal allowed flow limits per hydraulic zone. • The Control Center shall have a program for displaying sensors data historical trends. • The Control Center shall have an Off-Line program for the Field Units. • This is in addition to the current run-time unit's program. • The Remote Control Centre SW package shall operate on latest IBM compatible desktop computer with min 21” flat monitors with Operating Systems on Windows XP SP3, Windows 2003 Server SP1.

1

-

180000

... More
Automation at Pumping Station at Housing Chamber Impounding Reservoir & intermediate pump house near intake. Manufacturing, suppying, installing, testing and commissioning of brand new automation system at housing chamber & pump house near intake Including cost of material, installation of sensors, onsite fabrication works, electrical works including all. Including following items: Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new non contact type ultrasonic level sensors of measuring range minimum 10 meters. 2 wire sensors with 4-20 output, process connection M66�2 or flanges, transducer housing PTFE,PU/PC, Process Temperature -40�C ~ +70 �C, Accuracy class �0.5% of full range, installation with necessary bracket and protection cover arrangement and onsite calibration and commissioning, for water tank a) For housing chamber for impouding reservoir - 1 No b) For raw Water Sump-1 No c) Electrical and signal wiring for sensors-2 Job Ultrasonic Level sensors

2

-

97348

... More
Pressure sensors:- Providing Pressure sensors conforing to relavant standards with latest ammendments for pump Outlet Supplying, Installing,commissioning & testing of pressure transmitter CE markd with following technical parameters at Raw Water Pump House and Interfacing with PLC panel including mounting arrangement.The meters should satisfy following specifications. Accuracy Class & Display: � 0.5% of measured flow; 2 Line LCD Indicator Converter Type: Remote, field mounted Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz Otput: 4 to 20mA Cable Entry: 1/2"NPT Pressure Rating(Kg/cm2):16 Kg/cm2

4

-

191328

... More
Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new best efficient Electro Magnetic Bulk Flow water meters to measure both raw & pure water having minimum conductivity of 5uS/cm, of approved make or equivalent make & conforming to BIS or ISO standards based on the origin of the goods including the sensors, acceptance/routine tests shall be either conducted by M/S Fluid Control Research Institute, Palghat, Kerala or any of the laboratories approved by the National Accreditation Board for calibration laboratories[NABL]or EEC pattern approval certificates,Further the meters should satisfy following specifications. Accuracy Class & Display: ± 0.5% of measured flow; 2 Line LCD Indicator Converter Type: Remote, field mounted Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz Otput: 4 to 20mA Communication Interface’s 485 (MODBUS RTU) Cable Entry: 1/2"NPT Sensor Size (mm): 350 mm Pressure Rating(Kg/cm2):10 Kg/cm2 Design of the Measuring Sensor:Flanged-DIN Flange Material:CS Sensor Lining: Rubber/ PTFE Electrode Material: SS316 Earthing ring :None. With built-in earthing electrode. Measuring Tube: SS304 Coil Housing: CS Protection Class for Sensor: IP68 a) 350 mm Flow meter for Raw Water Inlet - 1 No b) Power Wiring- 2 Job c) Signal Wiring- 2 Job

1

-

498200

... More
__do__'300 mm Electromagnetic flow meter for pump Outlet

1

-

460500

... More
Three Phase electrical actuators for sluice valves at pump outlets: Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new Three Phase Rotary Electrical Actuators , Three Phase Electrical Actuator, To operate 200/250 mm Sluice Valve, Output Motion- Rotary (Multi Turn), Output Speed -20 RPM effective, Out Put Coupling- Bore & Keyway, Class of Protection- IP 65, Manual Over-ride, Travel Limit Switches-2NO + 2 NC-Potential Free Type. Qty: 2 Nos, Torque Limit Switches-2NO + 2 NC-Potential Free Type. Qty: 2 Nos, Local Position Indicator, Sq. Cage Induction Motor or surface cooled motor of required torque, 1.5 KW / 2 HP rating or higher . Supply (V AC), 415 VAC, 50Hz’s. ±10% 50 Hz, ±5 %(combined ±10), Local Control Panel Consists of Contactors , OLR , MCB, Control Transformer , Selector Switch 3 way 3 position (Local /off/Remote), Push Buttons (Open/stop/Close), Respective Indications etc including all necessory accessroies for indirect mouning with couplings with onsite fabrication work and electrical work, necessory three phase wiring and electrical connections for PLC panel including digital inputs, outputs and analog output for feedback.

4

-

956000

... More
Providing Instrumentation and other miscellanious pvc conduit , Power, instrumentation Cabling, earthiing work etc complete. Note:- Automation at pumphouse shall include electrical valve actuators, for outlet valves of pump, automation of pumpsets to perform programmed and manual operations through SCADA software, reservoir monitoring for the Sump, Realtime monitoring of the inlet flow and flow from the pump outlet, pressure, pumpsets parameter monitoring for pumpsets and data accumulation from all the sensors installed.

2

-

90000

... More
Control station at WTP in Annigeri town PLC Panel at Pump house: Manufacturing, Supplying, Installing, and successful fommissioning of brand new PLC panel for Pump house Pumphouse should be provided with the instrumentation panel which will be a PLC panel along with software to be programmed for automatic and manual commands,which should integrate with the pumps, valve atuators, installed sensors and hence the Control station panel for data acquisition and control such as current, voltage, power consumption by pumps, outlet flow, valve actuators at pumphouse and other sensors installed. which will be programmed for automated and remote pump operations, controlling valves at pumphouse etc. consisting following. PLC reputed make, operating voltage 24VDC, with USB port for programming, Ethernet port configurable for MODBUS TCP IP, programming and PC communication, with 14digital inputs and 10 digital outputs with add on card for atleast 8 analog inputs for pressure sensor and other nalog signals, RS 232 or RS 485 port with lifetime activated licensed programming software and application software in soft copy, including atleast 7" HMI with 64K coluted TFT display with touch and hard key, including ethernet port, RS485 and configurable RS 232 422 485 port with programming software and application software for user defined display screens. All panel accessories of standard make and as per electrical standard including protection fuses, auto manual key switch, emergency stop switch, and other keys and push buttons for manual operation and auto operationn from PLC and remote operation through SCADA over modbus TCP IP network, housed in IP 65 metal enclosure with atleasted 3 mm thick zinc plated mounting plate, lock and key arrangement for PLC panel, mounting on plinth. a) PLC unit -1 Nos b) Power Wiring- 1 Job c) Control Wiring-1 Job d) Switch Gear Items, SMPS etc- 1 set e) Panel with accessories- 1 Nos f)Panel Wiring- 1 Job g)Analog to Modbus converter- 1 Nos h) Relay Module - 1 Set i) Energy Meter with CT and PT- 1 set j) Modbus TCP IP module- 1 set k) PLC Panel at Pump house

1

-

447500

... More
Power Backup Unit with online ups: Providingt 2 KVA power backup unit shall be provided to power Entire PC console panel and installed sensors except valves and pumps to run in absense of power and continue its operation and data accumulation from the distribution OHT's and hence provide platform to observe and monitor the system in absence of power: a)2KVA Online ups with Batteries for Compouter and PLC Panel Unit- 1 Nos b) Installation and commissioning- 1 Job c)Power Wiring MCBs DB Box etc- 1 Job d) Power Backup Unit for Control station

1

-

154500

... More
Computer Unit:-Supply , delivery at site brand new Reputed brand server with all licensed operating software, MS office 2010 or higher with latest application software necessaory for SCADA software, database software my SQL etc complete, hardware configuration as intel Xeon processor latest 2/4 core, 8GB DDR2 RAM, 2 USB ports, Ethernet port, and all other accessories , atleast 22" LCD / LED display with HDMI cable, accessories like key board mouse, 8GB pendrive, laser printer of reputed make, the display unit shall be housed in an industrial grade PC enclosure panel to be supplied with all standard accessories like plint door lock and drawer for keypad and mouse

1

-

168000

... More
Automation at Pumping Station at WTP Manufacturing, suppying, installing and commisioning of brand new automation system at intermideate pumping station at WTP Including cost of material, installation of sensors, onsite fabrication works, electrical works including all. Including following items: Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new non contact type ultrasonic level sensors of measuring range minimum 10 meters. 2 wire sensors with 4-20 output, process connection M66�2 or flanges, transducer housing PTFE,PU/PC, Process Temperature -40�C ~ +70 �C, Accuracy class �0.5% of full range, installation with necessary bracket and protection cover arrangement and onsite calibration and commissioning, for water tank a) For OHT in WTP - 1 No b) For Pure Water Sump-1 No c) Electrical and signal wiring for sensors-2 Job Ultrasonic Level sensors

2

-

97348

... More
Pressure sensors:- Providing Pressure sensors conforing to relavant standards with latest ammendments for pump Outlet Supplying, Installing,commissioning & testing of pressure transmitter CE markd with following technical parameters at pure Water Pump House and Interfacing with PLC panel including mounting arrangement.The meters should satisfy following specifications. Accuracy Class & Display: � 0.5% of measured flow; 2 Line LCD Indicator Converter Type: Remote, field mounted Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz Otput: 4 to 20mA Cable Entry: 1/2"NPT Pressure Rating(Kg/cm2):16 Kg/cm2

2

-

95664

... More
Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new best efficient Electro Magnetic Bulk Flow water meters to measure both raw & pure water having minimum conductivity of 5uS/cm, of approved make or equivalent make & conforming to BIS or ISO standards based on the origin of the goods including the sensors, acceptance/routine tests shall be either conducted by M/S Fluid Control Research Institute, Palghat, Kerala or any of the laboratories approved by the National Accreditation Board for calibration laboratories[NABL]or EEC pattern approval certificates,Further the meters should satisfy following specifications. Accuracy Class & Display: ± 0.5% of measured flow; 2 Line LCD Indicator Converter Type: Remote, field mounted Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz Otput: 4 to 20mA Communication Interface’s 485 (MODBUS RTU) Cable Entry: 1/2"NPT Sensor Size (mm): 350 mm Pressure Rating(Kg/cm2):10 Kg/cm2 Design of the Measuring Sensor:Flanged-DIN Flange Material:CS Sensor Lining: Rubber/ PTFE Electrode Material: SS316 Earthing ring :None. With built-in earthing electrode. Measuring Tube: SS304 Coil Housing: CS Protection Class for Sensor: IP68 a) 350 mm Flow meter for Raw Water Inlet - 1 No b) Power Wiring- 2 Job c) Signal Wiring- 2 Job

1

-

498200

... More
__do__ '300 mm Electromagnetic flow meter for pump Outlet

1

-

460500

... More
Three Phase electrical actuators for sluice valves at pump outlets: Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new Three Phase Rotary Electrical Actuators , Three Phase Electrical Actuator, To operate existing 200/250 mm Sluice Valve, Output Motion- Rotary (Multi Turn), Output Speed -20 RPM effective, Out Put Coupling- Bore & Keyway, Class of Protection- IP 65, Manual Over-ride, Travel Limit Switches-2NO + 2 NC-Potential Free Type. Qty: 2 Nos, Torque Limit Switches-2NO + 2 NC-Potential Free Type. Qty: 2 Nos, Local Position Indicator, Sq. Cage Induction Motor or surface cooled motor of required torque, 1.5 KW / 2 HP rating. Supply (V AC), 415 VAC, 50Hz’s. ±10% 50 Hz, ±5 %(combined ±10), Local Control Panel Consists of Contactors , OLR , MCB, Control Transformer , Selector Switch 3 way 3 position (Local /off/Remote), Push Buttons (Open/stop/Close), Respective Indications etc including all necessory accessroies for indirect mouning with couplings with onsite fabrication work and electrical work, necessory three phase wiring and electrical connections for PLC panel including digital inputs, outputs and analog output for feedback.

2

-

478000

... More
Providing Instrumentation and other miscellaneous Pvc Conduit, cable tarys , Power , instrumentation Cabling, earthiing work : Note:- Automation at pumphouse shall include electrical valve actuators, for outlet valves of pump, automation of pumpsets to perform programmed and manual operations through SCADA software, reservoir monitoring for the Sump, Realtime monitoring of the inlet flow and flow from the pump outlet, pressure monitoring, pumpsets parameters for pumpsets and data accumulation from all the sensors installed.

1

-

45000

... More
Automation for Distribution OHT's at Annigeri town (4 Nos of OHT's) Reservoir management system for distribution OHTs. : Design, Size, Supply and Commissioning of Reservoir Management Systems (RMS) to enable to avoid the overflow of distribution OHTs and for uniform distribution of water to reservoirs. irrespective of its location and distance from the source of supply. Also system should be enable to record, monitoring and control of the instantaneous and cumulative flow Delivered to the Reservoirs. Reservoir management system shall run on external power supply but should be compatable to upgrate and run the same on solar based system. with power backup.The system for 4 Nos of distribution OHT's shall consits of following:

1

-

45000

... More
Manufacturing, supply, assembly at site, erection, testing, trail run & commissioning of brand new RTU (Remote Terminal Unit) including reputed brand, integrated PLC and display unit (monocolour), keypad for user interface, with 12 digital inputs, atleast 6 Digital relay outputs and 3 analog inputs ( settable as voltage or current analog inputs), atleast 2 serial ports configurable for RS 232 and RS 485, with GPRS modem dual band with RS 232 or RS 485 port with external antenna for GPRS communication, Modbus TCPIP configurable, to be supplied with all necessary lifetime activated licensed programming software and application software in soft copies, including all standard panel accessories like protection fuses, MCBs, interfacing relays for valve operation and other logical operations. Note : Remote terminal unit shall send data from all the sensors and valve actuators installed at distribution network reservoirs to control centre hosting scada software which will also have local control which can be programmed for necessary operations and hence can be remotely operated from SCADA from control station. Field controller unit shall have Logic board incorporating microcontroller / microprocessor and data storage components. To prevent reservoir overflow filed units must be able to close the valve during high level. Field Unit shall be with I/O port required for on-site sensor connection. I/O boards may be expanded/ replaced on-site. These may be inputs such as water meters, reservoir level, pressure meters, or general digital inputs, or outputs such as valves actuatorsetc. a) RTU instrument and installation- 4 Set b) Hardware and networking- 4 Set c) Prodective canbinet for RTU- 3 jobs d) Network Operator charges for 1 year for each RTU- 4 Jobs e) Installation with necessary accessories.- 4 Jobs GPRS RTU for Distribution OHT'S

4

-

370000

... More
Providing and installation of Power Backups for each RTU conforming to relavant standards with latest ammendments includes a) 1 KVA inverter Backup with 4 Hrs Backup- 3 Nos b) Installation and commissioning- 3 Nos c) Power Wiring MCBs DB Box etc- 3 Job Power Backup for Distribution OHT's with protective cabinet / cover .

4

-

344000

... More
Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new non contact type ultrasonic level sensors of measuring range minimum 10 meters. 2 wire sensors with 4-20 output, process connection M66�2 or flanges, transducer housing PTFE,PU/PC, Process Temperature -40�C ~ +70 �C, Accuracy class �0.5% of full range, installation with necessary bracket and protection cover arrangement and onsite calibration and commissioning, for water tank a) Ultrasonic Level Sesor for OTH- 4 Nos b) installation commissioning , eletrical wiring etc-4 Jobs c) Level sensors for OHT's

4

-

246400

... More
Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new best efficient Electro Magnetic Bulk Flow water meters to measure both raw & pure water having minimum conductivity of 5uS/cm, of approved make or equivalent make & conforming to BIS or ISO standards based on the origin of the goods including the sensors, acceptance/routine tests shall be either conducted by M/S Fluid Control Research Institute, Palghat, Kerala or any of the laboratories approved by the National Accreditation Board for calibration laboratories[NABL]or EEC pattern approval certificates,Further the meters should satisfy following specifications. Accuracy Class & Display: ± 0.5% of measured flow; 2 Line LCD Indicator Converter Type: Remote, field mounted Power Supply: Universal Power Supply 85 to 265VAC@45 to 65 Hz Otput: 4 to 20mA Communication Interface’s 485 (MODBUS RTU) Cable Entry: 1/2"NPT Sensor Size (mm): 200 Pressure Rating(Kg/cm2):10 Kg/cm2 Design of the Measuring Sensor:Flanged-DIN Flange Material:CS Sensor Lining: Rubber/ PTFE Electrode Material: SS316 Earthing ring :None. With built-in earthing electrode. Measuring Tube: SS304 Coil Housing: CS Protection Class for Sensor: IP68 a) Installation commissioning along with necessary fabrication works, mechanical fittings etc including all- 4 Jobs b) Power Wiring-4 Jobs c) Signal Wiring-4 JobsFlow meter for 200 mm dia Inlets of OHT's- 4 Nos

4

-

1300000

... More
__do__ 'Fow meters for 200 mm dia outlet of OHT'S-4 Nos

4

-

1300000

... More
Electrical Actuators with butterfly/globe valves for inlet (3 Nos) and outlet (3 Nos) valves valves of Distribution Reservoirs: Manufacture, supply & delivery, assembly at site, erection, testing, trail run & commissioning of brand new 200mm Motorized Butterfly/globe valve with manual override, single phase / 3 phase electrical actuators with butterfly/Globe valve whichever feasible for specific application, valve used for fixing motoriezed actuator should be from a board approved manufacturer, with fan cooled/surface cooled 0.5/1 HP or higher induction motor, auto, manual and hand wheel operated, with position indicator with designed torque suitable for valve, including all necessary accessories for indirect mounting with couplings with onsite fabrication work and electrical work, necessary single phase wiring and electrical connections for RTU panel including digital inputs, outputs and analog output for feedback. Local Control Panel Consists of Contactors , OLR , MCB, Control Transformer , Selector Switch 3 way 3 position (Local /off/Remote), Push Buttons (Open/stop/Close ) , Respective Indications etc a) Actuators with butterfly/Globe valves for Inlet and outles of OHTs for remote operation of valves from control station.- 200 mm Dia c) Installation , commissioning , onsite fabrication , eletrification etc- 8 Jobs Electrical Actuators for Distribution Reservoirs Note: The system should attain following Objectives. a) The System should be capable to achieve the Uniform Distribution of Water to all thereservoirs/Sumps in the Network irrespective its Elevation and Distance from the Source of Supply. b) The System shall trigger sms allerts to the concerned persons regarding water tank levels and should be capable to avoid the overflow of Reservoirs in the Networks. c) The system should be user locally programmable and operate remotely and isolte itself completely in absense of communication with the control centre. d) The System should be able to communicate with the control centre through GSM/GPRS based Remote terminal unit to record and generate the report of the instantaneous and Cumulative Flow Delivered to Every Reservoirs/Sumps in the Network. e) System should consist of power backup to be connected in absense of external electrical energy for a period of 4 hrs minimum. Compatable with solar system. Automation at distribution reservoir should be able to control and monitor inlet and outlet valves, its status, cummulative flow readings with flow meters, reservoir level and stock. Remote monitoring of entire system from control centre should be possible. The Remote terminal unit should be kept inside a protecive cover box suitable for outdoor installations.

8

-

1744000

... More
Providing, Installation, onsite commissioning of Online Chlorine analyzer Compatable with SCADA for realtime monitoring of Residual Chlorine at WTP. Chlorine analyzer should be able to communicate and Integrate with the Remote Terminal Unit. With Following specifications : Measurement Range : 0 to 10 ppm Lower Limit of Detection (LOD) : 30 ppb (0.03 ppm) or lower Limit of Quantitation (LOQ) : 90 ppb (0.09 ppm) or lower Resolution : 0.001 ppm (1 ppb) Accuracy : Free Chlorine: �3% of the reference test** (DPD) at constant pH less than 7.2 (�0.2 pH unit) �10% of the reference test** (DPD) at stable pH less than 8.5 (�0.5 pH unit from the pH at calibration) Total Chlorine: �10% of the reference test** (DPD) at stable pH less than 8.5 (�0.5 pH unit from the pH at calibration) �20% of the reference test** (DPD) at stable pH greater than 8.5 Repeatability : 30 ppb or 3%, whichever is greater Response Time : Free Chlorine: 140 seconds or less for 90% change (T90) at a stable temperature and pH Total Chlorine: 100 seconds or less for 90% change (T90) at a stable temperature and pH Sampling Time : Continuous Pressure Limit : 0.5 bar, no pressure impulses and/or vibrations Sample pH : 4-9 Sample Temperature (compensated for fluctuations) : 5 to 45�C (41 to 113�F) Power Requirements : 12 Vdc, 30 mA maximum (supplied by controller)

1

-

200145

... More
ONLINE WATER QUALITY MONITORING SYSTEM at WTP: Online Turbidity Meter Supply install, commissioning and integration of Online Turbidity Meter for pure water quality monitoring with SCADA system. Meter shall be installed at Outlet of pure water of WTP to monitor turbidity of pure water with Necessary Communication interface to integrate with PLC Panel . a) Cabling for communication with PLC and SCADA System d) Other acessories ,Power Wiring & Signal Wiring etc complete.

1

-

332560

... More
Digital Photometer (Battery Opertaed) :Supply of Digital portable battery operated photometer for onsite assement of residual chlorine at distribution reservoirs / on field. Measuring range 0 - 5ppm ; OT / DPD based analysis with supply of test consumables required for operation for the same .

1

-

47525

... More
Online pH Meter:Supply install, commissioning and integration of online pH meter for monitoring at WTP . Meter shall be connected to the PLC and SCADA system for real time monitoring and data accumulation from the conrol room .pH should have automatic temp compensastion and auto calibration , including other acessories including Power Wiring & Signal Wiring etc complete .

1

-

152589

... More
PART -B Operation & Maintenance for a period of 5 years (60 months) including one year DLP of the Water Supply System. office establishment and procurements of equipments required for Operation & Maintenance for a period of 60 months of the proposed Water Supply System of Annigeri Town OFFICE ESTABLISHMENT & EQUIPMENTS Supplying of Board approved make Handheld machines including application software, High speed processor, batttery back up, AC adapter etc complete with all lead and lift as directed by the Engineer-in-charge

4

-

172000

... More
Supplying of Board approved make computer-Desktop with Preloaded operating system Configuration: Intel core i7 operating system : Microsoft Windows 10 or any other recent version of operating system. Detail Configuration : Intel Core i7, 3.2 GHz, 6 MB L3 Cache Chipset : Intel 6 Series or better on OEM Motherboard, Memory : 4 GB 2133 MHz RAM with 64 GB Extendibility, Hard Disk : 500 GB 7200rpm ATA HDD, Monitor 47 cm 18.5'' larger TFT, Standard 104 keys Keyboard, mouse : Optical with sub Interface Mouse, Ports : 6 USB Ports, 1 serial, front sub & audio, mike panel, Cabinet : Mini Tower, DVD ROM : 8x or Better DVD ROM, Network : 10/100/1000 on Board integrated Network Port, Operating system : Windows 10 Professional and certification of authentication Mcafee Antivirus (Latest Version) for One Year License With Media, Ms Office 2007 Standard INIDC Molp w/o Media (non Academic) etc complete with all lead and lift as directed by the Engineer-in-charge

1

-

55950

... More
Supplying of Board approved make Lap-Top HP Eilter Book 1040 g2 intel i-5-5300, 8GB, 256 GB, Win 10 Pro 14 full HD with touch Mobile Workstation Genuine windows 10 versions of Free Dos, Designed to meet the military standard Mil-Std-810G for vibration, dust, altitude and high and low temperature operation, Workstation - Caliber discrete graphics, AMD FirePro M 5850, Nvidia quadro 1000 M, or Nvida quadro 2000M, Whitescreen 14 Inch. diagonal LED - backlit display, HD + wide viewing angle FHD wide viewing angle or FHD ultra vide viewing angle with HP Dream Colour, Up to four SODIMMs on Configurations with quad core processor, for system memory upto 32 GB. 1. AMD Eyefinity Technology for multi-monitor support. 2. Displayport for high resolution support.3. SRS premium sound optimized for high fidelity audio. 3. 5th Generation Intel Core i5 processors. 4. Intel core i5 with vPro Technology (Optional). 5. Flexible wireless connectivity options. Optional integrated HP has 2340 HSPA + Mobile Broadband Module connects to both HSPA and HSPA + (UMTS) networks and provides GPS functionality Optional integrated HP up 2340 EV-DO/HSPA Mobile Broadband Module (Bogi 3000) etc complete with all lead and lift as directed by the Engineer-in-charge

1

-

76237

... More
Supplying & installing HP Laser Jet printer Pro MFP M128fnpreinstalled introdusory HP Laserjet Black Cartidge 700 pages installation guide, Print speed black (normal A4) - 20ppm, first page out black(A4, ready) - as fast as 7 sec, print quality black (best)-up to 600x600x2dpi (1200 dpi effective output), print technology-laser, duty cycle(monthly, A4)- up to 8000 pages, Network capability-yes, recommended monthly page volume-250 to 2000, memory std.-128MB, memory max.-128 MB, processor speed-266 MHz, print languages-host based printing etc complete with all lead and lift as directed by the Engineer-in-charge

1

-

21100

... More
Supplying and establishing office room of 150 Sqm including partition cubicles of Board approved make wooden panels/ laminates with drawers of three workstations, revolving chairs - 3 Nos, Office chairs- 20 No's, Steel Tables- 4 No's, Almars -3No's etc complete with all lead and lift as directed by the Engineer-in-charge

1

-

198026

... More
Supplying Smart phone dual sim 4G mobile handsets of Board approved make including android system, 8GB internal memory expandable upto 32 GB, GPRS, WiFi, EDGE, Blue tooth, camera, Li-Ion 2300 mAh battery and sim card etc complete with all lead and lift as directed by the Engineer-in-charge

6

-

31794

... More
Butt fusion Welding Machine: Supplying delivery and testing at site (Fusion Provide/George Fisher/Equivalent approved makes of Butt-fusion welding machine for butt welding of HDPE pipes & fittings with a diameter range from 75 mm to 315 mm dia as under: Material PP,PE 80, PVDF, PE 100, Pipe diameter range Outside- � = 75-315 mm, Planer- Motor Monophase-alternating current-motor Power 1050 Watt,Voltage 230 V (� 10% ), Current : 4 , 0 A Frequency 50 Hz (� 10% ), RPM n2 of planer approx. 60 revs/min, Elements: Switch on / off with fixing device Connecting cable and plug with earthling contact, Heating element-Power 2500 Watt, Voltage 230 V (� 10% ),Current : 11, 7 A (� 10% ), Frequency 50 Hz , Outside- � 350 mm Surface Antistick -coated, Elements: Electronic temperature control, Control lamps, switch on / off Connecting cable and plug with earthling contact, Hydraulic aggregate-Power 315Watt, Voltage 230 V (� 10% ), current : 1 , 5 A, Frequency 50 Hz , Hydraulic oil tank, Electromotor and pump-RPM 2700 (revs/min), Max.pressure of pump approx. 120 bar, Working pressure 100 bar,Volume velocity 1, 9 I/min, Basic frame-Material frame: Machine steel, Material reduction inserts : Aluminium, Cylinder - � 40 mm, Piston rod - � 35 mm Length of stroke of cylinder : 150 mm max. force (per cylinder): (F= P* A) 2945 N (at 100 bar) Velocity of piston rod: 6 , 5 cm/s 1.6 Equipment and accessories : The following accessories are part of the first delivery : 1 x Socket wrench size 27 1 each Hexagonal socket screw short size 3; 6; 7; 8 1 each Hexagonal socket screw with T-geip size 4; 5 optional Reduction inserts, roller brackets for the pipes etc complete with all lead and lift as directed by the Engineer-in-charge

1

-

350000

... More
Providing distribution pipeline and House Service Connections within Annigeri town during O&M period : Cutting road surface for pipeline trenches and disposing off the excavated stuff with all lead and lift as directed including barricading, danger ighting etc., in the following classifications etc, complete with all lead and lift as directed by the Engineer Incharge. - Do- for Cutting Macadam Road

266.4

-

92174.4

... More
- Do- for Cutting Asphalt Road

42.19

-

26790.65

... More
- Do- for Cutting Concrete Road

153.9

-

196068.6

... More
Earth work excavation for pipeline trenches (except building works) including depositing on bank with all lead including shoring, strutting, barricading, danger lighting and using sight rails and boning rods at every 100 metres wherever necessary as directed in the following strata.In all soils mixed with boulders of upto 10cms. size and exclusive of disintegrated rock etc, complete with all lead and lift as directed by the Engineer Incharge.

1018

-

266716

... More
-do- In disintegrated rock, soft rock, soft shale and medium hard rock comprising of Lime stone, sand stone, hard shale, schiest, fissured rock wihtout resorting to blasting etc, complete with all lead and lift as directed by the Engineer Incharge.

364

-

215488

... More
-do- in Hard Rock by Chisteling etc, complete with all lead and lift as directed by the Engineer Incharge.

73

-

174105

... More
Providing Murrum / Gravel Bedding for the pipeline trenches including watering and consolidation by punners etc., complete with all lead and lift (In Black Cotton soil and rock reaches) etc., complete with all lead and lift as directed by the Engineer In-

213.12

-

55198.08

... More
Supplying HDPE pipes conforming to IS 4984:1995 with latest amendments and conveying to work site including loading and unloading at both destination and rolling, lowering into trenches, laying true to line and jointing of pipes and specials by electrofusion welding, including encasing the pipe around to a depth not less than 15cms with soft gravel or selected earth available from the excavation etc., complete giving hydraulic test as per relevant ISS with all lead and lift including testing and commissioning. The rate is exclusive of required specials and fittings etc.,complete (Contractor will make his own arrangement for procuring water for testing) HDPE Grade-PE-100,PN-8 etc, complete with all lead and lift as directed by the Engineer Incharge. - Do- for 75mm dia

1218

-

239154.3

... More
- Do- for 90mm dia

34

-

8889.3

... More
-Do- for 110mm dia

371

-

135173.85

... More
-Do- for 160mm dia

49

-

34831.65

... More
-Do- for 200mm dia

104

-

111930

... More
Supply and delivery of Resilient seated soft sealing DI Sluice valves with body bonnet of ductile iron of Grade GGG40, wedge fully rubber lined with EPDM and seals of NBR and the valves should be of vaccum tight and 100% leak proof with face dimensions as per BS 5163-89/IS 14846-2000/DIN/3202 F4/f5. The stem sealing should be with toroidal sealing rings (Minimum 2 O-rings) All the valves should be with Electrostatic powder coating both inside and outside with pocket less body passage. The valves shall be supplied with suitable size galvanized bolts and nuts of required numbers etc, complete with all lead and lift as directed by the Engineer Incharge. . D.I. Sluice Valves PN 1.6. -Do- 80mm dia PN 1.6

10

-

85520

... More
-Do- for 100mm dia PN 1.6

2

-

21676

... More
-Do- for 150mm dia PN 1.6

2

-

37930

... More
-Do- for 200mm dia PN 1.6

1

-

30082

... More
Refilling pipeline trenches and foundation with selected available earth from trench excavation and foundation including watering, consolidation in layers of 15 cms., thickness including disposing off the surplus earth etc, complete with all lead and lift as directed by the Engineer Incharge.

1497

-

154191

... More
Supply and installation of water connections to individual houses upto water meter point (which shall be fixed about one meter from customer boundary) and includes civil works like Earthwork excavation for the pipeline trenches for laying of MDPE/GI pipes for the house connections in all types of soils , disintegrated rock, soft rock, hard rock, including cutting of any road using machine cutter, crossing drains, compound, cutting any surfaces along the pipelines such as tiles/floor/concrete/ or any other surfaces using machine cutter, boring the wall surfaces comprising of BBM or SSM for conveying the pipelines to customer property, restoring the damaged portions inside or outside the property premises, refilling etc. complete. Supply and laying of MDPE PE-80, PN 12.5 pipes with specials such as Electrofusion tapping Tee or saddles of Virgin Compounded PE 100 material, Black colour of pressure rating PN 16 /SDR 11 or higher grade of approved make conforming to standard specifications with brass cutter, flow regulator, water tight cap with "O" ring, long spigot, cutting edges for making hole tapping suitable to HDPE distribution mains by electro fusion welding as per BS EN 12201-3 & EN 1555-3 Standards. The Product should be tested to comply with BS 6920 for drinking water service in WRC NSF, UK and DVGW certificate. Germany. Tapping Tee or Saddles with coupler and compression fittings with cost of Gl pipes, all specials such as GI tee, Gl elbow GI coupler, stopper etc, and brass or SS tap as shown in Fig. no. 2.1, 2.2 & 2.3 for the following diameters etc, complete with all lead and lift as directed by the Engineer Incharge. -Do- for 15mm dia

500

-

2907000

... More
Supply of Gunmetal Ball valve of non-rising stem, screwed in bonnet, inside screw, integral seats, screwed female ends to IS: 554/BS 21/IsO 7, unbreakable sheet metal Hand wheel conforming to IS:778 Class-1 including provision of re-packing under pressure etc, complete with all lead and lift as directed by the Engineer Incharge.

500

-

95000

... More
Providing 50 mm Dia HDPE Sleeve pipe with allied accessories at ferrule point of HSC to assist in regulating flow with allen key etc, complete with all lead and lift as directed by the Engineer Incharge.

500

-

115000

... More
Supply and fixing of HDPE water meter box with locking arrangements to protect the water meter of Class "B Multijet type of size 15 to 32 mm including HDPE box with base dia 300mm x lid dia 200mm x height 250mm with openable lid and the cover is buried below GL with lid flush with GL including earth work excavation for 600mm x 600mm and base sand filling for 100mm thick over which the cover is placed and enclosed by PCC 1:2:4 Using 12-20mm BG jelly for an height of 150mm and refilling wIith excavated earth for balance 100mm height, disposal of excess carth with all lead and lifts etc complete as per drawing enclosed etc, complete with all lead and lift as directed by the Engineer Incharge.

500

-

250000

... More
Supplying and fixing multijet class B inferential type, AMR compatable water meters with IP 68 protection totalizer confirming to IS 779 with its latest amendments of following size to service connections including conveying and fixing of necessary G.I. specials etc, complete with all lead and lift as directed by the Engineer Incharge. -Do- for 15mm dia

500

-

823000

... More
Restoration of Road Providing, laying, spreading and compacting crushed stone aggregates of granite / Trap / basalt of specific sizes to water bound macadam specifications including spreading in uniform thickness, hand packing, rolling with 3 wheeled steel / vibratory roller 8-10 MORTH specification No.404 tonnes in stages to proper grade and camber, applying and brooming requisite type of screening / binding Materials to fill up the interstices of coarse aggregates, watering and compacting to the required density. Complete as per specification.using crushable type such as Moorum or Gravel for Grading - II etc.complete, with all lead and lift as directed by the Engineer in charge. .

189.45

-

430809.3

... More
Providing, laying, spreading and compacting crushed stone aggregates of granite / Trap / basalt of specific sizes to water bound macadam specifications including spreading in uniform thickness, hand packing, rolling with 3 wheeled steel / vibratory roller 8-10 MORTH specification No.404 tonnes in stages to proper grade and camber, applying and brooming requisite type of screening / binding Materials to fill up the interstices of coarse aggregates, watering and compacting to the required density. Complete as per specification.using Type B 11.2 MM Grading - III etc.complete, with all lead and lift as directed by the Engineer in charge. .

189.45

-

451648.8

... More
Providing and applying tack coat using 80/100 grade bitumen (VG-10) in boiler fitted with spray set distributor at the rate of 0.20 kg per sqm on the existing prepared bituminous surface cleaned with mechanical broom. Complete as per specifications including cost of all labour, HOM of machineries complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

562.5

-

6750

... More
Providing and laying bituminous macadam on prepared surface with crushed coarse aggregates as per design mix with formula for base /binding course including loading of aggregates of F.E. loader, hot mixing of stone aggregates and bitumen in hot mix plant, transporting the mixed material in tipper to paver and laying mixed materials with paver finisher to the required level and grade, rolling by smooth wheeled, vibratory & tandem rollers to achieve the desired density, but excluding cost of primer / tack coat & including lead, lift and cost of all materials, labour, HOM complete as per specifications. -do- using 120 TPH capacity Asphalt batch mix plant with sensor paver Gr-1 (80 to 100 mm) with 3.3% VG-30 bitumen etc.complete, with all lead and lift as directed by the Engineer in charge. .

28.13

-

178653.63

... More
Providing and Laying 20mm thick mix seal surfacing type 'B' on prepared surface in a single course composed of specified graded crushed aggregates 5.6mm to 13.2mm size 0.027 cum/sqm premixed with bitumen binder at 1.90 kg/sqm of VG-30 (60/70) in a minimix plant 6/10 tone capacity, laying manually and rolling with power roller 8-10 tone excluding cost of tack coat including cost of all materials, labour, HOM complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

562.5

-

97312.5

... More
Providing and laying in position plain cement concrete of mix 1:2:4 with OPC @ 240Kgs with 20mm and down size graded granite metal coarse aggregates @ 0.878 cum and fine aggregates @ 0.53cum, machine mixed, concrete laid in layers not exceeding 15 cms. Thick, well compacted, in foundation and plinth & cills, including cost of all materials, labour, HOM of machinery, curing complete as per specifications etc.complete, with all lead and lift as directed by the Engineer in charge. .

153.9

-

933526.62

... More
Operation & Maintenance during the 1st year ( ie., defects liability period) of water supply disribution system to Annigeri town which includes pressure and quality management using specialised techniques & personnel, billing etc., including transportation, man power, etc., The minimum supervisory staff with 3 years of experience shall include; Site Engineer (Diploma)(Civil)-1 No., Data Entry Operator-1 No, water analyst (BSc. Graduate)-1no, Sample taker (SSLC) - 1 Nos. Watchman-1No. Helper-2No., Fitter-1 No.Waterman(Valveman)-1Nos., meter reader-3 Nos, The administrative staff shall include minimum 1 No. of supervisory Graduate, House keeping & security arrangements for the offices established by the contractor shall include a minimum of 1 No House keeping and Literatory-1No.,Communication system includes rent and usage charges of Mobiles -3 Nos, The material cost in case of breakdown & repairs within the defect liability period shall be borne by the contractor. The rate includes Internet charges & office stationaries for the office established by the contractor at Annigeri town, Supply of chlorine gas-0.5 Ton, information, education and comunnication(IEC), hiring of vehicles-1No. of Jeep or Car or Trax 1 No, Internet charges etc, with all lead and lift as directed by the Engineer-in-charge.

12

-

4337364

... More
Operation & Maintenance during the 2nd year of water supply disribution system to Annigeri town which includes pressure and quality management using specialised techniques & personnel, billing etc., including transportation, man power, etc., The minimum supervisory staff with 3 years of experience shall include; Site Engineer (Diploma)(Civil)-1 No., Data Entry Operator-1 No, water analyst (BSc. Graduate)-1no, Sample taker (SSLC) - 1 Nos. Watchman-1No. Helper-2No., Fitter-2 No.Waterman(Valveman)-1Nos., meter reader-3 Nos, The administrative staff shall include minimum 1 No. of supervisory Graduate, House keeping & security arrangements for the offices established by the contractor shall include a minimum of 1 No House keeping and Literatory-1No.,Communication system includes rent and usage charges of Mobiles -3 Nos, The rate includes Internet charges & office stationaries for the office established by the contractor at Honnavar town, Supply of chlorine gas-1.0 Ton, PAC powder-1.0Ton information, education and comunnication(IEC), hiring of vehicles-1No. of TATA ace or equivalent make vehicles and Jeep or Car 1 No, Internet charges etc, with all lead and lift as directed by the Engineer-in-charge.

12

-

4890312

... More
Operation & Maintenance during the 3rd year of water supply disribution system to Annigeri town which includes pressure and quality management using specialised techniques & personnel, billing etc., including transportation, man power, etc., The minimum supervisory staff with 3 years of experience shall include; Site Engineer (Diploma)(Civil)-1 No.,Data Entry Operator-1 No, water analyst (BSc. Graduate)-1no, Sample taker (SSLC) - 1 Nos. Watchman-1No. Helper-2No., Fitter-2 No.Waterman(Valveman)-1Nos., meter reader-3 Nos, The administrative staff shall include minimum 1 No. of supervisory Graduate, House keeping & security arrangements for the offices established by the contractor shall include a minimum of 1 No House keeping and Literatory-1No.,Communication system includes rent and usage charges of Mobiles -3 Nos, The rate includes Internet charges & office stationaries for the office established by the contractor at Honnavar town, Supply of chlorine gas-1.0 Ton, PAC powder-1.0Ton information, education and comunnication(IEC), hiring of vehicles-1No. of TATA ace or equivalent make vehicles and Jeep or Car 1 No, Internet charges etc, with all lead and lift as directed by the Engineer-in-charge.

12

-

5277876

... More
Operation & Maintenance during the 4th year of water supply disribution system to Annigeri town which includes pressure and quality management using specialised techniques & personnel, billing etc., including transportation, man power, etc., The minimum supervisory staff with 3 years of experience shall include; Site Engineer (Diploma)(Civil)-1 No., Data Entry Operator-1 No, water analyst (BSc. Graduate)-1no, Sample taker (SSLC) - 1 Nos. Watchman-1No. Helper-2No., Fitter-2 No.Waterman(Valveman)-1Nos., meter reader-3 Nos, The administrative staff shall include minimum 1 No. of supervisory Graduate, House keeping & security arrangements for the offices established by the contractor shall include a minimum of 1 No House keeping and Literatory-1No.,Communication system includes rent and usage charges of Mobiles -3 Nos, The rate includes Internet charges & office stationaries for the office established by the contractor at Honnavar town, Supply of chlorine gas-1.0 Ton, PAC powder-1.0Ton information, education and comunnication(IEC), hiring of vehicles-1No. of TATA ace or equivalent make vehicles and Jeep or Car 1 No, Internet charges etc, with all lead and lift as directed by the Engineer-in-charge.

12

-

5702868

... More
Operation & Maintenance during the 5th year of water supply disribution system to Annigeri town which includes pressure and quality management using specialised techniques & personnel, billing etc., including transportation, man power, etc., The minimum supervisory staff with 3 years of experience shall include; Site Engineer (Diploma)(Civil)-1 No., Data Entry Operator-1 No, water analyst (BSc. Graduate)-1no, Sample taker (SSLC) - 1 Nos. Watchman-1No. Helper-2No., Fitter-2 No.Waterman(Valveman)-1Nos., meter reader-3 Nos, The administrative staff shall include minimum 1 No. of supervisory Graduate, House keeping & security arrangements for the offices established by the contractor shall include a minimum of 1 No House keeping and Literatory-1No.,Communication system includes rent and usage charges of Mobiles -3 Nos, The rate includes Internet charges & office stationaries for the office established by the contractor at Honnavar town, Supply of chlorine gas-1.0 Ton, PAC powder-1.0Ton information, education and comunnication(IEC), hiring of vehicles-1No. of TATA ace or equivalent make vehicles and Jeep or Car 1 No, Internet charges etc, with all lead and lift as directed by the Engineer-in-charge.

12

-

6168804

... More
Providing 0ne number of diploma engineer in Electrical or Electronics / instrumantion for the operation & maintenance of SCADA system The Job involves deputation of Engineers, helpers, at site for supervision, maintenance & trouble shooting of SCADA system, including training of Department operators. So as to ensure 100% reliable performance of all SCADA system, associated equipments, devices, giving feedback of operating performed and corrective measures required including carrying out preventive maintenance works finishing the flow, pressure residual chlorine datas etc. in hard copy and Soft copy etc. complete .

60

-

963600

... More
Providing one number of helpers for for the operation & maintenance of SCADA system.

60

-

816300

... More
Operation & Maitenance of SCADA System for a period of 48 months after defect liability period . Replacement of UPS / inverter battery after worn out per piece, including transport and installation charging etc complete

4

-

26000

... More
Actuator mechanical part replacement with new part conformimg to relevant is with altest amentdments including transportion

4

-

48000

... More
Level sensor replacement with new one

2

-

97348

... More
Pressure sensor replacement with new one

2

-

32000

... More
Cable laying and replacement for sensor and actuators, Electromagnetic Flow meter at RTU due to physical damage etc

50

-

9000

... More
Replacement of parts and spares of Electromagnetic flow meter

2

-

40000

... More
Satellite internet service provider charges on monthly basis for minimum 512 kbps speed with 99.99% up time and minimum 1 static IP with specifications as per SCADA software requirement

60

-

408000

... More
Service provider changes for GPRS data on monthly basis for VPN / GPRS/ 4G required for communication from canal intake , IR pump house , IPS pump house & OHTS etc required for data acquisition from Remote Terminal Units

60

-

84000

... More
Annual Maintenance of Batteries for UPS at Master control room and at remote terminal unit per unit battery per year.

4

-

7600

... More
Maintenance on annual basis with database back up and scheduled maintenance and software services for application software and modifications there of including replcament of parts such as fuse , mcb, relays , connectors, power supply cards etc & other parts in PLC panel , RTU etc per year

4

-

200000

... More
Renewal of software's for security and virus protection per year

4

-

14600

... More
Scheduled maintenance of server, firmware, power supply etc as per specifications of OEM per year

4

-

200000

... More
Scheduled maintenance of Chlorine analyser, turbidity meter & PH meter with scheduled annual part replacement per year for all above meters

4

-

460000



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.